B08_Attachment_6_Fire_Inspection_Documentation_0001.pdf
PDF 2 MB Posted
- Attached to
- YOSE-FIRE PROTECTION SYSTEM TESTING Federal contract opportunity
- Solicitation number
- 140P8525Q0037
About this file
These are fire protection system inspection and maintenance reports for multiple facilities in Yosemite National Park, conducted by Granite Fire Protection, Inc. on August 12, 2024. The documents cover inspections of various fire suppression systems including water spray fixed systems, wet pipe fire sprinkler systems, and dry chemical pre-engineered fire extinguishing systems at locations such as the Yosemite Museum, Ranger Station house, 6160A Duplex House, and Yosemite NP Maintenance facility.
The inspection reports detail comprehensive evaluations of system components, identifying several maintenance requirements and deficiencies. Key findings include the need to replace high-pressure hoses, out-of-date gauges, nitrogen bottles, sprinklers with corrosion, fire pumps with internal seal leaks, and addressing issues like freeze protection. Most systems were partially or fully functional, with specific recommendations for repairs and replacements to ensure continued operational readiness of the fire protection infrastructure across these Yosemite National Park facilities.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P8525Q0037_Amd_0001.pdf | ||
| B08_Attachment_5_Fire_Inspection_Documentation_0001.pdf | ||
| B08_Attachment_4_Fire_Inspection_Documentation_0001.pdf | ||
| B08_Attachment_3_Wage_Determination_2015-5661.pdf | ||
| Sol_140P8525Q0037.pdf | ||
| B08_Attachment_2_System_Inventory-FY_25.xlsx | XLSX spreadsheet | |
| B08_Attachment_1_SOW_Fire_Suppression_Inspection-FY_25.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Inspection, Testing, and Maintenance Cover Sheet NFPA25 as amended by CCR, Title 19
Property Information:
Name: Occupancy/Use:
Address: Construction Type:
City: No. Stories:
ZIP: Year Constructed:
Contact:
Telephone:
Contractor Information: Number of System Risers
Name: Copy sent to:
Address: Owner Date:
City: Fire AHJ Date:
State: Contractor Date:
Telephone:
NOTES:
1) For specific inspection, testing, and maintenance requirements and information, see NFPA 25, 2011 edition as amended by California Code of Regulations, Title 19, §901 to §906.
2) Inspection items may be performed by the owner in accordance with California Code of Regulations, Title 19, §904.1(a)
CA License#:
Job #:
Performed by:
Check box for each system inspected and enter the number of forms used for inspection.
Check boxes (Fail or Pass) to indicate status of inspected system at end of inspection.
Forms Included with this Report NFPA 25 Chapter Number of Forms N/A Fail* Pass
Automatic Sprinkler System 5
Standpipe and Hose System 6
Private Water Supply System 7
Fire Pump 8
Water Storage Tank 9
Water Spray System 10
Foam Water Sprinkler System 11
Water Mist System 12
Concerns that are Not Deficiencies (i.e. Non-Sprinklered Areas) Yes No
*See "Deficiencies and Comments" section at end of each respective form.
AES 1 September 3, 2013
Water Spray Fixed System
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Inspection Report 1 of 4
Property Information Contractor or Licensed Owner Information
Building Name Name
Address Address
City St. Zip
City License # Phone Contact Person SFM Job # Phone CSLB Misc.
This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached:
INSPECTION, TESTING, AND MAINTENANCE
I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable
Item Description NFPA 25 CA ed.
Reference Date Comments Only P,F,N/A
Inspection
1.1 I Backflow Preventer Chapter 13
1.2 I Check Valves Chapter 13
1.3 I Control Valves (Sealed) Chapter 13
1.4 I Control Valves (Locked, Supervised) Chapter 13
1.5 I Deluge Valve
10.2.2, Chapter 13
1.6 I Detection Systems NFPA 72
1.7 I Detector Check Valves Chapter 13
1.8 I Drainage 10.2.8
1.9 I Electric Motor 10.2.9
Chapter 8
1.10 I Engine Drive 10.2.9
Chapter 8
1.11 I Fire Pump 10.2.9
Chapter 8
1.12 I Fittings 10.2.4, 10.2.4.1
1.13 I Fittings (Rubber Gasketed) 10.2.3.1, Annex
1.14 I Gravity Tanks 10.2.10, Chapter 9
1.15 I Hangers 10.2.4.2
1.16 I Heat (Deluge Valve House) 10.2.1.5
Chapter 13
1.17 I Nozzles
10.2.1.1, 10.2.1.2, 10.2.1.6, 10.2.5.1, 10.2.5.2
1.18 I Pipe
10.2.1.1, 10.2.1.2, 10.2.4, 10.2.4.1,
1.19 I Pressure Tank 10.2.10, Chapter 9
Form AES 7 Sept. 3, 2013
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Inspection Report 2 of 4
Property Information Contractor or Licensed Owner Information
Building Name Name
Address Job #
City
INSPECTION, TESTING, AND MAINTENANCE
I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable
Item Description NFPA 25 CA ed.
