Attach_2_-_Combined_Plans_and_Inspection_Report.pdf

PDF 17 MB Posted

Attached to
RECOAT LAS VEGAS BAY RAW WATER TANK
Solicitation number
140P8124B0003
Issued by

About this file

This document appears to be an Attachment 2 - Combined Plans and Inspection Report, related to the federal contract opportunity for Recoating the Las Vegas Bay Raw Water Tank at Lake Mead National Recreation Area in Nevada. The key details are as follows:

The contract opportunity is solicitation number 140P8124B0003, issued by the Department of the Interior National Park Service Pacific West Region. The requirement is to recoat the Las Vegas Bay raw water tank. The document provides the combined plans and inspection report for this tank recoating project. It includes details on the tank inspection, necessary repairs, surface preparation, coating system, quality control, and safety requirements. The document appears to be a technical specification or performance work statement outlining the detailed scope of work and standards for the tank recoating services required under this contract opportunity.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

E-mail david@potabledivers.com

Andy Johnson Dive Supervisor

Potable Divers Inc.

PO Box 474

Vernal, UT 84078-0474

Phone: (866) 789-3483

Facilities Management and Engineering

National Park Service, Interior Region 8

Phone: 702-293-8984

Submitted By:

Potable Water Storage Tank

Submitted To:

Lake Mead National Recreation Area H. Scott Bell

Las Vegas Bay

Field Report 20-Jan-23

Underwater Cleaning and Inspection

Concrete Storage Tank

Concrete

Satisfactory Y X N

Earth Covered Y N X

Cracking Y X N

Efflorescence Present Y N X

Spalling Y N X

Scaling Y N X

Exposed Aggregate Y N X

Strength Members

Exposed Y N X

Seams/Joints Good condition

Low Areas No

Conclusion/Discrepancies: The Exterior roof has

Extensive superficial cracks.

Satisfactory Y X N

Construction Aluminum

Coating

Corrosion Y N X

Proper Design Y X N

Locked Y X N

Gasket Y X N

Hinge

Hatch Size 3 FT X 5 FT

Conclusion/Discrepancies Both hatches and gaskets are in good condition.

Satisfactory Y X N

Construction Steel

Coating

Corrosion Y X N

Proper Design Y X N

Screens Y X N

Sealed Edges & Seams Y X N

Cap/Cover Y X N

Conclusion/Discrepancies Screen and vent are in good condition. Minor surface corrosion noted.

EXTERIOR ROOF

ACCESS HATCH

VENTS

Earth Embanked Y X N

Cracking Y X N

Efflorescence Present Y X N

Spalling Y N X

Scaling Y N X

Exposed Aggregate Y N X

Strength Members

Exposed Y N X

Seams/Joints Good condition

Honeycombing Y N X

Conclusion/Discrepancies: The shell is partially earth embanked. Shell is in good condition one small crack with efflorescence prersent.

Construction None

Satisfactory Y N

Coating

Satisfactory Y N

Oxidized Y N

Pitting Y N

Delamination Y N

Corrosion % Y N

Welds/Joints

Supports

Safety Cage/Climb Y N

Conclusion/Discrepancies No exterior ladder.

Coating PVC

Satisfactory Y X N

Oxidized Y N

Pitting Y N

Delamination Y N

Corrosion % Y N X

Welds/Joints

Supports

Screens Y X N

Attachments

Foundation Good condition

Conclusion/Discrepancies Overflow and outfall are in good condition.

OVERFLOW STRUCTURE

EXTERIOR SHELL

EXTERIOR LADDER

Cracking Y N X

Spalling Y N X

Exposed Aggregate Y N X

Erosion / Undermining Y N X

Seismic Restraints None

Corrosion Y N

Tight Y N

Conclusion/Discrepancies Foundation is in good condition no issues noted.

Locations

Coating

Satisfactory Y X N

Oxidized Y N

Pitting Y N

Delamination Y N

Corrosion % Y N

Welds/Joints

Conclusion/Discrepancies

No other man way entires other than the roof access

FOUNDATION

MANWAY ENTRIES

Cracking Y N X

Efflorescence Present Y N X

Spalling Y N X

Scaling Y N X

Exposed Aggregate Y N X

Strength Members

Exposed / Corrosion Y N X

Seams/Joints Good condition

Honeycombing Y N X

Vent Penetration Good condition

Roof Hatch Good condition

Conclusion/Discrepancies: Roof is in good condition no issues noted.

