The reports cover fire extinguisher inspections, fire alarm system inspections, and wet pipe sprinkler system inspections across multiple buildings at the Pearl Harbor National Memorial location. Key findings include: 50 fire extinguishers passed inspection at the National Memorial with no deficiencies; fire alarm systems at the Admin Offices Building, Building 612 Maintenance, Building D Classrooms, and Museum Exhibits G & H reveal multiple critical deficiencies including expired backup batteries (sealed lead-acid batteries with expired manufacturer date codes), failed speaker/strobe devices, non-operational transmitter communicators, and malfunctioning elevator recall systems. The Admin Offices system specifically shows 9 failed battery components and 1 failed speaker-strobe in the 1st Floor Elevator Lobby. Building D Classrooms experienced transmitter offline conditions and LED control failures. The wet pipe sprinkler systems for Buildings G, H, and I show generally satisfactory conditions with proper valve operations and pressure readings, though several systems lack complete control valve identification signage, and Building I exhibits painted sprinkler heads, missing escutcheons, and discolored bulbs requiring replacement. The Theater Building I system documented flooded crawl spaces preventing heat detector testing and waterflow switch manual resets. All inspections were reviewed by Joe Schranck and submitted by Ron Reano or Eddie Erlandiz of Kinetix Fire, with contact information at 583 Abbott Drive, Broomall, PA 19008.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRE EXTINGUISHER INSPECTION REPORT
www.kinetixfire.com
Date of Inspection: February 2, 2026 Technician: Edward Erlandiz Jr. Title: Technician COF #2023-041 ICC# 9326680 Protected Property Inspection Company
Name: Pearl Harbor National Memorial Name: Kinetix Fire Address: 1 Arizona Memorial Place Address: 583 Abbott Drive City: Honolulu City: Broomall State: HI Zip: 96818 State: PA Zip: 19008 Contact: Luther M. Sargent Contact: Inspection/Sales Department Phone: 808-520-0895 Phone: 877-223-3000
FIRE EXTINGUISHERS INSPECTION
Ext # Serial # Manufacturer Type Location Size Pass/Fail 6-Year
Required Hydro
Required Date of
Manufacture Comments
1 197692 Badger ABC #2 10lbs Pass No No 2008 Serviced October 2024 2 559716 Amerex ABC #3 5lbs Pass No No 2022 Serviced September 2024 3 474978 Amerexl ABC #4 5lbs Pass No No 2007 Serviced September 2024 4 444923 Ansul ABC #5 10lbs Pass No No 2008 Serviced September 2024 5 849191 Buckeye ABC #6 5lbs Pass No No 2009 Serviced September 2024 6 561788 Amerex ABC #7 5lbs Pass No No 2007 Serviced September 2024 7 78290040 Kidde ABC #8 5.5lbs Pass No No 2018 Serviced September 2024 8 853343 First Alert ABC #9 2.5lbs Pass No No 2013 Serviced September 2024 9 617383 Badger ABC #10 5lbs Pass No No 2001 Serviced September 2024
10 559722 Amerex ABC #11 5lbs Pass No No 2007 Serviced September 2024 11 671699 Badger ABC #12 5lbs Pass No No 2000 Serviced September 2024 12 588399 Amerex ABC #13 5lbs Pass No No 2007 Serviced September 2024 13 473495 Amerex ABC #14 5lbs Pass No No 2007 Serviced September 2024 14 885103 Badger ABC #15 5lbs Pass No No 1997 Serviced September 2024 15 571621 Amerex ABC #16 5lbs Pass No No 2007 Serviced September 2024 16 681539 Amerex ABC #17 5lbs Pass No No 2007 Serviced September 2024 17 561793 Amerex ABC #18 5lbs Pass No No 2007 Serviced September 2024 18 466697 Amerex ABC #19 5lbs Pass No No 2007 Serviced September 2024 19 572708 Amerex ABC #20 5lbs Pass No No 2007 Serviced September 2024 20 559719 Amerex ABC #21 5lbs Pass No No 2007 Serviced September 2024 21 898326 Badger ABC #22 5lbs Pass No No 2008 Serviced September 2024 22 885064 Badger ABC #23 5lbs Pass No No 1997 Serviced September 2024 23 173366 Badger ABC #25 5lbs Pass No No 2005 Serviced September 2024 24 78290048 Kidde ABC #26 5.5lbs Pass No No 2008 Serviced October 2024 25 958615 Amerex ABC #27 5lbs Pass No No 2007 Serviced September 2024 26 3305101 Badger ABC #28 2.5lbs Pass No No 2015 Serviced September 2024 27 80154426 Kidde ABC #29 10lbs Pass No No 2016 Serviced September 2024 28 802801 Badger ABC #30 10lbs Pass No No 2006 Serviced September 2024 29 63511786 Amerex ABC #31 2.5lbs Pass No No 2019 Serviced September 2024
FIRE EXTINGUISHER INSPECTION REPORT
30 588925 Amerex ABC #32 5lbs Pass No No 2007 Serviced September 2024 31 960575 Amerex ABC #33 5lbs Pass No No 2007 Serviced September 2024 32 402359 Ansul ABC #35 20lbs Pass No No 2008 Serviced October 2024 33 403269 Grinnell ABC #36 20lbs Pass No No 2007 Serviced October 2024 34 796164 Badger ABC #37 10lbs Pass No No 2004 Serviced September 2024 35 403019 Grinnell ABC #38 20lbs Pass No No 1998 Serviced October 2024 36 341540 Buckeye ABC #39 10lbs Pass No No 2005 Serviced October 2024 37 833652 Badger ABC #40 10lbs Pass No No 2004 Serviced September 2024 38 341534 Buckeye ABC #41 10lbs Pass No No 2005 Serviced October 2024 39 719274 Badger ABC #42 10lbs Pass No No 2007 Serviced October 2024 40 04693740 Amerex ABC #43 10lbs Pass No No 2022 Inspected February 2026 41 197632 Badger ABC #44 10lbs Pass No No 2008 Serviced September 2024 42 473492 Amerex ABC #45 5lbs Pass No No 2007 Serviced September 2024 43 71092 Badger ABC #46 10lbs Pass No No 2007 Serviced September 2024 44 04693711 Amerex ABC #47 10lbs Pass No No 2022 Inspected February 2026 45 36231840 Kidde ABC #48 2.4lbs Pass No No 2024 Inspected February 2026 46 36231839 Kidde ABC #49 2.4lbs Pass No No 2024 Inspected February 2026 47 50023045 Kidde ABC #50 2.4lbs Pass No No 2025 Inspected February 2026 48 50023046 Kidde ABC #51 2.4lbs Pass No No 2025 Inspected February 2026 49 50023044 Kidde ABC #52 2.4lbs Pass No No 2025 Inspected February 2026 50 50023047 Kidde ABC #53 2.4lbs Pass No No 2025 Inspected February 2026
# Pass # Fail # 6-Year Service
# Hydro Service Comments/Notes
Total Extinguishers 50 0 0 0 (x9) 2.4/ 2.5lbs ABC FEs (x25) 5 /5.5lbs ABC FEs (x13) 10lbs ABC FEs (x3) 20lbs ABC FEs All Fire Extinguishers are satisfactory at this inspection#46 #16 Serial (466697) Amerex 5lbs #24 Serial (12234194) Kidde 5.5lbs #34 Serial (334452) First Alert 5lbs #46 Serial (71092) Badger 10lbs Previously inspected 10-25 but not on property at this inspection date.
