Attachment_4_Questions_and_Answers_140P8323Q0073_0001.pdf
PDF 31 KB Posted
- Attached to
- Supply and Deliver Windows, MORA
- Solicitation number
- 140P8323Q0073
About this file
This document contains questions and answers to supplement a solicitation for the supply and delivery of windows for Mount Rainier National Park. The National Park Service seeks windows with pine interiors that do not require sealing. Specifications require low-e glass with a U-factor of 0.29 and a SHGC of 0.25. The solicitation number is 140P8323Q0073 and was issued by the Department of the Interior National Park Service Pacific West Region to procure windows for maintenance, repair and operations uses at Mount Rainier National Park. Bidders must make pen and ink changes to the statement of work where answers herein provide different information.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sol_140P8323Q0073_Amd_0001.pdf | ||
| Attachment_1_Specifications_140P8323Q0073.pdf | ||
| Attachment_3_Forms_to_Return_with_Quote_140P8323Q0073.docx | DOCX document | |
| Sol_140P8323Q0073.pdf | ||
| Attachment_2_Photos_Elevations_140P8323Q0073.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
140P8323Q0073, Amendment 0001 Supply and Deliver Windows
Attachment 4 Questions & Answers (9/6/2023) Mount Rainier National Park
The following are questions/answers to supplement the Statement of Work in the solicitation, and in some cases may provide some different information than what is stated in the Statement of
Work. Where there are differences, quoters shall make pen and ink changes in those sections in the Statement of Work with the information provided in this Q and A.
QUESTION 1: Is interior priming/painting/stain & clear coating required for the pine surfaces?
ANSWER: No sealer is required on the interior pine wood. National Park Service will seal the interiors of the windows.
QUESTION 2: Is a specific Low E type or U-value/SHGC required?
ANSWER: Low E, .29 U factor and .25 SHGC required.