B09_-_SolicitationAmendment2_Atch_4_263213_REVISED_0002.pdf

PDF 172 KB Posted

Attached to
Provide and Install Generator and all wiring Federal contract opportunity
Solicitation number
140P6221Q0011
Issued by
Department of the Interior National Park Service Midwest Region

View the file

Other files for this federal contract opportunity

Other files attached to Provide and Install Generator and all wiring, newest first.
File Type Posted
B09_-_SolicitationAmendment4_Atch_6_31200_Trenching_0004.pdf PDF
B09_-_SolicitationAmendment4_Atch_7_Pics_0004.pdf PDF
Sol_140P6221Q0011_Amd_0004.pdf PDF
Sol_140P6221Q0011_Amd_0003.pdf PDF
B09_-_SolicitationAmendment2_Atch_5_263600_REVISED_0002.pdf PDF
Sol_140P6221Q0011_Amd_0002.pdf PDF
Sol_140P6221Q0011_Amd_0001.pdf PDF
B08_-_SolicitationAttachment3WD.pdf PDF
Sol_140P6221Q0011.pdf PDF
B08_-_SolicitationAttachment2Drawings.pdf PDF
B08_-_SolicitationAttachment1Specs.pdf PDF
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

140P6221Q0011 Attachment 4 Page 1 of 11

GASEOUS ENGINE GENERATORS 263213 - 1

SECTION 263213 - GASEOUS ENGINE GENERATORS

PART 1 - GENERAL

1.1 SUMMARY

A. Section includes packaged engine generators for emergency use with the following features:

1. Natural gas engine.

2. Gaseous fuel system.

3. Control and monitoring.

4. Generator overcurrent and fault protection.

5. Generator, exciter, and voltage regulator.

B. Related Requirements:

1. Section 263600 "Transfer Switches" for transfer switches including sensors and relays to initiate automatic-starting and -stopping signals for engine generators.

1.2 DEFINITIONS

A. EPS: Emergency power supply.

B. EPSS: Emergency power supply system.

1.3 ACTION SUBMITTALS

A. Product Data: For each type of product.

B. Shop Drawings:

1. Include plans and elevations for engine generator and other components specified.

2. Include details of equipment assemblies. Indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.

3. Identify fluid drain ports and clearance requirements for proper fluid drain.

4. Include diagrams for power, signal, and control wiring. Complete schematic, wiring, and interconnection diagrams showing terminal markings for EPS equipment and functional relationship between all electrical components.

1.4 INFORMATIONAL SUBMITTALS

A. Qualification Data: For Installer and testing agency.

B. Source quality-control reports.

140P6221Q0011 Attachment 4 Page 2 of 11

GASEOUS ENGINE GENERATORS 263213 - 2

C. Field quality-control reports.

D. Warranty.

1.5 CLOSEOUT SUBMITTALS

A. Operation and maintenance data.

1.6 QUALITY ASSURANCE

A. Installer Qualifications: An authorized representative who is trained and approved by manufacturer.

B. Testing Agency Qualifications: Accredited by NETA.

1. Testing Agency's Field Supervisor: Certified by NETA to supervise on-site testing.

1.7 WARRANTY

A. Manufacturer's Warranty: Manufacturer agrees to repair or replace components of packaged engine generators and associated auxiliary components that fail in materials or workmanship within specified warranty period.

1. Warranty Period: Two (2) years from date of Substantial Completion.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Generac Model QT150 with Nexus controller (basis of design)

B. Cummins

C. Kohler

D. Caterpillar

2.2 PERFORMANCE REQUIREMENTS

A. B11 Compliance: Comply with B11.19.

B. NFPA Compliance:

1. Comply with NFPA 37.

2. Comply with NFPA 70.

3. Comply with NFPA 110 requirements for Level 2 EPSS.<DELETE SENTENCE>

140P6221Q0011 Attachment 4 Page 3 of 11

GASEOUS ENGINE GENERATORS 263213 - 3

C. UL Compliance: Comply with UL 2200.

D. Environmental Conditions: Engine generator system shall withstand the following environmental conditions without mechanical or electrical damage or degradation of performance capability:

1. Ambient Temperature: 5 to 104 deg F.

2. Relative Humidity: Zero to 95 percent.

2.3 ENGINE GENERATOR ASSEMBLY DESCRIPTION

A. Factory-assembled and -tested, water-cooled engine, with brushless generator and accessories.

B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and use.