Submitted To: Submitted By:
Pearl Harbor National Park Ron Reano
Kinetix
583 Abbott Drive
Broomall, PA 19008
P: 877.223.3000
E: rreano@kinetixfire.com
Reviewed by:
Joe Schranck
2026-01-29
Fire Protection Inspection Report
Pearl Harbor National Park Admin Offices | 25118
1 www.kinetixfire.com
Admin Offices Fire Alarm Inspection
Date of Inspection: January-29-2026 21:59 Technician: Ronald Reano Title: Lead Fire Alarm Technician
Type of Inspection: ☑ Annual ☐ Semi-Annual ☐ Quarterly Protected Property Inspection Company
Name: Pearl Harbor National Park Building Admin Offices
Name: Kinetix Fire
Address: 1 Arizona Street Address: 583 Abbott Drive
City: Aiea City: Broomall State: Hawaii Zip: 96701 State: PA Zip: 19008 Contact: Anna Welland Contact: Inspection/Service Department Phone: 808-766-5956 Phone: 877-223-3000
System Owner Name: Pearl Harbor National Park Address: 1 Arizona Street City: Aiea State: Hawaii Zip: 96701
Type of Fire Alarm System System ID: PARK_ADMIN OFFICES Type: Local Does this system include mass notification? No
Fire Alarm Signaling System Monitoring Is this system monitored off-site? Yes If yes, make and model of DACT: King Fisher 77-565 If yes, provide name, location, and phone number of monitoring company: Regional Dispatch Center Honolulu, HI 808-474- Any special procedures needed prior to or upon completion of testing?
No
Were building occupants notified prior to testing? If so, who? Yes Anna Welland Were building occupants notified upon completion of testing? If so, who?
Yes Anna Welland
Was system restored to normal operation upon completion of testing? If no, why not?
Yes
Power Supply System Primary Power (Dedicated):
☑ Yes ☐ No ☐ N/A
Locked Out? ☐ Yes ☑ No ☐ N/A Disconnecting Means Location: Office 103A Panel F Section 2 Circuit 79
Secondary: Battery Voltage/Amp Hour Rating: (4) 12VDC/35AH Battery Type: Battery Type: ☐ Dry-Cell ☐ Nickel-Cadmium ☑ Sealed Lead-Acid ☐ Lead-Acid ☐ Other (Specify):
Tested Ok? ☐ Yes ☐ No ☑ N/A Location: FACP
Battery Condition: ☐ Pass ☑ Fail Notes/Comments: Expired manufacturers date code.
Load Voltage: ☐ Pass ☑ Fail Notes/Comments: Expired manufacturers date code.
Discharge Test: ☐ Pass ☑ Fail Notes/Comments: Expired manufacturers date code.
Charger Test: ☑ Pass ☐ Fail Notes/Comments:
Remote Panel Batteries: ☐ Pass ☑ Fail Notes/Comments: See Remote Panel Test Log Engine Driven Generator Rating: NA Tested Ok? NA
Fueled by: NA Storage Capacity: NA Fire Alarm Signaling System Deficiencies
The inspection company certifies that the features of the system, as indicated herein, were tested, inspected, and/or maintained in accordance with the adopted NFPA standards and local codes. Any deficiencies from adopted NFPA Standards or applicable codes:
☐ No ☑ Yes (Please refer to deficiency comments page) Alarm Initiating Devices
2 www.kinetixfire.com
Device Tested Deficiencies Remarks Manual Pull Stations 9 0 Heat Detectors 2 0 Smoke Detectors 11 0 Duct Detectors NA Waterflow NA
Alarm Indicating Devices Device Number Failed Deficiency Description Bells NA Horns/Strobes NA Chimes NA Speakers 0 Speaker Strobes
Strobe failed to activate 1st Floor Elevator Lobby. P/N:
Edwards EST 757-8A-RS70 Red
Remote Annunciators Fire Alarm Strobes 0 MNS Strobes NA Sounder Bases NA Visual Signals 0 IR Detectors NA Other NA
Alarm Notification Appliances Circuit Information Number of alarm notification appliance circuits: 10 Are circuits monitored for integrity? ☑ Yes ☐ No
Supervisory Initiating Devices Device Tested Deficiencies Remarks Tamper Switches NA Low Air Switches NA
Pressure Switches NA Temperature Switches NA Water Supply Level NA
Fire Pump NA Control Unit
Manufacturer: Edwards Model #: EST-3 Type: Addressable with voice Circuit Style: Class A Software Revision: 05.21.00 Date of Last Software Revision: 01/19/24 Device Tested Deficiencies Remarks Lamps/LEDs/LCDs Pass No Fuses NA Trouble Signals Pass No Zone Disable Pass No Disconnect Switches NA
Supervisory Signals Pass No Ground Fault Pass No Transmit Off Premises Pass No Remote Power Panels Pass No Are all devices uniquely identified where applicable? ☑ Yes ☐ No
3 www.kinetixfire.com
Device Test Log
Device ID Device Type Location Result Notes 01020001 Smoke Detector 105 Elevator Machine Room Pass 01020002 Smoke Detector 103A Office (Vending Rear) Pass 01020003 Smoke Detector 106 Maintenance (Above FACP) Pass 1020004 Smoke Detector 204 NPS #1 Pass
01020005 Smoke Detector 204 NPS #2 Pass 01020006 Smoke Detector 205 Break Room/Kitchen Pass 01020007 Smoke Detector 203 Count Room Pass 01020008 Smoke Detector 201 Office Pass 01020009 Smoke Detector 200 Office Pass 01020010 Smoke Detector 202 Office Pass 1020011 Heat Detector 1st Floor Elevator Lobby Pass
01020012 Smoke Detector Elevator Top of Shaft Not Tested No access to Elevator Top of Shaft, will need Elevator Technician for access.
01020014 Heat Detector 2nd Floor Elevator Lobby Pass 01020126 Pull Station 212 Corridor Pass 01020127 Pull Station 2nd Floor Elevator Lobby Pass 01020128 Pull Station 109 Outside Rear Entry Women’s
Restroom Pass
01020129 Pull Station 103A Vending Rear Exit Pass 01020130 Pull Station 1st Floor Elevator Lobby Pass 01020131 Pull Station 108 Outside Men’s Restroom Front Entry Pass 01020132 Pull Station 103 Outside Vending Front Entry Pass 1020133 Pull Station 101 Server Room Pass
01020134 Pull Station 102 LE Cashe Storage Room Pass 01020143 Module Primary Elevator Recall Relay Pass Confirmed Relay module activated at FACP, but Elevator did not recall.
01020144 Module Alternate Elevator Recall Relay Pass Confirmed Relay module activated at FACP, but Elevator did not recall.
Inspection Deficiencies Tested heat detectors for 1st and 2nd Floor Lobby recalls but Elevator did not recall. Possible issue on Elevator side.
(2) 12volt 35ah batteries in FACP EST-3 located in rear janitors closet top row have an expired manufacturers date code.
(2) 12volt 35ah batteries in FACP EST-3 located in rear janitors closet bottom row have an expired manufacturers date code.
(2) 12volt 7ah batteries in power supply FEP #1 BPS10A located in rear janitors closet have an expired manufacturers date code.
(1) 12volt 2.5ah battery in King Fisher interface communicator panel battery tested flat.
(1) 12volt 2.5ah battery in King Fisher transmitter communicator has an expired manufacturers date code.
Speaker/Strobe located in 1st Floor Elevator Lobby failed to activate. (P/N: Edwards EST 757-8A-RS70 Red)
Remote Panel Test Log Panel Type Panel Location Class
A/B Battery
Type Battery 1 Volts/Ah
Battery 2 Volts/Ah
Pass/Fail Comments
Power Supply Rear Janitors closet FACP
EST3 Top Row
(2)12V/35AH
A Sealed Lead-Acid
0.00V/0.00AH 0.00V/0.00AH Fail Expired manufacturers date code.
Power Supply Rear Janitors closet FACP
EST3
A Sealed Lead-Acid
0.00V/0.00AH 0.00V/0.00AH Fail Expired manufacturers date code.
