SPALDING SITE

SCALE: 1" = 400'

PROJECT LOCATION

SCALE: 1"= 50'

Digitally signed by Quin Clements Date:

2019.04.30 09:55:04 -07'00'

Digitally signed by Quin Clements Date:

2019.04.30 09:55:28 -07'00'

SCALE IN FEET

10 5 0 10 20

Digitally signed by Quin Clements Date:

09:55:49 -07'00' signed by Quin Clements Date:

2019.04.30 09:56:11

NTS

DEMOLISH ABANDONED AIR COMPRESSOR

NTS

EXISTING TREATMENT SYSTEM

NTS

REMOVE WELL AND BOOSTER PUMP CONTROLS

Digitally signed by Quin Clements Date:

2019.04.30 09:56:33

6" signed by Quin Clements Date:

2019.04.30 09:57:02

Digitally signed by Quin Clements Date: 2019.04.30 09:57:30 -07'00'

SODIUM HYPOCHLORITE

METERING PUMP PULSATRON LPK2 - VVC1

STOCK SOLUTION RAW STRENGTH 12.5%

FEED SOLUTION CONCENTRATION 125,000 PPM

REQUIRED FEED PUMP RATE 0.05 GPH

REQUIRED OUTPUT ADJUSTMENT 37%

METERING PUMP FLOWRANGE 0.001 - 0.13 GPH

RESIDUAL POST FILTRATION ≥ 0.5 PPM

POTASSIUM PERMANGANATE SETTINGS

METERING PUMP PULSATRON LPK2 - PTC1

SAT'D SOLUTION CONCENTRATION 63,000 PPM

REQUIRED FEED PUMP RATE 0.01 GPH

REQUIRED OUTPUT ADJUSTMENT 8%

METERING PUMP FLOW RANGE 0.001 - 0.13 GPH

DOSING LEVEL 0.2 PPM

RAW WATER FLOWRATE 55 GPM

TREATMENT SYSTEM CONTROLLER SETTINGS

TREATMENT CAPACITY 55 GPM

FILTER DIMENSIONS (4) 18" DIA. X 60" TALL

FILTER MEDIA 42" ATEC 741 MEDIA 6.2 FT3 EACH

TOTAL FILTER CAPACITY BEFORE BACKWASH 74,000 GALLONS

BACKWASH RATE PER FILTER 50 GPM

BACKWASH DURATION 5 MINUTES EACH FILTER

TOTAL BACKWASH QUANTITY 1,000 GALLONS

Digitally signed by Quin Clements Date:

2019.04.30 09:57:53

PLAN VIEW

3" BACKWASH LINE

RIGHT SIDE

FILTERS REMOVED

LEFT SIDE

FILTERS REMOVED

3" OUTLET LINE

3" GROOVED CAP

3" GROOVED CAP

3" BACKWASH LINE

3" FLANGE

3" INLET LINE

BY CON

BY CONTRACTOR

TANK AND LEG CUT

AWAY FOR CLARITY

BACKWASH

FRONT ELEVATION

RIGHT ELEVATIONLEFT ELEVATION

3" GROOVED CAP

SHIPPED LOOSE, 60" LONG 3"

BACKWASH ASS'Y WITH METER &

VALVE TO SET BACKWASH TO 50GPM.

ATEC CONTROLLER

CONTRACTOR

3" GROOVED CAP

3" GROOVED CAP

3" GROOVED

CAP

84"

BY

NOTE: CHECK SCALE

SCALE AT 22x34 - 1" = 1'-0"

SCALE AT 11x17 - 1/2" = 1'-0"

SCALE IN FEET

10 2

Digitally signed by Quin Clements Date:

2019.04.30 09:58:14

A

LIFTING LUGS (4) PROVIDED

6" x 4" x 1/4" BOX BEAMS

84"

4-FILTER SKID PLAN

A

SECTION A-A

3/4" DIA. HILTI KWIK BOLTS II

(SEE NOTES 1, 2, AND 3)

1/4" THICK S/S PAD

(SEE NOTE 4)

2" x 8" x 1/2" LIFTING

LUGS WITH 2 1/2" DIA. HOLE

SECTION THROUGH TANK

DEFLECTOR PLATE

(8" DIA. 10Ga S/S)

7 1

(see specifications for coating details)

A-570 CARBON STEEL

60" SIDE SHELL, 1/4" THICK,

18" HEAD, 1/4" CARBON STEEL,

42" ATEC 741 FILTER MEDIA

(20-40 US MESH)

(4) 5" x 3" x 1/4" ANGLE WITH 1" HOLE

METER SOCKET

SIGHT GLASS

3" GATE VALVE

BACKWASH ASSEMBLY

(SHIPPED LOOSE)

3"

ONE REQUIRED

NOTE: WEIGHT OF 4 FILTER SKID;

EMPTY 2,080#

WITH MEDIA AND WATER 7,500±#

(2) 4" x 8" x 1/4" x 18 1/4" LONG FORK

LIFT TUBES AT 36" CENTER TO CENTER

NOTE: CHECK SCALE

SCALE AT 11x17 - 1/2" = 1'-0" SCALE AT 22x34 - 1" = 1'-0"

SCALE IN FEET

0 1

BILL OF MATERIALS

NOTE: QUANTITIES SHOWN ARE FOR (1) ONE TANK

ITEM

Digitally signed by Quin Clements Date:

2019.04.30 09:58:35

PROVIDE MESH

SCREEN SECURED

WITH HOSE CLAMPS

6" AIR-GAP

3" BACKWASH LINE

CENTERED ABOVE

8" PIPE BELOW.

10" PVC PIPE

(4± LF LENGTH)

10" x 6" REDUCER

EXISTING 6" DUCTILE IRON

NTS

AIR-GAP DETAIL

NTS

POTASSIUM PERMANGANATE FEEDER

NTS

FLOW SWITCH

Digitally signed by Quin Clements Date:

09:58:57 -07'00'