B09_-_SolicitationAmendment2_Atch_5_263600_REVISED_0002.pdf

PDF 136 KB Posted

Attached to
Provide and Install Generator and all wiring Federal contract opportunity
Solicitation number
140P6221Q0011
Issued by
Department of the Interior National Park Service Midwest Region

View the file

Other files for this federal contract opportunity

Other files attached to Provide and Install Generator and all wiring, newest first.
File Type Posted
B09_-_SolicitationAmendment4_Atch_6_31200_Trenching_0004.pdf PDF
B09_-_SolicitationAmendment4_Atch_7_Pics_0004.pdf PDF
Sol_140P6221Q0011_Amd_0004.pdf PDF
Sol_140P6221Q0011_Amd_0003.pdf PDF
B09_-_SolicitationAmendment2_Atch_4_263213_REVISED_0002.pdf PDF
Sol_140P6221Q0011_Amd_0002.pdf PDF
Sol_140P6221Q0011_Amd_0001.pdf PDF
B08_-_SolicitationAttachment3WD.pdf PDF
B08_-_SolicitationAttachment2Drawings.pdf PDF
B08_-_SolicitationAttachment1Specs.pdf PDF
Sol_140P6221Q0011.pdf PDF
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

140P6221Q0011 Attachment 5 Page 1 of 6

TRANSFER SWITCHES 263600 - 1

SECTION 263600 - TRANSFER SWITCHES

PART 1 - GENERAL

1.1 SUMMARY

A. Section includes automatic transfer switches rated 600 V and less.

1.2 ACTION SUBMITTALS

A. Product Data: For each type of product.

B. Shop Drawings:

1. Include plans, elevations, sections, details showing minimum clearances, conductor entry provisions, gutter space, and installed features and devices.

2. Single-Line Diagram: Show connections between transfer switch, power sources, and load.

1.3 INFORMATIONAL SUBMITTALS

A. Source quality control reports.

B. Field quality-control reports.

1.4 CLOSEOUT SUBMITTALS

A. Operation and maintenance data.

1.5 QUALITY ASSURANCE

A. Installer Qualifications: An authorized representative who is trained and approved by manufacturer.

B. Testing Agency Qualifications: Accredited by NETA.

1. Testing Agency's Field Supervisor: Certified by NETA to supervise on-site testing.

1.6 WARRANTY

A. Manufacturer's Warranty: Manufacturer agrees to repair or replace components of transfer switch or transfer switch components that fail in materials or workmanship within specified warranty period.

140P6221Q0011 Attachment 5 Page 2 of 6

TRANSFER SWITCHES 263600 - 2

1. Warranty Period: Five years from date of Substantial Completion.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Generac Model RTSW200K3 with Nexus controller (basis of design)

B. Cummins

C. Kohler

D. Caterpillar

2.2 PERFORMANCE REQUIREMENTS

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. NEMA/UL Type 3R enclosure.

C. Service Disconnect.

D. Comply with NEMA ICS 3.

E. Comply with NFPA 110.<DELETE – PART E ‘NOT USED’>

F. Comply with UL 1008 unless requirements of these Specifications are stricter.

G. Tested Fault-Current Closing and Short-Circuit Ratings: Adequate for duty imposed by protective devices at installation locations in Project under the fault conditions indicated, based on testing according to UL 1008.

1. Where transfer switch includes internal fault-current protection, rating of switch and trip unit combination shall exceed indicated fault-current value at installation location.

H. Repetitive Accuracy of Solid-State Controls: All settings shall be plus or minus 2 percent or better over an operating temperature range of minus 20 to plus 70 deg C.

I. Resistance to Damage by Voltage Transients: Components shall meet or exceed voltage-surge withstand capability requirements when tested according to IEEE C62.62. Components shall meet or exceed voltage-impulse withstand test of NEMA ICS 1.

