B09_Solicitation_Amendment_2_Updated_Drawings_0002.pdf
PDF 3 MB Posted
- Attached to
- WICA VISITOR CENTER HVAC REMODEL
- Solicitation number
- 140P6325B0007
About this file
This document is an Addendum No. 1 for the NPS WICA HVAC project at Wind Cave National Park in Hot Springs, South Dakota, dated July 17th, 2025. The addendum provides updated mechanical and electrical drawings with specific modifications, including the demolition of VRF units in room PHONE 107, removal of existing equipment (E)XFT-102, updates to split system piping and outdoor unit locations, and additions to the Diffuser, Register and Grille schedule and Split System Air Conditioning Schedule.
Key electrical changes include the addition of SSCU-2 on Sheet E201, addition of SS-2 on Sheet E202, updates to the Equipment Schedule to include SSCU-2, and circuit breaker modifications in switchboard LGB and panel L2B. The addendum emphasizes that prior manufacturer approvals are general and for bidding purposes only, with final product approval contingent upon submittal of product data and shop drawings that meet specific design requirements and specifications. The document consists of two pages of written addendum items and ten pages of supplemental drawings.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
July 17th, 2025 Addendum No. 1 - 1 009258.005
DATE: July 17th, 2025
FROM: The Schemmer Associates
1044 North 115th Street, Suite 300 Omaha, Nebraska 68154 Phone: (402) 493-4800
TO: Prospective Bidders and Plan Holders
RE: Addendum No. 1 to the Bidding Documents for:
NPS WICA HVAC
Schemmer Project No. 009258.005
This addendum is issued by the Architect to the Contractor. This Addendum shall be made a part of the Contract Documents. Acknowledge receipt of this Addendum shall be provided on the Bid Form. Failure to do so may subject Bidder to disqualification.
Prior approval of manufacturers is a general approval only for bidding purposes. Final approval of the products is contingent upon the submittal of product data and/or shop drawings which will have to meet the specific design requirements and the specifications.
This addendum consists of two (2) pages of written addendum items and ten (10) pages of supplemental drawings.
THE SCHEMMER ASSOCIATES INC.
July 17th, 2025 Addendum No. 1 - 2 009258.005
DRAWINGS
MECHANICAL
Item No. DM-1, Sheet M002
See reissued sheet for VRF unit demolition in room PHONE 107 and removal of (E)XFT-102 from plans.
Item No. DM-2, Sheet M101
See reissued sheet for split system piping and outdoor unit location.
Item No. DM-3, Sheet M102
See reissued sheet for split system installation and removal of (E)XFT-102 from plans.
Item No. DM-4, Sheet M501
See reissued sheet for added Diffuser, Register and Grille schedule, and modified Split System Air Conditioning Schedule, as well as removal of (E)XFT-102 from control valve schedule.
ELECTRICAL
Item No. EM-1, Sheet E002
See reissued sheet for mechanical unit demolition in room PHONE 107.
Item No. EM-2, Sheet E201
See reissued sheet for addition of SSCU-2.
Item No. EM-3, Sheet E202
See reissued sheet for addition of SS-2.
Item No. EM-4, Sheet E601
See reissued sheet for addition of SSCU-2 to Equipment Schedule.
Item No. EM-5, Sheet E701
See reissued sheet for addition circuit breaker for SSCU-2 in switchboard LGB.
Item No. EM-6, Sheet E702
See reissued sheet for update to circuit breaker for SSCU-1 in panel L2B.
END OF ADDENDUM NO. 1
M
M
M M
M
M M M
M
M
M
M
M
M
M
M
T
T
T
T
T
T T
T T
T
T
T
T
T
T
(E)XFT-115
(E)XFT-114(E)XFT-113(E)XFT-111(E)XFT-110
(E)XFT-116
(E)XFT-112
(E)XFT-106(E)XFT-104
(E)XFT-103
(E)XFT-109
(E)XFT-108
(E)XFT-107
3 3
(E)XFT-118
(E)XCUH-102
HWS
HWR
HW
R
HW
S
HW
S
HW
R
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
305107
80043
C U s e rs \a p o s p is il\
D o c u m e n ts
\R e v it te m p \0
-M E
C H
R a p o s p is il@ s c h e m m e r.
c o m .r v t
AJP
SXR
JEK
01/15/2025
009258.005
M002
DEMO FIRST FLOOR PLAN -
MECHANICAL
NPS WICA HVAC
009258005- 6- M002 DEMO FIRST FLOOR PLAN - MECHANICAL
WIND CAVE NATIONAL PARK
26611 US HIGHWAY 385
HOT SPRINGS, SD
REF. DEMO NOTES ( ):X
1 REMOVE EXISTING BLOWER COIL AND ASSOCIATED REFRIGERANT PIPING. ASSOCIATED
CONDENSATE PIPING TO REMAIN.
2 REMOVE EXISTING BRANCH SELECTOR BOX AND ASSOCIATED REFRIGERANT PIPING.
3 CONTRACTOR TO REMOVE EXISTING CONTROL VALVE. PREPARE FOR INSTALLATION OF NEW
CONTROL VALVE. SEE CONSTRUCTION PLANS AND SCHEDULES FOR ADDITIONAL
INFORMATION. CONTRACTOR TO FIELD VERIFY EXACT LOCATION OF CONTROL VALVES.
4 EXISTING HWS/HWR PIPING SERVING VAV SYSTEM TO REMAIN.
5 REMOVE EXISTING THERMOSTAT AND PREPARE FOR NEW THERMOSTAT INSTALLATION. IF
THERMOSTAT IS NOT INSTALLED AT 48" A.F.F. PACK WALL AND PREPARE FOR ADJACENT.
SCALE: 1/8" = 1'-0"
FIRST FLOOR PLAN - DEMO HVAC PIPING
VRF NOTE:
- CONTRACTOR TO RECORD AND DOCUMENT ALL EXISTING
VRF PIPE ROUTING PRIOR TO REMOVAL. NEW PIPING IS TO
BE INSTALLED IN SPACE OF REMOVED PIPING.
DATE INITIAL
07/17/2025
TRUE
NORTH
PLAN
NORTH
7/18/25
M
M
T
(E)VAV-101
(E)VAV-102
(E )V
AV
-2
(E)VAV-103
(E)XUH-001
(E)VAV-104
(E)VAV-105
(E)XUH-002
(E)XUH-003
(E)XUH-005
(E)XUH-004
(E)AHU-1
(E)AHU-2
CV-107CV-106
CV-105
BS-001
HRV-1
WEIGHT ROOM
UNEXCAVATED
UNEXCAVATED
UNEXCAVATED
MECH/ELEC/TELE
VRF UP
VRF UP
VRF
VRF
HWS UP TO (E)
XFT-108, 109
HWS UP TO (E)
XFT-107
HWS
HWR
HWR
HWS
BC-100A, 100B
BC-100A
BC-100B
CWS
HWR
HWS
CWR
CWS
CWR
SF-2
HWC-2
SSCU-2
VRF
RS/RL UP
RS/RL
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
305107
80043
C U s e rs \a p o s p is il\
D o c u m e n ts
\R e v it te m p \0
-M E
C H
R a p o s p is il@ s c h e m m e r.
c o m .r v t
AJP
SXR
JEK
01/15/2025
009258.005
M101
SUB-GRADE FLOOR PLAN -
MECHANICAL
NPS WICA HVAC
009258005- 6- M101 SUB-GRADE FLOOR PLAN - MECHANICAL
WIND CAVE NATIONAL PARK
26611 US HIGHWAY 385
HOT SPRINGS, SD
REF. NOTES ( ):X
1 INSTALL HRV-1 ON EXISTING HOUSEKEEPING PAD.
2 PROVIDE ALUMINUM JACKETING FOR ALL VRF PIPING ON EXTERIOR OF BUILDING.
3 REPLACE SUPPLY FAN (SF-2) AND HOT WATER COIL (HWC-2) SERVING (E) AHU-2.
CONTRACTOR TO MATCH EXISTING PARAMETERS. SEE SCHEDULE FOR MORE DETAILS.