C. EPSS Class: Engine generator shall be classified as Class 2 according to NFPA 110.<DELETE

SENTENCE – PART C ‘NOT USED’>

D. Service Load: 150 kVA.

E. Power Factor: 0.8, lagging.

F. Frequency: 60 Hz.

G. Voltage: 480-V ac.

H. Phase: Three-phase, Six-wire wye.

I. Induction Method: Naturally aspirated.

J. Governor: Adjustable isochronous, with speed sensing.

K. Mounting Frame: Structural-steel framework to maintain alignment of mounted components without depending on concrete foundation. Provide lifting attachments sized and spaced to prevent deflection of base during lifting and moving.

1. Rigging Diagram: Inscribed on metal plate permanently attached to mounting frame to indicate location and lifting capacity of each lifting attachment and engine generator center of gravity.

L. Capacities and Characteristics:

1. Power Output Ratings: Nominal ratings as indicated at 0.8 power factor excluding power required for the continued and repeated operation of the unit and auxiliaries.

2. Nameplates: For each major system component to identify manufacturer's name and address, and model and serial number of component.

M. Engine Generator Performance:

140P6221Q0011 Attachment 4 Page 4 of 11

GASEOUS ENGINE GENERATORS 263213 - 4

1. Steady-State Voltage Operational Bandwidth: 3 percent of rated output voltage, from no load to full load.

2. Transient Voltage Performance: Not more than 20 percent variation for 50 percent step-load increase or decrease. Voltage shall recover and remain within the steady-state operating band within three seconds.

3. Steady-State Frequency Operational Bandwidth: 0.5 percent of rated frequency, from no load to full load.

4. Steady-State Frequency Stability: When system is operating at any constant load within the rated load, there shall be no random speed variations outside the steady-state operational band and no hunting or surging of speed.

5. Transient Frequency Performance: Less than 5 percent variation for 50 percent step-load increase or decrease. Frequency shall recover and remain within the steady-state operating band within five seconds.

6. Output Waveform: At no load, harmonic content measured line to line or line to neutral shall not exceed 5 percent total and 3 percent for single harmonics. Telephone influence factor, determined according to NEMA MG 1, shall not exceed 50 percent.

7. Sustained Short-Circuit Current: For a three-phase, bolted short circuit at system output terminals, system shall supply a minimum of 250 percent of rated full-load current for not less than 10 seconds and then clear the fault automatically, without damage to generator system components.

8. Start Time: Comply with NFPA 110, Type 10, system requirements.<DELETE

SENTENCE>

2.4 ENGINE

A. Fuel: Natural gas.

B. Rated Engine Speed: 3600 rpm.

C. Lubrication System: Engine or skid mounted.

1. Filter and Strainer: Rated to remove 90 percent of particles 5 micrometers and smaller while passing full flow.

2. Thermostatic Control Valve: Control flow in system to maintain optimum oil temperature. Unit shall be capable of full flow and is designed to be fail-safe.

3. Crankcase Drain: Arranged for complete gravity drainage to an easily removable container with no disassembly and without use of pumps, siphons, special tools, or appliances.

D. Cooling System: Closed loop, liquid cooled, with radiator factory mounted on engine generator mounting frame and integral engine-driven coolant pump.

1. Coolant: Solution of 50 percent ethylene-glycol-based antifreeze and 50 percent water, with anticorrosion additives as recommended by engine manufacturer.

2. Size of Radiator: Adequate to contain expansion of total system coolant, from cold start to 110 percent load condition.

3. Temperature Control: Self-contained, thermostatic-control valve modulates coolant flow automatically to maintain optimum constant coolant temperature as recommended by engine manufacturer.

140P6221Q0011 Attachment 4 Page 5 of 11

GASEOUS ENGINE GENERATORS 263213 - 5

4. Coolant Hose: Flexible assembly with inside surface of nonporous rubber and outer covering of aging-, UV-, and abrasion-resistant fabric.

a. Rating: 50-psig (345-kPa) maximum working pressure with coolant at 180 deg F (82 deg C), and non-collapsible under vacuum.

b. End Fittings: Flanges or steel pipe nipples with clamps to suit piping and equipment connections.

