B08_Attachment_4_Fire_Inspection_Documentation_0001.pdf
PDF 5 MB Posted
- Attached to
- YOSE-FIRE PROTECTION SYSTEM TESTING Federal contract opportunity
- Solicitation number
- 140P8525Q0037
About this file
These are multiple fire protection system inspection reports for various buildings in Yosemite National Park, El Portal, and Wawona areas, dated August 2024. The documents are detailed annual fire sprinkler system inspection forms (AES 1 Sept. 3, 2013 template) for wet pipe fire sprinkler systems, covering approximately 50 different residential and historic buildings. Each report includes comprehensive inspection details such as riser information, quarterly and annual inspections, testing results, and specific deficiencies noted during the inspection.
Common deficiencies across multiple reports include outdated UL-listed fire protection gauges, missing control valve and test/drain signs, recalled sprinkler heads requiring replacement, flow switch and waterflow alarm issues, and missing or incorrect spare head box equipment. The inspections were performed by J Johnson & Donavan under California Code of Regulations Title 19, following NFPA 25 (2011 edition) standards. The reports systematically document the condition of fire suppression systems, with most buildings having multiple identified issues that require corrective action to maintain compliance with fire safety regulations.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| B08_Attachment_6_Fire_Inspection_Documentation_0001.pdf | ||
| Sol_140P8525Q0037_Amd_0001.pdf | ||
| B08_Attachment_5_Fire_Inspection_Documentation_0001.pdf | ||
| Sol_140P8525Q0037.pdf | ||
| B08_Attachment_2_System_Inventory-FY_25.xlsx | XLSX spreadsheet | |
| B08_Attachment_1_SOW_Fire_Suppression_Inspection-FY_25.docx | DOCX document | |
| B08_Attachment_3_Wage_Determination_2015-5661.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AES 1 Sept. 3, 2013
Inspection, Testing, and Maintenance Cover Sheet NFPA25 as amended by CCR, Title 19
Property Information:
Name: Residence
Occupancy/Use:
Choose an item.
Address: VaQ 0010
Construction Type: Choose an item.
City: Valley
No. Stories:
ZIP: 95389
Year Constructed:
Contact: Tim Modjeski
Telephone: 303-819-9916
Contractor Information:
Number of System Risers 1
Copy sent to:
Name: Owner Date:
Address
Fire AHJ Date:
City:
Contractor Date: 8/22/2024
State:
NOTES:
1) For specific inspection, testing, and maintenance requirements and information, see NFPA 25, 2011 edition as amended by California Code of Regulations, Title 19, §901 to §906.
2) Inspection items may be performed by the owner in accordance with California Code of Regulations, Title 19, §904.1(a)
Telephone:
CA License#: 905493
Job #: SV2407120072
Performed by: J Johnson & Donavan
Check box for each system inspected and enter the number of forms used for inspection. Check boxes (Fail or Pass) to indicate status of inspected system at end of inspection.
Forms Included with this Report
NFPA 25
Chapter
Number of Forms N/A Fail* Pass
Automatic Sprinkler System 5 1
Standpipe and Hose System 6
Private Water Supply System 7
Fire Pump 8
Water Storage Tank 9
Water Spray System 10
Foam Water Sprinkler System 11
Water Mist System 12
Concerns that are Not Deficiencies (i.e. Non-Sprinklered Areas) Yes No
*See "Deficiencies and Comments" section at end of each respective form.
Wet Pipe Fire Sprinkler System
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and Annual Report
Property Information
Contractor or Licensed Owner Information
Building Residence
Address VaQ 0010
City Valley License # 905493 Contact Tim Modjeski SFM Job # SV2407120072
Phone 303-819-9916 CSLB Misc.
Riser Information Main Drain Test (Annual)
Riser No.
Location Riser
Diameter Main Drain Diameter
Initial Static Pressure
Residual Pressure
Final Static Pressure
P,F,N/A
1 Laundry Room 1” 1” 86 8 55 P
This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached
Quarterly Inspections I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable
Item Description NFPA 25 CA ed.
Reference
Date Date Date Date
8/22/24
1.1 I Control Valves – Identification Sign 13.3.1 F
1.2 I Control Valves – Inspection 13.3.2 P
1.3 I Waterflow Alarm Devices 5.2.5 P
1.4 I Supervisory Devices 5.2.5 N/A
1.5 I Gauges (Wet Pipe Systems) 5.2.4.1 F
1.6 I Enter Water Supply Pressure Below Riser Check 5.2.4.1 psi psi N/A psi psi
1.7 I Enter Water Supply Pressure Above Riser Check 5.2.4.1 psi psi 86 psi psi
1.8 I Pressure Readings Acceptable 5.2.4.1 P
1.9 I
Hydraulic Design Information Sign (For Hydraulically Designed Systems) 5.2.6
N/A
1.10 I
General Information Sign (Not Required for System prior to 2007 Edition of NFPA 13)
5.2.8
N/A
1.11 I Heat Tape 5.2.7 N/A
1.12 I Spare Sprinklers 5.2.1.4 F
1.13 I Fire Department Connections 13.7 N/A
1.14 I Alarm Valves – Exterior Inspection 13.4.1 N/A
1.15 I Pressure Reducing Valves 13.5.1.1 N/A
1.16 I Backflow Preventers 13.6.1 N/A
1.17 I Small Hose Connections - Hose Valve*
5.1.6, 13.5.2
13.5.5.1 N/A
1.18 I PRV – Fire Sprinkler Systems 13.5.1.1 N/A
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III standpipe systems.
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and
Name
Address VaQ 0010 Job # SV2407120072 City Valley Misc.
ANNUAL INSPECTION, TESTING, AND MAINTENANCE
Include ALL Quarterly Inspections
I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable
Item
Description NFPA 25 CA ed.
Reference Date Comments Only P,F,N/A
1.19 I Sprinklers 5.2.1 8/22/24 F
1.20 I Buildings (Freeze Protection) 4.1.1.1 8/22/24 Owner’s Responsibility P
1.21 I Pipe and Fittings 5.2.2 8/22/24 P
1.22 I Hangers 5.2.3 8/22/24 P
1.23 I Seismic Braces 5.2.3 8/22/24 P
2.1 T
Field Service Test Required (Send Report to Fire Code Official)
5.3.1 If REQUIRED, Enter 'F' until results
are returned from Lab N/A
2.2 T
Recalled Sprinklers
If not present = Pass; If present = Fail Title 19 904.1(c) 8/22/24
F
2.3 T
Water Flow Alarm Devices 90 sec. maximum - (Enter Time ) 5.3.3
13.2.6 8/22/24 18 sec. P
2.4 T
Main Drain Test (Enter Data on Page 1 of this Form)
13.2.5
13.3.3.4 8/22/24
P
2.5 T Control Valve - Position 13.3.3.2 8/22/24 P
2.6 T Control Valve – Operation 13.3.3.1 8/22/24 P
2.7 T Supervisory Devices 13.3.3.5 N/A
2.8 T Backflow Preventer Assemblies 13.6.2 N/A
2.9 T
Small Hose Connections* w/PRV Hose Valves – Partial Flow Test
13.5.2.3 13.5.3.3
2.10 T PRV – Fire Sprinkler Systems 13.5.1.3 N/A
3.1 M Control Valves 13.3.4 N/A
3.2 M Small Hose Connections* 13.5.6.3 N/A
3.3
M Obstruction Investigation required
(If “Yes”, see Deficiencies and Comments Section for Results.)