Concrete

Satisfactory Y X N

Cracking Y N X

Efflorescence Present Y N X

Spalling Y N X

Scaling Y N X

Exposed Aggregate Y N X

Strength Members

Exposed / Corrosion Y X N

Seams/Joints Good condition

Honeycombing Y N X

Wall to Roof Seam Good condition

Baffle/Support Walls None

Conclusion/Discrepancies: The shell is in good condition no issues noted. Exposed rebar that is cosmetic.

Construction none

Satisfactory Y N

Spalling Y N

Cracking Y N

Scaling Y N

Honeycombing Y N

Coating Y N

Corrosion % Y N

Seams/Welds

Floor/Base Plates

Conclusion/Discrepancies:

INTERIOR ROOF

INTERIOR SHELL

SUPPORT COLUMNS

Cracking Y N X

Efflorescence Present Y N X

Spalling Y N X

Scaling Y N X

Exposed Aggregate Y N X

Strength Members

Exposed / Corrosion Y N X

Seams/Joints Good condition

Honeycombing Y N X

Floor to Wall Seam Good condition

Conclusion/Discrepancies: The floor is in good condition no issues noted. Sediment depth on average was 1/16 inch

Coating

Satisfactory Y X N

Blistering Y N

Cracking Y N

Peeling Y N

Holidays Y N

Pitting Y N

Corrosion % Y N

Seams/Welds

Conclusion/Discrepancies: No manway entries besides the roof entry hatch.

Construction Steel

Satisfactory Y X N

Coating

Satisfactory Y X N

Blistering Y N X

Cracking Y N X

Peeling Y N X

Holidays Y N X

Pitting Y N X

Corrosion Y N X

Seams/Welds Good conditrion

Safety Cage/Climb Y N X

Conclusion/Discrepancies: No issues noted.

Coated steel ladder.

FLOOR

MANWAY ENTRIES

LADDER

Influent

Construction Steel

Coating

Satisfactory Y X N

Blistering Y N X

Cracking Y N X

Peeling Y N X

Holidays Y N X

Pitting Y N X

Corrosion 10% Y X N

Seams/Welds Fair condition

Conclusion/Discrepancies: The inlet has corrosion.

Effluent

Construction Steel

Coating

Satisfactory Y X N

Blistering Y N X

Cracking Y N X

Peeling Y N X

Holidays Y N X

Pitting Y X N

Corrosion 20% Y X N

Seams/Welds Fair condition

Conclusion/Discrepancies: Outlet has corrosion and moderate pitting.

Drain

Construction Steel

Coating

Satisfactory Y X N

Blistering Y N X

Cracking Y N X

Peeling Y N X

Holidays Y N X

Pitting Y X N

Corrosion 25% Y X N

Seams/Welds Fair condition

Conclusion/Discrepancies: Corrosion with moderate pitting.

APPURTENANCES

Location Entry point

Coating

Satisfactory Y X N

Blistering Y N X

Cracking Y N X

Peeling Y N X

Holidays Y N X

Pitting Y N X

Corrosion 10% Y X N

Seams/Welds Fair condition

Conclusion/Discrepancies: Funnel and flange have surface corrosion.

Based on the results of this underwater inspection and the cleaning which took place, it appears this tank is in full operational condition and should continue to provide a reliable water storage capacity for potable water use with proper maintenance.

PDI concurs with the recommendations of AWWA that all potable water reservoirs or storage tanks be cleaned and inspected at least every five years and in some cases, depending upon source waters, type and quantities of sediment, and presence (or lack thereof) of cathodic protection systems, more frequently.

The following recommendations are made to provide continued, uninterrupted service of your water storage tank:

1 Your tank should be inspected and cleaned every five years, as suggested by the AWWA.

Routine inspections and cleanings provide ample time to perform remedial repairs to abnormalities discovered before having a chance to become problematic.

2 Roof has extensive superficial cracks Recommend applying a coating on the exterior of the roof to prevent water from traveling into the cracks and corroding the rebar that could cause interior spalling of the concrete.

3 Both tanks are in good condition interior recommendation is to install sacraficial anodes to the inlets, outlets and drains of both tanks.

Conclusion

Recommendations

OVERFLOW