4 INSTALL NEW OA MOTORIZED DAMPER SERVING INLET OF (E) AHU-2. CONTRACTOR TO
MATCH EXISTING SIZE AND VOLTAGE. UNIT IS TO HAVE FAIL-CLOSED OPERATION AND BE
CONNECTED TO EXISTING BAS SYSTEM.
5 CONTRACTOR TO INSTALL SSCU-2 ON HOUSEKEEPING PAD. PROVIDE ALUMINUM JACKETING
FOR ALL RS/RL PIPING ON EXTERIOR OF BUILDING.
6 SIZE AND INSTALL REFRIGERANT PIPING PER MANUFACTURER'S REQUIREMENTS AND THE
SPECIFICATIONS. COORDINATE RS/RL PIPE ROUTING IN ROOM WITH EXISTING EQUIPMENT
AND STORAGE ITEMS.
SCALE: 1/8" = 1'-0"
SUB-GRADE PLAN - HVAC PIPING
VRF NOTE:
- VRF SYSTEM IS SHOWN AS A SCHEMATIC LAYOUT.
- VRF SYSTEM IS TO BE THREE-PIPE REFRIGERANT FLOW SYSTEM.
- CONTRACTOR IS TO SIZE AND INSTALL VRF PIPING PER MANUFACTURER'S REQUIREMENTS.
- CONTRACTOR IS TO ROUTE PIPING IN THE SAME SPACE PREVIOUSLY USED FOR VFR WHEN POSSIBLE.
DATE INITIAL
07/17/2025
TRUE
NORTH
PLAN
NORTH
M
M
M
M
M
M
M
M
MMM
M
M M
M
T
T
T
T
T
T
T
T
T
T
T
T T
T
T BC-105
BC-111
BC-106 BC-107
BC-110
BC-108
BC-112
BC-109
BC-102
BC-103
BC-104
(E)P-3
(E)P-4
BC-101
(E)ET
(E)XCUH-101
(E)XFT-106
(E)XFT-112
(E)XFT-116
(E)XFT-115
(E)XFT-114(E)XFT-113(E)XFT-111(E)XFT-110
(E)XCUH-102
(E)XFT-109
(E)XFT-108
(E)XFT-118
(E)XFT-107
(E)XFT-104
(E)XFT-103
(E)XFT-117
LIBRARY
OFFICE
DRAFTING
STOR
OFFICE
OFFICE
WOMEN
MEN
HALL
BOILER ROOM
READY ROOM
ADMIN. STOR
PHONE
EVIDENCE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
CV-209
HWR
HWS
CV-201
CV-101
CV-204
CV-205
CV-202
CV-203
CV-102
(E)XFT-105
CV-104
CV-112
CV-211
CV-212
CV-110CV-109
CV-210
ELEV
MEN
WOMEN
OFFICE
OFFICE
STORAGE
DECK
MAINTENANCE
CV-207
CV-108 IN
CABINET
CV-111
CV-103 IN
CABINET
1 VR
F
VRF DN
VRF DN
VRF
VRF
BC-104
BC-103
BC-101
BC-102
BC-111
BC-105
BC-106
BC-107
BC-108
BC-112
BC-110
BC-109
CD
HWR
HW
S
HW
R
HWS
HWR
HW
S
HW
R
HWS
HWR HWR
HWS
HW
S
HW
R
HWS
HW
R
HWR
HWS
(E)BP-1
SS-22
3/4" CD
6x6 R-1
RS/RL
RS/RL DN
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
305107
80043
C U s e rs \a p o s p is il\
D o c u m e n ts
\R e v it te m p \0
-M E
C H
R a p o s p is il@ s c h e m m e r.
c o m .r v t
AJP
SXR
JEK
01/15/2025
009258.005
M102
FIRST FLOOR PLAN -
MECHANICAL
NPS WICA HVAC
009258005- 6- M102 FIRST FLOOR PLAN - MECHANICAL
WIND CAVE NATIONAL PARK
26611 US HIGHWAY 385
HOT SPRINGS, SD
REF. NOTES ( ):X
1 NEW BLOWER COIL TO BE INSTALLED IN EXISTING BLOWER COIL LOCATION. EXISTING
CONDENSATE LINE TO BE CONNECTED TO NEW BLOWER COIL.
2 CONTRACTOR TO FIELD VERIFY EXACT LOCATION OF SS-2 IN PHONE 107. COORDINATE
INSTALLATION WITH EXISTING ROOM CONDITIONS.
3 CONTRACTOR TO CONNECT 3/4" CD TO EXISTING CONDENSATE LINE FROM UNIT THAT WAS
REMOVED IN PHONE 107.
4 PROVIDE TRANSFER GRILLE IN WALL. COORDINATE EXACT SIZE WITH PARK STAFF.
5 SIZE AND INSTALL REFRIGERANT PIPING PER MANUFACTURER'S REQUIREMENTS AND THE
SPECIFICATIONS. PIPE ROUTING IS TO BE IN SAME LOCATION THAT WAS PREVIOUSLY USED
FOR REFRIGERANT PIPING SERVING THE FAN COIL REMOVED IN PHONE 107 UNLESS NOTED
ON DRAWINGS.
SCALE: 1/8" = 1'-0"
FIRST FLOOR PLAN - HVAC PIPING
VRF NOTE:
- VRF SYSTEM IS SHOWN AS A SCHEMATIC LAYOUT.
- VRF SYSTEM IS TO BE THREE-PIPE REFRIGERANT FLOW SYSTEM.
- CONTRACTOR IS TO SIZE AND INSTALL VRF PIPING PER MANUFACTURER'S REQUIREMENTS.
- CONTRACTOR IS TO ROUTE PIPING IN THE SAME SPACE PREVIOUSLY USED FOR VFR WHEN POSSIBLE.
DATE INITIAL
07/17/2025
TRUE
NORTH
PLAN
NORTH
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
305107
80043
C U s e rs \a p o s p is il\
D o c u m e n ts
\R e v it te m p \0
-M E
C H
R a p o s p is il@ s c h e m m e r.
c o m .r v t
AJP
SXR
JEK
01/15/2025
009258.005
M501
SCHEDULE - MECHANICAL
NPS WICA HVAC
009258005- 6- M501 SCHEDULE - MECHANICAL
WIND CAVE NATIONAL PARK
26611 US HIGHWAY 385
HOT SPRINGS, SD
2. VRF SYSTEM IS TO BE INTEGRATED INTO EXISTING JOHNSON CONTROLS BAS SYSTEM.
NOTES: 1. FIELD COORDINATE EXACT SYSTEM PIPING ARRANGEMENT.