E. Muffler/Silencer: Critical type, sized as recommended by engine manufacturer and selected with exhaust piping system to not exceed engine manufacturer's engine backpressure requirements.

1. Minimum sound attenuation of 25 dB at 500 Hz.

2. Sound level measured at a distance of 25 feet (8 m) from exhaust discharge after installation is complete shall be 79 dBA or less.

F. Air-Intake Filter: Standard-duty, engine-mounted air cleaner with replaceable dry-filter element and "blocked filter" indicator.

G. Starting System: 12-V electric, with negative ground.

1. Components: Sized so they are not damaged during a full engine-cranking cycle, with ambient temperature at maximum specified in "Performance Requirements" Article.

2. Cranking Motor: Heavy-duty unit that automatically engages and releases from engine flywheel without binding.

3. Battery: Lead acid, with capacity within ambient temperature range specified in "Performance Requirements" Article to provide specified cranking cycle at least three times without recharging.

4. Battery Cable: Size as recommended by engine manufacturer for cable length indicated.

Include required interconnecting conductors and connection accessories.

5. Battery Compartment: Factory fabricated of metal with acid-resistant finish and thermal insulation. Thermostatically controlled heater shall be arranged to maintain battery above 50 deg F (10 deg C) regardless of external ambient temperature within range specified in "Performance Requirements" Article. Include accessories required to support and fasten batteries in place. Provide ventilation to exhaust battery gases.

6. Battery Stand: Factory-fabricated, two-tier metal with acid-resistant finish designed to hold the quantity of battery cells required and to maintain the arrangement to minimize lengths of battery interconnections.

7. Battery-Charging Alternator: Factory mounted on engine with solid-state voltage regulation and 30-A minimum continuous rating.

8. Battery Charger: Current-limiting, automatic-equalizing and float-charging type designed for lead-acid batteries. Unit shall comply with UL 1236 and include the following features:

a. Operation: Equalizing-charging rate of 2 A shall be initiated automatically after battery has lost charge until an adjustable equalizing voltage is achieved at battery terminals. Unit shall then be automatically switched to a lower float-charging mode and shall continue to operate in that mode until battery is discharged again.

b. Automatic Temperature Compensation: Adjust float and equalize voltages for variations in ambient temperature from minus 40 to 140 deg F (minus 40 to plus 60

140P6221Q0011 Attachment 4 Page 6 of 11

GASEOUS ENGINE GENERATORS 263213 - 6

deg C) to prevent overcharging at high temperatures and undercharging at low temperatures.

c. Automatic Voltage Regulation: Maintain constant output voltage regardless of input voltage variations up to plus or minus 10 percent.

d. Ammeter and Voltmeter: Flush mounted in door. Meters shall indicate charging rates.

9. Accessories:

a. Cold Weather Kit.

b. Base Plug Kit

2.5 GASEOUS FUEL SYSTEM

A. Natural Gas Piping: Comply with requirements in Section 231123 "Facility Natural Gas Piping."

B. Gas Train: Comply with NFPA 37.

C. Engine Fuel System:

1. Natural Gas, Vapor-Withdrawal System:

a. Carburetor.

b. Secondary Gas Regulators: One for each fuel type, with atmospheric vents piped to building exterior.

c. Fuel-Shutoff Solenoid Valves: NRTL-listed, normally closed, safety shutoff valves; one for each fuel source.

2. Fuel Filters: One for each fuel type.

3. Manual Fuel Shutoff Valves: One for each fuel type.

4. Flexible Fuel Connectors: Minimum one for each fuel connection.

2.6 CONTROL AND MONITORING

A. Automatic Starting System Sequence of Operation: When mode-selector switch on the control and monitoring panel is in the automatic position, remote-control contacts in one or more separate automatic transfer switches initiate starting and stopping of engine generator. When mode-selector switch is switched to the on position, engine generator starts. The off position of same switch initiates engine generator shutdown. When engine generator is running, specified system or equipment failures or derangements automatically shut down engine generator and initiate alarms.

B. Manual Starting System Sequence of Operation: Switching On-Off switch on the generator control panel to the on position starts engine generator. The off position of same switch initiates engine generator shutdown. When engine generator is running, specified system or equipment failures or derangements automatically shut down engine generator and initiate alarms.