4 www.kinetixfire.com
BottomRow
(2)12V/35AH
Power Supply Rear Janitors closet FEP 1
BPS10A
(2)12V/7AH
A Sealed Lead-Acid
0.00V/0.00AH 0.00V/0.00AH Fail Expired manufacturers date code.
Power Supply Rear Janitors closet FEP 2
BPS10A
(2)12V/7AH
A Sealed Lead-Acid
12.37V/4.00AH 13.42V/4.69AH Pass
Communicator Rear Janitors closet King
Fisher Interface Panel
(1)12V/2.5AH
B Sealed Lead-Acid
0.00V/0.00AH V/AH Fail Battery tested flat.
Communicator King Fisher Transmitter
(1)12V/2.5AH
B Sealed Lead-Acid
0.00V/0.00AH V/AH Fail Expired manufacturers
Signature
Customer Signature
Technician Signature
Kinetix
583 Abbott Drive
Broomall, PA 19008
P: 877.223.3000
E: rreano@kinetixfire.com
Pearl Harbor National Park Building 612 Maintenance | 25118
Building 612 Fire Alarm Inspection
Date of Inspection: January-29-2026 21:00 Technician: Ronald Reano Title: Lead Fire Alarm Technician
Type of Inspection: ☑ Annual ☐ Semi-Annual ☐ Quarterly Protected Property Inspection Company
Name: Pearl Harbor National Park Building 612 Maintenance Shop
Name: Kinetix Fire
Address: 1 Arizona Street Address: 583 Abbott Drive
City: Aiea City: Broomall State: Hawaii Zip: 96701 State: PA Zip: 19008 Contact: Anna Welland Contact: Inspection/Service Department Phone: 808-766-5956 Phone: 877-223-3000
System Owner Name: Pearl Harbor National Park Address: 1 Arizona Street City: Aiea State: Hawaii Zip: 96701
Type of Fire Alarm System System ID: PARKS_Bldg.612_Maint Type: Local Does this system include mass notification? No
Fire Alarm Signaling System Monitoring Is this system monitored off-site? Yes If yes, make and model of DACT: Radionics D2071A - Account
#AAH4-0780
If yes, provide name, location, and phone number of monitoring company: Alert Alarm Hawaii Honolulu 808-521-5000 Any special procedures needed prior to or upon completion of testing?
No
Were building occupants notified prior to testing? If so, who? Yes Maintenance - Anna Welland Were building occupants notified upon completion of testing? If so, who?
Yes Maintenance - Anna Welland
Was system restored to normal operation upon completion of testing? If no, why not?
Yes
Power Supply System Primary Power (Dedicated):
☑ Yes ☐ No ☐ N/A
Locked Out? ☐ Yes ☑ No ☐ N/A Disconnecting Means Location: 2nd Floor Panel L2 Circuit 10 Secondary: Battery Voltage/Amp Hour Rating: (2) 12VDC/7AH Battery Type: Battery Type: ☐ Dry-Cell ☐ Nickel-Cadmium ☑ Sealed Lead-Acid ☐ Lead-Acid ☐ Other (Specify):
Tested Ok? ☑ Yes ☐ No ☐ N/A Location: FACP
Battery Condition: ☑ Pass ☐ Fail Notes/Comments:
Load Voltage: ☑ Pass ☐ Fail Notes/Comments:
Discharge Test: ☑ Pass ☐ Fail Notes/Comments:
Charger Test: ☑ Pass ☐ Fail Notes/Comments:
Remote Panel Batteries: ☑ Pass ☐ Fail Notes/Comments:
Engine Driven Generator Rating: NA Tested Ok? NA
Fueled by: NA Storage Capacity: NA Fire Alarm Signaling System Deficiencies
The inspection company certifies that the features of the system, as indicated herein, were tested, inspected, and/or maintained in accordance with the adopted NFPA standards and local codes. Any deficiencies from adopted NFPA Standards or applicable codes:
☐ No ☑ Yes (Please refer to deficiency comments page)
Device Tested Deficiencies Remarks
Manual Pull Stations 4 0 Heat Detectors 4 1 Smoke Detectors 9 0 Duct Detectors NA Waterflow 1 0
Alarm Indicating Devices Device Number Failed Deficiency Description Bells NA Horns/Strobes 0 Chimes NA Speakers NA Speaker Strobes NA Remote Annunciators NA Fire Alarm Strobes NA MNS Strobes NA Sounder Bases NA Visual Signals 0 IR Detectors NA Other NA
Alarm Notification Appliances Circuit Information Number of alarm notification appliance circuits: 2 Are circuits monitored for integrity? ☑ Yes ☐ No
Supervisory Initiating Devices Device Tested Deficiencies Remarks Tamper Switches 2 0 Low Air Switches NA Pressure Switches NA Temperature Switches NA Water Supply Level NA Fire Pump NA
Control Unit Manufacturer: GE Model #: FSP-502 Type: Hardwired/Conventional Circuit Style: Class B Software Revision: NA Date of Last Software Revision: NA Device Tested Deficiencies Remarks Lamps/LEDs/LCDs Pass No Fuses NA Trouble Signals Pass No Zone Disable Pass No Disconnect Switches NA
Supervisory Signals NA Ground Fault Pass No Transmit Off Premises Pass No
Heat detector located on 1st Floor Mauka Bay 2 High Ceiling: No activation signal at Main FACP. (P/N: GE EC20RRU-3)
Device Test Log Device ID Device Type Location Result Notes
Zone 1 Pull Station 1st Floor Bay 1 Exit by FACP Pass Zone 1 Pull Station 1st Floor Makai Bay 3 Pass Zone 1 Pull Station 1st Floor Mauka Bay Pass Zone 1 Pull Station 2nd Floor Stairs Pass Zone 3 Smoke Detector 2nd Floor Makai Pass Zone 3 Smoke Detector 2nd Floor Mauka Pass Zone 4 Tamper Switch Main Riser #1 Pass Zone 4 Tamper Switch Main Riser #2 Pass Zone 4 Waterflow Switch Main Riser Pass Zone 5 Smoke Detector 1st Floor Mauka Exit Pass Zone 5 Smoke Detector 1st Floor Makai Exit Pass Zone 5 Smoke Detector 1st Floor Breakroom Pass Zone 5 Smoke Detector 1st Floor Office Pass Zone 5 Smoke Detector 1st Floor Restrooms Pass Zone 5 Heat Detector 1st Floor Makai Bay 1 Center Pass Zone 5 Heat Detector 1st Floor Makai Bay 1 Corner Pass Zone 5 Heat Detector 1st Floor Mauka Bay 2 High Ceiling Fail Zone 5 Smoke Detector 1st Floor Mauka Bay 3 Lower Smoke Left Pass Zone 5 Smoke Detector 1st Floor Mauka Bay 3 Lower Smoke Right Pass Zone 5 Heat Detector 1st Floor Mechanical Room Pass
Remote Panel Test Log Panel Type Panel
Location Class A/B
Battery Type
Battery 1 Volts/Ah
Battery 2 Volts/Ah
Pass/Fail Comments
Power Supply Entrance Hallway
FACP FS502
(2)12V/7AH
B Sealed Lead-Acid
12.00V/5.60AH 12.00V/7.00AH Pass
Communicator Entrance Hallway
Radionics D2071A
(1)12V/7AH
B Sealed Lead-Acid
12.00V/7.00AH V/AH Pass
Kinetix
583 Abbott Drive
Broomall, PA 19008
P: 877.223.3000
E: rreano@kinetixfire.com
Pearl Harbor National Park Building 612 Maintenance | 25118
Date of Inspection: January-29-2026 21:00 Technician: Ronald Reano Title: Lead Fire Alarm Technician
Type of Inspection: ☑ Annual ☐ Semi-Annual ☐ Quarterly Protected Property Inspection Company
Name: Pearl Harbor National Park Building 612 Maintenance Shop
Name: Kinetix Fire
Address: 1 Arizona Street Address: 583 Abbott Drive
City: Aiea City: Broomall State: Hawaii Zip: 96701 State: PA Zip: 19008 Contact: Anna Welland Contact: Inspection/Service Department Phone: 808-766-5956 Phone: 877-223-3000
System Owner Name: Pearl Harbor National Park Address: 1 Arizona Street City: Aiea State: Hawaii Zip: 96701
Type of Fire Alarm System System ID: PARKS_Bldg612_Maint Type: Local Does this system include mass notification? No
Fire Alarm Signaling System Monitoring Is this system monitored off-site? Yes If yes, make and model of DACT: Radionics D2071A - Account
#AAH4-0780
If yes, provide name, location, and phone number of monitoring company: Alert Alarm Hawaii Honolulu 808-521-5000 Any special procedures needed prior to or upon completion of testing?
