B08_Attachment_6_NPS_Acceptance_Checklist_0001.pdf

PDF 125 KB Posted

Attached to
Grand Canyon National Park, AZ: Follow-On Potable
Solicitation number
140PP027Q0009
Issued by
Not on record

About this file

This is a field inspection checklist template for Emergency Potable Water Hauling Services at the South Rim under Contract 140PS126P0049. The checklist is used to verify compliance and quality standards for each water delivery load prior to unloading at designated sites.

The inspection covers ten primary items: verification that the trailer ID matches the approved vehicle list and manifest; confirmation that the driver is on the accepted roster with appropriate Commercial Driver's License (CDL) and tank vehicle endorsement; documentation of chlorine dose added as shown on the manifest; measurement of free chlorine levels (0.7 to 1.5 mg/L); pH testing (7.5 to 8.5); recording of temperature and conductivity (informational only, no pass/fail criteria); turbidity measurement (≤1.0 NTU); visual and odor inspection confirming clear, colorless water with no particles, sheen, or objectionable odor; and verification that the truck is full at the standard 6,000-gallon capacity or documentation of alternative volume. Items 4, 5, 9, and 10 are critical parameters that, if marked "No," require immediate rejection and COR notification. All other deficiencies must be flagged and reported to the Contracting Officer's Representative (COR) within two hours during regular business hours, including weekends. The inspector signs and dates the checklist and indicates final approval or rejection with required explanation.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Field Checklist: Per-Load Water Inspection Emergency Potable Water Hauling Services, South Rim · Contract 140PS126P0049

Site (check one):

Date and time:

Inspector:

# Item Reading / entry Units Yes if … Yes No

1 Trailer ID On the approved vehicle list, and matches the manifest. ☐ ☐

2 Driver name ☐ ☐

3 Chlorine dose added (qty) Dose shown on the manifest. ☐ ☐

4 Free chlorine mg/L Value 0.7 to 1.5. ☐ ☐

5 pH Value 7.5 to 8.5 ☐ ☐

6 Temperature °C / °F Record only. No pass/fail criterion. ☐ ☐

7 Conductivity µS/cm Record only. No pass/fail criterion. ☐ ☐

8 Turbidity NTU ≤1.0 NTU. ☐ ☐

9 Visual and odor check ☐ ☐

10 Truck is full Truck is full. Indicate volume if other than 6,000 gallons. ☐ ☐

11 Notes

Approve unloading?

If a box is No

• Item 4, 5, 9, or 10: Do not approve unloading; contact COR immediately

• All other items flag as deficencies for contractor to correct. Notify COR within 2 hours within regular business hours (including weekends).

Inspector signature: Date and time: ______________________

☐ Water Treatment Plant ☐ Tank A Overfill

On the accepted driver roster (CDL with tank vehicle (N) endorsement).

Clear and colorless; no particles, sheen, or objectionable odor.

☐ Yes ☐ No: reject. Reason: ______________________________