BS-001 SEE PLANS 16 419 208 1 60 1.6 20 TRANE TCMBM1016KA11N4 1,2
MAX CAP TOTAL MBH VOLTS PH HZ MCA MOPMARK LOCATION NO. OF PORTS
COOLING ELECTRICAL
MANUFACTURER AND MODEL NUMBER REMARKS
BRANCH SELECTOR SCHEDULE
4. CONTROL VALVE LISTED AS SUPPLEMENTARY SHALL BE CONTROLLED BY AN AUXILLARY HEATING RELAY FROM THE THERMOSTAT SERVING PRIMARY HEATING...
3. CONTROL VALVE LISTED AS PRIMARY HEATING FUNCTION SHALL BE CONTROLLED BY IT'S OWN THERMOSTAT.
2. VALVE IS TO BE TWO-WAY VALVE WITH BRONZE BODY AND FLOATING POINT CONTROL. VALVE IS TO BE FAIL-OPEN TYPE.
NOTES: 1. VALVE IS TO BE CONNECTED TO BACNET BAS.
CV-212 2-WAY XFT-219 PRIMARY N/A 0.5 1 1,2,4
CV-211 2-WAY XFT-220 PRIMARY N/A 0.75 1 1,2,3
CV-210 2-WAY XFT-214,215,216,217 SUPPLEMENTARY (E) VAV-206 8 1-1/4 1,2,4
CV-209 2-WAY XFT-213,218 PRIMARY N/A 1 1-1/4 1,2,3
CV-208 2-WAY XFT-211,212 SUPPLEMENTARY (E) VAV-205 4 1-1/4 1,2,4
CV-207 2-WAY XFT-209,210 SUPPLEMENTARY (E) VAV-204 4 1-1/4 1,2,4
CV-206 2-WAY XFT-208 SUPPLEMENTARY (E) VAV-203 4 1-1/4 1,2,4
CV-205 2-WAY XFT-207 PRIMARY N/A 0.5 1 1,2,3
CV-204 2-WAY XFT-205 PRIMARY N/A 0.5 1-1/4 1,2,3
CV-203 2-WAY XFT-206 PRIMARY N/A 0.5 1 1,2,3
CV-202 2-WAY XFT-203,204 SUPPLEMENTARY BC-203 2 1 1,2,4
CV-201 2-WAY XFT-201,202 SUPPLEMENTARY BC-201 2 1 1,2,4
CV-113 2-WAY XFT-106 SUPPLEMENTARY BC-110 0.75 1 1,2,4
CV-112 2-WAY XFT-112 SUPPLEMENTARY BC-111 0.5 1 1,2,4
CV-111 2-WAY XFT-116 SUPPLEMENTARY BC-109 1.5 1-1/4 1,2,4
CV-110 2-WAY XFT-113,114,115 SUPPLEMENTARY BC-112 2 1-1/4 1,2,4
CV-109 2-WAY XFT-111 SUPPLEMENTARY BC-108 0.5 1-1/4 1,2,4
CV-108 2-WAY XFT-110 SUPPLEMENTARY BC-107 0.5 1-1/4 1,2,4
CV-107 2-WAY XFT-108,109 SUPPLEMENTARY BC-103 3.75 1-1/4 1,2,4
CV-106 2-WAY XFT-107 SUPPLEMENTARY BC-104 1.25 1-1/4 1,2,4
CV-105 2-WAY XFT-118 PRIMARY N/A 1.25 1 1,2,3
CV-104 2-WAY XFT-105 SUPPLEMENTARY BC-101 0.5 1 1,2,4
CV-103 2-WAY XFT-117 SUPPLEMENTARY BC-102 1.5 1 1,2,4
CV-102 2-WAY XFT-104 PRIMARY N/A 0.5 1 1,2,3
CV-101 2-WAY XFT-101,103 PRIMARY N/A 2.25 1-1/4 1,2,3
MARK TYPE SERVES HEATING FUNCTION PRIMARY HEATING DEVICE FLOW GPM
EXISTING LINE
SIZE (IN.) REMARKS
CONTROL VALVE SCHEDULE
4. PROVIDE UNIT WITH SCR CONTROL.
3. PROVIDE UNIT FACTORY DISCONNECT SWITCH.
2. UNIT IS TO BE CONTROLLED BY SPLIT SYSTEM DEHUMIDICATION SEQUENCE.
NOTES: 1. UNIT IS TO BE CONNECTED TO EXISTING BACNET BAS SYSTEM.
EDH-1 SS-1 320 1.5 208 3 60 GREENHECK IDHB 1,2
KW VOLTS PH HZMARK SERVES
AIRFLOW
(CFM)
HEATER ELECTRICAL DATA
MANUFACTURER AND MODEL
NUMBER REMARKS
ELECTRIC DUCT HEATER SCHEDULE
NOTES: 1. CONTRACTOR TO PROVIDE AND INSTALL DIRECT REPLACEMENT OF EXISTING AHU-2 SUPPLY FAN. CONTRACTOR TO VERIFY AND MATCH ALL EXISTING FAN PARAMETERS PRIOR TO ORDERING.
SF-2 MECH RM. AHU-2 HORIZONTAL DRAW THRU 675 1.0 1.93 2142 1750 1 208 3 SEE NOTE 1 1
TYPE CFM EXT SP... TOTAL SP... RPM RPM HP VOLTS PH
MARK LOCATION SERVES
FAN DATA ELECTRICAL DATA (60 HZ AC)
BASIS OF DESIGN NOTES
FAN SCHEDULE
5. UNIT IS TO HAVE INTEGRAL DISCONNECT.
4. UNIT IS TO HAVE INTEGRAL CONDENSATE PUMP.
3. PROVIDE UNIT WITH REMOTE WALL MOUNTED THERMOSTAT. INSTALL AT 48" A.F.F.
2. VRF SYSTEM IS TO BE INTEGRATED INTO EXISTING JOHNSON CONTROLS BAS SYSTEM.
NOTES: 1. SCHEDULED CAPACITIES ARE BASED ON 80/67 RA AND 95/75 AMBIENT OA CONDITIONS FOR COOLING, 70/60 RA AND 50/45 AMBIENT OA CONDITIONS FOR HEATING.