C. Provide minimum run-time control set for 15 minutes, with override only by operation of a remote emergency-stop switch.

140P6221Q0011 Attachment 4 Page 7 of 11

GASEOUS ENGINE GENERATORS 263213 - 7

D. Comply with UL 508A.

E. Configuration: Operating and safety indications, protective devices, basic system controls, and engine gages shall be grouped in a common control and monitoring panel mounted on the engine generator. Mounting method shall isolate the control panel from engine generator vibration. Panel shall be powered from the engine generator battery.

F. Control and Monitoring Panel:

1. Digital controller with integrated LCD display, controls, and microprocessor, capable of local and remote control, monitoring, and programming, with battery backup.

2. Instruments: Located on the control and monitoring panel and viewable during operation.

a. Engine lubricating-oil pressure.

b. Engine-coolant temperature.

c. DC voltmeter (alternator battery charging).

d. Running-time meter.

e. AC ammeter, for each phase.

f. AC frequency meter.

g. Generator-voltage adjusting rheostat.

3. Controls and Protective Devices: Controls, shutdown devices, and common visual alarm indication as required by NFPA 110 for Level 2 system,<DELETE PORITON OF SENTENCE> including the following:

a. Cranking control equipment.

b. Run-Off-Auto switch.

c. Overcrank alarm.<DELETE>

d. Overcrank shutdown device.

e. High engine temperature. <DELETE>

f. High engine temperature shutdown device.

g. Overspeed alarm. <DELETE>

h. Overspeed shutdown device.

i. Coolant high-temperature alarm. <DELETE>

j. Coolant high-temperature shutdown device.

k. EPS load indicator. <DELETE>

l. Contacts for local and remote common alarm. <DELETE>

2.7 GENERATOR OVERCURRENT AND FAULT PROTECTION

A. Overcurrent protective devices for the entire EPSS shall be coordinated to optimize selective tripping when a short circuit occurs. Coordination of protective devices shall consider both utility and EPSS as the voltage source.

1. Overcurrent protective devices for the EPSS shall be accessible only to authorized personnel.

B. Generator Circuit Breaker: Molded-case, thermal-magnetic type; 100 percent rated; complying with UL 489.

140P6221Q0011 Attachment 4 Page 8 of 11

GASEOUS ENGINE GENERATORS 263213 - 8

1. Tripping Characteristic: Designed specifically for generator protection.

2. Trip Rating: Matched to generator output rating.

3. Shunt Trip: Connected to trip breaker when engine generator is shut down by other protective devices.

4. Mounting: Adjacent to, or integrated with, control and monitoring panel.

2.8 GENERATOR, EXCITER, AND VOLTAGE REGULATOR

A. Comply with NEMA MG 1.

B. Drive: Generator shaft shall be directly connected to engine shaft. Exciter shall be rotated integrally with generator rotor.

C. Electrical Insulation: Class H.

D. Stator-Winding Leads: Brought out to terminal box to permit future reconnection for other voltages if required. Provide 12-lead alternator.

E. Range: Provide limited range of output voltage by adjusting the excitation level.

F. Construction shall prevent mechanical, electrical, and thermal damage due to vibration, overspeed up to 125 percent of rating, and heat during operation at 110 percent of rated capacity.

G. Voltage Regulator: Solid-state type, separate from exciter, providing automatic voltage regulation<ADD TO SENTENCE> performance. as specified and as required by NFPA

110.<DELETE PORTION OF SENTENCE>

1. Maintain voltage within 5 percent on one step, full load.<DELETE>

2. Provide anti-hunt provision to stabilize voltage.<DELETE>

3. Maintain frequency within 25 percent and stabilize at rated frequency within five seconds.<DELETE>

2.9 SOURCE QUALITY CONTROL

A. Prototype Testing: Factory test engine generator using same engine model, constructed of identical or equivalent components and equipped with identical or equivalent accessories.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Interruption of Existing Electrical Service: Do not interrupt electrical service to facilities occupied by Owner or others unless permitted under the following conditions and then only after arranging to provide temporary electrical service according to requirements indicated:

1. Notify COR no fewer than Five working days in advance of proposed interruption of electrical service.

140P6221Q0011 Attachment 4 Page 9 of 11

GASEOUS ENGINE GENERATORS 263213 - 9

B. Comply with packaged engine generator manufacturers' written installation and alignment instructions and with NFPA110<DELETE PORTION OF SENTENCE>.