J. Service-Rated Transfer Switch:

1. Comply with UL 869A and UL 489.

2. Provide terminals for bonding the grounding electrode conductor to the grounded service conductor.

3. In systems with a neutral, the bonding connection shall be on the neutral bus.

140P6221Q0011 Attachment 5 Page 3 of 6

TRANSFER SWITCHES 263600 - 3

4. Provide removable link for temporary separation of the service and load grounded conductors.

5. Service Disconnecting Means: Externally operated, manual mechanically actuated.

K. Neutral Terminal: Solid and fully rated unless otherwise indicated.

L. Factory Wiring: Train and bundle factory wiring and label, consistent with Shop Drawings, by color-code or by numbered or lettered wire and cable with printed, tape or shrinkable sleeve markers at terminations.

1. Designated Terminals: Pressure type, suitable for types and sizes of field wiring indicated.

2. Power-Terminal Arrangement and Field-Wiring Space: Suitable for top, side, or bottom entrance of feeder conductors as indicated.

3. Control Wiring: Equipped with lugs suitable for connection to terminal strips.

M. Enclosures: General-purpose NEMA 250, Type 3R, complying with NEMA ICS 6 and UL 508, unless otherwise indicated.

2.3 CONTACTOR-TYPE AUTOMATIC TRANSFER SWITCHES

A. Switch Characteristics: Designed for continuous-duty repetitive transfer of full-rated current between active power sources.

1. Limitation: Switches using molded-case switches or circuit breakers or insulated-case circuit-breaker components are unacceptable.

2. Contacts: Silver composition or silver alloy for load-current switching. Contactor-style automatic transfer-switch units, rated 600 A and higher, shall have separate arcing contacts.

3. Conductor Connectors: Suitable for use with conductor material and sizes.

4. Main and Neutral Lugs: Mechanical type.

5. Ground Lugs and Bus-Configured Terminators: Mechanical type.

6. Ground bar.

7. Connectors shall be marked for conductor size and type according to UL 1008.

B. Automatic Open-Transition Transfer Switches: Interlocked to prevent the load from being closed on both sources at the same time.

1. Sources shall be mechanically and electrically interlocked to prevent closing both sources on the load at the same time.

C. Signal-Before-Transfer Contacts: A set of normally open/normally closed dry contacts operates in advance of retransfer to normal source. Interval shall be adjustable from 1 to 30 seconds.

D. Automatic Transfer-Switch Controller Features:

1. All timing and sensing functions originate in the generator controller.

140P6221Q0011 Attachment 5 Page 4 of 6

TRANSFER SWITCHES 263600 - 4

PART 3 - EXECUTION

3.1 INSTALLATION

A. Annunciator and Control Panel Mounting: Flush in wall unless otherwise indicated.

B. Comply with NECA 1.

3.2 CONNECTIONS

A. Wiring to Remote Components: Match type and number of cables and conductors to generator sets, motor controls, control, and communication requirements of transfer switches as recommended by manufacturer. Increase raceway sizes at no additional cost to Owner if necessary to accommodate required wiring.

B. Wiring Method: Install cables in raceways and cable trays except within electrical enclosures.

Conceal raceway and cables except in unfinished spaces.

C. Wiring within Enclosures: Bundle, lace, and train conductors to terminal points with no excess and without exceeding manufacturer's limitations on bending radii.

D. Final connections to equipment shall be made with liquid tight, flexible metallic conduit no more than 18 inches (457 mm) in length.

3.3 FIELD QUALITY CONTROL

A. Perform the following tests and inspections with the assistance of a factory-authorized service representative:

1. Visual and Mechanical Inspection:

a. Compare equipment nameplate data with Drawings and Specifications.

b. Inspect physical and mechanical condition.

c. Inspect anchorage, alignment, grounding, and required clearances.

d. Verify that the unit is clean.

e. Verify appropriate lubrication on moving current-carrying parts and on moving and sliding surfaces.

f. Verify that manual transfer warnings are attached and visible.

g. Verify tightness of all control connections.

h. Inspect bolted electrical connections for high resistance using one of the following methods, or both:

1) Use of low-resistance ohmmeter.

2) Verify tightness of accessible bolted electrical connections by calibrated torque-wrench method according to manufacturer's published data.

i. Perform manual transfer operation.

j. Verify positive mechanical interlocking between normal and alternate sources.

k. Perform visual and mechanical inspection of surge arresters.