14.3
Yes No
N/A
3.4 M System Returned to Service 4.5.3 8/22/24
Yes No
P
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III standpipe
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and
Address VaQ 0010 Job # SV2407120072
D = Deficiency C = Comment (Indicate type )
Item Date Riser D C Deficiencies and Comments Indicate all equipment, devices and parts that were repaired or replaced
*****ANNUAL FIRE SPRINKLER INSPECTION*****
1.5 8/22/24 1 X UL listed fire protection gauge out dated on riser & gauge ball valve kit
1.12 8/22/24 1 X Add 3 capacity head box with ½” white residential 155* pendants, white ½” residential HSW & wrench(es) to fit heads.
2.2 8/22/24 1 X 7 recalled white CSC LF ½” semi recessed pendants installed.
1.19 8/22/24 1 X Missing 1 white semi recessed escutcheon at kitchen.
1.1 8/22/24 1 X Add Control Valve & Test/ Drain signs to valves on riser.
END OF REPORT
Check here if additional Deficiencies and Comments are listed on Form AES9.
See Correction Form AES 10 for corrected deficiencies.
Number attached
I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.
Check box if Annual Inspection, Testing & Maintenance Items are Completed in the Indicated Quarter
Quarter 1st - Annual 2nd - Annual 3rd - Annual 4th - Annual
Date 8/22/24
Print Name Jeremy Johnson
Signature J.Johnson
Address: VaQ 0012 requirements and information, see NFPA 25, 2011
Forms Included with this Report
NFPA 25
Chapter
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and
Address VaQ 0012
Phone 303-819-9916 CSLB Misc.
Riser Information Main Drain Test (Annual)
Riser No.
Location Riser
Diameter Main Drain Diameter
Initial Static Pressure
Residual Pressure
Final Static Pressure
1 Kitchen Water heater closet 1” 1” 71 25 73 P
This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached
I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable
Item Description NFPA 25 CA ed.
Reference
Date Date Date Date
8/22/24
1.1 I Control Valves – Identification Sign 13.3.1 F
1.2 I Control Valves – Inspection 13.3.2 P
1.3 I Waterflow Alarm Devices 5.2.5 P
1.4 I Supervisory Devices 5.2.5 N/A
1.5 I Gauges (Wet Pipe Systems) 5.2.4.1 F
1.6 I Enter Water Supply Pressure Below Riser Check 5.2.4.1 psi psi N/A psi psi
1.7 I Enter Water Supply Pressure Above Riser Check 5.2.4.1 psi psi 71 psi psi
1.8 I Pressure Readings Acceptable 5.2.4.1 P
1.9 I
Hydraulic Design Information Sign (For Hydraulically Designed Systems) 5.2.6
N/A
1.10 I
General Information Sign
1.13 I Fire Department Connections 13.7 N/A
1.14 I Alarm Valves – Exterior Inspection 13.4.1 N/A
1.15 I Pressure Reducing Valves 13.5.1.1 N/A
1.16 I Backflow Preventers 13.6.1 N/A
1.17 I Small Hose Connections - Hose Valve*
5.1.6, 13.5.2
13.5.5.1 N/A
1.18 I PRV – Fire Sprinkler Systems 13.5.1.1 N/A
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III standpipe
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and
Address VaQ 0012 Job # SV2407120072
Reference Date Comments Only P,F,N/A
1.19 I Sprinklers 5.2.1 8/22/24 P
1.20 I Buildings (Freeze Protection) 4.1.1.1 8/22/24 Owner’s Responsibility P
1.21 I Pipe and Fittings 5.2.2 8/22/24 P
1.22 I Hangers 5.2.3 8/22/24 P
1.23 I Seismic Braces 5.2.3 8/22/24 P
2.1 T
Field Service Test Required (Send Report to Fire Code Official)
5.3.1 If REQUIRED, Enter 'F' until results
are returned from Lab N/A
2.2 T
Recalled Sprinklers
Water Flow Alarm Devices 90 sec. maximum - (Enter Time ) 5.3.3
13.2.6 8/22/24 sec. F
2.4 T
Main Drain Test (Enter Data on Page 1 of this Form)
2.6 T Control Valve – Operation 13.3.3.1 8/22/24 P
2.7 T Supervisory Devices 13.3.3.5 N/A
2.8 T Backflow Preventer Assemblies 13.6.2 N/A
2.9 T
Small Hose Connections* w/PRV Hose Valves – Partial Flow Test
N/A
3.4 M System Returned to Service 4.5.3 8/22/24
Yes No
P
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III standpipe
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and
Address VaQ 0012 Job # SV2407120072
1.1 8/22/24 1 X Add Control Valve, Test/Drain, & 911 bell signs to system.
1.5 8/22/24 1 X UL listed fire protection gauge out dated.
1.12 8/22/24 1 X No spare head box found. Add 3 capacity box, 3- white 155* ½” residential pendants & Socket style wrench to fit heads.
2.2 8/22/24 1 X 7 CSC LF recalled semi recessed ½” white pendants installed.
2.3 8/22/24 1 X Waterflow Failed the alarm test. Troubleshoot flow switch.
See Correction Form AES 10 for corrected deficiencies.
I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.
Check box if Annual Inspection, Testing & Maintenance Items are Completed in the Indicated Quarter
Quarter 1st - Annual 2nd - Annual 3rd - Annual 4th - Annual
Date 8/22/24
Address: VaQ 0013 requirements and information, see NFPA 25, 2011
Forms Included with this Report
NFPA 25
Chapter
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and
Address VaQ 0013
Phone 303-819-9916 CSLB Misc.
Riser Information Main Drain Test (Annual)
Riser No.
Location Riser
Diameter Main Drain Diameter
Initial Static Pressure
Residual Pressure
Final Static Pressure
1 Laundry Room 1” 1” 84 10 66 P
This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached
I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable
Item Description NFPA 25 CA ed.