No
Were building occupants notified prior to testing? If so, who? Yes Maintenance - Anna Welland Were building occupants notified upon completion of testing? If so, who?
Yes Maintenance - Anna Welland
Was system restored to normal operation upon completion of testing? If no, why not?
Yes
Power Supply System Primary Power (Dedicated):
☑ Yes ☐ No ☐ N/A
Locked Out? ☐ Yes ☑ No ☐ N/A Disconnecting Means Location: 2nd Floor Panel L2 Circuit 10 Secondary: Battery Voltage/Amp Hour Rating: (2) 12VDC/7AH Battery Type: Battery Type: ☐ Dry-Cell ☐ Nickel-Cadmium ☑ Sealed Lead-Acid ☐ Lead-Acid ☐ Other (Specify):
Tested Ok? ☑ Yes ☐ No ☐ N/A Location: FACP
Battery Condition: ☑ Pass ☐ Fail Notes/Comments:
Load Voltage: ☑ Pass ☐ Fail Notes/Comments:
Discharge Test: ☑ Pass ☐ Fail Notes/Comments:
Charger Test: ☑ Pass ☐ Fail Notes/Comments:
Remote Panel Batteries: ☑ Pass ☐ Fail Notes/Comments:
Engine Driven Generator Rating: NA Tested Ok? NA
Fueled by: NA Storage Capacity: NA Fire Alarm Signaling System Deficiencies
The inspection company certifies that the features of the system, as indicated herein, were tested, inspected, and/or maintained in accordance with the adopted NFPA standards and local codes. Any deficiencies from adopted NFPA Standards or applicable codes:
☐ No ☑ Yes (Please refer to deficiency comments page)
Manual Pull Stations 4 0 Heat Detectors 4 1 Smoke Detectors 9 0 Duct Detectors NA Waterflow 1 0
Alarm Indicating Devices Device Number Failed Deficiency Description Bells NA Horns/Strobes 0 Chimes NA Speakers NA Speaker Strobes NA Remote Annunciators NA Fire Alarm Strobes NA MNS Strobes NA Sounder Bases NA Visual Signals 0 IR Detectors NA Other NA
Alarm Notification Appliances Circuit Information Number of alarm notification appliance circuits: 2 Are circuits monitored for integrity? ☑ Yes ☐ No
Supervisory Initiating Devices Device Tested Deficiencies Remarks Tamper Switches 2 0 Low Air Switches NA Pressure Switches NA Temperature Switches NA Water Supply Level NA Fire Pump NA
Control Unit Manufacturer: GE Model #: FSP-502 Type: Hardwired/Conventional Circuit Style: Class B Software Revision: NA Date of Last Software Revision: NA Device Tested Deficiencies Remarks Lamps/LEDs/LCDs Pass No Fuses NA Trouble Signals Pass No Zone Disable Pass No Disconnect Switches NA
Supervisory Signals NA Ground Fault Pass No Transmit Off Premises Pass No
Heat detector located on 1st Floor Mauka Bay 2 High Ceiling: No activation signal at Main FACP. (P/N: GE EC20RRU-3)
Device Test Log Device ID Device Type Location Result Notes
Zone 1 Pull Station 1st Floor Bay 1 Exit by FACP Pass Zone 1 Pull Station 1st Floor Makai Bay 3 Pass Zone 1 Pull Station 1st Floor Mauka Bay Pass Zone 1 Pull Station 2nd Floor Stairs Pass Zone 3 Smoke Detector 2nd Floor Makai Pass Zone 3 Smoke Detector 2nd Floor Mauka Pass Zone 4 Tamper Switch Main Riser #1 Pass Zone 4 Tamper Switch Main Riser #2 Pass Zone 4 Waterflow Switch Main Riser Pass Zone 5 Smoke Detector 1st Floor Mauka Exit Pass Zone 5 Smoke Detector 1st Floor Makai Exit Pass Zone 5 Smoke Detector 1st Floor Breakroom Pass Zone 5 Smoke Detector 1st Floor Office Pass Zone 5 Smoke Detector 1st Floor Restrooms Pass Zone 5 Heat Detector 1st Floor Makai Bay 1 Center Pass Zone 5 Heat Detector 1st Floor Makai Bay 1 Corner Pass Zone 5 Heat Detector 1st Floor Mauka Bay 2 High Ceiling Fail Zone 5 Smoke Detector 1st Floor Mauka Bay 3 Lower Smoke Left Pass Zone 5 Smoke Detector 1st Floor Mauka Bay 3 Lower Smoke Right Pass Zone 5 Heat Detector 1st Floor Mechanical Room Pass
Location Class A/B
Battery Type
Battery 1 Volts/Ah
Battery 2 Volts/Ah
Pass/Fail Comments
Power Supply Entrance Hallway
FACP FS502
(2)12V/7AH
B Sealed Lead-Acid
12.00V/5.60AH 12.00V/7.00AH Pass
Communicator Entrance Hallway
Radionics D2071A
(1)12V/7AH
B Sealed Lead-Acid
12.00V/7.00AH V/AH Pass
Kinetix
583 Abbott Drive
Broomall, PA 19008
P: 877.223.3000
E: rreano@kinetixfire.com
Pearl Harbor National Park Building D Classrooms | 25118
Classrooms Fire Alarm Inspection
Date of Inspection: January-29-2026 14:30 Technician: Ronald Reano Title: Lead Fire Alarm Technician
Type of Inspection: ☑ Annual ☐ Semi-Annual ☐ Quarterly Protected Property Inspection Company
Name: Pearl Harbor National Park Building D Classrooms
Name: Kinetix Fire
Address: 1 Arizona Street Address: 583 Abbott Drive
City: Aiea City: Broomall State: Hawaii Zip: 96701 State: PA Zip: 19008 Contact: Anna Welland Contact: Inspection/Service Department Phone: 808-766-5956 Phone: 877-223-3000
System Owner Name: Pearl Harbor National Park Address: 1 Arizona Street City: Aiea State: Hawaii Zip: 96701
Type of Fire Alarm System System ID: PARKS_Classrooms Type: Local Does this system include mass notification? No
Fire Alarm Signaling System Monitoring Is this system monitored off-site? Yes If yes, make and model of DACT: King Fisher 77-406 If yes, provide name, location, and phone number of monitoring company: Regional Dispatch Center Honolulu 808-474-2222 Any special procedures needed prior to or upon completion of testing?
No
Were building occupants notified prior to testing? If so, who? Yes Anna Welland Were building occupants notified upon completion of testing? If so, who?
Yes Anna Welland
Was system restored to normal operation upon completion of testing? If no, why not?
No (1) Existing Trouble 0001 LOCAL TRBL ACT 0101061 Battery Trouble D:0615
Power Supply System Primary Power (Dedicated):
☑ Yes ☐ No ☐ N/A
Locked Out? ☐ Yes ☑ No ☐ N/A Disconnecting Means Location: West Side of Building Panel D Circuit 21
Secondary: Battery Voltage/Amp Hour Rating: (2) 12VDC/55AH Battery Type: Battery Type: ☐ Dry-Cell ☐ Nickel-Cadmium ☑ Sealed Lead-Acid ☐ Lead-Acid ☐ Other (Specify):
Tested Ok? ☐ Yes ☐ No ☑ N/A Location: FACP
Battery Condition: ☐ Pass ☑ Fail Notes/Comments: Expired manufacturers date code and batteries warped.
