B09_Solicitation_Amendment_1_Attach_1_Fire_Inspection_Report_0001.pdf
PDF 874 KB Posted
- Attached to
- PAIS FY26 REHABILITATE FIRE SUPPRESSION
- Solicitation number
- 140P6326Q0011
About this file
This document is a Job Summary and service report package from Firetrol Protection Systems, Inc. for fire protection system inspection and testing services provided to Padre Island National Seashore's Turtle Lab facility.
The work order (2601-4012) dated February 26, 2026, covers two primary services: Annual Sprinkler Inspection and Annual Backflow Inspection. The inspection was performed by licensed technician Kristin Strangmeyer (License #RME-I-3297835) at 20301 Park Road, Corpus Christi, Texas 78418. The facility operates both wet and dry sprinkler systems with associated backflow prevention assemblies. The inspection revealed multiple deficiencies requiring corrective action: the dry system is overdue for a 3-year air test and 5-year internal inspection; the wet system is overdue for a 5-year internal inspection and fire department connection hydrostatic test; the wet system lacks an Isolation Test Valve (ITV) for the waterflow switch; and the dry system's waterflow switch failed to send a signal to the control panel. A Yellow Tag was issued for the sprinkler system. The inspection results included 100% testing of all device types with most components passing (control valves, tamper switches, main drains, FDC, and alarm check valves), though one waterflow switch on the dry system failed. The invoice dated February 26, 2026 (Invoice #101072492) totaled $2,235.00 for labor ($1,445.00 annual backflow inspection and $790.00 annual sprinkler inspection) with payment terms of 3% discount if paid within 10 days, net 45 days, due by April 12, 2026. The service documentation includes General Terms and Conditions establishing Firetrol's limited liability, one-year warranty on parts and labor, and requirement that the property owner assumes responsibility for system maintenance and any damages from system failure.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sol_140P6326Q0011_Amd_0001.pdf | ||
| Sol_140P6326Q0011.pdf | ||
| B08_Solicitation_attach_2_WD.pdf | ||
| B08_Solicitation_Attach_1_SOW.docx | DOCX document | |
| B08_Solicitation_attach_3_Experience_Questionaire.xls | XLS spreadsheet |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
JOB SUMMARY
From Firetrol Protection Systems, Inc.
4410 Dillon Lane - Suite #38
Corpus Christi, TX 78415
(361) 851-2632 https://www.firetrol.net/
Job No. 45894816
Date 2/26/2026
Type Inspection
PO No.
Job For PADRE ISLAND NATIONAL
SEASHORE
PADRE ISLAND NATIONAL
SEASHORE
20301 PARK RD 22
CORPUS CHRISTI, TX 78418
Job description
Work Order - 2601-4012
Services
Annual Sprinkler Inspection
Annual Backflow Inspection
Disclaimers and Warranties
Unless specifically noted above, the following clarifications and exclusions are part of this quote:
1. This Proposal does not include demolition of devices, cable, etc. associated with the existing system.
2. Submittal drawing work is based on availability of AutoCAD compatible drawings from the Owner. If CAD drawings are not available, Firetrol reserves the right to request additional compensation for floor plan drawing development. Submittal drawing lead time is 6 weeks from date of contract award.
3. This Proposal does not include applicable sales tax.
4. This Proposal does not include applicable permits.
5. This Proposal does not include performance or payment bonds.
6. This Proposal does not include labor or material to install phone lines to the Fire Alarm Control Panel.
7. This Proposal does not include 120 VAC work. All 120 VAC for all panels to be provided by the others.
8. This Proposal does not include premium time; overtime or holiday work required as a result of project delays created by others will be justification for a Change Order.
9. This Proposal does include conduit, raceways, J hooks, sleeves, wire mold, rough-in boxes, back boxes, tile bridges, etc. as required for installation.
10. This Proposal does not include access panels or penetrations, cutting, or coring. These items shall be provided and installed by others.
11. This Proposal does not include UL or FM Global Certifications for system installation. All equipment will be UL Listed as required.
12. This Proposal does not include painting, patching, sheetrock repairs, etc. of any kind. This work shall be provided by others.
13. This Proposal does not include new ceiling tiles. Firetrol will do it best to not damage existing tile during removal and replacement. Tiles needing to be replaces due to the removal of old devices will be by others.
14. This Proposal does include fire stopping for penetrations made by Firetrol. All other fire rated caulking shall be provided and installed by others.
15. This Proposal does not include specialty lifts, scaffolding, etc. for access to high areas. Any specialty lifts or scaffolding will be provided by others.
16. All H.V.A.C./Electrical wiring, interlock wiring and power wiring as may be required to interface or power other building systems not provided.
Firetrol will provide relays and monitoring modules as required by specifications to be connected by others.
17. Cancellation Charges, in the event of project cancellation after award, Firetrol Protection Systems will invoice for any costs in place (i.e.
engineering, project management, material returns, etc.).
18. This Proposal includes a one (1) year Standard Parts and Labor Warranty.
19. This Proposal is good for 30 days and subject to repricing thereafter.
20. All work shall be subject to Firetrol Protection Systems, Inc. General Terms and Conditions.
GENERAL TERMS & CONDITIONS
Firetrol Protection Systems, Inc. recommends that the owner or owners representative follow all applicable state and local regulations and applicable NFPA standards for inspection, testing, and maintenance for all life safety system(s) on their property which may not be included in this service.
Please be advised that all system devices are required by the applicable NFPA standards to be inspected and/or tested 100%. The owner or owners representative is expected to provide access to all areas, if access is not provided, there may be an additional charge for a return trip to complete the inspection.
I have read and understand the terms and conditions below, and acknowledge that they are an integral part of this service / inspection agreement.
In response to the AIM Act and its findings regarding PFAS, PFOA, and PFOS. Firetrol will no longer drain, flush, disassemble, or remove piping or other apparatus that contain or been exposed to AFFF concentrate or solution. All such materials shall remain in the possession of the owner/client. Firetrol assumes no liability whatsoever for any claims related to the owner’s past, current or future PFAS, PFOA, and PFOS containing foam suppression systems.