Reference Date Comments Only P,F,N/A
1.20 I Steam Driver 10.2.9, Chapter 8
1.21 I Strainers 10.2.7
1.22 I Suction Tanks 10.2.10, Chapter 9
1.23 I Supports
10.2.1.1, 10.2.1.2, 10.2.4.2
1.24 I Water Flow Alarm Devices NFPA 72
1.25 I Water Supervisory Alarm Devices NFPA 72
1.26 I Supervisory Signal Devices
(Except Valve Supervisory Switches) NFPA 72
1.27 I Water Supply Piping 10.2.6.1
10.2.6.2
1.28 I UHSWSS-Detectors 10.4.2
1.29 I UHSWSS-Controllers 10.4.3
1.30 I UHSWSS-Valves 10.4.4
Test
2.0 T Backflow Preventer Chapter 13
2.1 T Check Valves Chapter 13
2.2 T Control Valves 13.3.3.1
2.3 T Deluge Valve 10.2.2, Chapter 13
2.4 T Detection Systems NFPA 72
2.5 T Detector Check Valve Chapter 13
2.6 T Electric Motor 10.2.0, Chapter 13
2.7 T Engine Drive 10.2.9, Chapter 8
2.8 T Fire Pump 10.2.9, Chapter 8
2.9 T Flushing Connection to Riser
(Part of Annual Test)
10.2.1.3, Section 10.3
2.10 T Gravity Tanks 10.2.10, Chapter 9
2.11 T Main Drain Test 13.3.3.4
2.12 T Manual Release 10.2.1.3, 10.3.6
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Inspection Report 3 of 4
Property Information Contractor or Licensed Owner Information
Building Name Name
Address Job #
City
INSPECTION, TESTING, AND MAINTENANCE
I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable
Item Description NFPA 25 CA ed.
Reference Date Comments Only P,F,N/A
2.13 T Nozzles
10.2.1.3, 10.2.1.6, Section 10.3
2.14 T Pressure Tank Section 10.2, Chapter 9
2.15 T Steam Driver 10.2.9, Chapter 8
2.16 T Strainers 10.2.1.3, 10.2.1.7, 10.2.7
2.17 T Suction Tanks 10.2.10, Chapter 9
2.18 T Water Flow Alarm Chapter 5
2.19 T Valve Supervisory Signal Devices Chapter 13
2.20 T Supervisory Signal Devices
(Except Valve Supervisory Switches) 13.2.6.2
2.21 T Water Spray System Test 10.3, Chapter 13
2.22 T Water Supply Flow Test 7.3.1
2.23 T UHSWSS 10.4
Maintenance
3.0 M Backflow Preventer Chapter 13
3.1 M Check Valves Chapter 13
3.2 M Control Valves 10.2.1.4, Chapter 13
3.3 M Deluge Valve 10.2.2, Chapter 13
3.4 M Detection Systems NFPA 72
3.5 M Detector Check Valve Chapter 13
3.6 M Electric Motor 10.2.9, Chapter 8
3.7 M Engine Drive 10.2.9, Chapter 8
3.8 M Fire Pump 10.2.9, Chapter 8
3.9 M Gravity Tanks 10.2.10, Chapter 9
3.10 M Pressure Tanks 10.2.6, Chapter9
3.11 M Steam Driver 10.2.9, Chapter 8
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Inspection Report 4 of 4
Property Information Contractor or Licensed Owner Information
Building Name Name
Address Job #
City
INSPECTION, TESTING, AND MAINTENANCE
I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable
Item Description NFPA 25 CA ed.
Reference Date Comments Only P,F,N/A
3.12 M Strainers 10.2.1.4, 10.2.1.6, 10.2.7
3.13 M Strainers - Baskets/Screen
10.2.1.4, 10.2.1.7, A10.2.7
3.14 M Suction Tanks 10.2.10, Chapter 9
3.15 M Water Spray System 10.2.1.4, Chapter 13
D = Deficiency C = Comment (Indicate type )
Item Date Riser D C Deficiencies and Comments Indicate all equipment, devices and parts that were repaired or replaced
Check here if additional Deficiencies and Comments are listed on Form AES 9.
See Correction Form AES 10 for corrected deficiencies.
Number attached:
Number attached:
I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.
Print Name
Signature Date
3742 W. Gettysburg Ave., Ste 102 – Fresno CA 93722 – Office (559) 233-2008 – Fax (559) 233-2009
SALES REP K. Hernandez JOB # SV2407120074 SYSTEM LOCATION 10707 Valley Administration
CUSTOMER Yosemite National Park TECHNICIAN Dennis Binion
ADDRESS 4414 Hills Studio CONTACT Tim Modjeski
Call Security Office PHONE 303-819-9916
SYSTEM TYPE: FM200 HALON SAPPHIRE INERGEN PREACTION DATE:
X 8/12/24
CONTROL PANEL
CONTROL PANEL CONDITION INDICATOR LAMPS BATTERIES
Manufacturer/Model Normal Alarm Trouble Power Alarm Trouble Volts AH Pass Fail Date
Pyrotronics F F F F F F None
BATTERY CONDITION: None
MONITORED BY: Central Control TROUBLE ALARM SUPERVISORY DISCHARGE
INITIATING DEVICES
TYPE:
IONIZATION HSSD PHOTOELECTRIC MANUFACTURER MODEL:
F
A = OPERATIONAL B = DIRTY C = PHYSICAL DAMAGE
NOTIFICATION APPLIANCES
TYPE QUANTITY
OPERATES 1ST
ALARM
OPERATES 2ND
ALARM
OPERATES
DURING
DISCHARGE
FUNTIONAL
YES NO
HORN 1
STROBE
BELL
HORN/STROBE
DISCHARGE HEAD
DISCHARGE HEADS MAIN RESERVE
FUNCTIONAL FUNTIONAL
TYPE
YES NO YES NO
Not Connected
SALES REP K. Hernandez JOB # SV2407120074 SYSTEM LOCATION 10707 Valley Administration
CUSTOMER Yosemite National Park TECHNICIAN Dennis Binion
ADDRESS 4414 Hills Studio CONTACT Tim Modjeski
AGENT STORAGE CONTAINERS
SERIAL # PSI
AGENT
WGT
BOTTLE
TYPE
INITIATOR
DATE
DIP TUBE
LEVEL
AMBIENT
TEMP SERIAL # PSI
AGENT
WGT
BOTTLE
TYPE INITIATOR DATE
ATM 4732 380 482 Pyro N/A N/A 73
ATM 4735 380 482 Pyro N/A N/A 73
PARTS REPLACED
PART ID NUMBER QTY I PU SO
DETECTORS