140P6221Q0011 Attachment 5 Page 5 of 6

TRANSFER SWITCHES 263600 - 5

l. Inspect control power transformers.

1) Inspect for physical damage, cracked insulation, broken leads, tightness of connections, defective wiring, and overall general condition.

2) Verify that primary and secondary fuse or circuit-breaker ratings match Drawings.

3) Verify correct functioning of draw out disconnecting contacts, grounding contacts, and interlocks.

2. Electrical Tests:

a. Perform insulation-resistance tests on all control wiring with respect to ground.

b. Perform a contact/pole-resistance test. Compare measured values with manufacturer's acceptable values.

c. Verify settings and operation of control devices.

d. Calibrate and set all relays and timers.

e. Verify phase rotation, phasing, and synchronized operation.

f. Perform automatic transfer tests.

g. Verify correct operation and timing of the following functions:

1) Normal source voltage-sensing and frequency-sensing relays.

2) Engine start sequence.

3) Time delay on transfer.

4) Alternative source voltage-sensing and frequency-sensing relays.

5) Automatic transfer operation.

6) Interlocks and limit switch function.

7) Time delay and retransfer on normal power restoration.

8) Engine cool-down and shutdown feature.

3. Measure insulation resistance phase-to-phase and phase-to-ground with insulation-resistance tester. Include external annunciation and control circuits. Use test voltages and procedure recommended by manufacturer. Comply with manufacturer's specified minimum resistance.

a. Check for electrical continuity of circuits and for short circuits.

b. Inspect for physical damage, proper installation and connection, and integrity of barriers, covers, and safety features.

c. Verify that manual transfer warnings are properly placed.

d. Perform manual transfer operation.

4. After energizing circuits, perform each electrical test for transfer switches stated in NETA ATS and demonstrate interlocking sequence and operational function for each switch at least three times.

a. Simulate power failures of normal source to automatic transfer switches and retransfer from emergency source with normal source available.

b. Simulate loss of phase-to-ground voltage for each phase of normal source.

c. Verify time-delay settings.

d. Verify pickup and dropout voltages by data readout or inspection of control settings.

140P6221Q0011 Attachment 5 Page 6 of 6

TRANSFER SWITCHES 263600 - 6

e. Verify proper sequence and correct timing of automatic engine starting, transfer time delay, retransfer time delay on restoration of normal power, and engine cool-down and shutdown.

B. Coordinate tests with tests of generator and run them concurrently.

C. Report results of tests and inspections in writing. Record adjustable relay settings and measured insulation and contact resistances and time delays. Attach a label or tag to each tested component indicating satisfactory completion of tests.

D. Transfer switches will be considered defective if they do not pass tests and inspections.

E. Remove and replace malfunctioning units and retest as specified above.

F. Prepare test and inspection reports.

3.4 DEMONSTRATION

A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain transfer switches and related equipment.

B. Training shall include testing ground-fault protective devices and instructions to determine when the ground-fault system shall be retested. Include instructions on where ground-fault sensors are located and how to avoid negating the ground-fault protection scheme during testing and circuit modifications.