NOTE: The Terms and Conditions below are not applicable if there is an existing agreement already in place at the time of this service and/or inspection. This may include a Master Service Agreement, Customer Purchase Agreement, or a Federal, State or Local Agreement such as GSA, NASPO, BuyBoard, TXMAS, etc.
The Seller makes no warranties, express, or implied, including, without limitation, warranties of merchantability and warranties of fitness for a particular purpose. No promise not contained herein or affirmation of fact made by any employee, agent or representative of the Seller shall constitute a warranty by the Seller or give rise to any liability or obligation. Seller's liability to purchaser for personal injury, death, or property damage arising from the performance under this contract shall be limited to the contract price.
Under no circumstances shall Seller have any responsibility, liability, or obligation for the performance or non-performance of the fire protection system.
Purchaser understands, acknowledges, and agrees that Seller is not an insurer or guarantor of the fire protection system and that Seller's inspection may not reveal all defects or deficiencies, if any, in the fire protection system. In no event shall Seller be liable for any special, indirect, incidental, consequential, or other damages to any third person including, but not limited to, purchaser(s) customers, invitees, or employees, irrespective of whether such claims or actions are based upon contract, warranty, negligence, tort, strict liability, or otherwise.
Any inspection and/or testing services provided are NOT a system survey or engineering analysis of the system and/or its design. Inspection and testing services that may be provided are designed to determine the functionality of the inspected systems at the time of the inspection/test, as per state requirements. Any Inspection and/or testing services provided are not intended to reveal design or installation flaws or code compliance violations.
ENTIRE CONTRACT
The provisions herein contained constitute all of the terms and conditions of this contract. No changes or additions hereto shall be binding upon Seller unless in writing and signed by an authorized representative of Seller. Any terms or conditions of Purchaser's order inconsistent herewith or in addition hereto shall be of no force and effect and are hereby expressly rejected and Purchaser's order shall be governed by only the terms and conditions appearing herein.
PROPOSALS AND CONTRACT
Seller's proposals, when accepted, and any resulting contract, are not subject to cancellation, suspension or reduction in amount, except with Seller's written consent and upon terms, which reimburse Seller for work performed, reasonable overhead and lost profit.
PAYMENT
Terms of payment have been set at net 10-days. A service charge will be charged and added to the prices on all payments past due and owed by the
Purchaser under this contract, at a rate of 25% per annum, or if such rate is prohibited under applicable law, then at such maximum rate as is under applicable law. Purchaser shall pay all attorney's fees incurred in the collection of past due accounts.
LOCAL AHJ RECORD KEEPING FEES
Unless specifically noted in your proposal, the Contract Pricing does not include any record keeping or processing fees incurred by the local AHJ and will be added to your invoices as applicable.
DELAYS
Seller shall not be liable for any damage or penalty for delays in work due to acts of God, acts or omissions of the Purchaser, acts of civil or military authorities, Government regulations or priorities, fires, floods, epidemics, quarantine restrictions, war, riots, strikes, differences with workmen, accidents to machinery, car shortages, inability to obtain necessary labor, materials or manufacturing facilities, vendor supply chain issues, delay in transportation, defaults of Seller's subcontractors, failure of or delay in furnishing correct or complete information by Purchaser with respect to location or other details of work to be performed hereunder, impossibility or impracticability of performance or any other cause beyond the control of Seller, whether or not similar to the foregoing. In the event of any delay caused as aforesaid, the completion shall be extended for a period equal to any such delay, and this contract shall not be void or avoidable as a result of any such delay. In case work is temporarily discontinued by reason of any of the foregoing, all unpaid installments of the contract price less an amount equal to the value of material and labor not furnished shall be due and payable upon receipt of the invoice by Purchaser.
EXCAVATION
In the event the work herein includes excavation, the Purchaser shall pay as an extra to the contract price the cost for any additional work performed by the seller due to water, quicksand, rock or other unforeseen obstruction encountered or if shoring is required.
SITE FACILITIES
Purchaser shall furnish all necessary facilities for performance of its work by Seller, adequate space for storage and handling of material, light, water, heat, local telephone, watchman and crane and elevator service, if available, and necessary permits. Where wet pipe system is installed, Purchaser shall supply and maintain sufficient heat to prevent freezing of the system.
STRUCTURE AND SITE CONDITIONS
While employees of Seller will exercise reasonable care in this respect, Seller shall be under no responsibility for loss or damage due to the character, condition or use of foundations, walls, or other structures not erected by it or resulting from excavation in proximity thereto, nor for damage resulting from concealed piping, wiring, fixtures or other equipment or conditions or water pressure. All shoring or protection of foundations, walls, or other structures subject to being disturbed by any excavation required hereunder shall be the responsibility of the Purchaser unless otherwise specified. Purchaser warrants the sufficiency of the structure to support the fire alarm and/or fire sprinkler system and its related equipment. The purchaser shall have all things in readiness for service, including, but not limited to, other materials, floor or suitable working base, connections, and facilities at the time technician is onsite.
In the event the purchaser fails to have all things in readiness for service at the job site, the Purchaser shall reimburse Seller for any and all expenses caused by such failure to have such things in readiness. Failure to make areas available to Seller during performance in accord with schedules, which are the basis of Seller's proposal, shall be considered a failure to have all things in readiness for erection in accord with the terms of this contract.
INTERFERENCES
Purchaser shall be responsible to coordinate the work of other trades (ducting, piping, electrical, etc.) and Purchaser shall be responsible for additional costs incurred by Seller arising out of interferences to Seller's work caused by such other trades.