BC-203 WALL MOUNT BS-001 270 R-410A 11.6 13.1 208 1 60 0.24 15 TRANE TPKFYP012LM140B 1,2,3,4,5
BC-202 WALL MOUNT BS-001 270 R-410A 11.6 13.1 208 1 60 0.24 15 TRANE TPKFYP012LM140B 1,2,3,4,5
BC-201 WALL MOUNT BS-001 174 R-410A 5.8 6.5 208 1 60 0.24 15 TRANE TPKFYP006LM140B 1,2,3,4,5
BC-112 WALL MOUNT BS-001 321 R-410A 14.6 16.5 208 1 60 0.24 15 TRANE TPKFYP015LM140B 1,2,3,4,5
BC-111 WALL MOUNT BS-001 174 R-410A 5.8 6.5 208 1 60 0.24 15 TRANE TPKFYP006LM140B 1,2,3,4,5
BC-110 WALL MOUNT BS-001 270 R-410A 11.6 13.1 208 1 60 0.24 15 TRANE TPKFYP012LM140B 1,2,3,4,5
BC-109 WALL MOUNT BS-001 174 R-410A 5.8 6.5 208 1 60 0.24 15 TRANE TPKFYP006LM140B 1,2,3,4,5
BC-108 WALL MOUNT BS-001 216 R-410A 7.8 8.7 208 1 60 0.24 15 TRANE TPKFYP008LM140B 1,2,3,4,5
BC-107 WALL MOUNT BS-001 174 R-410A 5.8 6.5 208 1 60 0.24 15 TRANE TPKFYP006LM140B 1,2,3,4,5
BC-106 WALL MOUNT BS-001 174 R-410A 5.8 6.5 208 1 60 0.24 15 TRANE TPKFYP006LM140B 1,2,3,4,5
BC-105 WALL MOUNT BS-001 174 R-410A 5.8 6.5 208 1 60 0.24 15 TRANE TPKFYP006LM140B 1,2,3,4,5
BC-104 WALL MOUNT BS-001 174 R-410A 5.8 6.5 208 1 60 0.24 15 TRANE TPKFYP006LM140B 1,2,3,4,5
BC-103 WALL MOUNT BS-001 399 R-410A 17.5 19.4 208 1 60 0.24 15 TRANE TPKFYP018LM140B 1,2,3,4,5
BC-102 WALL MOUNT BS-001 216 R-410A 7.8 8.7 208 1 60 0.24 15 TRANE TPKFYP008LM140B 1,2,3,4,5
BC-101 WALL MOUNT BS-001 270 R-410A 11.6 13.1 208 1 60 0.24 15 TRANE TPKFYP012LM140B 1,2,3,4,5
BC-100B WALL MOUNT BS-001 216 R-410A 7.8 8.7 208 1 60 0.24 15 TRANE TPKFYP008LM140B 1,2,3,4,5
BC-100A WALL MOUNT BS-001 216 R-410A 7.8 8.7 208 1 60 0.24 15 TRANE TPKFYP008LM140B 1,2,3,4,5
RATED CAP TOTAL
MBH
RATED CAP TOTAL
MBH VOLTS PH HZ MCA MOPMARK TYPE
BRANCH SELECTOR
BOX
NOMINAL
CFM REFRIGERANT
COOLING HEATING ELECTRICAL
MANUFACTURER AND MODEL NUMBER REMARKS
VRF BLOWER COIL SCHEDULE
NOTES: 1. CONTRACTOR TO PROVIDE DIRECT REPLACEMENT OF EXISTING COIL. CONTRACTOR TO FIELD VERIFY COIL SIZE AND CONNECTION DIMENSIONS PRIOR TO ORDERING.
HWC-2 MECH. RM AHU-2 675 0.05 331 1 14 x 21 12 -10 68 58.3 200 180.3 6.3 6.8 DAIKIN 1
EAT DB (°F) LAT DB (°F) EWT (°F) LWT (°F)
FLOW
(GPM) WPD FTMARK LOCATION SERVES CFM
APD
(IN WG)
MAX FV
(FPM) MIN ROWS SIZE H x W (IN) FPI
AIRSIDE DATA
MIN CAP MBH
WATERSIDE DATA
MANUFACTURER AND
MODEL NUMBER REMARKS
HOT WATER HEATING COIL SCHEDULE
5. PROVIDE UNIT WITH PANEL HEATER AND LOW AMBIENT KIT.
4. PROVIDE UNIT WITH SNOW/HAIL GUARDS.
3. VRF SYSTEM IS TO BE INTEGRATED INTO EXISTING JOHNSON CONTROLS BAS SYSTEM.
2. FIELD COORDINATE EXACT SYSTEM PIPING ARRANGEMENT IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS.
NOTES: 1. PROVIDE UNIT WITH 24" MANUFACTURER STAND. ANCHOR UNIT TO CONCRETE HOUSEKEEPING PAD WITH VIBRATION ISOLATORS.
HRV-1 SEE PLANS BS-001 R-410A 155.2 172.7 126 -18 66/64 110/100 208 3 60 TRANE TURYP1683N40A 1,2,3,4,5
MCA MOP VOLT PH HZMARK LOCATION SERVES REF TYPE
NOMINAL
CAP CLG (MBH)
NOMINAL CAP
HTG (MBH)
COOLING
AMBIENT TEMP
(°F)
HEATING
AMBIENT TEMP
(°F)
ELECTRICAL DATA
MANUFACTURER AND MODEL NUMBER REMARKS
HEAT RECOVERY UNIT SCHEDULE
8. INSTALL UNIT ON CONCRETE HOUSEKEEPING PAD.
7. PROVIDE UNIT WITH CONTROLLER FOR DEHUMIDIFICATION MODE. UNIT IS TO BE CONNECTED TO EDH-1.
6. PROVIDE UNIT WITH BACNET CONTROLLER. UNIT IS TO BE INTEGRATED INTO JOHNSON CONTROLS SYSTEM.
5. PROVIDE UNIT WITH MICROBLUE CONDENSATE PUMP IF UNIT DOES NOT HAVE INTEGRAL CONDENSATE LIFT MECHANISM.
4. PROVIDE UNIT WITH HEAT PUMP WIND BAFFLES.
3. PROVIDE UNIT WITH 12" PATE ROOF CURB OR EQUAL.
2. PROVIDE WITH HARD WIRED, WALL MOUNTED THERMOSTAT.
NOTES: 1. PROVIDE WITH FACTORY INSULATED REFRIGERANT LINESETS SIZED PER MANUFACTURER REQUIREMENTS.
SS-2 PHONE 107 810 80 67 23.3 22.8 27.2 9.8 - MITSUBISHI PLA-AE24NL SSCU-2 GRADE 95 R454B MITSUBISHI PUZ-AK24NLHZ 24 39 208 1 60 1,2,4,5,6,8
SS-1 MUSEUM STORAGE 321 80 67 11.6 21.8 17.5 9.8 - MITSUBISHI PEAD-AA12NL SSCU-1 ROOF 95 R454B MITSUBISHI PUZ-AK12NL 16 27 208 1 60 1-7
DB WB
AIRSIDE DATA EAT (°F)
RATED CAP (MBH)
EFFICIENCY
(SEER)
RATED CAP @ 47°F
(MBH)
EFFICIENCY
(HSPF)
ELEC HEAT
(KW) MCA MOCP VOLTS PH HZLOCATION
SUPPLY
AIR
CFM
COOLING COIL DATA HEATING DATA
MANUFACTURER AND MODEL
NUMBER MARK LOCATION
AMB TEMP
(°F) REFER TYPE
MANUFACTURER AND MODEL
NUMBERMARK
INDOOR UNIT DATA OUTDOOR UNIT DATA
ELECTRICAL DATA
REMARKS
SPLIT SYSTEM AIR CONDITIONING SCHEDULE
GENERAL EQUIPMENT NOTE:
-AIRFLOWS AND CAPACITIES ARE SCHEDULED FOR OPERATION AT 4100.0 FEET ABOVE SEA LEVEL.