Load Voltage: ☐ Pass ☑ Fail Notes/Comments: Expired manufacturers date code and batteries warped.
Discharge Test: ☐ Pass ☑ Fail Notes/Comments: Expired manufacturers date code and batteries warped.
Charger Test: ☑ Pass ☐ Fail Notes/Comments:
Remote Panel Batteries: ☑ Pass ☐ Fail Notes/Comments:
Engine Driven Generator Rating: NA Tested Ok? NA
Fueled by: NA Storage Capacity: NA Fire Alarm Signaling System Deficiencies
The inspection company certifies that the features of the system, as indicated herein, were tested, inspected, and/or maintained in accordance with the adopted NFPA standards and local codes. Any deficiencies from adopted NFPA Standards or applicable codes:
☐ No ☑ Yes (Please refer to deficiency comments page)
Manual Pull Stations 4 0 Heat Detectors NA Smoke Detectors 1 0 Duct Detectors NA Waterflow NA
Alarm Indicating Devices Device Number Failed Deficiency Description Bells NA Horns/Strobes NA Chimes NA Speakers 0 Speaker Strobes 0 Remote Annunciators NA Fire Alarm Strobes NA MNS Strobes NA Sounder Bases NA Visual Signals 0 IR Detectors NA Other NA
Alarm Notification Appliances Circuit Information Number of alarm notification appliance circuits: 5 Are circuits monitored for integrity? ☑ Yes ☐ No
Supervisory Initiating Devices Device Tested Deficiencies Remarks Tamper Switches NA Low Air Switches NA
Pressure Switches NA Temperature Switches NA Water Supply Level NA
Fire Pump NA Control Unit
Manufacturer: Edwards Model #: EST3 Type: Addressable with voice Circuit Style: Class A Software Revision: 05.45.00 Date of Last Software Revision: 01/19/24 Device Tested Deficiencies Remarks Lamps/LEDs/LCDs
Fail Yes LED Disable buttons on Main FACP do not light up when pressed. P/N: Edwards 3-12/S2R LED Control.
Fuses NA Trouble Signals Pass No Zone Disable Pass No Disconnect Switches NA
Supervisory Signals Pass No Ground Fault Pass No Transmit Off Premises
Fail Yes No signals received at RDC due to Transmitter being offline from bad battery and possible bad fuse.
01020002 Smoke Detector Office A Above FACP Pass Will need Phoenix Pacific to update message changes on Main FACP.
1020126 Pull Station Office A by FACP Pass Will need Phoenix Pacific to update message changes on Main FACP.
1020127 Pull Station Superintendent office Pass Will need Phoenix Pacific to update message changes on Main FACP.
01020128 Pull Station Private Office Back Exit Pass Will need Phoenix Pacific to update message changes on Main FACP.
01020129 Pull Station Private Office Front Entry Pass
(2) 12volt 55ah FACP EST-3 batteries have an expired manufacturers date code and batteries are warped.
(1) 12volt 2.5ah battery in King Fisher Interface communicator panel failed testing: Test measured low voltage and amp hour.
(1) 12volt 2.5ah battery in King Fisher transmitter communicator panel failed testing: Battery tested flat. Transmitter is offline due to bad battery and possible bad fuse.
No signals received at RDC due to Transmitter being offline from bad battery and possible bad fuse.
Failed Discrepancy for Main FACP Microphone functions not working (P/N: Edwards ASU). Will need Phoenix Pacific to troubleshoot/program or replace ASU.
Remote Panel Test Log Panel Type Panel
Location Class A/B
Battery Type
Battery 1 Volts/Ah
Battery 2 Volts/Ah
Pass/Fail Comments
Power Supply FACP EST-3
(2)12V/55AH
A Sealed Lead-Acid
0.00V/0.00AH 0.00V/0.00AH Fail Expired manufacturers date code and batteries warped.
Power Supply FEP BPS10A
(2)12V/7AH
A Sealed Lead-Acid
12.00V/5.60AH 12.00V/7.00AH Pass
Communicator King Fisher Interface
Panel
(1)12V/2.5AH
B Sealed Lead-Acid
11.03V/0.25AH V/AH Fail Battery test measured low voltage and amp hour.
Communicator King Fisher Transmitter
(1)12V2.5AH
B Sealed Lead-Acid
0.00V/0.00AH V/AH Fail Battery tested flat.
Transmitter is offline due to bad battery and possible bad fuse.
Submitted To:
Submitted By:
Pearl Harbor National Memorial Eddie Erlandiz Kinetix 583 Abbott Drive Broomall, PA 19008 P: 877.223.3000 E: eerlandiz@kinetixfrie.com
2026-02-02
Wet Pipe Sprinkler Report
Pearl Harbor Parks Building G | 25118
WET PIPE SPRINKLER INSPECTION
Date of Inspection: February-02-2026 Technician: Eddie Erlandiz Type of Inspection: ☐ Monthly ☐ Quarterly ☐ Semi-Annual ☑ Annual ☐ Bi-Annual
Protected Property Inspection Company Name: Pearl Harbor National Park Building G Name: Kinetix Fire Address: 1 Arizona Memorial Place Address: 583 Abbott Drive City: Honolulu City: Broomall State: Hawaii Zip: 96818 State: PA Zip: 19008 Contact: Luther M. Sargent Contact: Inspection/Service Department Phone: 808-528-8754 Phone: 877-223-3000
System Details Manufacturer: Viking Model: J-1 Serial Number: Unknown System Size: 6" Area Covered: Building G General Information Yes No N/A Is the building occupied and the same occupancy since the last inspection? ☑ ☐ ☐ Is the building fully sprinklered and the entire system in service? ☑ ☐ ☐ Is the system unchanged since the last inspection? ☑ ☐ ☐ System in service at time of inspection? ☑ ☐ ☐ System tagged and left in service? ☑ ☐ ☐ System left out of service (will not operate)? ☐ ☑ ☐ System red tagged (non-compliant)? ☐ ☑ ☐ Pertinent parties notified before testing? ☑ ☐ ☐ Pertinent parties notified of test conclusion? ☑ ☐ ☐ Alarm panel clear upon conclusion of inspection? ☑ ☐ ☐ System returned to service? ☑ ☐ ☐ Notes:
Monthly Wet Pipe Inspection Yes No N/A
1. Supply pressure gauge psi? 72 PSI
2. System pressure gauge psi? 72 PSI
3. Gauges appear to be in good condition? ☑ ☐ ☐
4. Control valves in normal open or closed position? ☑ ☐ ☐
5. Control valves properly locked or supervised? ☑ ☐ ☐
6. Control valves accessible? ☑ ☐ ☐
7. Control valves provided with appropriate wrenches? ☐ ☐ ☑
8. Control valves free from external leaks? ☑ ☐ ☐
9. Control valve identification signs in place? ☐ ☑ ☐
10. System control valve sign indicates area served? ☑ ☐ ☐
11. Backflow valves electronically supervised or locked in open position? ☑ ☐ ☐
12. Reduced pressure backflow not in continuous discharge? ☐ ☐ ☑
13. Alarm valve gauges indicate normal supply water pressure? ☑ ☐ ☐
14. Alarm Valve free of physical damage? ☑ ☐ ☐
15. Alarm/trim valves are in appropriate open or closed position? ☑ ☐ ☐
16. Alarm valve retarding chamber or alarm drain not leaking? ☑ ☐ ☐
17. System riser sign indicates area of coverage, location of auxiliary systems and location of auxiliary drains?
Notes: Recommend add 1" auxiliary drain plugs and signs to end of cross mains on the side of both ends of the building North and South.