LIMITATIONS OF LIABILITY
The Seller makes NO WARRANTIES, EXPRESS, OR IMPLIED, INCLUDING, WITHOUT LIMITATION, WARRANTIES OF MERCHANTABILITY AND
WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE. No promise not contained herein or affirmation of fact made by any employee, agent or representative of the Seller shall constitute a warranty by the seller or give rise to any liability or obligation. Seller's liability to Purchaser for personal injury, death, or property damage arising from the performance under this contract shall be limited to the contract price. Purchaser shall hold Seller harmless from any and all third-party claims for personal injury, death or property damage, arising from Purchaser's failure to maintain these systems or keep them in operative condition, whether based upon contract, warranty, tort, strict liability or otherwise. In no event shall Seller be liable for any special, indirect, incidental, consequential or liquidated, penal or any economic damage of any character, including but not limited to loss of use of the Purchaser's property, lost profits or lost production, whether claimed by the Purchaser or by any third party, irrespective of whether claims or actions for such damages are based upon contract, warranty, negligence, tort, strict liability or otherwise.
WARRANTY
Seller agrees that for a period of one (1) year after completion of said service it will, at its expense, repair or replace defective materials or workmanship supplied or performed during this service/repair by Seller. Upon completion of the service work, the system will be turned over to the Purchaser fully inspected, tested, and in operative condition. As it is thereafter the responsibility of the Purchaser to maintain it in operative condition, it is understood that the Seller does not guarantee the operation of the system. Seller further warrants the products of other manufacturers supplied hereunder, to the extent of the warranty of the respective manufacturer but no longer than one-year. ALL OTHER EXPRESS OR IMPLIED WARRANTIES OF MERCHANTABILITY
OF FITNESS OR OTHERWISE ARE HEREBY EXCLUDED.
MODIFICATIONS AND SUBSTITUTIONS
Seller reserves the right to modify material of Seller's design sold hereunder and/or the drawings and specifications relating thereto, or to substitute material of later design to fulfil this contract providing that the modifications or substitutions will not materially affect the performance of the material, or lessen in any way the utility of the material to the Purchaser.
SEVERABILITY
Should any part, term, or provision of this contract be found by the courts to be illegal or in conflict with any law of the state where made, the validity of the remaining portions or provisions shall not be affected thereby.
ASSIGNMENT
Any assignment of this contract by Purchaser without the written consent of Seller shall be void. Seller may assign this contract to its subsidiaries and affiliates.
CHANGES, ALTERATIONS, ADDITIONS
Changes, alterations, and additions to the plans, specifications, or construction schedule for this contract shall be invalid unless approved in writing by
Seller. Changes approved by Seller, which increase or decrease the cost of work to Seller, shall constitute a corresponding increase or decrease in the contract price as herein provided. The value of additional work shall be agreed upon in writing prior to the performance of said work. However, if no agreement is reached prior to the performance of additional work approved in the manner herein described, and Seller elects to continue performance so as to avoid delays, then the estimate of Seller's Estimating Department as to the value of the work shall be deemed accepted by the Purchaser.
PRICES
In addition to the prices specified herein, Purchaser shall pay for all extra work requested by Purchaser or made necessary because of incompleteness of or inaccuracy in plans or other information submitted by Purchaser with respect to location, type of occupancy, or other details of work to be performed hereunder. In the event the layout of Purchaser's facilities has been altered, or is altered by Purchaser prior to completion of this contract, Purchaser shall advise Seller, and prices, delivery, and completion dates quoted herein shall be changed by Seller as may be required.
LEGAL NOTICE
For the purposes of any notice permitted or required to be given hereunder, such notice or notices shall be deemed given when received.
CLAIMS
Any claims against Seller arising hereunder shall be deemed waived unless they are presented in writing, with particulars, within ten (10) days after they arise.
TERMS AND CONDITION/TECHNICAL SPECIFICATIONS
The terms and conditions specified herein shall be in addition to those put in Seller's technical specifications and Seller's authorized representative shall resolve any inconsistencies.
ARBITRATION
At the option of the Seller, any controversy or claim arising out of or relating to this contract, or the breach thereof, shall be settled by arbitration in accordance with the Rules of the American Arbitration Association, and judgment upon the award rendered by the Arbitrator(s) may be entered in any court having jurisdiction thereof. Any arbitration proceeding shall be held in the same jurisdiction as the location of the work performed.
OVERTIME
Unless otherwise specified by Purchaser, all service work will be performed during regular working hours. If Purchaser shall require any overtime labor, Purchaser agrees to reimburse Seller for the overtime premium cost including all related payroll costs, plus Seller's overhead and profit, payable monthly, one (1) month after overtime expense was incurred.
PROPRIETARY DATA
All specifications, drawings, designs, descriptive matter, and other data furnished by Seller to Purchaser pertaining to the work proposed herein shall be deemed proprietary and shall be kept in confidence by Purchaser and shall not be disclosed to any third party except as may be necessary in the performance of any contract with the Seller. In the event Seller requests the return of any such proprietary material and/or any reproductions thereof, Purchaser shall promptly return the same to Seller.
DEFAULT
In case of any default by Purchaser, Seller shall be entitled to payment for all work performed, all termination costs incurred, and any other costs incurred by Seller, including overhead and profit. All such remedies of Seller are cumulative and not exclusive. Default by Purchaser shall consist of: Failure to pay any installment of price when due, no demand being necessary, or any act or omission on the part of Purchaser whereby Seller is prevented from completing said service, or receivership, bankruptcy, assignment for the benefit of creditors or any other form of insolvency proceedings by or against
Purchaser or in case said premises or said system shall be attached, liened or seized by process of law and such attachment or lien shall not be vacated or seizure terminated within ten (10) days after its occurrence.
BACK CHARGE
No charges shall be levied by the Purchaser against the Seller unless, (48) hrs prior written notice is given to Seller to correct any alleged deficiencies/clean-up which necessitates such charges and unless deficiencies are the direct fault of Seller.
OSHA
Purchaser will indemnify and hold harmless the Seller from and against any claims, demands or damages resulting from the enforcement of the
Occupational Safety Health Act (Public Law 91-596), unless said claims, demands or damages are a direct result of causes within the exclusive control of
Seller.