Reference
Date Date Date Date
8/22/24
1.1 I Control Valves – Identification Sign 13.3.1 F
1.2 I Control Valves – Inspection 13.3.2 P
1.3 I Waterflow Alarm Devices 5.2.5 P
1.4 I Supervisory Devices 5.2.5 N/A
1.5 I Gauges (Wet Pipe Systems) 5.2.4.1 F
1.6 I Enter Water Supply Pressure Below Riser Check 5.2.4.1 psi psi N/A psi psi
1.7 I Enter Water Supply Pressure Above Riser Check 5.2.4.1 psi psi 84 psi psi
1.8 I Pressure Readings Acceptable 5.2.4.1 P
1.9 I
Hydraulic Design Information Sign (For Hydraulically Designed Systems) 5.2.6
N/A
1.10 I
General Information Sign
1.13 I Fire Department Connections 13.7 N/A
1.14 I Alarm Valves – Exterior Inspection 13.4.1 N/A
1.15 I Pressure Reducing Valves 13.5.1.1 N/A
1.16 I Backflow Preventers 13.6.1 N/A
1.17 I Small Hose Connections - Hose Valve*
5.1.6, 13.5.2
13.5.5.1 N/A
1.18 I PRV – Fire Sprinkler Systems 13.5.1.1 N/A
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III standpipe
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and
Address VaQ 0013 Job # SV2407120072
Reference Date Comments Only P,F,N/A
1.19 I Sprinklers 5.2.1 8/22/24 P
1.20 I Buildings (Freeze Protection) 4.1.1.1 8/22/24 Owner’s Responsibility P
1.21 I Pipe and Fittings 5.2.2 8/22/24 F
1.22 I Hangers 5.2.3 8/22/24 P
1.23 I Seismic Braces 5.2.3 8/22/24 P
2.1 T
Field Service Test Required (Send Report to Fire Code Official)
5.3.1 If REQUIRED, Enter 'F' until results
are returned from Lab N/A
2.2 T
Recalled Sprinklers
Water Flow Alarm Devices 90 sec. maximum - (Enter Time ) 5.3.3
13.2.6 8/22/24 13 sec. F
2.4 T
Main Drain Test (Enter Data on Page 1 of this Form)
2.6 T Control Valve – Operation 13.3.3.1 8/22/24 P
2.7 T Supervisory Devices 13.3.3.5 N/A
2.8 T Backflow Preventer Assemblies 13.6.2 N/A
2.9 T
Small Hose Connections* w/PRV Hose Valves – Partial Flow Test
N/A
3.4 M System Returned to Service 4.5.3 8/22/24
Yes No
P
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III standpipe
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and
Address VaQ 0013 Job # SV2407120072
1.1 8/22/24 1 X Add Control Valve, Test/Drain & 911 bell signs to system.
1.5 8/22/24 1 X UL listed fire protection gauge out dated on riser.
1.12 8/22/24 1 X Add 1 white 155* residential HSW & socket style wrench for V2730 heads to spare box.
2.3 8/22/24 1 X Waterflow time 13 secs – adjust waterflow to 30-90 seconds
1.21 8/22/24 1 X Add broken ½” residential head to drain outlet.
See Correction Form AES 10 for corrected deficiencies.
I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.
Check box if Annual Inspection, Testing & Maintenance Items are Completed in the Indicated Quarter
Quarter 1st - Annual 2nd - Annual 3rd - Annual 4th - Annual
Date 8/22/24
Address: VaQ 0042 requirements and information, see NFPA 25, 2011
Forms Included with this Report
NFPA 25
Chapter
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and
Address VaQ 0042
Phone 303-819-9916 CSLB Misc.
Riser Information Main Drain Test (Annual)
Riser No.
Location Riser
Diameter Main Drain Diameter
Initial Static Pressure
Residual Pressure
Final Static Pressure
1 Water Heater Closet 1” 1” 140 5 110 P
This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached
I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable
Item Description NFPA 25 CA ed.
Reference
Date Date Date Date
8/22/24
1.1 I Control Valves – Identification Sign 13.3.1 F
1.2 I Control Valves – Inspection 13.3.2 P
1.3 I Waterflow Alarm Devices 5.2.5 P
1.4 I Supervisory Devices 5.2.5 N/A
1.5 I Gauges (Wet Pipe Systems) 5.2.4.1 F
1.6 I Enter Water Supply Pressure Below Riser Check 5.2.4.1 psi psi N/A psi psi
1.7 I Enter Water Supply Pressure Above Riser Check 5.2.4.1 psi psi 140 psi psi
1.8 I Pressure Readings Acceptable 5.2.4.1 F
1.9 I
Hydraulic Design Information Sign (For Hydraulically Designed Systems) 5.2.6
N/A
1.10 I
General Information Sign
1.13 I Fire Department Connections 13.7 N/A
1.14 I Alarm Valves – Exterior Inspection 13.4.1 N/A
1.15 I Pressure Reducing Valves 13.5.1.1 N/A
1.16 I Backflow Preventers 13.6.1 N/A
1.17 I Small Hose Connections - Hose Valve*
5.1.6, 13.5.2
13.5.5.1 N/A
1.18 I PRV – Fire Sprinkler Systems 13.5.1.1 N/A
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III standpipe
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and
Address VaQ 0042 Job # SV2407120072
Reference Date Comments Only P,F,N/A
1.19 I Sprinklers 5.2.1 8/22/24 P
1.20 I Buildings (Freeze Protection) 4.1.1.1 8/22/24 Owner’s Responsibility P
1.21 I Pipe and Fittings 5.2.2 8/22/24 P
1.22 I Hangers 5.2.3 8/22/24 P
1.23 I Seismic Braces 5.2.3 8/22/24 P
2.1 T
Field Service Test Required (Send Report to Fire Code Official)
5.3.1 If REQUIRED, Enter 'F' until results
are returned from Lab N/A
2.2 T
Recalled Sprinklers
Water Flow Alarm Devices 90 sec. maximum - (Enter Time ) 5.3.3
13.2.6 8/22/24 28 sec. P
2.4 T
Main Drain Test (Enter Data on Page 1 of this Form)
2.6 T Control Valve – Operation 13.3.3.1 8/22/24 P
2.7 T Supervisory Devices 13.3.3.5 N/A
2.8 T Backflow Preventer Assemblies 13.6.2 N/A
2.9 T
Small Hose Connections* w/PRV Hose Valves – Partial Flow Test
N/A
3.4 M System Returned to Service 4.5.3 8/22/24
Yes No
P
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III standpipe
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and
Address VaQ 0042 Job # SV2407120072
1.1 8/22/24 1 X Add 2 Control Valve, 1 Test/Drain, & 1 911 bell sign to system.
1.12 8/22/24 1 X 2 Central Omega Recalled heads & wrench in spare head box. Replace with white ½” 155* Residential pendants and socket style head wrench.
2.2 8/22/24 1 X 15 Recalled white CSC LF semi recessed 155* pendants installed.
1.5 8/22/24 1 X UL listed fire protection gauge outdated on riser. Sowing excessive pressure.
See Correction Form AES 10 for corrected deficiencies.
I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.
Check box if Annual Inspection, Testing & Maintenance Items are Completed in the Indicated Quarter
Quarter 1st - Annual 2nd - Annual 3rd - Annual 4th - Annual
Date 8/22/24
Name: Residence Apts
Address: VaQ 0046
Number of System Risers 4 requirements and information, see NFPA 25, 2011
Forms Included with this Report
NFPA 25
Chapter
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and
Building Residence Apts
Address VaQ 0046
City License # 905493
Phone 303-819-9916 CSLB Misc.
Riser Information Main Drain Test (Annual)
Riser No.