C. Coordinate this training with that for generator equipment.

END OF SECTION 263600

PART 1 - GENERAL
1.1 SUMMARY
A. Section includes automatic transfer switches rated 600 V and less.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Shop Drawings:
1. Include plans, elevations, sections, details showing minimum clearances, conductor entry provisions, gutter space, and installed features and devices.
2. Single-Line Diagram: Show connections between transfer switch, power sources, and load.
1.3 INFORMATIONAL SUBMITTALS
A. Source quality control reports.
B. Field quality-control reports.
1.4 CLOSEOUT SUBMITTALS
A. Operation and maintenance data.
1.5 QUALITY ASSURANCE
A. Installer Qualifications: An authorized representative who is trained and approved by manufacturer.
B. Testing Agency Qualifications: Accredited by NETA.
1. Testing Agency's Field Supervisor: Certified by NETA to supervise on-site testing.
1.6 WARRANTY
A. Manufacturer's Warranty: Manufacturer agrees to repair or replace components of transfer switch or transfer switch components that fail in materials or workmanship within specified warranty period.
1. Warranty Period: Five years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Generac Model RTSW200K3 with Nexus controller (basis of design)
B. Cummins
C. Kohler
D. Caterpillar
2.2 PERFORMANCE REQUIREMENTS
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
B. NEMA/UL Type 3R enclosure.
C. Service Disconnect.
D. Comply with NEMA ICS 3.
E. Comply with NFPA 110.<DELETE – PART E ‘NOT USED’>
F. Comply with UL 1008 unless requirements of these Specifications are stricter.
G. Tested Fault-Current Closing and Short-Circuit Ratings: Adequate for duty imposed by protective devices at installation locations in Project under the fault conditions indicated, based on testing according to UL 1008.
1. Where transfer switch includes internal fault-current protection, rating of switch and trip unit combination shall exceed indicated fault-current value at installation location.
H. Repetitive Accuracy of Solid-State Controls: All settings shall be plus or minus 2 percent or better over an operating temperature range of minus 20 to plus 70 deg C.
I. Resistance to Damage by Voltage Transients: Components shall meet or exceed voltage-surge withstand capability requirements when tested according to IEEE C62.62. Components shall meet or exceed voltage-impulse withstand test of NEMA ICS 1.
J. Service-Rated Transfer Switch:
1. Comply with UL 869A and UL 489.
2. Provide terminals for bonding the grounding electrode conductor to the grounded service conductor.
3. In systems with a neutral, the bonding connection shall be on the neutral bus.
4. Provide removable link for temporary separation of the service and load grounded conductors.
5. Service Disconnecting Means: Externally operated, manual mechanically actuated.
K. Neutral Terminal: Solid and fully rated unless otherwise indicated.
L. Factory Wiring: Train and bundle factory wiring and label, consistent with Shop Drawings, by color-code or by numbered or lettered wire and cable with printed, tape or shrinkable sleeve markers at terminations.
1. Designated Terminals: Pressure type, suitable for types and sizes of field wiring indicated.
2. Power-Terminal Arrangement and Field-Wiring Space: Suitable for top, side, or bottom entrance of feeder conductors as indicated.
3. Control Wiring: Equipped with lugs suitable for connection to terminal strips.