Property owner assumes all liability for any damages that may be related to the failure (or partial failure) of their fire protection/life safety system(s) due to any deficiency or impairment (whether identified herein or not.) Firetrol Protection Systems, Inc. will provide you a quotation upon request to repair all deficiencies/impairments noted. Should you have any questions or require any additional information, please do not hesitate to contact our office.
4410 DILL0N LANE SUITE 38
Corpus Christi, TX X 78415 Office (361) 851-2632 Fax (361) 851-1886
WO# 2601-4012
Site Name Main Contact
Street Address Contact Title
City State Zip Contact phone #
Contact email
On this day, Firetrol Protection Systems, Inc. performed service and/or tested and inspected your facility's system. It is our duty to inform you that your facility's system is not in compliance as noted below
THE LOCATION LISTED ABOVE HAS BEEN ISSUED THE FOLLOWING TAG:
Fire Alarm: Standpipe:
Corrected: Corrected:
Sprinkler: X Kitchen:
Corrected: Corrected:
Extinguisher:
Corrected:
corrective action.
Technician Signature:
Printed Name:
Lic #:
Date:
361-9498173
ONSITE
GREG SMITH
2/26/2026
RMEI-3297835
Kristin Strangmeyer
2/26/2026
Maint
Greg Smith
361-851-2632 to schedule corrective service. Until these deficiencies are corrected, Firetrol relinquishes all responsibilities and We would appreciate the opportunity to repair your system and bring it into compliance. Please contact our Service Department at liabilities. Your prompt attention to this matter is greatly appreciated.
Customers Signature:
Printed Name:
Dry system is over due for a 3 yr air test and a 5 yr internal Wet system is over due for a 5 yr internal and fdc hydro test
Wet system does not have an ITV for testing waterflow Dry system's waterflow did not send signal to panel.
Per state requirement we are required to inform you and the local authority having jurisdiction (Local Fire Marshal) to take
NON-COMPLIANT SYSTEM NOTIFICATION
20301 PART ROAD 22
PADRE ISLAND NATIONAL SEASHORE TURTLE LAB
Title:
Date:
Corpus Christi TX 78418
GREGORY_A_SMITH@NPS.GOV
2/20/2026
Red Tag Yellow Tag
The above indicates the tag has been attached (removed) to the system and that your system has the following deficiencies (corrections):
Red Tag Yellow Tag conditions from tag dated:
conditions from tag dated:
conditions from tag dated:
conditions from tag dated:
conditions from tag dated:
SCR-G-0292
ACR-1751168
ECR-1751432
RETIRED/ADDED DEVICES
No ITV for waterflow switch on wet system. No 5 year or 3 year ITM tag for either riser. Waterflow switch on dry system did not come in.
DEVICE DEFICIENCIES
2/26/2026
CUSTOMER
SIGNATURE
CUSTOMER
NAME Brian Slate DATE
INSPECTOR
SIGNATURE 2/26/2026DATEKristin Strangmeyer
INSPECTOR
NAME
RECOMMENDATIONS
Recommending the fdc sign get replaced by next inspection. Its faded.
No retired or added devices in this inspection
100% 4 0 0 100%
NFPA 25
NFPA 25 FDC 1
NFPA 25
Main Drain 2NFPA 25
Alarm Check Valve 2
NFPA 25
Tamper Switch 4
Waterflow Switch 3
Control Valves 4
Air/Water Gauges 4 4 0 0 100%NFPA 25
2 0 1 0
0 100% 0 100%
2 0 0 100%
0 100%
2/26/2026
2/26/26 8:00 AM Inspection/Test Completion Date/TimeInspection/Test Start Date/Time
DEVICE INSPECTION RESULT SUMMARY
NFPA 25
10:00 AM
2/26/2027Next Inspection Date:Corpus Christi Tx 78418
NOT TESTEDFAILEDPASSED % INSPECTEDTEST PERFORMED DEVICE TYPE TOTAL
4 0 0
City, State, Zip:
2/26/26
Fire Sprinkler Systems * Standpipes * Fire Pumps * Fire Alarm & Detection Systems Specialty Fire Suppression Systems * Fire Extinguishers & Cabinets * Central Station Monitoring
Address:
Facility Name:
Customer:
ANNUAL SPRINKLER INSPECTION & TEST REPORT
20301 Park Rd
Turtle Lab
Padre Island National Seashore Inspector:
Inspection Performed Under NFPA 25 2014 & NFPA 72 2010
RME-I-3297835
Kristin Strangmeyer
Date of Inspection:
License #:
4410 Dillon Lane #38, Corpus Christi, TX 78415 Phone 361-851-2632; Fax 361-851-1886
ECR-1751432
4 Passed
Riser Room Wet System Control Valve Supervised Victaulic Control Valve Passed
Riser Room Dry System Control Valve Supervised Victaulic Control Valve
2/26/2027
CONTROL VALVES INSPECTION & TEST
# LOCATION DESCRIPTION
SECURED
METHOD MAKE
City, State, Zip: Corpus Christi Tx 78418 Next Inspection Date:
Passed
DEVICE
TYPE RESULT
Riser Room Backflow Valve #1 Supervised Victaulic Control Valve Passed
Riser Room Backflow Valve #2 Supervised Victaulic Control Valve
ANNUAL SPRINKLER INSPECTION & TEST REPORT
Facility Name: Turtle Lab License #: RME-I-3297835
Inspection Performed Under NFPA 25 2014 & NFPA 72 2010
Address: 20301 Park Rd Date of Inspection: 2/26/2026
Customer: Padre Island National Seashore Inspector: Kristin Strangmeyer
ECR-1751432
ANNUAL SPRINKLER INSPECTION & TEST REPORT
Facility Name: Turtle Lab License #: RME-I-3297835
Address: 20301 Park Rd Date of Inspection: 2/26/2026
Inspection Performed Under NFPA 25 2014 & NFPA 72 2010
Customer: Padre Island National Seashore Inspector: Kristin Strangmeyer
City, State, Zip: Corpus Christi Tx 78418 Next Inspection Date: 2/26/2027
Riser Room Backflow Valve #2 N/A Victaulic Butterfly Passed
TAMPER SWITCH INSPECTION & TEST
# LOCATION DESCRIPTION ADDRESS MAKE DEVICE TYPE RESULT
Riser Room Backflow Valve #1 N/A Victaulic Butterfly Passed
Passed
Riser Room Dry System Control Valve N/A Victaulic Butterfly Passed
Riser Room Wet System Control Valve N/A Victaulic Butterfly
ECR-1751432
N/A Potter Vane
WATERFLOW SWITCH INSPECTION & TEST
# LOCATION DESCRIPTION ADDRESS MAKE DEVICE TYPE RESULT
ANNUAL SPRINKLER INSPECTION & TEST REPORT
Facility Name: Turtle Lab License #: RME-I-3297835
Inspection Performed Under NFPA 25 2014 & NFPA 72 2010
Customer: Padre Island National Seashore Inspector:
20301 Park Rd Date of Inspection:
Kristin Strangmeyer
Yes What was the number of seconds that the water flow signal was delayed? N/A Is flow switch free of damage with its electrical connections secure?