LOCATION MODEL CEIL UFLR ATTIC DUCT
TYPE
LOCATION MODEL CEIL UFLR ATTIC DUCT
TYPE
SMOKE HEAT SMOKE HEAT
Front Room F
Back Room F
Center Room F
Visitor Room F
Entrance Hall F
SALES REP K. Hernandez JOB # SV2407120074 SYSTEM LOCATION 10707 Valley Administration
CUSTOMER Yosemite National Park TECHNICIAN Dennis Binion
ADDRESS 4414 Hills Studio CONTACT Tim Modjeski
Deficiencies and Comments
Indicate all equipment, devices and parts that were repaired or replaced
DEFECTS:
1 Nothing Was tied in, The System was completely deactivated
3 Not tested – tanks (2 qty) need to be Hydro Tested (date on tanks 1984)
SEQUENCE OF OPERATION:
Not tested – tanks need to be Hydro Tested (date on tanks 1984)
Tanks located under building – access is behind the building
ADDITIONAL NOTES:
Covers inside Building with nozzles in each room
Technician Signature Dennis Binion Date 8/12/2024
Inspection, Testing, and Maintenance Cover Sheet NFPA25 as amended by CCR, Title 19
Property Information:
Name: Occupancy/Use:
Address: Construction Type:
City: No. Stories:
ZIP: Year Constructed:
Contact:
Telephone:
Contractor Information: Number of System Risers
Name: Copy sent to:
Address: Owner Date:
City: Fire AHJ Date:
State: Contractor Date:
Telephone:
NOTES:
1) For specific inspection, testing, and maintenance requirements and information, see NFPA 25, 2011 edition as amended by California Code of Regulations, Title 19, §901 to §906.
2) Inspection items may be performed by the owner in accordance with California Code of Regulations, Title 19, §904.1(a)
CA License#:
Job #:
Performed by:
Check box for each system inspected and enter the number of forms used for inspection.
Check boxes (Fail or Pass) to indicate status of inspected system at end of inspection.
Forms Included with this Report NFPA 25 Chapter Number of Forms N/A Fail* Pass
Automatic Sprinkler System 5
Standpipe and Hose System 6
Private Water Supply System 7
Fire Pump 8
Water Storage Tank 9
Water Spray System 10
Foam Water Sprinkler System 11
Water Mist System 12
Concerns that are Not Deficiencies (i.e. Non-Sprinklered Areas) Yes No
*See "Deficiencies and Comments" section at end of each respective form.
AES 1 September 3, 2013
Wet Pipe Fire Sprinkler System
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and Annual Report 1 of 3
Property Information Contractor or Licensed Owner Information
Building Name Name
Address Address
City St. Zip
City License # Phone
Contact Person SFM Job # CSLB Misc.
Riser Information Main Drain Test (Annual) Riser No. Location Riser
Diameter Main Drain Diameter
Initial Static Pressure
Residual Pressure
Final Static Pressure P,F,N/A
This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached
Quarterly Inspections I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable
Item Description NFPA 25 CA ed.
Reference
Date Date Date Date
1.1 I Control Valves – Identification Sign 13.3.1
1.2 I Control Valves – Inspection 13.3.2
1.3 I Waterflow Alarm Devices 5.2.5
1.4 I Supervisory Devices 5.2.5
1.5 I Gauges (Wet Pipe Systems) 5.2.4.1
1.6 I Enter Water Supply Pressure Below Riser Check 5.2.4.1 psi psi psi psi
1.7 I Enter Water Supply Pressure Above Riser Check 5.2.4.1 psi psi psi psi
1.8 I Pressure Readings Acceptable 5.2.4.1
1.9 I Hydraulic Design Information Sign
(For Hydraulically Designed Systems) 5.2.6
1.10 I General Information Sign
(Not Required for System prior to 2007 Edition of NFPA 13) 5.2.8
1.11 I Heat Tape 5.2.7
1.12 I Spare Sprinklers 5.2.1.4
1.13 I Fire Department Connections 13.7
1.14 I Alarm Valves – Exterior Inspection 13.4.1
1.15 I Pressure Reducing Valves 13.5.1.1
1.16 I Backflow Preventers 13.6.1
1.17 I Small Hose Connections - Hose Valve* 5.1.6, 13.5.2
13.5.5.1
1.18 I PRV – Fire Sprinkler Systems 13.5.1.1
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III standpipe systems.
Form AES 2.1 Sept. 3, 2013
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and Annual Report 2 of 3
Property Information Contractor or Licensed Owner Information
Building Name Name
Address Job #
City
ANNUAL INSPECTION, TESTING, AND MAINTENANCE
Include ALL Quarterly Inspections
I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable
Item Description NFPA 25 CA ed.
Reference Date Comments Only P,F,N/A
1.19 I Sprinklers 5.2.1
1.20 I Buildings (Freeze Protection) 4.1.1.1 Owner’s Responsibility
1.21 I Pipe and Fittings 5.2.2
1.22 I Hangers 5.2.3
1.23 I Seismic Braces 5.2.3
2.1 T Field Service Test Required
(Send Report to Fire Code Official) 5.3.1 If REQUIRED, Enter 'F' until results are returned from Lab
2.2 T Recalled Sprinklers
If not present = Pass; If present = Fail
Title 19 904.1(c)
2.3 T Water Flow Alarm Devices
90 sec. maximum - (Enter Time )
5.3.3
13.2.6 sec.