Quarterly Wet Pipe Inspection Yes No N/A
1. Adequate drainage provided before flow testing? ☑ ☐ ☐
2. Alarm devices appear free of physical damage? ☑ ☐ ☐
3. Main drain test conducted downstream of backflow? ☑ ☐ ☐
4. Main drain test conducted downstream of PRV? ☐ ☐ ☑
5. Supply water gauge reading before flow (static) PSI? 72 PSI
6. Gauge reading during stable flow (residual) PSI? 63 PSI
7. Time for supply pressure to return to normal (sec)? 3 Seconds
8. Full flow pressure (residual) < 10% reduction from prior or original test? ☐ ☐ ☑
9. Hydraulic nameplate attached and legible? ☑ ☐ ☐
10. Pressure reducing control valves indicate open? ☐ ☐ ☑
11. Pressure reducing valve (PRV) not leaking and in good condition? ☐ ☐ ☑
12. PRV maintaining downstream pressure per design? ☐ ☐ ☑
13. PRV handwheel installed and not broken? ☐ ☐ ☑
14. FDC is visible and accessible? ☑ ☐ ☐
15. FDC swivels/couplings undamaged/rotate smoothly? ☑ ☐ ☐
16. FDC plugs/caps in place/undamaged? ☑ ☐ ☐
17. FDC gaskets in place and in good condition? ☑ ☐ ☐
18. FDC identification sign in place? ☑ ☐ ☐
19. FDC check valve not leaking? ☑ ☐ ☐
20. FDC automatic drain valve in place and operating properly? ☐ ☐ ☑
21. FDC clapper is in place and operating properly? ☑ ☐ ☐
22. FDC obstructions removed as necessary? ☑ ☐ ☐
23. FDC has approved locking caps/plugs? ☑ ☐ ☐
24. Inspected interior of FDC if proper caps/plugs are in place? ☑ ☐ ☐
25. Back flushed the FDC (If required per UFC)? ☐ ☐ ☑ Notes:
Semi-Annual Wet Pipe Inspection Yes No N/A
1. Supervisory switches initiated distinct signal during first two hand wheel revolutions or before valve stem moved one-fifth from normal position?
2. Signal restored only when valve returned to normal position? ☑ ☐ ☐
3. Water flow alarm tested and operational? ☑ ☐ ☐
4. Test conducted with inspector's test connection? ☑ ☐ ☐
5. Test conducted with bypass connection (freezing weather)? ☐ ☐ ☑
6. Test conducted per manufacturer's instructions? ☑ ☐ ☐ Notes:
Annual Wet Pipe Inspection Yes No N/A
1. Hangers and seismic bracing appears undamaged and tightly attached? ☑ ☐ ☐
2. Piping appears free of mechanical damage, leakage, corrosion, external loading? ☑ ☐ ☐
3. Sprinklers appear free of leakage, corrosion, foreign materials, paint, and physical damage?
4. Sprinklers appear properly oriented? ☑ ☐ ☐
5. Clearance appears to be adequate between sprinkler and building contents? ☑ ☐ ☐
Sprinkler Head Information Size Finish Temperature Rating Type Manufacturer Year Wrench 1/2" Chrome 155*F Upright QR Viking 1997 Yes 1/2" Brass 155*F Upright QR Viking 2010 Yes
Control Valve Report ID Type Size Location Open/Close Secured
(Specify) Proper Signage
Condition Comments
Main Riser Control Valve
OS&Y 6" Outside of Building
East near rear electrical room
Open Supervised Yes Good
6. Glass bulbs appear full of liquid? ☑ ☐ ☐
7. Spare sprinklers are of proper number (at least 6), type and temperature rating? ☑ ☐ ☐
8. Spare sprinklers stored where temperature maximum is 100°F? ☑ ☐ ☐
9. Wrench available for each type of sprinkler? ☑ ☐ ☐
10. Building is secure such as not to expose piping to freezing conditions? ☑ ☐ ☐
11. Adequate heat is provided maintaining temperatures 40° F or higher? ☑ ☐ ☐
12. Date of last FDC hydro test (Performed every 5 years)? Unknown
13. Antifreeze system has a test connection at the most remote portion, the interface with the wet pipe system, and when the capacity exceeds 150 gal. one additional connection for every 100 gal?
14. Antifreeze solution freezing point *F? NA *F
15. Antifreeze solution freezing point after adjustment? NA *F
16. Operating stems of OS&Y (inc. backflow) valves lubricated? ☑ ☐ ☐
17. Valve completely closed and reopened? ☑ ☐ ☐
18. Control valves (inc. backflow and PIV) operated through full range and returned to normal position?
19. PIV's opened until spring or torsion felt in rod? ☐ ☐ ☑
20. PIV's and OS&Y's backed 1/4 turn from full open? ☑ ☐ ☐
21. Backflow prevention assembly forward flow tested? ☐ ☐ ☑
22. System demand flow was achieved through the device? ☐ ☐ ☑
23. Forward flow test conducted at max rate possible (only where connections do not permit full flow test)?
24. Forward flow test conducted without measuring flow (device ≤ 2" and outlet sized to flow system demand)?
25. Backflow preventer Internally inspected (where shortages last > 1 year)? ☐ ☐ ☑
26. Forward flow test satisfied by annual fire pump flow test? ☐ ☐ ☑
27. Backflow flow test conducted as required by the AHJ? ☐ ☐ ☑
28. PRV control valves partial flow test conducted and adequate to unseat valve? ☐ ☐ ☑
29. Are there sprinklers over 50 years old? ☐ ☑ ☐
30. Are there dry sprinklers over 10 years old? ☐ ☐ ☑
31. Are there heads subject for recall? ☐ ☑ ☐
32. Are there quick response heads over 20 years old? ☐ ☑ ☐ Notes: Spare Head Cabinet located in Building H rear electrical Room for Both Buildings G & H.
Inspection Test Valve
Gate 1" Inside the park south side of Building near Exhibit exit.
Closed Normally Closed Valve for testing only
Yes Good
Inspection Deficiencies Control valve identification signs in place?
Missing one alarm test line identification sign.
Kinetix
583 Abbott Drive
Broomall, PA 19008
P: 877.223.3000
E: rreano@kinetixfire.com
Pearl Harbor National Park Museum Exhibit G & H | 25118
Museum Exhibit G&H Fire Alarm Inspection
Date of Inspection: January-29-2026 22:36 Technician: Ronald Reano Title: Lead Fire Alarm Technician
Type of Inspection: ☑ Annual ☐ Semi-Annual ☐ Quarterly Protected Property Inspection Company
Name: Pearl Harbor National Park Museum Exhibit G & H
Name: Kinetix Fire
Address: 1 Arizona Street Address: 583 Abbott Drive
City: Aiea City: Broomall State: Hawaii Zip: 96701 State: PA Zip: 19008 Contact: Anna Welland Contact: Inspection/Service Department Phone: 808-766-5956 Phone: 877-223-3000
System Owner Name: Pearl Harbor National Park Address: 1 Arizona Street City: Aiea State: Hawaii Zip: 96701
Type of Fire Alarm System System ID: PARKS_G & H Type: Local Does this system include mass notification? No
Fire Alarm Signaling System Monitoring Is this system monitored off-site? Yes If yes, make and model of DACT: King Fisher 77-209 If yes, provide name, location, and phone number of monitoring company: Regional Dispatch Center Honolulu, HI 808-474- Any special procedures needed prior to or upon completion of testing?
No
Were building occupants notified prior to testing? If so, who? Yes Anna Welland Were building occupants notified upon completion of testing? If so, who?
Yes Anna Welland
Was system restored to normal operation upon completion of testing? If no, why not?