Passed
2/26/2026
City, State, Zip: Corpus Christi Tx 78418 Next Inspection Date: 2/26/2027
Address:
Riser Room Wet System
Open test connection/bypass. Did water flow activate the alarm? No
Riser Room Wet System at Top of Retard Chamber N/A Potter Pressure Passed
Is flow switch free of damage with its electrical connections secure? Yes What was the number of seconds that the water flow signal was delayed? 15 Open test connection/bypass. Did water flow activate the alarm? Yes
Open test connection/bypass. Did water flow activate the alarm? No
Failed
Is flow switch free of damage with its electrical connections secure? Yes What was the number of seconds that the water flow signal was delayed? 0
Riser Room Dry System N/A Potter Pressure
ECR-1751432
Corpus Christi Tx 78418 Next Inspection Date: 2/26/2027
Address: 20301 Park Rd Date of Inspection: 2/26/2026
City, State, Zip:
SIZE STATIC PSI
MAIN DRAIN INSPECTION & TEST
# LOCATION DESCRIPTION
Return Time to
Static PSI RESULT
RESIDUAL
PSI
ANNUAL SPRINKLER INSPECTION & TEST REPORT
Facility Name: Turtle Lab License #: RME-I-3297835
Inspection Performed Under NFPA 25 2014 & NFPA 72 2010
Customer: Padre Island National Seashore Inspector: Kristin Strangmeyer
Do results differ by more than 10% from previous test? No
Riser Room Wet System
Passed
5 Passed1-1/4" 65 40
Do results differ by more than 10% from previous test? No
Riser Room Dry System 2" 55 50
ECR-1751432
Inspection Performed Under NFPA 25 2014 & NFPA 72 2010
# LOCATION RESULTCONNECTION TYPE
2/26/2026
Inspector:
By Entrance Passed
DESCRIPTION MAKE
Dual SwivelsN/A
e. Is identification signs are in place ?
Yes
g. Ball drip valve is functional ?
Kristin Strangmeyer
City, State, Zip: Corpus Christi Tx 78418 Next Inspection Date: 2/26/2027
(FDC) FIRE DEPARTMENT CONNECTIONS INSPECTION & TEST
Facility Name: Turtle Lab License #: RME-I-3297835
Address: 20301 Park Rd Date of Inspection:
ANNUAL SPRINKLER INSPECTION & TEST REPORT
d. Are gaskets in place in good condtion ?
c. Are plugs/caps are in place ?
N/A
Yes Yes Yes
f. FDC clapper is functional?
Yes Yes
b. Do coupling/swivels operate correctly ?
a.Is FDC Visible / Accessible ?
4" Threaded Dual 2.5" Swivel
Customer: Padre Island National Seashore
ECR-1751432
ALARM CHECK VALVES INSPECTION & TEST
# LOCATION BRAND MODEL SIZEDESCRIPTION (WET OR DRY?)
Riser Room Wet System
RESULT
Tyco CV-2 2.5" Passed
Kristin Strangmeyer
ANNUAL SPRINKLER INSPECTION & TEST REPORT
Facility Name: Turtle Lab License #: RME-I-3297835
Inspection Performed Under NFPA 25 2014 & NFPA 72 2010
Customer: Padre Island National Seashore Inspector:
Address: 20301 Park Rd Date of Inspection: 2/26/2026
City, State, Zip: Corpus Christi Tx 78418 Next Inspection Date: 2/26/2027
PassedRiser Room Dry System Tyco DPV-1 4"
ECR-1751432
Kristin Strangmeyer
ANNUAL SPRINKLER INSPECTION & TEST REPORT
Facility Name: Turtle Lab License #: RME-I-3297835
Inspection Performed Under NFPA 25 2014
Customer: Padre Island National Seashore Inspector:
Address: 20301 Park Rd Date of Inspection: 2/26/2026
City, State, Zip: Corpus Christi Tx 78418 Next Inspection Date: 2/26/2027
Riser Room Passed
AIR/WATER GAUGES INSPECTION
# LOCATION RESULTDESCRIPTION DEVICE TYPE GAUGE READING
65WaterWet System Top Gauge
Wet System Bottom Gauge
Riser Room PassedDry System Bottom Gauge Water 65
Riser Room Passed30AirDry System Top Gauge
Riser Room Passed65Water
ECR-1751432
41 Water motor gong functioned properly?
Control valve sealed, locked or supervised?
Inspection Performed Under NFPA 25 2014 & NFPA 72 2010
ANNUAL SPRINKLER INSPECTION & TEST REPORT
Hydraulic data nameplate—securely attached to riser/legible?
Address:
Inspector:Customer: Kristin Strangmeyer
Facility Name: Turtle Lab License #: RME-I-3297835
Padre Island National Seashore
20301 Park Rd
City, State, Zip: Corpus Christi Tx 78418 Next Inspection Date:
Control valve free from damage or leaks?