2.4 T Main Drain Test
(Enter Data on Page 1 of this Form)
13.2.5 13.3.3.4
2.5 T Control Valve - Position 13.3.3.2
2.6 T Control Valve – Operation 13.3.3.1
2.7 T Supervisory Devices 13.3.3.5
2.8 T Backflow Preventer Assemblies 13.6.2
2.9 T Small Hose Connections*
w/PRV Hose Valves – Partial Flow Test
13.5.2.3 13.5.3.3
2.10 T PRV – Fire Sprinkler Systems 13.5.1.3
3.1 M Control Valves 13.3.4
3.2 M Small Hose Connections* 13.5.6.3
3.3 M
Obstruction Investigation required (If “Yes”, see Deficiencies and Comments Section for Results.)
14.3 Yes No
3.4 M System Returned to Service 4.5.3
Yes No
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III standpipe systems.
D = Deficiency C = Comment (Indicate type )
Item Date Riser D C Deficiencies and Comments Indicate all equipment, devices and parts that were repaired or replaced
California Code of Regulations - Title 19 Inspection, Testing, and Maintenance
Quarterly and Annual Report 3 of 3
Property Information Contractor or Licensed Owner Information
Building Name Name Address Job #
City
D = Deficiency C = Comment (Indicate type )
Item Date Riser D C Deficiencies and Comments (cont.)
Indicate all equipment, devices and parts that were repaired or replaced
Check here if additional Deficiencies and Comments are listed on Form AES 9.
See Correction Form AES 10 for corrected deficiencies.
Number attached:
Number attached:
I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.
Check box if Annual Inspection, Testing & Maintenance Items are Completed in the Indicated Quarter
Quarter 1st - Annual 2nd - Annual 3rd - Annual 4th - Annual
Date
Print Name
Signature
Fidel Chavez
Form AES 21 Sept. 3, 2013
Dry Chemical Pre-Engineered California Code of Regulations - Title 19 Semi-Annual
Fire Extinguishing System Inspection, Testing, and Maintenance Report
Property Information
Contractor or Licensed Owner Information
Building Name Yosemite NP Maint. Name HCI Systems
Address Tioga Rd Hwy 120 & 140 Address 3742 W Gettysburg Ave, Suite 102
El Portal Battery Storage City Fresno St. CA Zip 93722 City Yosemite NP License # 905493 Phone (559) 233-2008
Contact Person Tim Modjeski SFM Job # SV2407120074
Phone 303-819-9916 CSLB Misc.
System Information
Cylinder Size(s) 70 lb. Last Hydrostatic Test Date(s) 2005 Duct Size(s) 16" x 16" System Location R/S Exterior System Mfr. Pyro-Chem Model # Monarch Protected Area Type Hazmat Storage Dimensions 8' x 24' Fuel/Air Shut Off: Mechanical Electrical
Fixed Temperature Sensing Elements (Such as Fusible Links)
Quantity Temp Mfg Date
Install Quantity
Date Temp
Mfg Date
Install Date
2 280* 2024(NEW) 2024
Inspection, Testing and Maintenance
I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable
Item Description NFPA 17 CA ed.
Reference Date Comments Only P,F,N/A
1.1 I
Manual Actuators are Unobstructed (i.e. Remote Pull Station)
11.2.1.1(2) 8/12/24
P
1.2 I Tamper Indicators & Seals Intact 11.2.1.1(3) 8/12/24
1.3 I Maintenance Tag in Place
11.2.1.1(4)
CCR T-19 §906 8/12/24
1.4 I No Obvious Physical Damage 11.2.1.1(5) 8/12/24 P
1.5 I
Gauge Readings within Proper Limits (Stored Pressure)
11.2.1.1(6) 8/12/24
1.6 I Blow-Off Caps in Place & Undamaged 11.2.1.1(7) 8/12/24
1.7 I
Protected Equipment or Hazard Has Not Been Replaced, Modified or Relocated
11.2.1.1(8) 8/12/24 P
2.1 T
Automatic Detection, Manual Actuation, Shutdowns and Auxiliary Equipment Functioned Correctly 11.3.1.4 8/12/24
P
2.2 T Alarm Signals Functioned Correctly 11.3.1.4 8/12/24 N/A
2.3 T Releasing Devices Operable 11.3.1.4 8/12/24
3.1 M
All Agent Containers within Acceptable Hydrostatic Test Dates 11.5.1(1) 8/12/24
F
3.2 M
All Auxiliary Pressure Containers and/or Hose Assemblies within Acceptable Hydrostatic Test Dates
11.5.1(2)(3) 8/12/24
3.3 M Cartridge Weights within Acceptable Limits 11.3.1.1(2) 8/12/24 P
3.4 M Nozzles are Correct, Clean & Properly Aimed 11.3.1.1(2) 8/12/24 P
3.5 M Expellant Gas containers are Full and Free of Defects 11.3.1.1(2) 8/12/24 P
3.6 M Hose Assemblies Checked 11.3.1.1(2) 8/12/24
N/A
3.7 M Distribution Piping Unobstructed and Contiguous 11.3.1.1(3) 8/12/24 P
Form AES 21 Sept. 3, 2013
Dry Chemical Pre-Engineered California Code of Regulations - Title 19 Semi-Annual
Fire Extinguishing System Inspection, Testing, and Maintenance Report
Property Information
Contractor or Licensed Owner Information
Building Name Yosemite NP Maint. Name HCI Systems
Address Tioga Rd Hwy 120 & 140 Job # SV2407120074
City Yosemite NP
Inspection, Testing, and Maintenance
I = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable
Item
Description NFPA 17 CA ed.