Location Riser
Diameter Main Drain Diameter
Initial Static Pressure
Residual Pressure
Final Static Pressure
P,F,N/A
1 Apt 46-A Water Heater Closet 1” 1” 140 9 90 P
2 Apt 46-B Water Heater Closet 1” 1” 102 23 85 P
3 Apt 46-C Water Heater Closet 1” 1” 92 10 86 P
4 Apt 46-D Water Heater Closet 1” 1” 260 155 215 F
This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached
I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable
Item Description NFPA 25 CA ed.
Reference
Date Date Date Date
8/22/24
1.1 I Control Valves – Identification Sign 13.3.1 F
1.2 I Control Valves – Inspection 13.3.2 P
1.3 I Waterflow Alarm Devices 5.2.5 P
1.4 I Supervisory Devices 5.2.5 N/A
1.5 I Gauges (Wet Pipe Systems) 5.2.4.1 F
1.6 I Enter Water Supply Pressure Below Riser Check 5.2.4.1 psi psi N/A psi psi
1.7 I Enter Water Supply Pressure Above Riser Check 5.2.4.1 psi psi * psi psi
1.8 I Pressure Readings Acceptable 5.2.4.1 F
1.9 I
Hydraulic Design Information Sign (For Hydraulically Designed Systems) 5.2.6
N/A
1.10 I
General Information Sign
1.13 I Fire Department Connections 13.7 N/A
1.14 I Alarm Valves – Exterior Inspection 13.4.1 N/A
1.15 I Pressure Reducing Valves 13.5.1.1 N/A
1.16 I Backflow Preventers 13.6.1 N/A
1.17 I Small Hose Connections - Hose Valve*
5.1.6, 13.5.2
13.5.5.1 N/A
1.18 I PRV – Fire Sprinkler Systems 13.5.1.1 N/A
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III standpipe
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and
Address VaQ 0046 Job # SV2407120072
Reference Date Comments Only P,F,N/A
1.19 I Sprinklers 5.2.1 8/22/24 F
1.20 I Buildings (Freeze Protection) 4.1.1.1 8/22/24 Owner’s Responsibility P
P1.21 I Pipe and Fittings 5.2.2 8/22/24 P
1.22 I Hangers 5.2.3 8/22/24 P
1.23 I Seismic Braces 5.2.3 8/22/24 P
2.1 T
Field Service Test Required (Send Report to Fire Code Official)
5.3.1 If REQUIRED, Enter 'F' until results
are returned from Lab N/A
2.2 T
Recalled Sprinklers
Water Flow Alarm Devices 90 sec. maximum - (Enter Time ) 5.3.3
13.2.6 8/22/24 sec. F
2.4 T
Main Drain Test (Enter Data on Page 1 of this Form)
2.6 T Control Valve – Operation 13.3.3.1 8/22/24 P
2.7 T Supervisory Devices 13.3.3.5 N/A
2.8 T Backflow Preventer Assemblies 13.6.2 N/A
2.9 T
Small Hose Connections* w/PRV Hose Valves – Partial Flow Test
N/A
3.4 M System Returned to Service 4.5.3 8/22/24
Yes No
P
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III standpipe
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and
Address VaQ 0046 Job # SV2407120072
1.1 8/22/24 1-4 X Add 2 Control Valve, 1 Test/ Drain, & 1 911 bell sign to each riser.
1.5 8/22/24 1-4 X UL listed fire protection gauge out dated on each riser.
1.8 8/22/24 4 X UL listed fire protection gauge showing excessive pressure.
1.12 8/22/24 2-4 X Spare head box missing. Add 3 capacity box with 3 white 155* ½” residential pendants & Socket style head wrench to fit heads to water heater closets in B, C, & D
1.12 8/22/24 1 X Spare head box missing socket style head wrench for TY2234 heads.
2.2 8/22/24 1-4 X White recalled CSC LF 155* ½” semi recessed pendants installed. A (8), B (7), C (7), D (8).
1.19 8/22/24 4 X 1 Damaged white semi recessed recalled residential 155* pendant in Apt 46-D.
2.3 8/22/24 1,2,4 X Electric bell not ringing during water flow for Apts A, B, C, & D. Ran ITVs 2 minutes each.
See Correction Form AES 10 for corrected deficiencies.
I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.
Check box if Annual Inspection, Testing & Maintenance Items are Completed in the Indicated Quarter
Quarter 1st - Annual 2nd - Annual 3rd - Annual 4th - Annual
Date 8/22/24
Address: VaQ 0061 requirements and information, see NFPA 25, 2011
Forms Included with this Report
NFPA 25
Chapter
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and
Address VaQ 0061
Phone 303-819-9916 CSLB Misc.
Riser Information Main Drain Test (Annual)
Riser No.
Location Riser
Diameter Main Drain Diameter
Initial Static Pressure
Residual Pressure
Final Static Pressure
1 Laundry Room 1” 1” 48 10 50 P
This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached
I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable
Item Description NFPA 25 CA ed.
Reference
Date Date Date Date
8/22/24
1.1 I Control Valves – Identification Sign 13.3.1 F
1.2 I Control Valves – Inspection 13.3.2 P
1.3 I Waterflow Alarm Devices 5.2.5 P
1.4 I Supervisory Devices 5.2.5 N/A
1.5 I Gauges (Wet Pipe Systems) 5.2.4.1 F
1.6 I Enter Water Supply Pressure Below Riser Check 5.2.4.1 psi psi N/A psi psi
1.7 I Enter Water Supply Pressure Above Riser Check 5.2.4.1 psi psi 48 psi psi
1.8 I Pressure Readings Acceptable 5.2.4.1 P
1.9 I
Hydraulic Design Information Sign (For Hydraulically Designed Systems) 5.2.6
N/A
1.10 I
General Information Sign
1.12 I Spare Sprinklers 5.2.1.4 P
1.13 I Fire Department Connections 13.7 N/A
1.14 I Alarm Valves – Exterior Inspection 13.4.1 N/A
1.15 I Pressure Reducing Valves 13.5.1.1 N/A
1.16 I Backflow Preventers 13.6.1 N/A
1.17 I Small Hose Connections - Hose Valve*
5.1.6, 13.5.2
13.5.5.1 N/A
1.18 I PRV – Fire Sprinkler Systems 13.5.1.1 N/A
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III standpipe
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and
Address VaQ 0061 Job # SV2407120072
Reference Date Comments Only P,F,N/A
1.19 I Sprinklers 5.2.1 8/22/24 F
1.20 I Buildings (Freeze Protection) 4.1.1.1 8/22/24 Owner’s Responsibility P
1.21 I Pipe and Fittings 5.2.2 8/22/24 P
1.22 I Hangers 5.2.3 8/22/24 P
1.23 I Seismic Braces 5.2.3 8/22/24 F
2.1 T
Field Service Test Required (Send Report to Fire Code Official)
5.3.1 If REQUIRED, Enter 'F' until results
are returned from Lab N/A
2.2 T
Recalled Sprinklers
Water Flow Alarm Devices 90 sec. maximum - (Enter Time ) 5.3.3
13.2.6 8/22/24 sec. F
2.4 T
Main Drain Test (Enter Data on Page 1 of this Form)
2.6 T Control Valve – Operation 13.3.3.1 8/22/24 P
2.7 T Supervisory Devices 13.3.3.5 N/A
2.8 T Backflow Preventer Assemblies 13.6.2 N/A
2.9 T
Small Hose Connections* w/PRV Hose Valves – Partial Flow Test
N/A
3.4 M System Returned to Service 4.5.3 8/22/24
Yes No
P
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III standpipe
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and
Address VaQ 0061 Job # SV2407120072
1.1 8/22/24 1 X Add Control Valve sign to control valve.