DATE INITIAL
07/17/2025
2. SINGLE DEFLECTION GRILLE, WITH 3/4" BLADE SPACING.
NOTES: 1. FACE SIZE TO BE NECK SIZE + ADDITIONAL LENGTH FROM MOUNTING FRAME.
R-1 SURFACE NOTE 1 SEE PLANS 35 NONE STEEL / WHITE 0.1 25 KRUEGER S80 1,2
MARK
MOUNTING
TYPE FACE SIZE (IN.) NECK SIZE (IN.) BLADE ANGLE VOLUME CONTROL MATERIAL / FINISH MAX PD (IN WG)
MAX NC AT PD
SHOWN BASIS OF DESIGN REMARKS
DIFFUSER, REGISTER AND GRILLE SCHEDULE
7/21/25
EXTG PANEL 'L1B'
EXTG PANEL 'L1A'
D1
D1
D2
OFFICE
OFFICE
DRAFTING
STOR
LIBRARY
OFFICE
READY ROOM
BOILER ROOM
ADMIN. STOR
HALL
WOMEN
MEN
PHONE
BREAK ROOM
OFFICE
OFFICE
OFFICE
EVIDENCE
EVIDENCE
129 OFFICE
OFFICE
OFFICE
128 OFFICE
OFFICE
OFFICE
OFFICE
STORAGE
WOMEN
MEN
ELEV
FOYER
ELEV. EQUIP.
MAINTENANCE
(E)BS-103
(E)BS-104
(E)BC-107
D2
(E)BS-105
(E)BS-106
(E)BS-107
(E)BC-102
D2
BC-101
D1
(E)BS-101
D1
(E)BS-102 (E)BC-106
D2
(E)BC-108
D2
(E)BC-110
D2
(E)BC-112
D2
(E)BC-109
D2
(E)BC-105
D2
(E)BC-111
D2
(E)BC-103
D2
(E)BC-104
D2
D1
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
305107
80043
C U s e rs \j b in g e \D o c u m e n ts \R e v it te m p
\0
-E L
E C
R jb in g e .r v t
DJL
DJL
JCB
01/15/2025
009258.005
E002
FIRST FLOOR PLAN -
DEMOLITION
NPS WICA HVAC
009258005- 7- E002 FIRST FLOOR PLAN - DEMOLITION
WIND CAVE NATIONAL PARK
26611 US HIGHWAY 385
HOT SPRINGS, SD
REF. DEMO NOTES ( ):DX
D1 MECHANICAL EQUIPMENT TO BE REMOVED. DEMOLISH ALL ASSOCIATED
CONDUIT, CONDUCTORS, AND CONTROL WIRING.
D2 MECHANICAL EQUIPMENT TO BE REMOVED AND REPLACED IN-PLACE.
MAINTAIN ALL ASSOCIATED CONDUIT AND CONDUCTORS FOR NEW
EQUIPMENT CONNECTION.
SCALE: 1/8" = 1'-0"
FIRST FLOOR PLAN - ELECTRICAL DEMOLITION
DATE INITIAL
07/17/2025
PLAN
NORTH
TRUE
07/18/2025
SWBD 'LGB'
EXTG PANEL 'EM'
EXTG PANEL 'LGA'
SWBD 'MDC'
LGA - 15,17
BS-001
LGA - 10,12
BC-100A
LGA - 10,12
BC-100B
LGB - 4
HRV-1
MECH/ELEC/TELE
WEIGHT ROOM
XFMR 'UTILITY'
(E)AHU-2
WP, G
LGB - 1
SSCU-2
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
305107
80043
C U s e rs \j b in g e \D o c u m e n ts \R e v it te m p
\0
-E L
E C
R jb in g e .r v t
DJL
DJL
JCB
01/15/2025
009258.005
E201
SUB-GRADE FLOOR PLAN -
POWER
NPS WICA HVAC
009258005- 7- E201 SUB-GRADE FLOOR PLAN - POWER
WIND CAVE NATIONAL PARK
26611 US HIGHWAY 385
HOT SPRINGS, SD
REF. NOTES ( ):X
2 ASSOCIATED UNIT SUPPLY FAN AND HEATING COIL TO BE REPLACED
IN-KIND. COORDINATE WITH MECH FOR RECONNECTION OF POWER.
RECONNECT DEVICES TO EXISTING CIRCUIT/CONDUCTORS.
SCALE: 1/8" = 1'-0"
SUB-GRADE FLOOR PLAN - POWER & AUXILIARY SYSTEMS
DATE INITIAL
07/17/2025
PLAN
NORTH
TRUE
EXTG PANEL 'L1A'
EXTG PANEL 'L1B'
L1A - 7,9
BC-101
OFFICE
OFFICE
DRAFTING
STOR
LIBRARY
OFFICE
READY ROOM
BOILER ROOM
ADMIN. STOR
HALL
WOMEN
MEN
PHONE
BREAK ROOM
OFFICE
OFFICE
OFFICE
EVIDENCE
EVIDENCE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
STORAGE
WOMEN
MEN
ELEV
FOYER
ELEV. EQUIP.
MAINTENANCE
L1A - 7,9
BC-102
L1A - 7,9
BC-111
L1A - 7,9
BC-105
L1A - 7,9
BC-110
L1A - 7,9
BC-106
L1A - 7,9
BC-107
L1A - 7,9
BC-108
L1A - 7,9
BC-112
L1A - 7,9
BC-109
L1A - 7,9
BC-103
L1A - 7,9
BC-104
SS-2
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
305107
80043
C U s e rs \j b in g e \D o c u m e n ts \R e v it te m p
\0
-E L
E C
R jb in g e .r v t
DJL
DJL
JCB
01/15/2025
009258.005
E202
FIRST FLOOR PLAN -
POWER
NPS WICA HVAC
009258005- 7- E202 FIRST FLOOR PLAN - POWER
WIND CAVE NATIONAL PARK
26611 US HIGHWAY 385
HOT SPRINGS, SD
REF. NOTES ( ):X
1 CONNECT MECHANICAL EQUIPMENT TO EXISTING CIRCUIT/CONDUCTORS
AT THIS LOCATION.
SCALE: 1/8" = 1'-0"
FIRST FLOOR PLAN - POWER & AUXILIARY SYSTEMS
DATE INITIAL
07/17/2025
PLAN
NORTH
TRUE
GENERAL EQUIPMENT SCHEDULE NOTES:
A. THIS SCHEDULE DISPLAYS SIZING INFORMATION THAT IS GENERIC IN
NATURE. SCHEDULE DOES NOT ITEMIZE ALL INSTANCES OF
EQUIPMENT. CONTRACTOR SHALL REFER TO THE PLANS FOR FINAL
QUANTITIES AND LOCATIONS.
B. MOUNT ALL DISCONNECTS AND STARTERS ON ASSOCIATED
EQUIPMENT UNLESS SHOWN OTHERWISE. MAINTAIN WORKING
CLEARANCES PER NEC; COORDINATE WITH MECHANICAL
CONTRACTOR.
C. BCU = BOX COVER UNIT (COOPER #SSY / #STY OR EQUAL) WITH FUSE.
D. NFD OR FD = NON-FUSED OR FUSED DISCONNECT SWITCH.
E. CS/NFD, FD = COMBINATION STARTER/ NON OR FUSED DISCONNECT
SWITCH.