Reference Date Comments Only P,F,N/A
3.8 M
Dry Chemical is Not Caked
(Non-Pressurized) 11.3.1.1(4) 8/12/24
3.9 M No Signs of Corrosion or Damage to the Agent Cylinders 11.3.1.3 8/12/24
3.10 M
Fixed-Temperature Sensing Elements Maintained or Replaced 11.3.2 8/12/24
3.11 M
Dry Chemical is Not Caked (Stored Pressure Tank Every 6 Years) 11.3.1.2 8/12/24
D = Deficiency C = Comment (Indicate type )
Item Date Riser D C Deficiencies and Comments Indicate all equipment, devices and parts that were repaired or replaced
3.1 8/12/24 X
Hydrotest Due on system cylinder
3.2 8/12/24 X 16 gram CO2 Cart. needs to be replaced
No fan shutdowns , need to check with AHJ to find out if fans need to shut down
Check here if additional Deficiencies and Comments are listed on Form AES 9. Number attached:
See Correction Form AES 10 for corrected deficiencies. Number attached:
I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR Title 19 Sections 901 to 906 and that the equipment is fully operable except as noted in the “Deficiencies and Comments” section of this form.
Print Name Dennis Binion
Signature Dennis Binion Date: 8/12/24
| 1336021-YOSE-8-2024-VaB 0576 Valley District Museum.pdf |
| 1335685-YOSE-8-2024-WaB 4414 Hill Studio.pdf |
| 1335428-YOSE-8-2024-MaQ 2000 Res Ranger Station.pdf |
| 1335441-YOSE-8-2024-MaQ 6160 Duplex Rm House.pdf |
| 1336531-YOSE-8-2024-El Portal Battery Storage Bldg.pdf |
| OwnerDate: |
| 0: 08/12/2024 |
| Sprinkler NA: |
| 0: Yes |
| 1: Yes |
| 2: Yes |
| 3: Yes |
| 4: Yes |
| 5: Yes |
| 6: Yes |
| 7: Off |
| Sprinkler Fail: |
| 0: Off |
| 1: Off |
| 2: Off |
| 3: Off |
| 4: Off |
| 5: Off |
| 6: Off |
| 7: Yes |
| Sprinkler Pass: |
| 0: Off |
| 1: Off |
| 2: Off |
| 3: Off |
| 4: Off |
| 5: Off |
| 6: Off |
| 7: Off |
| Building Name: Yosemite Museum |
| ContractorName: Granite Fire Protection, Inc. |
| PropertyAddress: 9037 Village Drive |
| ContractorAddress: PO BOX 1963 |
| ContractorCity: Oakhurst |
| ContractorSTate: CA |
| ZIP: 93644 |
| PropertyCity: Yosemite |
| CALicense: 1088467 |
| ContractorTelephone: 559-676-5094 |
| Contact Person: Carrie |
| CBSFM: Yes |
| SFM License: [A6957] |
| JobNumber: 0824-1201 |
| PropertyPhone: 209-379-1089 |
| CBCSLB: Yes |
| CB 2: |
| 9: Off |
| AES 2: |
| 9 Number: |
| Chapter 13: |
| 0: 08/12/2024 |
| 1: |
| 2: |
| 3: |
| 4: |
| 5: |
| 6: |
| 7: |
| 8: |
| 9: |
| 10: |
| 11: |
| 12: |
| 13: |
| 14: |
| 15: |
| 16: |
| 17: |
| 18: |
| Text10: |
| 0: |
| 1: |
| 2: |
| 3: |
| 4: |
| 5: |
| 6: |
| 7: |
| 8: |
| 9: |
| 10: |
| 11: |
| 12: |
| 13: |
| 14: |
| 15: |
| 16: |
| 17: |
| 18: |
| DD1: |
| 0: [P] |
| 1: [P] |
| 2: [P] |
| 3: [N/A] |
| 4: [N/A] |
| 5: [N/A] |
| 6: [P] |
| 7: [N/A] |
| 8: [P] |
| 9: [F] |
| 10: [F] |
| 11: [P] |
| 12: [P] |
| 13: [P] |
| 14: [P] |
| 15: [N/A] |
| 16: [F] |
| 17: [P] |
| 18: [P] |
| Date8_af_date: |
| 0: 08/12/2024 |
| 1: |
| 2: |
| 3: |
| 4: |
| 5: |
| 6: |
| 7: |
| 8: |
| 9: |
| 10: |
| Comments2: |
| 0: |
| 1: |
| 2: |
| 3: |
| 4: |
| 5: |
| 6: |
| 7: |
| 8: |
| 9: |
| 10: |
| 12: |
| 13: |
| 14: |
| 15: |
| 16: |
| 17: |
| 18: |
| 19: |
| 20: |
| 21: |
| 23: |
| DD2: |
| 0: |
| 0: [N/A] |
| 1: [ P] |
| 2: [N/A] |
| 3: [ P] |
| 4: [ P] |
| 5: [ P] |
| 6: [ P] |
| 7: [ P] |
| 8: [N/A] |
| 9: [N/A] |
| 10: |
| 0: [N/A] |
| 1: [N/A] |
| 13: [ P] |
| 14: [ P] |
| 15: [N/A] |
| 16: [N/A] |
| 17: [N/A] |
| 18: [N/A] |
| 19: [N/A] |
| 20: [ P] |
| 21: |
| 0: [ P] |
| 1: [N/A] |
| 2: [ P] |
23: [ P]
| Date9_af_date: |
| 0: |
| 1: |
| 2: |
| 3: |
| 4: |
| 5: |
| 6: |
| 7: |
| 8: |
| 9: |
| 10: |
| 11: |
| 12: |
| Date3: |
| 0: 08/12/2024 |
| 1: |
| 2: |
| 3: |
| 4: |
| 5: |
| 6: |
| 7: |
| 8: |
| 9: |
| 10: |
| 11: |
| 12: |
| 13: |
| 14: |
| 15: |
| 16: |
| 17: |
| 18: |
| 0: |
| 1: |