1.5 8/22/24 1 X Replace out dated UL listed fire protection gauge on riser.
2.2 8/22/24 1 X 14 recalled CSC LF white semi recessed 155* ½” pendants installed.
2.3 8/22/24 1 X Unable to locate bell. Ran ITV for 2 minutes. No alarm activation.
1.23 8/22/24 1 X Reattach existing Unistrut clamp to existing Unistrut.
1.12 8/22/24 1 X Add 3 capacity head box, 3 white ½” TY2234 pendants & socket style head wrench to fit Tyco heads.
See Correction Form AES 10 for corrected deficiencies.
I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.
Check box if Annual Inspection, Testing & Maintenance Items are Completed in the Indicated Quarter
Quarter 1st - Annual 2nd - Annual 3rd - Annual 4th - Annual
Date 8/22/24
Form AES 2.1 Sept. 3, 2013
Name: Yosemite National Park Occupancy/Use:
Address: VAQ 049 Residence Valley Construction Type:
City: Yosemite National Park No. Stories:
ZIP: 95389 Year Constructed:
Contact:
Tim Modjeski
303-819-9916
Contractor Information: Number of System Risers: 1
Name: HCI Systems, Inc.
Address: 3742 W. Gettysburg Ave Ste. 102
X Owner Date:
City: Fresno
Fire AHJ Date: N/A
State: CA
X Contractor Date: 8/22/2024
Telephone: 559-233-2008
CA License #: 905493
1) For specific inspection, testing, and maintenance requirements and information, see NFPA 25, 2011 edition as amended by California Code of Regulations, Title 19, §901 to §906
2) Inspection items may be performed by the owner in
Performed by: Jeremy Johnson
Check box for each system inspected and enter the number of forms used for inspection.
Check boxes (Fail or Pass) to indicate status of inspected system at end of inspection.
Forms included with this Report
NFPA 25
Chapter
Number of Forms N/A Fail* Pass
Automatic Sprinkler System 5 2 X
Standpipe and Hose System 6 0
Private Water Supply System 7 0
Fire Pump 8 0
Water Storage Tank 9 0
Water Spray System 10 0
Foam Water Sprinkler System 11 0
Water Mist System 12 0
Concerns that are Not Deficiencies (i.e. Non-Sprinklered Areas) Yes X No
*See “Deficiencies and Comments” section at end of each respective form.
California Code of Regulations – Title 19
Inspection, Testing, and Maintenance Quarterly and
Building Name Yosemite National Park Name HCI Systems, Inc.
Address VAQ 049 Residence Valley Address 3742 W. Gettysburg Ave Ste. 102
City Fresno St. CA Zip 93722
City Yosemite National Park License # 905493 Phone 559-233-2008
Contact Person Tim Modjeski SFM Job # SV2407120072
Phone 303-819-9916 CSLB Misc.
Riser Information Main Drain Test (Annual)
Riser No.
Location Riser
Diameter Main Drain Diameter
Initial Static Pressure
Residual Pressure
Final Static Pressure
WF
sec
P,F, N/A
1 Downstairs Water Heater Closet 1” 1” 105 30 90 7 P
This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached 1
I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not applicable
Item Description NFPA 25 CA ed.
Reference
Date
8/22/24
1.1 I Control Valves – Identification Sign 13.3.1 F
1.2 I Control Valves – Inspection 13.3.2 P
1.3 I Waterflow Alarm Devices 5.2.5 P
1.4 I Supervisory Devices 5.2.5 N/A
1.5 I Gauges (Wet Pipe Systems) 5.2.4.1 F
1.6 I Enter Water Supply Pressure Below Riser Check 5.2.4.1 psi psi N/A psi psi
1.7 I Enter Water Supply Pressure Above Riser Check 5.2.4.1 psi psi 105 psi psi
1.8 I Pressure Readings Acceptable 5.2.4.1 P
1.9 I
Hydraulic Design Information Sign (For hydraulically Designed Systems)
5.2.6 F
1.10 I
General Information Sign (Not Required for System prior to 2007 Edition of NFPA 13)
5.2.8 N/A
1.11 I Heat Tape 5.2.7 N/A
1.12 I Spare Sprinklers 5.2.1.4 F
1.13 I Fire Department Connections 13.7 N/A
1.14 I Alarm Valves – Exterior Inspection 13.4.1 P
1.15 I Pressure Reducing Valves 13.5.1.1 P
1.16 I Backflow Preventers 13.6.1 N/A
1.17 I Small Hose Connections – Hose Valve*
5.1.6, 13.5.2
13.5.5.1 N/A
1.18 I PRV – Fire Sprinkler Systems 13.5.1.1 N/A
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III standpipe systems.
California Code of Regulations – Title 19 Inspection, Testing, and Maintenance
Quarterly and Annual Report
Address VAQ 049 Residence Valley Job # SV2407120072
City Yosemite National Park
I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not applicable
Item Description
NFPA 25
CA ed.
Referenc e
8/22/24 Comments Only P,F,N/A
1.19 I Sprinklers 5.2.1 F
1.20 I Buildings (Freeze Protection) 4.1.1.1 Owner’s Responsibility P
1.21 I Pipe and Fittings 5.2.2 P
1.22 I Hangers 5.2.3 P
1.23 I Seismic Braces 5.2.3 P
2.1 T
Field Service Test Required (Send Report to Fire Code Official)
5.3.1 If REQUIRED, Enter “F” until results are
returned from Lab.
NA
2.2 T
Recalled Sprinklers If not present = Pass; If present = Fail
Title 19 904.1(c)
F
2.3 T
Water Flow Alarm Devices 90 sec. maximum – (Enter Time)
5.3.3 13.2.6
F
2.4 T
Main Drain Test (Enter Data on Page 1 of this Form)
13.2.5 13.3.3.4
P
2.5 T Control Valve – Position 13.3.3.2 N/A
2.6 T Control Valve – Operation 13.3.3.1 N/A
2.7 T Supervisory Devices 13.3.3.5 N/A
2.8 T Backflow Preventer Assemblies 13.6.2 N/A
2.9 T
Small Hose Connections* W/PRV Hose Valves – Partial Flow Test
13.5.2.3 13.5.3.3
N/A
2.10 T PRV – Fire Sprinkler Systems 13.5.1.3 N/A
3.1 M Control Valves 13.3.4 N/A
3.2 M Small Hose Connections* 13.5.6.3 N/A
3.3 M
Obstruction Investigation required (If “Yes”, see Deficiencies and Comments Section for Results.)