Yes
Power Supply System Primary Power (Dedicated):
☑ Yes ☐ No ☐ N/A
Locked Out? ☐ Yes ☑ No ☐ N/A Disconnecting Means Location: Outside Building G Switch Gear Panel G Circuit 16 Disconnect
Secondary: Battery Voltage/Amp Hour Rating: (4) 12VDC/35AH Battery Type: Battery Type: ☐ Dry-Cell ☐ Nickel-Cadmium ☑ Sealed Lead-Acid ☐ Lead-Acid ☐ Other (Specify):
Tested Ok? ☐ Yes ☐ No ☑ N/A Location: FACP
Battery Condition: ☐ Pass ☑ Fail Notes/Comments: Expired manufacturers date code.
Load Voltage: ☐ Pass ☑ Fail Notes/Comments: Expired manufacturers date code.
Discharge Test: ☐ Pass ☑ Fail Notes/Comments: Expired manufacturers date code.
Charger Test: ☑ Pass ☐ Fail Notes/Comments:
Remote Panel Batteries: ☐ Pass ☑ Fail
Notes/Comments: Expired manufacturers date code. See Remote Panel Test Log.
Engine Driven Generator Rating: NA Tested Ok? NA
Fueled by: NA Storage Capacity: NA Fire Alarm Signaling System Deficiencies
The inspection company certifies that the features of the system, as indicated herein, were tested, inspected, and/or maintained in accordance with the adopted NFPA standards and local codes. Any deficiencies from adopted NFPA Standards or applicable codes:
Alarm Initiating Devices Device Tested Deficiencies Remarks Manual Pull Stations 6 0 Heat Detectors NA Smoke Detectors 1 0 Duct Detectors NA Waterflow 2 0
Alarm Indicating Devices Device Number Failed Deficiency Description Bells NA Horns/Strobes NA Chimes NA Speakers 0 Speaker Strobes 0 Remote Annunciators NA Fire Alarm Strobes NA MNS Strobes NA Sounder Bases NA Visual Signals 0 IR Detectors NA Other NA
Alarm Notification Appliances Circuit Information Number of alarm notification appliance circuits: 6 Are circuits monitored for integrity? ☑ Yes ☐ No
Supervisory Initiating Devices Device Tested Deficiencies Remarks Tamper Switches 2 0 Low Air Switches NA Pressure Switches NA Temperature Switches NA Water Supply Level NA Fire Pump NA
Control Unit Manufacturer: Edwards Model #: EST3 Type: Addressable Circuit Style: Class A Software Revision: 03.70.00 Date of Last Software Revision: 04/02/12 Device Tested Deficiencies Remarks Lamps/LEDs/LCDs Pass No Fuses NA Trouble Signals Pass No Zone Disable Pass No Disconnect Switches NA
Supervisory Signals Pass No Ground Fault Pass No Transmit Off Premises
Fail Yes No signals received at RDC. Transmitter is offline due to bad battery and possible bad fuse.
Inspection Deficiencies
(2) 12volt 35ah batteries located in Building G Back Storage Room FACP EST-3 Top Row have an expired manufacturers date code.
(2) 12volt 7ah batteries located in Building G Back Storage Room BPS10A have an expired manufacturers date code.
(1) 12volt 2.5ah battery in King Fisher Interface Panel communicator has an expired manufacturers date code.
(1) 12volt 2.5ah battery in King Fisher transmitter communicator battery is flat. Transmitter is offline due to bad battery and possible bad fuse. No signals received at RDC. Transmitter is offline due to bad battery and possible bad fuse.
01020001 Smoke Detector Above FACP Pass 1020131 Pull Station Building H Exit Pass
01020132 Waterflow Switch Building H Pressure Switch Pass 01020133 Pull Station Building G Entry Pass 01020134 Pull Station Building G Exit Pass 01020135 Pull Station Building H Storage Room Pass 01020136 Tamper Switch Building H Tamper Pass 01020137 Pull Station Building H Entry Pass 01020138 Pull Station Building G Storage Room Pass 01020139 Tamper Switch Building G Tamper Pass 01020140 Waterflow Switch Building G Pressure Switch Pass
Location Class A/B
Battery Type
Battery 1 Volts/Ah
Battery 2 Volts/Ah
Pass/Fail Comments
Power Supply Building G Back Storage Room FACP
EST3 Top Row
(2)12V/35AH
A Sealed Lead-Acid
0.00V/0.00AH 0.00V/0.00AH Fail Expired manufacturers date code.
Power Supply Building G Back Storage Room FACP
EST3 Bottom Row
(2)12V/35AH
A Sealed Lead-Acid
0.00V/0.00AH 0.00V/0.00AH Fail Expired manufacturers date code.
Power Supply Building G Back Storage
Room
BPS10A
(2)12V/7AH
A Sealed Lead-Acid
0.00V/0.00AH 0.00V/0.00AH Fail Expired manufacturers date code.
Communicator King Fisher Interface
Panel
(1)12V/2.5AH
B Sealed Lead-Acid
0.00V/0.00AH 0.00V/0.00AH Fail Expired manufacturers date code.
Communicator King Fisher Transmitter
(1)12V/2.5AH
B Sealed Lead-Acid
0.00V/0.00AH 0.00V/0.00AH Fail Battery flat.
Transmitter is offline due to bad battery and possible bad fuse.
Kinetix 583 Abbott Drive Broomall, PA 19008
E: eerlandiz@kinetixfire.com
2026-02-02
Pearl Harbor Parks Building H | 25118
Date of Inspection: February-02-2026 Technician: Eddie Erlandiz Type of Inspection: ☐ Monthly ☐ Quarterly ☐ Semi-Annual ☑ Annual ☐ Bi-Annual
Protected Property Inspection Company Name: Pearl Harbor National Park Building H Name: Kinetix Fire Address: 1 Arizona Memorial Place Address: 583 Abbott Drive City: Honolulu City: Broomall State: Hawaii Zip: 96818 State: PA Zip: 19008 Contact: Luther M. Sargent Contact: Inspection/Service Department Phone: 808-528-8754 Phone: 877-223-3000
System Details Manufacturer: Viking Model: J-1 Serial Number: Unknown System Size: 4" Area Covered: Building H General Information Yes No N/A Is the building occupied and the same occupancy since the last inspection? ☑ ☐ ☐ Is the building fully sprinklered and the entire system in service? ☑ ☐ ☐ Is the system unchanged since the last inspection? ☑ ☐ ☐ System in service at time of inspection? ☑ ☐ ☐ System tagged and left in service? ☑ ☐ ☐ System left out of service (will not operate)? ☐ ☑ ☐ System red tagged (non-compliant)? ☐ ☑ ☐ Pertinent parties notified before testing? ☑ ☐ ☐ Pertinent parties notified of test conclusion? ☑ ☐ ☐ Alarm panel clear upon conclusion of inspection? ☑ ☐ ☐ System returned to service? ☑ ☐ ☐ Notes:
Monthly Wet Pipe Inspection Yes No N/A
1. Supply pressure gauge psi? 78 PSI
2. System pressure gauge psi? 58 PSI
3. Gauges appear to be in good condition? ☑ ☐ ☐
4. Control valves in normal open or closed position? ☑ ☐ ☐
5. Control valves properly locked or supervised? ☑ ☐ ☐
6. Control valves accessible? ☑ ☐ ☐
7. Control valves provided with appropriate wrenches? ☐ ☐ ☑
8. Control valves free from external leaks? ☑ ☐ ☐
9. Control valve identification signs in place? ☐ ☑ ☐
10. System control valve sign indicates area served? ☑ ☐ ☐
11. Backflow valves electronically supervised or locked in open position? ☑ ☐ ☐
12. Reduced pressure backflow not in continuous discharge? ☐ ☐ ☑
13. Alarm valve gauges indicate normal supply water pressure? ☑ ☐ ☐
14. Alarm Valve free of physical damage? ☑ ☐ ☐
15. Alarm/trim valves are in appropriate open or closed position? ☑ ☐ ☐
16. Alarm valve retarding chamber or alarm drain not leaking? ☑ ☐ ☐
17. System riser sign indicates area of coverage, location of auxiliary systems and location of
Notes:
Quarterly Wet Pipe Inspection Yes No N/A
1. Adequate drainage provided before flow testing? ☑ ☐ ☐
2. Alarm devices appear free of physical damage? ☑ ☐ ☐
3. Main drain test conducted downstream of backflow? ☑ ☐ ☐
4. Main drain test conducted downstream of PRV? ☐ ☐ ☑
5. Supply water gauge reading before flow (static) PSI? 78 PSI
6. Gauge reading during stable flow (residual) PSI? 58 PSI
7. Time for supply pressure to return to normal (sec)? 3 Seconds
8. Full flow pressure (residual) < 10% reduction from prior or original test? ☐ ☐ ☑
9. Hydraulic nameplate attached and legible? ☑ ☐ ☐
10. Pressure reducing control valves indicate open? ☐ ☐ ☑
11. Pressure reducing valve (PRV) not leaking and in good condition? ☐ ☐ ☑
12. PRV maintaining downstream pressure per design? ☐ ☐ ☑
13. PRV handwheel installed and not broken? ☐ ☐ ☑
14. FDC is visible and accessible? ☑ ☐ ☐
15. FDC swivels/couplings undamaged/rotate smoothly? ☑ ☐ ☐
16. FDC plugs/caps in place/undamaged? ☑ ☐ ☐
17. FDC gaskets in place and in good condition? ☑ ☐ ☐
18. FDC identification sign in place? ☑ ☐ ☐
19. FDC check valve not leaking? ☑ ☐ ☐
20. FDC automatic drain valve in place and operating properly? ☐ ☐ ☑
21. FDC clapper is in place and operating properly? ☑ ☐ ☐
22. FDC obstructions removed as necessary? ☑ ☐ ☐
23. FDC has approved locking caps/plugs? ☑ ☐ ☐
24. Inspected interior of FDC if proper caps/plugs are in place? ☑ ☐ ☐
25. Back flushed the FDC (If required per UFC)? ☐ ☐ ☑ Notes:
Semi-Annual Wet Pipe Inspection Yes No N/A
1. Supervisory switches initiated distinct signal during first two hand wheel revolutions or before valve stem moved one-fifth from normal position?