| 2: |
| 3: |
| 4: |
| Text4: |
| 0: |
| 1: |
| 2: |
| 3: |
| 4: |
| 5: |
| 6: |
| 7: |
| 8: |
| 9: |
| 10: |
| DD3: |
| 0: [F] |
| 1: [F] |
| 2: [N/A] |
| 3: [P] |
| 4: [P] |
| 5: [P] |
| 6: [P] |
| 7: [P] |
| 8: [P] |
| 9: [P] |
| 10: [N/A] |
| 11: [N/A] |
| 12: [P] |
| 13: [P] |
| 14: [N/A] |
| 15: [P] |
| 16: [P] |
| 17: [N/A] |
| 18: |
| 0: [P] |
| 1: [P] |
| 2: [N/A] |
| 3: [N/A] |
| 4: [N/A] |
| Text5: |
| 0: |
| 1: |
| 2: |
| 3: |
| 4: |
| 5: |
| 6: |
| 7: |
| 8: |
| 9: |
| 10: |
| 11: |
| Date2_af_date: |
| 0: 08/12/2024 |
| 1: |
| 2: |
| 3: |
| Text3: |
| 0: |
| 1: |
| 2: |
| 3: |
| DD4: |
| 0: [P] |
| 1: [P] |
| 2: [P] |
| 3: [F] |
| Check Box1: |
| 0: |
| 0: Yes |
| 1: Off |
| 1: |
| 0: Yes |
| 1: Off |
| 2: |
| 0: Yes |
| 1: Off |
| 3: |
| 0: Yes |
| 1: Off |
| 4: |
| 0: Yes |
| 1: Off |
| 5: |
| 0: Yes |
| 1: Off |
| 6: |
| 0: Off |
| 1: Yes |
| 7: |
| 0: Off |
| 1: Yes |
| 8: |
| 0: Off |
| 1: Yes |
| 9: |
| 0: Off |
| 1: Yes |
| 10: |
| 0: Off |
| 1: Yes |
| 11: |
| 0: Off |
| 1: Off |
| 12: |
| 0: Off |
| 1: Off |
| 13: |
| 0: Off |
| 1: Off |
| 14: |
| 0: Off |
| 1: Off |
| ItemRow6: 1.11 |
| DateRow6: |
| RiserRow6: |
| Deficiencies and Comments Indicate all equipment devices and parts that were repaired or replacedRow6: Jockey pump and fire pump have water coming from nitrogen exhaust. |
| ItemRow7: |
| DateRow7: |
| RiserRow7: |
| Deficiencies and Comments Indicate all equipment devices and parts that were repaired or replacedRow7: Replace both filters in vesda systems asap. |
| ItemRow8: |
| DateRow8: |
| RiserRow8: |
| Deficiencies and Comments Indicate all equipment devices and parts that were repaired or replacedRow8: Replace rod and ball float in sup drain that is broken. Made temp repair to drain water. |
| ItemRow9: |
| DateRow9: |
| RiserRow9: |
| Deficiencies and Comments Indicate all equipment devices and parts that were repaired or replacedRow9: Flushed system and all spare water reserve bottles. Done 8-12-24 |
| ItemRow10: |
| DateRow10: |
| RiserRow10: |
| Deficiencies and Comments Indicate all equipment devices and parts that were repaired or replacedRow10: Replaced empty nitrogen bottle with full GFP testing bottle and took for refill. Done 8-12-24 |
| ItemRow11: |
| DateRow11: |
| RiserRow11: |
| Deficiencies and Comments Indicate all equipment devices and parts that were repaired or replacedRow11: Cleaned all strainers and screens. Done 8-12-24 |
| ItemRow12: |
| DateRow12: |
| RiserRow12: |
| Deficiencies and Comments Indicate all equipment devices and parts that were repaired or replacedRow12: |
| ItemRow13: |
| DateRow13: |
| RiserRow13: |
| Deficiencies and Comments Indicate all equipment devices and parts that were repaired or replacedRow13: |
| ItemRow14: |
| DateRow14: |
| RiserRow14: |
| Deficiencies and Comments Indicate all equipment devices and parts that were repaired or replacedRow14: |
| ItemRow15: |
| DateRow15: |
| RiserRow15: |
| Deficiencies and Comments Indicate all equipment devices and parts that were repaired or replacedRow15: |
| CB AES9: Off |
| AES9 Number: |
| CB AES10: Off |
| AES10 Number: |
| SignatureDate: 08/12/2024 |
| PropertyName: Ranger Station house |
| Address 1: 8095 Hetch hetchy rd |
| PropertyZIP: 95389 |
| Contact: Carrie Topper |
| ContactTelephone: 2093791089 |
| DDOccupancyUse: [ ] |
| DDConstructionType: [ ] |
| NumberStories: |
| YrConstructed: |
| Inspector: [Robert Guiliacci] |
| DDOwner: On |
| Fire AHJ: Off |
| AHJDate: |
| Contractor: On |
| ContractorDate: 08/12/2024 |
| AutoSprinkler: Off |
| 5: 0 |
| Standpipe: Off |
| 6: 0 |
| PrivateWater: Off |
| 7: 0 |
| FirePump: Off |
| 8: 0 |
| WaterStorage: Off |
| 9: 0 |
| WaterSpray: Off |
| 10: 0 |
| Foam: Off |
| 11: 0 |
| WaterMist: On |
