Questions_and_Answers_07022021_0005.pdf

PDF 205 KB Posted

Attached to
Sewer Force Main Replacement for Lake Mead NRA Federal contract opportunity
Solicitation number
140P8121R0011
Issued by
Department of the Interior National Park Service Pacific West Region

About this file

This document provides responses to questions submitted for the Sewer Force Main Replacement for Lake Mead NRA solicitation. The wet well plans attached show it has a diameter of 8 feet and the overflow tank an estimated capacity of 10,000 gallons. Observation of surrounding manholes will be needed during shutdowns to check for sewage backing up into gravity lines as the wet well fills. The solicitation seeks replacement of the Cottonwood Cove force main within Lake Mead National Recreation Area for the National Park Service Pacific West Region.

View the file

Other files for this federal contract opportunity

Other files attached to Sewer Force Main Replacement for Lake Mead NRA, newest first.
File Type Posted
Sol_140P8121R0011_Amd_0009.pdf PDF
Questions_and_Answers_07092021_0009.docx DOCX document
Revised_Price_Schedule_06302021_0008.pdf PDF
Sol_140P8121R0011_Amd_0008.pdf PDF
Sol_140P8121R0011_Amd_0007.pdf PDF
Geomembrane_Specs_0007.pdf PDF
CC_All_Valve_Inventory_Rev2_0007.pdf PDF
Questions_and_Answers_07082021_0007.pdf PDF
Lagoon_Liner_As_Builts_0007.pdf PDF
CC_Lagoon_Plans_0007.pdf PDF
Sol_140P8121R0011_Amd_0006.pdf PDF
Sol_140P8121R0011_Amd_0005.pdf PDF
Revision_2_SF_1442_Continuation_Section_A-M_06302021_0004.pdf PDF
Sol_140P8121R0011_Amd_0004.pdf PDF
B11_SITE_VISIT_0003.pdf PDF
Sol_140P8121R0011_Amd_0003.pdf PDF
Revision_1_SF_1442_Continuation_Section_A-M_0003.pdf PDF
Revised_Price_Schedule_06042021_0002.pdf PDF
Sol_140P8121R0011_Amd_0002.pdf PDF
Sewer_Forced_Main_Plans_0001.pdf PDF
Sol_140P8121R0011_Amd_0001.pdf PDF
SF25A.pdf PDF
SF25.pdf PDF
SF24.pdf PDF
Sol_140P8121R0011.pdf PDF
SF_1442_Continuation_and_Attachments.pdf PDF
Show all 26

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Cottonwood Cove Force Main Replacement

140P8121R0011

Submitted Questions: Response #1

Are there any AS‐BUILT plans for the wet well? I am trying to get a capacity of the wet in order to calculate the maximum shutdown times for the connections at the starting valve and lagoon diversion.

Yes. They are attached to this document.

The wet well is 8’ in diameter. The overflow tank is estimated to be 10,000 gallons.

The wet well has gravity lines coming into it. The sewage will back up into the gravity lines as the wet well is filling up. Observation of the surrounding manholes must be made to observe for sewage backing up into the gravity lines during the shutdown operation.