C. Equipment Mounting:

1. Install packaged engine generators on cast-in-place concrete equipment bases.

2. Coordinate size and location of concrete bases for packaged engine generators. Cast anchor-bolt inserts into bases. Concrete, reinforcement, and formwork requirements are specified with concrete.

D. Install packaged engine generator to provide access, without removing connections or accessories, for periodic maintenance.

E. Gaseous Fuel Piping:

1. Natural gas piping, valves, and specialties for gas distribution are specified in Section 231123 "Facility Natural Gas Piping."

F. Electrical Wiring: Install electrical devices furnished by equipment manufacturers but not specified to be factory mounted.

3.2 CONNECTIONS

A. Piping installation requirements are specified in other Sections. Drawings indicate general arrangement of piping and specialties.

B. Connect fuel piping adjacent to packaged engine generator to allow service and maintenance.

C. Gaseous Fuel Connections:

1. Connect fuel piping to engines with a ball valve and union and flexible connector.

2. Install manual shutoff valve in a remote location to isolate gaseous fuel supply to the generator.

D. Balance single-phase loads to obtain a maximum of 10 percent unbalance between any two phases.

3.3 IDENTIFICATION

A. Install a sign indicating the generator neutral is bonded to the main service neutral at the main service location.

3.4 FIELD QUALITY CONTROL

A. Manufacturer's Field Service: Engage a factory-authorized service representative to test and inspect components, assemblies, and equipment installations, including connections.

B. Tests and Inspections:

140P6221Q0011 Attachment 4 Page 10 of 11

GASEOUS ENGINE GENERATORS 263213 - 10

1. Perform tests recommended by manufacturer and each visual and mechanical inspection and electrical and mechanical test listed in first two subparagraphs below, as specified in NETA ATS. Certify compliance with test parameters.

a. Visual and Mechanical Inspection:

1) Compare equipment nameplate data with Drawings and the Specifications.

2) Inspect physical and mechanical condition.

3) Inspect anchorage, alignment, and grounding.

4) Verify that the unit is clean.

b. Electrical and Mechanical Tests:

1) Perform insulation-resistance tests according to IEEE 43.

a) Machines Larger Than 200 hp (150 kW): Test duration shall be 10 minutes. Calculate polarization index.

b) Machines 200 hp (150 kW) or Less: Test duration shall be one minute. Calculate the dielectric-absorption ratio.

2) Test protective relay devices.

3) Verify phase rotation, phasing, and synchronized operation as required by the application.

4) Functionally test engine shutdown for low oil pressure, overtemperature, overspeed, and other protection features as applicable.

5) Conduct performance test according to NFPA 110.<DELETE>

6) Verify correct functioning of the governor and regulator.

2. NFPA 110 Acceptance Tests: Perform tests required by NFPA 110 that are additional to those specified here including, but not limited to, single-step full-load pickup test.<DELETE>

3. Battery-Charger Tests: Verify specified rates of charge for both equalizing and float-charging conditions.

4. System Integrity Tests: Methodically verify proper installation, connection, and integrity of each element of engine generator system before and during system operation. Check for air, exhaust, and fluid leaks.

5. Voltage and Frequency Transient Stability Tests: Use recording oscilloscope to measure voltage and frequency transients for 50 and 100 percent step-load increases and decreases, and verify that performance is as specified.

6. Harmonic-Content Tests: Measure harmonic content of output voltage at 25 and 100 percent of rated linear load. Verify that harmonic content is within specified limits.

C. Coordinate tests with tests for transfer switches and run them concurrently.

D. Test instruments shall have been calibrated within the past 12 months, traceable to NIST Calibration Services, and adequate for making positive observation of test results. Make calibration records available for examination on request.

E. Leak Test: After installation, charge exhaust, coolant, and fuel systems and test for leaks. Repair leaks and retest until no leaks exist.

140P6221Q0011 Attachment 4 Page 11 of 11

GASEOUS ENGINE GENERATORS 263213 - 11

F. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation for generator and associated equipment.

G. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.

H. Remove and replace malfunctioning units and retest and reinspect as specified above.

I. Retest: Correct deficiencies identified by tests and observations, and retest until specified requirements are met.

J. Report results of tests and inspections in writing. Record adjustable relay settings and measured insulation resistances, time delays, and other values and observations. Attach a label or tag to each tested component indicating satisfactory completion of tests.