| 12: 0 |
| Concerns: Off |
| Yes: Off |
| No: On |
| PropertyAddress2: |
| Contact PersonRow1: |
| License: 1088467 |
| SFMCheckBox: Yes |
| SFM: A6957 |
| CSLBCheckBox: Yes |
| CSLB: C-16 |
| Address: 42484 CA-41 |
| ContractCity: Oakhurst |
| ContractState: CA |
| ContractZIP: 93644 |
| Phone: 559-676-5094 |
| Misc: Annual Inspection |
| Riser NoRow1: 1 |
| LocationRow1: RISER ROOM IN NE INTERIOR BEDROOM |
| Riser DiameterRow1: 1" |
| Main Drain DiameterRow1: 1/2" |
| Initial Static PressureRow1: 28 |
| Residual PressureRow1: 45 |
| Final Static PressureRow1: 45 |
| PFNARow1: F |
| Riser NoRow2: |
| LocationRow2: |
| Riser DiameterRow2: |
| Main Drain DiameterRow2: |
| Initial Static PressureRow2: |
| Residual PressureRow2: |
| Final Static PressureRow2: |
| PFNARow2: |
| Riser NoRow3: |
| LocationRow3: |
| Riser DiameterRow3: |
| Main Drain DiameterRow3: |
| Initial Static PressureRow3: |
| Residual PressureRow3: |
| Final Static PressureRow3: |
| PFNARow3: |
| Riser NoRow4: |
| LocationRow4: |
| Riser DiameterRow4: |
| Main Drain DiameterRow4: |
| Initial Static PressureRow4: |
| Residual PressureRow4: |
| Final Static PressureRow4: |
| PFNARow4: |
| Riser NoRow5: |
| LocationRow5: |
| Riser DiameterRow5: |
| Main Drain DiameterRow5: |
| Initial Static PressureRow5: |
| Residual PressureRow5: |
| Final Static PressureRow5: |
| PFNARow5: |
| RiserCheckBox: Off |
| Number2: |
| 9FormsAttached: |
| Date1stQtr: 08/13/24 |
| Date1331: P |
| Date1332: P |
| Date525: F |
| Date525_5: N/A |
| Date5241: P |
| 1: |
| 61stQtr: 0 |
| 621stQtr: 45 |
| 62ndQtr: |
| 622ndQtr: |
| 63rdQtr: |
| 623rdQtr: |
| 64thQtr: |
| 624thQtr: |
| psi5241: P |
| psi137: N/A |
| psi1341: N/A |
| psi13511: N/A |
| psi1361: P |
| psi516 1352 13551: N/A |
| psi13511_5: N/A |
| Date2ndQtr: |
| Date1331_2: |
| Date1332_2: |
| Date525_2: |
| Date525_6: |
| Date5241_2: |
| psi5241_2: |
| psi526_2: |
| psi528_2: |
| psi527_2: |
| psi5214_2: |
| psi137_2: |
| psi1341_2: |
| psi13511_2: |
| psi1361_2: |
| psi516 1352 13551_2: |
| psi13511_6: |
| Date3rdQtr: |
| Date1331_3: |
| Date1332_3: |
| Date525_3: |
| Date525_7: |
| Date5241_3: |
| psi5241_3: |
| psi526_3: |
| psi528_3: |
| psi527_3: |
| psi5214_3: |
| psi137_3: |
| psi1341_3: |
| psi13511_3: |
| psi1361_3: |
| psi516 1352 13551_3: |
| psi13511_7: |
| psi526: N/A |
| psi528: N/A |
| psi527: N/A |
| psi5214: P |
| Date4thQtr: |
| Date1331_4: |
| Date1332_4: |
| Date525_4: |
| Date525_8: |
| Date5241_4: |
| psi5241_4: |
| psi526_4: |
| psi528_4: |
| psi527_4: |
| psi5214_4: |
| psi137_4: |
| psi1341_4: |
| psi13511_4: |
| psi1361_4: |
| psi516 1352 13551_4: |
| psi13511_8: |
| AddressRow1: |
| City: GROVELAND, CA 95321 |
| Name: Granite Fire Protection, Inc. |
| Job: 1023-0302 |
| Date521: 08-13-24 |
| Comments Only521: |
| PFNA521: F |
| Date4111: |
| PFNAOwners Responsibility: P |
| Date522: |
| Owners Responsibility522: |
| PFNA522: P |
| Date523: |
| Owners Responsibility523: |
| PFNA523: P |
| Date523_2: |
| Owners Responsibility523_2: |
| PFNA523_2: P |
| Date531: |
| PFNAIf REQUIRED Enter F until results are returned from Lab: N/A |
| DateTitle 19 9041c: |
| If REQUIRED Enter F until results are returned from LabTitle 19 9041c: |
| PFNATitle 19 9041c: P |
| 533 1326: |
| Text1: |
| sec: F |
| 1325 13334: |
| Text2: |
| 13332: |
| 13331: |
| Text6: |
| Text7: |
| 13335: |
| Text8: |
| Text9: N/A |
| 1362: |
| Text11: P |
| 13523 13533: |
| Text12: |
| Text13: P |
| 13513: |
| Text14: |
| Text15: N/A |
| 1334: |
| Text16: |
| Text17: P |
| 13563: |
| Text18: |
| Text19: N/A |
| 143: |
| Group3: |
| 3: Choice2 |
| 4: Choice1 |
| Yes No: N/A |
| 453: |
| Yes No_2: P |
| ItemRow1: 1.10 |
| DateRow1: 08-12-2024 |
| RiserRow1: |
| DefDC: Choice1 |
