Attachment_E_Vendor_Questions_and_Clarifications_0001.pdf

PDF 104 KB Posted

Attached to
Outdoor Walk-in Cooler, Olympic NP
Solicitation number
140P8324Q0041
Issued by

About this file

This document is an attachment providing clarifications for Solicitation #140P8324Q0041 for an Outdoor Walk-In Cooler for Olympic National Park. The key details are:

The solicitation is for a new build of an outdoor walk-in cooler, with no demolition involved. The temperature requirements are specified in Section 11 41 24, Part 2.1E. There are no specific equipment brand or type requirements, but the electrical requirements indicate that existing Panel A will supply power to the cooler per manufacturer's requirements. For the base item, the cooler shelter specifications are provided in Section 10 73 23, while for the optional item the drawings provide additional details. The concrete slab requirements are noted in Section 03 30 00, specifying a level and flat surface with no sloping or crowning needed. Overall, this document clarifies technical specifications and requirements for this federal contract opportunity.

View the file

Other files

File Type Posted
Sol_140P8324Q0041_Amd_0002.pdf PDF
Sol_140P8324Q0041_Amd_0001.pdf PDF
Attachment_A_Specifications.pdf PDF
Sol_140P8324Q0041.pdf PDF
Attachment_D_Forms_to_Return_with_Quote.docx DOCX document
Attachment_B_Drawings.pdf PDF
Attachment_C_DOL_Wage_Determination.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RFQ #140P8324Q0041, Outdoor Walk-In Cooler Olympic N.P.

Attachment E: Clarifications

Clarifications for Solicitation #140P8324Q0041

This document provides clarifications to Attachment A, Project Specifications, and Attachment B, Drawings, based on queries submitted during the solicitation phase and/or raised during the site visit. The responses are incorporated into the contract.

1. Confirm there is no demo involved and that this is a new build.

Response: This is a new build and no demolition is involved.

2. What are the temperature requirements for the cooler?

Response: Refer to specification section 11 41 24, Part 2.1E

3. Do you have any equipment requirements? Brands and types: Air cooled/water cooled?

Response: Refer to specification section 11 41 24, Part 2

4. What are the electrical locations and requirements? Will electricity be brought to the cooler or will that need to be supplied and if so where from?

Response: Existing Panel A is shown on the drawings and supplying the cooler with electricity per manufacture’s requirements and any applicable permits is part of the requirements.

5. Do you have any shelter specifications, or are you just wanting it to be covered from weather?

Response: For the Base Item, refer to specification section 10 73 23. For Option Item A, refer to the drawings, sheet 2 of 2

6. Are there any concrete specifications? I.e. Depth?

Response: Refer to the drawing section detail and specification section 03 30 00.

7. Is there any desire to slightly slope the concrete slab or slightly crown?

Response: No, the cooler needs to sit on a level and flat surface. Refer to specification section 03 30 00, Part 3.