Date of Inspection: 11/15/2023
2/26/2027
Passed
N/A
Inspection Questions
Wet System
Passed PassedDo gauges show normal pressure?
Dry System 1Sprinkler System Type
Control valve in the correct (open or closed) positon?
Passed
N/A
Passed
Alarm check valve retard chamber/alarm devices not leaking?
Passed Control valve Accessible?
Passed
Passed Passed PassedAlarm check valve Accessible?
N/A
Exterior of dry pipe valves is free of damage, trim valves are in correct open or closed position, and intermediate chamber is not leaking?
Passed
Passed
Alarm check valve free from damage or leaks?
Control valve proper signage?
N/A
N/A N/A
Passed
Main drain test—if the sole supply is through a backflow preventer? (See main drain test page)
Alarm devices—free of damage?
Sprinklers tested or replaced per appropriate testing schedule?
Hose racks—inspected per NFPA 1962?
Pressure reducing valve is in the open position/mot leaking?
No damage or leaks to sprinkler heads?
Sprinkler heads free of corrosion, foreign material, or paint?
Sprinkler heads installed in proper orientation?
Sprinkler heads have fluid in glass bulbs?
Pressure reducing valve is maintaining downstream pressure?
Pressure reducing valve is in good condition?
Priming Water - test level Quick opening device tested?
Dry pipe valve interior—following trip test?
Passed Passed Passed Passed
Water Supply Source Passed Building—wet piping not exposed to freezing temperatures? N/A
Pipes & fittings are in good condition/no external corrosion? Passed No leaks or mechanical damage to pipes or fittings? Passed Correct alignment—no external loads? Passed
Passed Spare sprinklers—proper number and type. Complete with wrench? Passed Hangers and seismic bracing—not damaged or loose? Passed
N/A
Building—prior to onset of freezing weather—all openings are closed, no water-filled pipe is exposed to freezing temps
N/A 5 Year Inspection completed? N/A
Next InspectionN/A
Visual Activated?
YesYesYesYes
Yes
TycoBy Front Entry Signal Delayed
Location/Description Make Test Valve Closed? Alarm Leak Tight?
Passed Does location have heat tracing? N/A Specific gravity or anti-freeze system Tested? Proper identification? N/A
3 Year Inspection completed? N/A
Backflow preventer—flow test? Passed
All control valves operated through full range of motion and returned to normal position? Passed Specific gravity or anti-freeze system (if present)? N/A Backflow preventer—test? Passed
Next Inspection
ECR-1751432
Inspection Performed Under NFPA 25 2014 & NFPA 72 2010
NFPA 8.3.3
Annual Flow
Testing
8.3.3.2 The pertinent visual observations, measurements, and adjustments specified in the following checklists shall be conducted annually while the pump is running and flowing water under the specified output condition:
3. For electric motor–driven pumps, the pump shall not be shut down until the pump has run for 10 minutes.
4. For diesel motor–driven pumps, the pump shall not be shut down until the pump has run for 30 minutes.
c. Record the simultaneous (approximate) readings of pump suction and discharge pressures and pump discharge flow
b. Record the electric motor voltage and current (all lines)
a. Record the electric motor voltage and current (all lines)
2. At each flow condition:
b. Check the pressure relief valve (if installed) for proper operation
a. Check the circulation relief valve for operation to discharge water
Chapter 6 Standpipe and Hose Systems
NFPA 25 6.2.2
Gauges 6.2.2.2 Gauges on automatic dry standpipe systems shall be inspected weekly to ensure that normal air or nitrogen and water pressure are being maintained.
6.2.2.3 Where air pressure supervision is connected to a constantly attended location, gauges shall be inspected monthly.
6.2.2.1 Gauges on automatic wet and semiautomatic dry standpipe systems shall be inspected quarterly to ensure that they are in good condition and that normal water supply pressure is being maintained.
Chapter 8 Fire Pumps
1. At no-flow condition (churn) as follows:
ANNUAL SPRINKLER INSPECTION & TEST REPORT
Customer: Padre Island National Seashore Inspector: Kristin Strangmeyer
Facility Name: Turtle Lab
City, State, Zip: Corpus Christi Tx 78418 Next Inspection Date: 2/26/2027
License #: RME-I-3297835
Address: 20301 Park Rd Date of Inspection: 2/26/2026
TEST METHOD - Reference NFPA 25 2014
5.2.4.1* Gauges on wet pipe and deluge sprinkler systems shall be inspected quarterly to ensure that they are in good condition and that normal water supply pressure is being maintained.
NFPA 25 5.2 5.2.2* Pipe and Fittings. Sprinkler pipe and fittings shall be inspected annually from the floor level.
Chapter 5 Sprinkler Systems
5.2.4.2 Gauges on dry and preaction systems shall be inspected weekly to ensure that normal air or nitrogen and water pressures are being maintained.
5.2.4.3 Where air pressure supervision is connected to a constantly attended location, gauges shall be inspected monthly.
NFPA 25 5.3.1
Sprinklers
5.3.1.1* Where required by this section, sample sprinklers shall be submitted to a recognized testing laboratory acceptable to the authority having jurisdiction for field service testing.
See Table 5.1.1.2 & section 5.3.1 for additional details.
NFPA 25 5.2.6* 5.2.6* Hydraulic Design Information Sign. The hydraulic design information sign shall be inspected quarterly to verify that it is provided, attached securely to the sprinkler riser, and is legible.
5.2.5 Waterflow Alarm and Supervisory Signal Initiating Device. Waterflow alarm and supervisory signal initiating devices shall be inspected quarterly to verify that they are free of physical damage.
NFPA 25 5.2.5
Waterflow Alarm and Supervisory
5.2.4.4* For dry pipe or preaction systems protecting freezers with two air pressure gauges on the air line(s) between the compressor and the dry pipe or preaction valve, the air pressure gauge near the compressor shall be compared weekly to the pressure gauge above the dry pipe or preaction valve.