F. INT = INTEGRAL DISCONNECT FURNISHED WITH EQUIPMENT.
G. FHPMC = FRACTIONAL HORSEPOWER MANUAL CONTROLLER.
H. IHPMC = INTEGRAL HORSEPOWER MANUAL CONTROLLER.
I. STE = THERMAL ELEMENT SWITCH. PROVIDE THERMAL UNIT.
J. EXP = DEVICE TO BE EXPLOSION-PROOF.
K. ALL SWITCHES, DISCONNECTS, ETC SHALL BE LOCKABLE.
L. ALL SWITCHES, DISCONNECTS, ETC SHALL BE NEMA 3R WHERE
REQUIRED.
M. PROVIDE FUSES AS SHOWN; REVISE SIZES PER ACTUAL NAMEPLATE
DATA.
N. STARTER ACCESSORIES:STARTER ACCESSORIES:
1. CONTROL TRANSFORMER
2. H-O-A SWITCH
3. RED RUN LIGHT
4. 2 NO CONTACTS; 2 NC CONTACTS
O. PROVIDE DUCT DETECTOR, SHUTDOWN RELAY, AND ACCESSORIES
AS REQUIRED TO SHUTDOWN HVAC EQUIPMENT 2000 CFM OR HIGHER
PER NFPA AND AHJ.
EQUIPMENT SCHEDULE NOTES:
1. PROVIDES POWER TO INTERIOR UNIT 'SS-1'.
2. UNIT CONTROLLED VIA EXISTING JOHNSON CONTROL SYSTEM. SEE
MECH FOR ADDITIONAL INFORMATION.
3. UNIT CONTROLLED VIA THERMOSTAT. SEE MECH FOR ADDITIONAL
INFORMATION.
4. UNIT CONTROLLED VIA SCR CONTROL. SEE MECH FOR ADDITIONAL
INFORMATION.
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
305107
80043
C U s e rs \j b in g e \D o c u m e n ts \R e v it te m p
\0
-E L
E C
R jb in g e .r v t
DJL
DJL
JCB
01/15/2025
009258.005
E601
EQUIPMENT SCHEDULE
NPS WICA HVAC
009258005- 7- E601 EQUIPMENT SCHEDULE
WIND CAVE NATIONAL PARK
26611 US HIGHWAY 385
HOT SPRINGS, SD
EQUIPMENT SCHEDULE
DEVICE DEVICE DESCRIPTION VOLTAGE PH KW FLA HP
STARTER / DISCONNECT
PLUG CONFIG
RECEPT
CONFIG FEEDER SIZE NOTES TYPE SIZE FUSE
BC-100A BLOWER COIL 208 V 1 - 0.3 - INT - - - - 2#12, 1#12G - 3/4"C 2,3
BC-100B BLOWER COIL 208 V 1 - 0.3 - INT - - - - 2#12, 1#12G - 3/4"C 2,3
BC-101 BLOWER COIL 208 V 1 - 0.4 - INT - - - - 2#12, 1#12G - 3/4"C 2,3
BC-102 BLOWER COIL 208 V 1 - 0.3 - INT - - - - 2#12, 1#12G - 3/4"C 2,3
BC-103 BLOWER COIL 208 V 1 - 0.5 - INT - - - - 2#12, 1#12G - 3/4"C 2,3
BC-104 BLOWER COIL 208 V 1 - 0.2 - INT - - - - 2#12, 1#12G - 3/4"C 2,3
BC-105 BLOWER COIL 208 V 1 - 0.2 - INT - - - - 2#12, 1#12G - 3/4"C 2,3
BC-106 BLOWER COIL 208 V 1 - 0.2 - INT - - - - 2#12, 1#12G - 3/4"C 2,3
BC-107 BLOWER COIL 208 V 1 - 0.2 - INT - - - - 2#12, 1#12G - 3/4"C 2,3
BC-108 BLOWER COIL 208 V 1 - 0.3 - INT - - - - 2#12, 1#12G - 3/4"C 2,3
BC-109 BLOWER COIL 208 V 1 - 0.2 - INT - - - - 2#12, 1#12G - 3/4"C 2,3
BC-110 BLOWER COIL 208 V 1 - 0.4 - INT - - - - 2#12, 1#12G - 3/4"C 2,3
BC-111 BLOWER COIL 208 V 1 - 0.2 - INT - - - - 2#12, 1#12G - 3/4"C 2,3
BC-112 BLOWER COIL 208 V 1 - 0.4 - INT - - - - 2#12, 1#12G - 3/4"C 2,3
BC-201 BLOWER COIL 208 V 1 - 0.2 - INT - - - - 2#12, 1#12G - 3/4"C 2,3
BC-202 BLOWER COIL 208 V 1 - 0.4 - INT - - - - 2#12, 1#12G - 3/4"C 2,3
BC-203 BLOWER COIL 208 V 1 - 0.4 - INT - - - - 2#12, 1#12G - 3/4"C 2,3
BS-001 BRANCH SELECTOR BOX 208 V 1 1.17 - - NFD 30A/2P - - - 2#12, 1#12G - 3/4"C 2
EDH-1 ELECTRIC DUCT HEATER 208 V 3 1.5 - - INT - - - - 3#12, 1#12G - 3/4"C 4
HRV-1 HEAT RECOVERY UNIT 208 V 3 - 48.2 - FD 100A/3P 70A - - 3#4, 1#8G - 1-1/4"C 2
SSCU-1 SPLIT SYSTEM - OUTDOOR 208 V 1 - 7.5 - NFD 30A/2P - - - 2#12, 1#12G - 3/4"C 1
SSCU-2 SPLIT SYSTEM - OUTDOOR 208 V 1 - 18 - NFD 30A/2P - - - 2#10, 1#10G - 3/4"C 1
DATE INITIAL
07/17/2025
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
305107
80043
C U s e rs \j b in g e \D o c u m e n ts \R e v it te m p
\0
-E L
E C
R jb in g e .r v t
DJL
DJL
JCB
01/15/2025
009258.005
E701
ELECTRICAL PANEL
SCHEDULES
NPS WICA HVAC
009258005- 7- E701 ELECTRICAL PANEL SCHEDULES
WIND CAVE NATIONAL PARK
26611 US HIGHWAY 385
HOT SPRINGS, SD
MCB: Main Circuit Breaker
LOCK: Lockable Circuit Breaker EXTG: Existing Circuit Breaker
GFI: GFCI Circuit Breaker MLO: Main Lug Only
FCB: Feeder Circuit Breaker MCCB: Molded Case Circuit Breaker
Legend: Notes:
Total Est. Demand Current (80% Rated): 87 A
Continuous Current @ 125%: 87 A
Non-Cont. Current @ 100%: 0 A
EQP_CONT 25049 VA 100.00% 25049 VA Total Est. Demand Current (100% Rated): 70 A
REC 180 VA 100.00% 180 VA Total Est. Demand: 25229 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
70 A
25229 VA
5 SPARE 3 125 A 0 VA
4 HRV-1 - EXTERIOR 3 110 A 17365 VA
3 (EXTG) PANEL 'L2B' 3 250 A 3864 VA
2 (EXTG) SPACE 3 -- --