2. Signal restored only when valve returned to normal position? ☑ ☐ ☐
3. Water flow alarm tested and operational? ☑ ☐ ☐
4. Test conducted with inspector's test connection? ☑ ☐ ☐
5. Test conducted with bypass connection (freezing weather)? ☐ ☐ ☑
6. Test conducted per manufacturer's instructions? ☑ ☐ ☐ Notes:
Annual Wet Pipe Inspection Yes No N/A
1. Hangers and seismic bracing appears undamaged and tightly attached? ☑ ☐ ☐
2. Piping appears free of mechanical damage, leakage, corrosion, external loading? ☑ ☐ ☐
3. Sprinklers appear free of leakage, corrosion, foreign materials, paint, and physical damage?
1/2" Chrome 155*F Upright QR Viking 2010 Yes 1/2" Brass 155*F Upright QR Viking 2010 Yes
Control Valve Report ID Type Size Location Open/Close Secured
(Specify) Proper Signage
Condition Comments
Main Riser Control Valve
OS&Y 4" Outside of Building
South near rear electrical room.
Open Supervised Yes Good
6. Glass bulbs appear full of liquid? ☑ ☐ ☐
7. Spare sprinklers are of proper number (at least 6), type and temperature rating? ☑ ☐ ☐
8. Spare sprinklers stored where temperature maximum is 100°F? ☑ ☐ ☐
9. Wrench available for each type of sprinkler? ☑ ☐ ☐
10. Building is secure such as not to expose piping to freezing conditions? ☑ ☐ ☐
11. Adequate heat is provided maintaining temperatures 40° F or higher? ☑ ☐ ☐
12. Date of last FDC hydro test (Performed every 5 years)? Unknown
13. Antifreeze system has a test connection at the most remote portion, the interface with the wet pipe system, and when the capacity exceeds 150 gal. one additional connection for every 100 gal?
14. Antifreeze solution freezing point *F? NA *F
15. Antifreeze solution freezing point after adjustment? NA *F
16. Operating stems of OS&Y (inc. backflow) valves lubricated? ☑ ☐ ☐
17. Valve completely closed and reopened? ☑ ☐ ☐
18. Control valves (inc. backflow and PIV) operated through full range and returned to normal position?
19. PIV's opened until spring or torsion felt in rod? ☐ ☐ ☑
20. PIV's and OS&Y's backed 1/4 turn from full open? ☑ ☐ ☐
21. Backflow prevention assembly forward flow tested? ☐ ☐ ☑
22. System demand flow was achieved through the device? ☐ ☐ ☑
23. Forward flow test conducted at max rate possible (only where connections do not permit full flow test)?
24. Forward flow test conducted without measuring flow (device ≤ 2" and outlet sized to flow system demand)?
25. Backflow preventer Internally inspected (where shortages last > 1 year)? ☐ ☐ ☑
26. Forward flow test satisfied by annual fire pump flow test? ☐ ☐ ☑
27. Backflow flow test conducted as required by the AHJ? ☐ ☐ ☑
28. PRV control valves partial flow test conducted and adequate to unseat valve? ☐ ☐ ☑
29. Are there sprinklers over 50 years old? ☐ ☑ ☐
30. Are there dry sprinklers over 10 years old? ☐ ☐ ☑
31. Are there heads subject for recall? ☐ ☑ ☐
Notes: Spare Head Cabinet located in Building H rear electrical Room for Both Buildings G & H.
Inspection Test Valve
Gate 1" Located on the East corner the Building.
Closed Normally Closed Valve for testing only
Yes Good
Inspection Deficiencies Control valve identification signs in place?
Missing one alarm test line identification sign. Existing Control Valve, Alarm Line and Inspection Test Valve signs are faded and need to be replaced.
Sprinklers appear free of leakage, corrosion, foreign materials, paint, and physical damage?
Painted fire sprinkler head underneath canopy.
Deficiency Images
Kinetix 583 Abbott Drive Broomall, PA 19008
E: eerlandiz@kinetixfire.com
2026-02-03
Pearl Harbor Parks Building I | 25118
Date of Inspection: February-03-2026 Technician: Eddie Erlandiz Type of Inspection: ☐ Monthly ☐ Quarterly ☐ Semi-Annual ☑ Annual ☐ Bi-Annual
Protected Property Inspection Company Name: Pearl Harbor National Park Building I Name: Kinetix Fire Address: 1 Arizona Memorial Place Address: 583 Abbott Drive City: Honolulu City: Broomall State: Hawaii Zip: 96818 State: PA Zip: 19008 Contact: Luther M. Sargent Contact: Inspection/Service Department Phone: 808-528-8754 Phone: 877-223-3000
System Details Manufacturer: Viking Model: J-1 Serial Number: Unknown System Size: 4" Area Covered: Building I General Information Yes No N/A Is the building occupied and the same occupancy since the last inspection? ☑ ☐ ☐ Is the building fully sprinklered and the entire system in service? ☑ ☐ ☐ Is the system unchanged since the last inspection? ☑ ☐ ☐ System in service at time of inspection? ☑ ☐ ☐ System tagged and left in service? ☑ ☐ ☐ System left out of service (will not operate)? ☐ ☑ ☐ System red tagged (non-compliant)? ☐ ☑ ☐ Pertinent parties notified before testing? ☑ ☐ ☐ Pertinent parties notified of test conclusion? ☑ ☐ ☐ Alarm panel clear upon conclusion of inspection? ☑ ☐ ☐ System returned to service? ☑ ☐ ☐ Notes:
Monthly Wet Pipe Inspection…