NFPA 25 5.2.4
Gauges
ECR-1751432
ANNUAL SPRINKLER INSPECTION & TEST REPORT
Customer: Padre Island National Seashore Inspector: Kristin Strangmeyer
Inspection Performed Under NFPA 25 2014 & NFPA 72 2010
Facility Name: Turtle Lab License #: RME-I-3297835
Address: 20301 Park Rd Date of Inspection: 2/26/2026
Chapter 13 Valves, Valve Components, and Trim
NFPA 25 13.2.5
Main Drain Test
13.2.5.2 In systems where the sole water supply is through a backflow preventer and/or pressure-reducing valves, the main drain test of at least one system downstream of the device shall be conducted on a quarterly basis.
NFPA 25 13.2.6
Waterflow 13.2.6.1 Mechanical waterflow alarm devices, including but not limited to water motor gongs, shall be tested quarterly.
City, State, Zip: Corpus Christi Tx 78418 Next Inspection Date: 2/26/2027
TEST METHOD - Reference NFPA 25 2014
NFPA 13.3.2
Inspections
13.3.2.1 All valves shall be inspected weekly.
13.3.2.1.1 Valves secured with locks or supervised in accordance with applicable NFPAstandards shall be permitted to be inspected monthly.
13.3.2.1.2 Control valve supervisory alarm devices shall be inspected quarterly to verify that they are free of physical damage.
NFPA 25 13.4.1
13.4.1.1* Alarm valves and system riser check valves shall be externally inspected monthly and shall verify the following:
(1) The gauges indicate normal supply water pressure is being maintained.
(2) The valve is free of physical damage.
(3) All valves are in the appropriate open or closed position.
(4) The retarding chamber or alarm drains are not leaking.
13.4.3.1.6 The preaction or deluge valve shall be externally inspected monthly
(1) The valve is free from physical damage.
(2) All trim valves are in the appropriate open or closed position.
(3) The valve seat is not leaking.
(4) Electrical components are in service.
NFPA 25 13.4.4
13.4.4.1.4 The dry pipe shall be externally inspected monthly to verify the following:
(1) The valve is free of physical damage.
(2) All trim valves are in the appropriate open or closed position.
(3) The intermediate chamber is not leaking
For additional guidance on performing tests, see NFPA 72-2010: Table 14.4.5 and NFPA 25-2014: Table 5.1.1.2 & 8.1.1.2
NFPA 25 13.6
Backflow
Prevention Assemblies
13.6.1 Inspection. Inspection of backflow prevention assemblies shall be as described in 13.6.1.1 through 13.6.1.4.
13.6.1.1 The isolation valves on double check assemblies (DCA) and double check detector assemblies (DCDA) shall be inspected weekly to ensure that the valves are in the normal open position.
13.6.1.1.1 Valves secured with locks or electrically supervised in accordance with applicable NFPA standards shall be inspected monthly.
NFPA 25 13.7 Fire Department Connections
13.7.1 Fire department connections shall be inspected quarterlyto verify the following:
(1) The fire department connections are visible and accessible.
(2) Couplings or swivels are not damaged and rotate smoothly.
(3) Plugs or caps are in place and undamaged.
(4) Gaskets are in place and in good condition.
(5) Identification signs are in place.
(6) The check valve is not leaking.
(7) The automatic drain valve is in place and operating properly.
(8) The fire department connection clapper(s) is in place and operating properly.
(9)*Interior of the connection is inspected for obstructions.
Texas Commission on Environmental Quality
BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT
The following form must be completed for each assembly tested. A signed and dated original must be submitted to the public water supplier for recordkeeping *purposes:
NAME OF PWS:
PWS ID#:
PWS MAILING ADDRESS:
PWS CONTACT PERSON:
ADDRESS OF SERVICE:
The backflow prevention assembly detailed below has been tested and maintained as required by commission regulations and is certified to be operating within acceptable parameters.
TYPE OF BACKFLOW PREVENTION ASSEMBLY (BPA):
☐ Reduced Pressure Principle (RPBA) Reduced Pressure Principle-Detector (RPBA-D) Type II ☐
☐ Double Check Valve (DCVA) Double Check-Detector (DCVA-D) Type II ☐
☐ Pressure Vacuum Breaker (PVB) Spill-Resistant Pressure Vacuum Breaker (SVB)
Manufacturer: Main: Bypass: Size: Main: Bypass:
Model Number: Main: Bypass: BPA Location:
Serial Number: Main: Bypass: BPA Serves:
TEST RESULT
Reduced Pressure Principle Assembly (RPBA)
Type II
Assembly PVB & SVB
PASS ☐ DCVA
Relief Valve Bypass Check Air Inlet Check Valve
FAIL ☐ 1st Check 2nd Check***
Initial Test
Date:
Time:
Held at ____ psid
Closed Tight ☐
Leaked ☐
Held at ____ psid
Closed Tight ☐
Leaked ☐
Opened at ___ psid
Did not open ☐
Held at ____ psid
Closed Tight ☐
Leaked ☐
Opened at ____ psid
Did not open ☐
Did it fully open
(Yes ☐ /No ☐)
Held at _____ psid
Leaked ☐
Repairs and
Materials
Used**
Main:
Bypass:
Test After
Repair
Date:
Time:
Held at ____ psid
Closed Tight ☐
Held at ____ psid
Closed Tight ☐
Opened at ___ psid
Held at ____ psid
Closed
Tight ☐
Opened at ____ psid Held at _____ psid
Reason for test: New ☐ Existing ☐ Replacement ☐ Old Model/Serial #
Is the assembly installed in accordance with manufacturer recommendations and/or local codes? ☐ Yes ☐ No
Is the assembly installed on a non-potable water supply (auxiliary)? ☐ Yes ☐ No
*** 2nd check: numeric reading required for DCVA only
Differential pressure gauge used: Potable: ☐ Non-Potable: ☐
Make/Model: SN: Date tested for accuracy :
Remarks:
Company Name: Licensed Tester Name
(Print/Type):
Company Address: Licensed Tester Name (Signature):
Company Phone #: BPAT License #
License Expiration Date:
The above is certified to be true at the time of testing.
* TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS [30 TAC §290.46(B)]
** USE ONLY MANUFACTURER'S REPLACEMENT PARTS
TCEQ-20700 (Revision 04-04-2019) Page 1 of 1
Kristin Strangmeyer
BP0023995
12/17/2027
Firetrol Protection Systems
4410 Dillon Ln Ste 38 Corpus Christi, Tx 78415
361.851.2632
2.67.9
WATTS
LF919QT
10188
3/4" Riser Rm Fireline Bypass
X X
X
X
X X2/26/26
9:31AM
BACFLOW UNLIMITED 01180325 2/11/26
X
NATIONAL SEASHORE TUTLE LAB 20301 PARK ROAD 22 CORPUS CHRISTI, TX
Texas Commission on Environmental Quality
BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT
The following form must be completed for each assembly tested. A signed and dated original must be submitted to the public water supplier for recordkeeping *purposes:
NAME OF PWS:
PWS ID#:
PWS MAILING ADDRESS:
PWS CONTACT PERSON:
ADDRESS OF SERVICE:
The backflow prevention assembly detailed below has been tested and maintained as required by commission regulations and is certified to be operating within acceptable parameters.
TYPE OF BACKFLOW PREVENTION ASSEMBLY (BPA):
☐ Reduced Pressure Principle (RPBA) Reduced Pressure Principle-Detector (RPBA-D) Type II ☐
☐ Double Check Valve (DCVA) Double Check-Detector (DCVA-D) Type II ☐
☐ Pressure Vacuum Breaker (PVB) Spill-Resistant Pressure Vacuum Breaker (SVB)
Manufacturer: Main: Bypass: Size: Main: Bypass:
Model Number: Main: Bypass: BPA Location:
Serial Number: Main: Bypass: BPA Serves:
TEST RESULT
Reduced Pressure Principle Assembly (RPBA)
Type II
Assembly PVB & SVB
PASS ☐ DCVA
Relief Valve Bypass Check Air Inlet Check Valve
FAIL ☐ 1st Check 2nd Check***
Initial Test
Date:
Time:
Held at ____ psid
Closed Tight ☐
Leaked ☐
Held at ____ psid
Closed Tight ☐
Leaked ☐
Opened at ___ psid
Did not open ☐
Held at ____ psid
Closed Tight ☐
Leaked ☐
Opened at ____ psid
Did not open ☐
Did it fully open
(Yes ☐ /No ☐)
Held at _____ psid
Leaked ☐
Repairs and
Materials
Used**
Main:
Bypass:
Test After
Repair
Date:
Time:
Held at ____ psid
Closed Tight ☐
Held at ____ psid
Closed Tight ☐
Opened at ___ psid
Held at ____ psid
Closed
Tight ☐
Opened at ____ psid Held at _____ psid
Reason for test: New ☐ Existing ☐ Replacement ☐ Old Model/Serial #
Is the assembly installed in accordance with manufacturer recommendations and/or local codes? ☐ Yes ☐ No
Is the assembly installed on a non-potable water supply (auxiliary)? ☐ Yes ☐ No
*** 2nd check: numeric reading required for DCVA only
Differential pressure gauge used: Potable: ☐ Non-Potable: ☐
Make/Model: SN: Date tested for accuracy :
Remarks:
Company Name: Licensed Tester Name
(Print/Type):
Company Address: Licensed Tester Name (Signature):
Company Phone #: BPAT License #
License Expiration Date:
The above is certified to be true at the time of testing.
* TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS [30 TAC §290.46(B)]
** USE ONLY MANUFACTURER'S REPLACEMENT PARTS
TCEQ-20700 (Revision 04-04-2019) Page 1 of 1
Kristin Strangmeyer
BP0023995
12/17/2027
Firetrol Protection Systems
4410 Dillon Ln Ste 38 Corpus Christi, Tx 78415
361.851.2632
2.69.4
Ames
LFCOLT 500-BF
XL-2130
4" Riser Rm Fireline
X X
X
X
X X2/26/26
9:07AM
BACFLOW UNLIMITED 01180325 2/11/26
X
NATIONAL SEASHORE TUTLE LAB 20301 PARK ROAD 22 CORPUS CHRISTI, TX
101072492Invoice Nbr:
Bill To: PADRE ISLAND NATIONAL SEASHORE Attn: BRIAN SLATE
PO BOX 181300
CORPUS CHRISTI, TX 78480
Invoice Date: 02/26/2026
Ship To: PADRE ISLAND NATIONAL SEASHORE
20301 PARK RD 22
CORPUS CHRISTI, TX 78418
Customer Nbr Cust PO No. Firetrol WO No. Date Completed Terms
4601157 2601-4012 02/26/2026 3% 10 NET 45 04/12/2026
Due Date
Invoice Notes:
02-26-26 Annual sprinkler inspection failed.
Annual backflow on two fireline backflow passed. There was a main assembly and a bypass assembly.
Service \ Item Description Unit Description Qty Price Amount
LABOR
BACKFLOW INSPECTION ANNUAL 1.00 1,445.00 1,445.00
INSPECTION SPRINKLER ANNUAL 1.00 790.00 790.00
Thank you for choosing Firetrol Protection Systems
Fire Sprinkler E-Lighting Maintenance
Life Safety Range Hoods Repair
Firetrol Protection Systems, Inc.
4410 Dillon Lane Suite 38 Corpus Christi, TX 78415 Phone: 361-851-2632 Fax: 361-851-1886
Fire Alarm Inspections Special Hazards
Extinguishers 24/7 Service Backflow Preventers
Please Remit To: Firetrol Protection Systems, Inc.
4410 Dillon Lane Suite 38 Corpus Christi, TX 78415 Phone: 361-851-2632 Fax: 361-851-1886 We gladly accept VISA, MC, DISCOVER, and AMEX
2,235.00Sub Total
0.00Sales Tax
2,235.00TOTAL
Invoice Totals