1 EQP_CONT SSCU-2 2 30 A 4000 VA
CKT Circuit Description # of Poles Trip Rating Load Remarks
Mounting: SURFACE Wires: 4 FCB / MCB Rating: 400 A
Supply From: MDC Phases: 3 MLO / MCB: MLO
Location: MECH/ELEC/TELE 001 Volts: 208Y/120 A.I.C. Rating: 42K
Extg Switchboard: LGB
MCB: Main Circuit Breaker
LOCK: Lockable Circuit Breaker EXTG: Existing Circuit Breaker
GFI: GFCI Circuit Breaker MLO: Main Lug Only
FCB: Feeder Circuit Breaker MCCB: Molded Case Circuit Breaker
Legend: Notes:
Total Est. Demand Current (80% Rated): 4 A
Continuous Current @ 125%: 4 A
Non-Cont. Current @ 100%: 0 A
Total Est. Demand Current (100% Rated): 4 A
EQP_CONT 1295 VA 100.00% 1295 VA Total Est. Demand: 1295 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 0 A 6 A 6 A
Total Load: 0 VA 647 VA 647 VA
29 (EXTG) MAINT OFFICE 20 A 1 0 0 1 20 A (EXTG) SECURITY 30
27 (EXTG) MAINT OFFICE 20 A 1 0 0 1 20 A (EXTG) OUTSIDE PHONE BOX 28
25 (EXTG) MAINT OFFICE 20 A 1 0 0 1 20 A (EXTG) AHU-2 PREHEAT 26
23 -- -- -- 0 0 1 20 A (EXTG) STORE ROOM LIGHTS 24
21 -- -- -- 0 0 1 20 A (EXTG) SPARE 22
19 (EXTG) AHU-2 15 A 3 0 0 1 20 A (EXTG) JOHNSON CONTROL 20
17 -- -- -- 585 0 -- -- -- 18
15 BS-001 - MECH/ELEC/TELE 001 20 A 2 585 0 -- -- -- 16
13 (EXTG) RECEPTS SOUTH RM WEIGHT... 20 A 1 0 0 3 20 A (EXTG) CHILLER PUMP 14
11 (EXTG) ADDITIONAL RECEPTS RMS OFFICE 20 A 1 0 62 -- -- -- 12
9 (EXTG) FIRE ALARM COMPRESSOR CIRCUIT 20 A 1 0 62 2 15 A BC-100A/B - WEIGHT ROOM 003 10
7 (EXTG) GFI AIR HANDLER CONTROL 20 A 1 0 0 1 20 A (EXTG) MAINT OFFICE RADIO & DESK PLUGS... 8
5 (EXTG) SINK WALL MAINT. OFFICE 20 A 1 0 0 1 20 A (EXTG) JOHNSON CONTROL 6
3 (EXTG) LIGHTS & UNIT HEATER-1 002-003 20 A 1 0 0 1 20 A (EXTG) REC 4
1 (EXTG) REC LIGHTS 001 20 A 1 0 0 1 20 A (EXTG) UNIT HEATER B 2
CKT Circuit Description Trip P A B C P Trip Circuit Description CKT
Mounting: SURFACE Wires: 4 FCB / MCB Rating: 100 A
Supply From: MDC Phases: 3 MLO / MCB: MLO
Location: MECH/ELEC/TELE 001 Volts: 208Y/120 A.I.C. Rating:
Extg Branch Panel: LGA
DATE INITIAL
07/17/2025
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
305107
80043
C U s e rs \j b in g e \D o c u m e n ts \R e v it te m p
\0
-E L
E C
R jb in g e .r v t
DJL
DJL
JCB
01/15/2025
009258.005
E702
ELECTRICAL PANEL
SCHEDULES
NPS WICA HVAC
009258005- 7- E702 ELECTRICAL PANEL SCHEDULES
WIND CAVE NATIONAL PARK
26611 US HIGHWAY 385
HOT SPRINGS, SD
MCB: Main Circuit Breaker
LOCK: Lockable Circuit Breaker EXTG: Existing Circuit Breaker
GFI: GFCI Circuit Breaker MLO: Main Lug Only
FCB: Feeder Circuit Breaker MCCB: Molded Case Circuit Breaker
Legend: Notes:
Total Est. Demand Current (80% Rated): 3 A
Continuous Current @ 125%: 3 A
Non-Cont. Current @ 100%: 0 A
Total Est. Demand Current (100% Rated): 2 A
EQP_CONT 728 VA 100.00% 728 VA Total Est. Demand: 728 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 4 A 4 A 0 A
Total Load: 364 VA 364 VA 0 VA
71 -- -- -- 0 0 -- -- -- 72
69 -- -- -- 0 0 -- -- -- 70
67 (EXTG) BOILER PUMPS 20 A 3 0 0 3 60 A (EXTG) HOT WATER HEATER 68
65 (EXTG) PANEL OUTLET 20 A 1 0 0 1 20 A (EXTG) WOMENS OUTLET 66
63 -- -- -- 0 0 -- -- -- 64
61 (EXTG) WOMENS HAND DRYER 20 A 2 0 0 2 20 A (EXTG) WOMENS HAND DRYER 62
59 (EXTG) REC 130, EFB WATER COOLER CHB 20 A 1 0 0 1 20 A (EXTG) REC 115, 116 60
57 (EXTG) ELEVATOR LIGHTS 20 A 1 0 0 1 20 A (EXTG) REC 112, 115, 114 58
55 (EXTG) OUTSIDE LIGHTS & COMPUTER REC... 20 A 1 0 0 1 20 A (EXTG) REC 115, 116, 117, 118 56
53 (EXTG) TIME CLOCK 20 A 1 0 0 1 20 A (EXTG) REC RECIRC. PUMP 54
51 (EXTG) LIGHTS FOYER 103, 124 20 A 1 0 0 1 20 A (EXTG) LIGHTS 123, 135 52
49 (EXTG) LIGHTS 115-118 20 A 1 0 0 1 20 A (EXTG) LIGHTS 119-122 50
47 (EXTG) LIGHTS 112, 114 20 A 1 0 0 1 20 A (EXTG) SPARE 48
45 (EXTG) LIGHTS 108-106 20 A 1 0 0 1 20 A (EXTG) LIGHTS 126 46
43 (EXTG) LIGHTS 107-110 20 A 1 0 0 1 20 A (EXTG) LIGHTS 125, 134 44
41 SPACE -- 1 -- -- 1 -- SPACE 42
39 SPACE -- 1 -- -- 1 -- SPACE 40
37 SPACE -- 1 -- -- 1 -- SPACE 38
35 (EXTG) TRACK LIGHT N WALL 20 A 1 0 0 -- -- -- 36
33 -- -- -- 0 0 2 15 A (EXTG) WOMENS UPSTAIRS HAND DRYER LEFT 34
31 (EXTG) MENS UPSTAIRS HAND DRYER RIGHT 15 A 2 0 0 -- -- -- 32