14.3 Yes
No N/A
3.4 M System Returned to Service 4.5.3
Yes
No P
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III
D = Deficiency C = Comment (Indicate type)
Item Date Riser D C Deficiencies and Comments
Indicate all equipment, devices and parts that were repaired or replaced
2.3 8/22/24 1 X Waterflow time 7 secs. – adjust between 30-90 seconds as required
1.1 8/22/24 1 X No control valve sign on sprinkler system ‘Previous Deficiency’
1.9 8/22/24 1 X No hydraulic signage ‘Previous Deficiency’
1.1 8/22/24 1 X Missing Main Drain sign or sticker on Riser
1.5 8/22/24 1 X Riser gauge expired (1995) – replace 1 qty wet gauge
California Code of Regulations – Title 19 Inspection, Testing, and Maintenance
Quarterly and Annual Report
Address VAQ 049 Residence Valley Job # SV2407120072
Deficiencies and Comments (cont.)
Indicate all equipment, devices and parts that were repaired or replaced
1.12 8/22/24 1 X Missing Spare Box & wrench for ½” 155* Semi White RES Pendants in spare head box & spares (3 qty ½” 155* RES White Pendants
1.19&2.2 8/22/24 1 X Recalled Central sprinklers – replace 9 qty downstairs & 4 upstairs – ½” 155* RES Pendants
Check here if additional Deficiencies and Comments are listed on Form AES 9. Number attached: 0
See Correction Form AES 10 for corrected deficiencies. Number attached: 0
I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.
Quarter 1st – Annual 2nd – Annual 3rd – Annual 4th – Annual
Date 8/22/2024
Name: Yosemite National Park Occupancy/Use:
Address: VAQ 062 Residence Valley Construction Type:
City: Yosemite National Park No. Stories:
ZIP: 95389 Year Constructed:
Contact:
Tim Modjeski
303-819-9916
Contractor Information: Number of System Risers: 1
Name: HCI Systems, Inc.
Address: 3742 W. Gettysburg Ave Ste. 102
X Owner Date:
City: Fresno
Fire AHJ Date: N/A
State: CA
X Contractor Date: 8/22/2024
Telephone: 559-233-2008
CA License #: 905493
1) For specific inspection, testing, and maintenance requirements and information, see NFPA 25, 2011 edition as amended by California Code of Regulations, Title 19, §901 to §906
2) Inspection items may be performed by the owner in
Performed by: Jeremy Johnson
Check box for each system inspected and enter the number of forms used for inspection.
Check boxes (Fail or Pass) to indicate status of inspected system at end of inspection.
Forms included with this Report
NFPA 25
Chapter
Number of Forms N/A Fail* Pass
Automatic Sprinkler System 5 2 X
Standpipe and Hose System 6 0
Private Water Supply System 7 0
Fire Pump 8 0
Water Storage Tank 9 0
Water Spray System 10 0
Foam Water Sprinkler System 11 0
Water Mist System 12 0
Concerns that are Not Deficiencies (i.e. Non-Sprinklered Areas) Yes X No
*See “Deficiencies and Comments” section at end of each respective form.
California Code of Regulations – Title 19
Inspection, Testing, and Maintenance Quarterly and
Address VAQ 062 Residence Valley Address 3742 W. Gettysburg Ave Ste. 102
City Fresno St. CA Zip 93722
City Yosemite National Park License # 905493 Phone 559-233-2008
Contact Person Tim Modjeski SFM Job # SV2407120072
Phone 303-819-9916 CSLB Misc.
Riser Information Main Drain Test (Annual)
Riser No.
Location Riser
Diameter Main Drain Diameter
Initial Static Pressure
Residual Pressure
Final Static Pressure
WF
sec
P,F, N/A
1 Water Heater Closet by Back Door 1” 1” 95 30 80 F P
This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached 1
I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not applicable
Item Description NFPA 25 CA ed.
1.1 I Control Valves – Identification Sign 13.3.1 F
1.2 I Control Valves – Inspection 13.3.2 P
1.3 I Waterflow Alarm Devices 5.2.5 P
1.4 I Supervisory Devices 5.2.5 N/A
1.5 I Gauges (Wet Pipe Systems) 5.2.4.1 F
1.6 I Enter Water Supply Pressure Below Riser Check 5.2.4.1 psi psi N/A psi psi
1.7 I Enter Water Supply Pressure Above Riser Check 5.2.4.1 psi psi 95 psi psi
1.8 I Pressure Readings Acceptable 5.2.4.1 P
1.9 I
Hydraulic Design Information Sign (For hydraulically Designed Systems)
5.2.6 F
1.10 I
General Information Sign (Not Required for System prior to 2007 Edition of NFPA 13)
5.2.8 N/A
1.11 I Heat Tape 5.2.7 N/A
1.12 I Spare Sprinklers 5.2.1.4 F
1.13 I Fire Department Connections 13.7 N/A
1.14 I Alarm Valves – Exterior Inspection 13.4.1 P
1.15 I Pressure Reducing Valves 13.5.1.1 P
1.16 I Backflow Preventers 13.6.1 N/A
1.17 I Small Hose Connections – Hose Valve*
5.1.6, 13.5.2
13.5.5.1 N/A
1.18 I PRV – Fire Sprinkler Systems 13.5.1.1 N/A
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III
California Code of Regulations – Title 19 Inspection, Testing, and Maintenance
Quarterly and Annual Report
Address VAQ 062 Residence Valley Job # SV2407120072
I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not applicable
Item Description
NFPA 25
CA ed.
Referenc e
8/22/24 Comments Only P,F,N/A
1.19 I Sprinklers 5.2.1 F
1.20 I Buildings (Freeze Protection) 4.1.1.1 Owner’s Responsibility P
1.21 I Pipe and Fittings 5.2.2 P
1.22 I Hangers 5.2.3 P
1.23 I Seismic Braces 5.2.3 P
2.1 T
Field Service Test Required (Send Report to Fire Code Official)
5.3.1 If REQUIRED, Enter “F” until results are
returned from Lab.
NA
2.2 T
Recalled Sprinklers If not present = Pass; If present = Fail
Title 19 904.1(c)
F
2.3 T
Water Flow Alarm Devices 90 sec. maximum – (Enter Time)
5.3.3 13.2.6
F
2.4 T
Main Drain Test (Enter Data on Page 1 of this Form)
13.2.5 13.3.3.4
P
2.5 T Control Valve – Position 13.3.3.2 N/A
2.6 T Control Valve – Operation 13.3.3.1 N/A
2.7 T Supervisory Devices 13.3.3.5 N/A
2.8 T Backflow Preventer Assemblies 13.6.2 N/A
2.9 T
Small Hose Connections* W/PRV Hose Valves – Partial Flow Test
13.5.2.3 13.5.3.3
N/A
2.10 T PRV – Fire Sprinkler Systems 13.5.1.3 N/A
3.1 M Control Valves 13.3.4 N/A
3.2 M Small Hose Connections* 13.5.6.3 N/A
3.3 M
Obstruction Investigation required (If “Yes”, see Deficiencies and Comments Section for Results.)