M. Enclosures: General-purpose NEMA 250, Type 3R, complying with NEMA ICS 6 and UL 508, unless otherwise indicated.

2.3 CONTACTOR-TYPE AUTOMATIC TRANSFER SWITCHES
A. Switch Characteristics: Designed for continuous-duty repetitive transfer of full-rated current between active power sources.
1. Limitation: Switches using molded-case switches or circuit breakers or insulated-case circuit-breaker components are unacceptable.
2. Contacts: Silver composition or silver alloy for load-current switching. Contactor-style automatic transfer-switch units, rated 600 A and higher, shall have separate arcing contacts.
3. Conductor Connectors: Suitable for use with conductor material and sizes.
4. Main and Neutral Lugs: Mechanical type.
5. Ground Lugs and Bus-Configured Terminators: Mechanical type.
6. Ground bar.
7. Connectors shall be marked for conductor size and type according to UL 1008.
B. Automatic Open-Transition Transfer Switches: Interlocked to prevent the load from being closed on both sources at the same time.
1. Sources shall be mechanically and electrically interlocked to prevent closing both sources on the load at the same time.
C. Signal-Before-Transfer Contacts: A set of normally open/normally closed dry contacts operates in advance of retransfer to normal source. Interval shall be adjustable from 1 to 30 seconds.
D. Automatic Transfer-Switch Controller Features:
1. All timing and sensing functions originate in the generator controller.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Annunciator and Control Panel Mounting: Flush in wall unless otherwise indicated.
B. Comply with NECA 1.
3.2 CONNECTIONS
A. Wiring to Remote Components: Match type and number of cables and conductors to generator sets, motor controls, control, and communication requirements of transfer switches as recommended by manufacturer. Increase raceway sizes at no additional cost...
B. Wiring Method: Install cables in raceways and cable trays except within electrical enclosures. Conceal raceway and cables except in unfinished spaces.
C. Wiring within Enclosures: Bundle, lace, and train conductors to terminal points with no excess and without exceeding manufacturer's limitations on bending radii.
D. Final connections to equipment shall be made with liquid tight, flexible metallic conduit no more than 18 inches (457 mm) in length.
3.3 FIELD QUALITY CONTROL
A. Perform the following tests and inspections with the assistance of a factory-authorized service representative:
1. Visual and Mechanical Inspection:
a. Compare equipment nameplate data with Drawings and Specifications.
b. Inspect physical and mechanical condition.
c. Inspect anchorage, alignment, grounding, and required clearances.
d. Verify that the unit is clean.
e. Verify appropriate lubrication on moving current-carrying parts and on moving and sliding surfaces.
f. Verify that manual transfer warnings are attached and visible.
g. Verify tightness of all control connections.
h. Inspect bolted electrical connections for high resistance using one of the following methods, or both:
1) Use of low-resistance ohmmeter.
2) Verify tightness of accessible bolted electrical connections by calibrated torque-wrench method according to manufacturer's published data.
i. Perform manual transfer operation.
j. Verify positive mechanical interlocking between normal and alternate sources.
k. Perform visual and mechanical inspection of surge arresters.
l. Inspect control power transformers.
1) Inspect for physical damage, cracked insulation, broken leads, tightness of connections, defective wiring, and overall general condition.
2) Verify that primary and secondary fuse or circuit-breaker ratings match Drawings.
3) Verify correct functioning of draw out disconnecting contacts, grounding contacts, and interlocks.
2. Electrical Tests:
a. Perform insulation-resistance tests on all control wiring with respect to ground.
b. Perform a contact/pole-resistance test. Compare measured values with manufacturer's acceptable values.
c. Verify settings and operation of control devices.
d. Calibrate and set all relays and timers.
e. Verify phase rotation, phasing, and synchronized operation.
f. Perform automatic transfer tests.
g. Verify correct operation and timing of the following functions:
1) Normal source voltage-sensing and frequency-sensing relays.
2) Engine start sequence.
3) Time delay on transfer.
4) Alternative source voltage-sensing and frequency-sensing relays.
5) Automatic transfer operation.
6) Interlocks and limit switch function.
7) Time delay and retransfer on normal power restoration.
8) Engine cool-down and shutdown feature.
3. Measure insulation resistance phase-to-phase and phase-to-ground with insulation-resistance tester. Include external annunciation and control circuits. Use test voltages and procedure recommended by manufacturer. Comply with manufacturer's specifie...
a. Check for electrical continuity of circuits and for short circuits.
b. Inspect for physical damage, proper installation and connection, and integrity of barriers, covers, and safety features.
c. Verify that manual transfer warnings are properly placed.
d. Perform manual transfer operation.
4. After energizing circuits, perform each electrical test for transfer switches stated in NETA ATS and demonstrate interlocking sequence and operational function for each switch at least three times.
a. Simulate power failures of normal source to automatic transfer switches and retransfer from emergency source with normal source available.
b. Simulate loss of phase-to-ground voltage for each phase of normal source.
c. Verify time-delay settings.
d. Verify pickup and dropout voltages by data readout or inspection of control settings.
e. Verify proper sequence and correct timing of automatic engine starting, transfer time delay, retransfer time delay on restoration of normal power, and engine cool-down and shutdown.
B. Coordinate tests with tests of generator and run them concurrently.
C. Report results of tests and inspections in writing. Record adjustable relay settings and measured insulation and contact resistances and time delays. Attach a label or tag to each tested component indicating satisfactory completion of tests.
D. Transfer switches will be considered defective if they do not pass tests and inspections.
E. Remove and replace malfunctioning units and retest as specified above.
F. Prepare test and inspection reports.
3.4 DEMONSTRATION
A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain transfer switches and related equipment.
B. Training shall include testing ground-fault protective devices and instructions to determine when the ground-fault system shall be retested. Include instructions on where ground-fault sensors are located and how to avoid negating the ground-fault p...
C. Coordinate this training with that for generator equipment.

File details come from the government source that posted it. Updated .