29 -- -- -- 0 0 2 15 A (EXTG) MENS UPSTAIRS HAND DRYER LEFT 30
27 (EXTG) MENS DOWNSTAIRS HAND DRYER 20 A 2 0 0 1 20 A (EXTG) SPARE 28
25 (EXTG) REC 101 20 A 1 0 0 1 20 A (EXTG) JANITOR STORAGE ROOM 26
23 (EXTG) REC 101 20 A 1 0 0 1 20 A (EXTG) SPARE 24
21 (EXTG) REC 101 20 A 1 0 0 1 20 A (EXTG) TRACK LIGHT 101 22
19 (EXTG) REC 101 20 A 1 0 0 1 20 A (EXTG) TRACK LIGHT 101 20
17 -- -- -- 0 0 1 20 A (EXTG) TRACK LIGHT 101 18
15 (EXTG) TRACK LIGHTS 101 15 A 2 0 0 1 20 A (EXTG) TRACK LIGHT 101 16
13 (EXTG) TRACK LIGHTS 101 20 A 1 0 0 1 20 A (EXTG) TRACK LIGHT 101 14
11 (EXTG) HAND DRYER RIGHT 20 A 1 0 0 1 20 A (EXTG) TRACK LIGHT 101 12
9 -- -- -- 364 0 -- -- -- 10
7 BC-101 - BC-112 15 A 2 364 0 2 15 A SPARE 8
5 SPACE -- 1 -- -- 1 -- SPACE 6
3 SPACE -- 1 -- -- 1 -- SPACE 4
1 SPACE -- 1 -- -- 1 -- SPACE 2
CKT Circuit Description Trip P A B C P Trip Circuit Description CKT
Mounting: SURFACE Wires: 4 FCB / MCB Rating: 200 A
Supply From: MDC Phases: 3 MLO / MCB: MLO
Location: MAINTENANCE 119 Volts: 208Y/120 A.I.C. Rating:
Extg Branch Panel: L1A
MCB: Main Circuit Breaker
LOCK: Lockable Circuit Breaker EXTG: Existing Circuit Breaker
GFI: GFCI Circuit Breaker MLO: Main Lug Only
FCB: Feeder Circuit Breaker MCCB: Molded Case Circuit Breaker
Legend: Notes:
Total Est. Demand Current (80% Rated): 13 A
Continuous Current @ 125%: 13 A
Non-Cont. Current @ 100%: 0 A
EQP_CONT 3684 VA 100.00% 3684 VA Total Est. Demand Current (100% Rated): 11 A
REC 180 VA 100.00% 180 VA Total Est. Demand: 3864 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 7 A 14 A 13 A
Total Load: 784 VA 1592 VA 1488 VA
83 -- -- -- 0 -- 1 -- SPACE 84
81 -- -- -- 0 -- 1 -- SPACE 82
79 (EXTG) PANEL L1C 90 A 3 0 -- 1 -- SPACE 80
77 SPACE -- 1 -- -- 1 -- SPACE 78
75 (EXTG) EXHAUST FAN 220 15 A 1 0 -- 1 -- SPACE 76
73 (EXTG) SPARE 20 A 1 0 0 1 20 A (EXTG) SPARE 74
71 -- -- -- 0 0 1 20 A (EXTG) SPARE 72
69 -- -- -- 0 0 1 20 A (EXTG) SPARE 70
67 (EXTG) SPARE 50 A 3 0 0 1 20 A (EXTG) SPARE 68
65 (EXTG) EXIT LIGHT VENDING 20 A 1 0 0 1 20 A (EXTG) SPARE 66
63 (EXTG) RECEPTACLE VENDING 20 A 1 0 0 1 20 A (EXTG) SPARE 64
61 (EXTG) RECEPTACLE VENDING 20 A 1 0 0 1 30 A (EXTG) SPARE 62
59 -- -- -- 0 0 -- -- -- 60
57 (EXTG) SPARE 20 A 2 0 0 2 40 A (EXTG) SPARE 58
55 (EXTG) SPARE 20 A 1 0 0 -- -- -- 56
53 (EXTG) 222 N WALL RECEPTACLE MUSEUM... 20 A 1 0 0 2 20 A (EXTG) SPARE 54
51 (EXTG) HALL 220 RECEPTACLE MUSEUM... 20 A 1 0 0 1 20 A (EXTG) SPARE 52
49 (EXTG) RECEPTACLE BOOKSTORE 20 A 1 0 0 1 30 A (EXTG) SPARE 50
47 (EXTG) RECEPTACLE VENDING 20 A 1 0 0 1 30 A (EXTG) SPARE 48
45 (EXTG) SPARE 20 A 1 0 0 -- -- -- 46
43 (EXTG) RECEPTACLE VENDING 20 A 1 0 0 2 20 A (EXTG) SPARE 44
41 SPACE -- 1 -- -- 1 -- SPACE 42
39 SPACE -- 1 -- -- 1 -- SPACE 40
37 SPACE -- 1 -- -- 1 -- SPACE 38
35 SPACE -- 1 -- 0 -- -- -- 36
33 SPACE -- 1 -- 0 2 20 A (EXTG) SPARE 34
31 (EXTG) SPARE 20 A 1 0 0 1 20 A (EXTG) SPARE 32
29 (EXTG) UNDER COUNTER FRIDGE 20 A 1 0 0 1 20 A (EXTG) SPARE 30
27 -- -- -- 0 0 1 20 A (EXTG) SPARE 28
25 (EXTG) SPARE 30 A 2 0 500 -- -- -- 26
23 SPACE -- 1 -- 500 -- -- -- 24
21 -- -- -- 104 500 3 15 A EDH-1 - MUSEUM COLL. STORAGE 219 22
19 BC-201 - BC-203 15 A 2 104 180 1 20 A REC - ON ROOF 20
17 -- -- -- 0 988 -- -- -- 18
15 -- -- -- 0 988 2 20 A SSCU-1 - ON ROOF 16
13 (EXTG) HUMIDIFIER 20 A 3 0 0 1 20 A (EXTG) CABINET HEATER / AC 14
11 (EXTG) RECEPT E WALL VENDING RM 20 A 1 0 0 1 20 A (EXTG) 220 HALLWAY PLUG REC 214-215 12
9 (EXTG) EXHIBIT LIGHTS 20 A 1 0 0 1 20 A (EXTG) ATTIC RECEPT & EMERGENCY EXIT... 10
7 (EXTG) LIGHTS EXHIBIT 20 A 1 0 0 1 20 A (EXTG) PLUGS EXHIBIT 222, 214-215 8
5 (EXTG) LIGHTS MUSEUM STORAGE 20 A 1 0 0 1 20 A (EXTG) BREAK ROOM LIGHTS KITCHEN K... 6
3 (EXTG) LIGHTS EXHIBIT HALLWAY 20 A 1 0 0 1 20 A (EXTG) LIGHTS 214-215 4
1 (EXTG) LIGHTS 220 HALL 20 A 1 0 0 1 20 A (EXTG) LIGHTS 214-215 2
CKT Circuit Description Trip P A B C P Trip Circuit Description CKT
Mounting: RECESSED Wires: 4 FCB / MCB Rating: 200 A
Supply From: LGB Phases: 3 MLO / MCB: MLO
Location: VENDING & SEATING 218 Volts: 208Y/120 A.I.C. Rating:
Extg Branch Panel: L2B
DATE INITIAL
07/17/2025