| Deficiencies and Comments Indicate all equipment devices and parts that were repaired or replacedRow1: Replace (19) 3,000LB high pressure hoses that have exceeded 10year life expectancy. |
| ItemRow2: 3.15 |
| DateRow2: |
| RiserRow2: |
| DefDC2: Choice1 |
| Deficiencies and Comments Indicate all equipment devices and parts that were repaired or replacedRow2: Replace (2) out of date gauges 3,500 psi |
| ItemRow3: 2.14 |
| DateRow3: |
| RiserRow3: |
| DefDC3: Choice2 |
| Deficiencies and Comments Indicate all equipment devices and parts that were repaired or replacedRow3: Hydro and refill nitrogen bank 16 (300LB) bottles that have exceeded 10 years. |
| ItemRow4: 1.17 |
| DateRow4: |
| RiserRow4: |
| DefDC4: Choice2 |
| Deficiencies and Comments Indicate all equipment devices and parts that were repaired or replacedRow4: Replace (11) white, (4) brown, and (4) silver sprinklers that have corrosion from leaking seats. |
| ItemRow5: 1.11 |
| DateRow5: |
| RiserRow5: |
| DefDC5: Choice2 |
| Deficiencies and Comments Indicate all equipment devices and parts that were repaired or replacedRow5: Replace Fire pump and jockey pump that are leaking from internal seals |
| ItemRow1_2: |
| DateRow1_2: 08/13/24 |
| RiserRow1_2: 1 |
| DefDC6: Choice2 |
| Deficiencies and Comments cont Indicate all equipment devices and parts that were repaired or replacedRow1: 3) 300LB NITROGEN BOTTLES ON SYSTEM WITH (1) SPARE IN ROOM |
| ItemRow2_2: |
| DateRow2_2: |
| RiserRow2_2: |
| DefDC7: Choice2 |
| Deficiencies and Comments cont Indicate all equipment devices and parts that were repaired or replacedRow2: SYSTEM HAS 300GAL WATER/ ANTIFREEZE PLASTIC STORAGE TANK |
| Text21: |
| Text22: |
| Text23: |
| DefDC8: Choice2 |
| Text26: HI PSI NITROGEN SUPPLY HOSE REPLACED 2022 |
| Text27: |
| Text28: |
| Text29: |
| DefDC9: Choice2 |
| Text32: NITROGEN BOTTLES AT 2,100PSI |
| Text33: |
| Text34: |
| Text35: |
| DefDC10: Choice2 |
| Text38: ANTIFREEZE SYSTEM TESTED MIX AND FOUND FREEZE POINT AT 18* F |
| Text39: |
| Text40: |
| Text41: |
| DefDC11: Choice2 |
| Text44: SYSTEM NITROGEN REGULATED AT 45PSI |
| Text45: |
| Text46: |
| Text47: |
| DefDC12: Choice2 |
| Text50: REPLACE PUMP AND TANK ASAP. |
| Text51: |
| Text52: |
| Text53: |
| DefDC13: Choice2 |
| Text56: MANUAL PUMP ONLY ACTIVATED WITH BLK TOGGLE SWITCH LOCATED ON TOP OF PUMP |
| Text57: |
| Text58: |
| Text59: |
| DefDC14: Off |
| Text62: |
| Text63: |
| Text64: |
| Text65: |
| DefDC15: Off |
| Text68: |
| Text69: |
| Text70: |
| Text71: |
| DefDC16: Off |
| Text74: |
| Text75: |
| Text76: |
| Text77: |
| DefDC17: Off |
| Text80: |
| Text81: |
| Text82: |
| Text83: |
| DefDC18: Off |
| Text86: |
| Text87: |
| Text88: |
| Text89: |
| DefDC19: Off |
| Text92: |
| Text93: |
| Text94: |
| Text95: |
| DefDC20: Off |
| Text98: |
| Text20: |
| Text99: |
| Text100: |
| DefDC21: Off |
| Text103: |
| Text104: |
| Text105: |
| Text106: |
| DefDC22: Off |
| Text109: |
| Text110: |
| Text111: |
| Text112: |
| DefDC23: Off |
| Text115: |
| Text116: |
| Text117: |
| Text118: |
| DefDC24: Off |
| Text121: |
| Text122: |
| Text123: |
| Text124: |
| DefDC25: Off |
| Text127: |
| Text128: |
| Text129: |
| Text130: |
| DefDC26: Off |
| Text133: |
| Text134: |
| Text135: |
| Text136: |
| DefDC27: Off |
| Text139: |
| CheckboxDeficiencies: Off |
| DeficiencyNumberAttached: |
| CheckboxAES10: Off |
| AES10Number Attached: |
| CB1stAnnual: Yes |
| CB2ndAnnual: Off |
| CB3rdAnnual: Off |
| CB4thAnnual: Off |
| Date: 08/13/24 |
| Text144: |
| Text147: |
| Text150: |
| Print Name: Robert Guiliacci |
| Text145: |
| Text148: |
| Text151: |
| Signature: |
| Text146: |
| Text149: |
| Text152: |
File details come from the government source that posted it. Updated .