14.3 Yes
No N/A
3.4 M System Returned to Service 4.5.3
Yes
No P
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III
Deficiencies and Comments
Indicate all equipment, devices and parts that were repaired or replaced
2.3 8/22/24
1 X No Waterflow alarm while testing – replace waterflow device 1”
1.1 8/22/24
1 X No control valve sign on sprinkler system ‘Previous Deficiency’
1.9 8/22/24
1 X No hydraulic signage ‘Previous Deficiency’
1.1 8/22/24
1 X Missing Main Drain sign or sticker on Riser
1.5
1 X Riser gauge expired (1994) – replace 1 qty wet gauge
California Code of Regulations – Title 19 Inspection, Testing, and Maintenance
Quarterly and Annual Report
Address VAQ 062 Residence Valley Job # SV2407120072
Deficiencies and Comments (cont.)
Indicate all equipment, devices and parts that were repaired or replaced
1.12 8/22/24 1 X Missing Spare Box & wrench for ½” 155* Semi White RES Pendants in spare head box & spares (3 qty ½” 155* RES White Pendants
1.19&2.2 8/22/24 1 X Recalled Central sprinklers – replace 12 qty total – ½” 155* RES White Pendants
Check here if additional Deficiencies and Comments are listed on Form AES 9. Number attached: 0
See Correction Form AES 10 for corrected deficiencies. Number attached: 0
I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.
Quarter 1st – Annual 2nd – Annual 3rd – Annual 4th – Annual
Date 8/22/2024
Name: Nurses Dorm
Address: VaQ 0064 requirements and information, see NFPA 25, 2011
Forms Included with this Report
NFPA 25
Chapter
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and
Building Nurses Dorm
Address VaQ 0064
Phone 303-819-9916 CSLB Misc.
Riser Information Main Drain Test (Annual)
Riser No.
Location Riser
Diameter Main Drain Diameter
Initial Static Pressure
Residual Pressure
Final Static Pressure
1 Apartment G kitchen closet 1” 1” 55 10 45 P
This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached
I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable
Item Description NFPA 25 CA ed.
Reference
Date Date Date Date
8/22/24
1.1 I Control Valves – Identification Sign 13.3.1 F
1.2 I Control Valves – Inspection 13.3.2 P
1.3 I Waterflow Alarm Devices 5.2.5 P
1.4 I Supervisory Devices 5.2.5 N/A
1.5 I Gauges (Wet Pipe Systems) 5.2.4.1 F
1.6 I Enter Water Supply Pressure Below Riser Check 5.2.4.1 psi psi N/A psi psi
1.7 I Enter Water Supply Pressure Above Riser Check 5.2.4.1 psi psi 55 psi psi
1.8 I Pressure Readings Acceptable 5.2.4.1 P
1.9 I
Hydraulic Design Information Sign (For Hydraulically Designed Systems) 5.2.6
N/A
1.10 I
General Information Sign
1.13 I Fire Department Connections 13.7 N/A
1.14 I Alarm Valves – Exterior Inspection 13.4.1 N/A
1.15 I Pressure Reducing Valves 13.5.1.1 N/A
1.16 I Backflow Preventers 13.6.1 P
1.17 I Small Hose Connections - Hose Valve*
5.1.6, 13.5.2
13.5.5.1 N/A
1.18 I PRV – Fire Sprinkler Systems 13.5.1.1 N/A
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III standpipe
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and
Address VaQ 0064 Job # SV2407120072
Reference Date Comments Only P,F,N/A
1.19 I Sprinklers 5.2.1 8/22/24 P
1.20 I Buildings (Freeze Protection) 4.1.1.1 8/22/24 Owner’s Responsibility P
1.21 I Pipe and Fittings 5.2.2 8/22/24 P
1.22 I Hangers 5.2.3 8/22/24 P
1.23 I Seismic Braces 5.2.3 8/22/24 P
2.1 T
Field Service Test Required (Send Report to Fire Code Official)
5.3.1 If REQUIRED, Enter 'F' until results
are returned from Lab N/A
2.2 T
Recalled Sprinklers
Water Flow Alarm Devices 90 sec. maximum - (Enter Time ) 5.3.3
13.2.6 8/22/24 4 sec. F
2.4 T
Main Drain Test (Enter Data on Page 1 of this Form)
2.6 T Control Valve – Operation 13.3.3.1 8/22/24 P
2.7 T Supervisory Devices 13.3.3.5 N/A
2.8 T Backflow Preventer Assemblies 13.6.2 N/A
2.9 T
Small Hose Connections* w/PRV Hose Valves – Partial Flow Test
N/A
3.4 M System Returned to Service 4.5.3 8/22/24
Yes No
P
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III standpipe
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and
Address VaQ 0064 Job # SV2407120072
1.12 8/22/24 1 X Socket style wrench missing for TY5231 heads in spare head box.
1.5 8/22/24 1 X UL listed fire protection gauge on riser out dated.
1.1 8/22/24 1 X Add signage to riser: 4 Control Valve, 1 911 bell, & 1 Test/ Drain.
2.3 8/22/24 1 X Waterflow time 4 secs – adjust waterflow time 30-90 seconds.
X Inspectors Test Valve & Riser located bottom floor water heater closet.
See Correction Form AES 10 for corrected deficiencies.
I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.
Check box if Annual Inspection, Testing & Maintenance Items are Completed in the Indicated Quarter
Quarter 1st - Annual 2nd - Annual 3rd - Annual 4th - Annual
Date 8/22/24
NFPA25 as amended by CCR, Title 19
Property Information:
Name:
VaQ 0598 YNP Exploration Center Occupancy/Use: R1
Address: Valley Construction Type: Type III-A
City: Yosemite, CA No. Stories: 1
ZIP: 95389 Year Constructed:
Contractor Information: Number of System Risers 1
Name:
Owner Date: 8/22/2024
Address Fire AHJ Date:
City: Contractor Date:
State: NOTES:
1) For specific inspection, testing, and maintenance requirements and information, see NFPA 25, 2011
§904.1(a)
Telephone:
CA License#: 905493
Job #: SV2407120072
Performed by: Jeremy Johnson & Donavan
Check box for each system inspected and enter the number of forms used for inspection. Check boxes (Fail or Pass) to indicate status of inspected system at end of inspection.
Forms Included with this Report NFPA 25 Chapter Number of Forms N/A Fail* Pass
Automatic Sprinkler System 5 1
Standpipe and Hose System 6
Private Water Supply System 7
Fire Pump 8
Water Storage Tank 9
Water Spray System 10
Foam Water Sprinkler System 11
Water Mist Systemz 12
Fire Sprinkler System
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and Annual Report
Building VaQ 0598 YNP Exploration Center
Address Valley
City Yosemite, CA License # 905493 Contact Jeff McBride SFM Job # SV2407120072
Phone 410-668-8000 Ext 1087 CSLB Misc.
Riser Information Main Drain Test (Annual)
Riser No. Location Riser
Diameter Main Drain Diameter
Initial Static Pressure
Residual Pressure
Final Static Pressure P,F,N/A
1 INSIDE BLDG. 2 ½” 1 ¼” 65 35 55 P
This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached
Description NFPA 25 CA ed.
Date Date Date Date 8/22/24
1.1 I Control Valves – Identification Sign 13.3.1 P
1.2 I Control Valves – Inspection 13.3.2 P
1.3 I Waterflow Alarm Devices 5.2.5 P
1.4 I Supervisory Devices 5.2.5 P
1.5 I Gauges (Wet Pipe Systems) 5.2.4.1 F
1.6 I Enter Water Supply Pressure Below Riser Check 5.2.4.1 psi psi * psi psi
1.7 I Enter Water Supply Pressure Above Riser Check 5.2.4.1 psi psi 65 psi psi
1.8 I Pressure Readings Acceptable 5.2.4.1 P
1.9 I Hydraulic Design Information Sign
(For Hydraulically Designed Systems) 5.2.6 P
1.10 I
General Information Sign (Not Required for System prior to 2007 Edition of NFPA 13)
5.2.8 N/A
1.11 I Heat Tape 5.2.7 N/A
1.12 I Spare Sprinklers 5.2.1.4 P
1.13 I Fire Department Connections 13.7 P
1.14 I Alarm Valves – Exterior Inspection 13.4.1 N/A
1.15 I Pressure Reducing Valves 13.5.1.1 N/A
1.16 I Backflow Preventers 13.6.1 N/A
1.17 I Small Hose Connections - Hose Valve* 5.1.6, 13.5.2
13.5.5.1 N/A
1.18 I PRV – Fire Sprinkler Systems 13.5.1.1 N/A
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III standpipe
Fire Sprinkler System
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and Annual Report
Name J.Johnson
Address Valley Job # SV2407120072
City Yosemite, CA Misc.
I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable
Item Description NFPA 25 CA ed.
Reference Date Comments Only P,F,N/A
1.19 I Sprinklers 5.2.1 8/22/24 P
1.20 I Buildings (Freeze Protection) 4.1.1.1 Owner’s Responsibility N/A
1.21 I Pipe and Fittings 5.2.2 P
1.22 I Hangers 5.2.3 P
1.23 I Seismic Braces 5.2.3 P
2.1 T Field Service Test Required (Send
Report to Fire Code Official) 5.3.1 If REQUIRED, Enter 'F' until results are returned from Lab N/A
2.2 T Recalled Sprinklers
If not present = Pass; If present = Fail Title 19 904.1(c) N/A
2.3 T Water Flow Alarm Devices 90
sec. maximum - (Enter Time )
5.3.3 13.2.6
38 sec. P
2.4 T Main Drain Test
(Enter Data on Page 1 of this Form)
13.2.5 13.3.3.4
P
2.5 T Control Valve - Position 13.3.3.2 P
2.6 T Control Valve – Operation 13.3.3.1 P
2.7 T Supervisory Devices 13.3.3.5 P
2.8 T Backflow Preventer Assemblies 13.6.2 N/A
2.9 T Small Hose Connections* w/PRV Hose
Valves – Partial Flow Test
13.5.2.3 13.5.3.3
N/A
2.10 T PRV – Fire Sprinkler Systems 13.5.1.3 N/A
3.1 M Control Valves 13.3.4 P
3.2 M Small Hose Connections* 13.5.6.3 N/A
3.3 M
Obstruction Investigation required (If “Yes”, see Deficiencies and Comments Section for Results.)
14.3 Yes
No N/A
3.4 M System Returned to Service 4.5.3 Yes
No P
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III standpipe
Fire Sprinkler System
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and Annual Report
Name J.Johnson
Address Valley Job # SV2407120072
City Yosemite, CA Misc.
*****ANNUAL SPRINKLER INSPECTION*****
1.5 8/22/24 1 X RISER GAUGE DATED:2015 NEEDS TO BE REPLACED
Notes:
See Correction Form AES 10 for corrected deficiencies.
I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.
Check box if Annual Inspection, Testing & Maintenance Items are Completed in the Indicated Quarter
Quarter 1st - Annual 2nd - Annual 3rd - Annual 4th - Annual
Date 8/22/2024
Address: VaQ 0003 requirements and information, see NFPA 25, 2011
Forms Included with this Report
NFPA 25
Chapter
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and
Address VaQ 0003
Phone 303-819-9916 CSLB Misc.
Riser Information Main Drain Test (Annual)
Riser No.
Location Riser
Diameter Main Drain Diameter
Initial Static Pressure
Residual Pressure
Final Static Pressure
1 Laundry Room 1” 1” 84 10 66 P
This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached
I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable
Item Description NFPA 25 CA ed.
Reference
Date Date Date Date
8/22/24
1.1 I Control Valves – Identification Sign 13.3.1 F
1.2 I Control Valves – Inspection 13.3.2 P
1.3 I Waterflow Alarm Devices 5.2.5 P
1.4 I Supervisory Devices 5.2.5 N/A
1.5 I Gauges (Wet Pipe Systems) 5.2.4.1 F
1.6 I Enter Water Supply Pressure Below Riser Check 5.2.4.1 psi psi N/A psi psi
1.7 I Enter Water Supply Pressure Above Riser Check 5.2.4.1 psi psi 84 psi psi
1.8 I Pressure Readings Acceptable 5.2.4.1 P
1.9 I
Hydraulic Design Information Sign (For Hydraulically Designed Systems) 5.2.6
N/A
1.10 I
General Information Sign
1.13 I Fire Department Connections 13.7 N/A
1.14 I Alarm Valves – Exterior Inspection 13.4.1 N/A
1.15 I Pressure Reducing Valves 13.5.1.1 N/A
1.16 I Backflow Preventers 13.6.1 N/A
1.17 I Small Hose Connections - Hose Valve*
5.1.6, 13.5.2
13.5.5.1 N/A
1.18 I PRV – Fire Sprinkler Systems 13.5.1.1 N/A
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III standpipe
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and
Address VaQ 0003 Job # SV2407120072
Reference Date Comments Only P,F,N/A
1.19 I Sprinklers 5.2.1 8/22/24 P
1.20 I Buildings (Freeze Protection) 4.1.1.1 8/22/24 Owner’s Responsibility P
1.21 I Pipe and Fittings 5.2.2 8/22/24 F
1.22 I Hangers 5.2.3 8/22/24 P
1.23 I Seismic Braces 5.2.3 8/22/24 P
2.1 T
Field Service Test Required (Send Report to Fire Code Official)
5.3.1 If REQUIRED, Enter 'F' until results
are returned from Lab N/A
2.2 T
Recalled Sprinklers
Water Flow Alarm Devices 90 sec. maximum - (Enter Time ) 5.3.3
13.2.6…
This is the start of the file's text. The full file is on GovTribe.