3.5 DEMONSTRATION

A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain packaged engine generators.

END OF SECTION 263213

PART 1 - GENERAL
1.1 SUMMARY
A. Section includes packaged engine generators for emergency use with the following features:
1. Natural gas engine.
2. Gaseous fuel system.
3. Control and monitoring.
4. Generator overcurrent and fault protection.
5. Generator, exciter, and voltage regulator.
B. Related Requirements:
1. Section 263600 "Transfer Switches" for transfer switches including sensors and relays to initiate automatic-starting and -stopping signals for engine generators.
1.2 DEFINITIONS
A. EPS: Emergency power supply.
B. EPSS: Emergency power supply system.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Shop Drawings:
1. Include plans and elevations for engine generator and other components specified.
2. Include details of equipment assemblies. Indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.
3. Identify fluid drain ports and clearance requirements for proper fluid drain.
4. Include diagrams for power, signal, and control wiring. Complete schematic, wiring, and interconnection diagrams showing terminal markings for EPS equipment and functional relationship between all electrical components.
1.4 INFORMATIONAL SUBMITTALS
A. Qualification Data: For Installer and testing agency.
B. Source quality-control reports.
C. Field quality-control reports.
D. Warranty.
1.5 CLOSEOUT SUBMITTALS
A. Operation and maintenance data.
1.6 QUALITY ASSURANCE
A. Installer Qualifications: An authorized representative who is trained and approved by manufacturer.
B. Testing Agency Qualifications: Accredited by NETA.
1. Testing Agency's Field Supervisor: Certified by NETA to supervise on-site testing.
1.7 WARRANTY
A. Manufacturer's Warranty: Manufacturer agrees to repair or replace components of packaged engine generators and associated auxiliary components that fail in materials or workmanship within specified warranty period.
1. Warranty Period: Two (2) years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Generac Model QT150 with Nexus controller (basis of design)
B. Cummins
C. Kohler
D. Caterpillar
2.2 PERFORMANCE REQUIREMENTS
A. B11 Compliance: Comply with B11.19.
B. NFPA Compliance:
1. Comply with NFPA 37.
2. Comply with NFPA 70.
3. Comply with NFPA 110 requirements for Level 2 EPSS.<DELETE SENTENCE>
C. UL Compliance: Comply with UL 2200.
D. Environmental Conditions: Engine generator system shall withstand the following environmental conditions without mechanical or electrical damage or degradation of performance capability:
1. Ambient Temperature: 5 to 104 deg F.
2. Relative Humidity: Zero to 95 percent.
2.3 ENGINE GENERATOR ASSEMBLY DESCRIPTION
A. Factory-assembled and -tested, water-cooled engine, with brushless generator and accessories.
B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and use.
C. EPSS Class: Engine generator shall be classified as Class 2 according to NFPA 110.<DELETE SENTENCE – PART C ‘NOT USED’>
D. Service Load: 150 kVA.
E. Power Factor: 0.8, lagging.
F. Frequency: 60 Hz.
G. Voltage: 480-V ac.
H. Phase: Three-phase, Six-wire wye.
I. Induction Method: Naturally aspirated.
J. Governor: Adjustable isochronous, with speed sensing.
K. Mounting Frame: Structural-steel framework to maintain alignment of mounted components without depending on concrete foundation. Provide lifting attachments sized and spaced to prevent deflection of base during lifting and moving.
1. Rigging Diagram: Inscribed on metal plate permanently attached to mounting frame to indicate location and lifting capacity of each lifting attachment and engine generator center of gravity.
L. Capacities and Characteristics:
1. Power Output Ratings: Nominal ratings as indicated at 0.8 power factor excluding power required for the continued and repeated operation of the unit and auxiliaries.
2. Nameplates: For each major system component to identify manufacturer's name and address, and model and serial number of component.
M. Engine Generator Performance:
1. Steady-State Voltage Operational Bandwidth: 3 percent of rated output voltage, from no load to full load.
2. Transient Voltage Performance: Not more than 20 percent variation for 50 percent step-load increase or decrease. Voltage shall recover and remain within the steady-state operating band within three seconds.
3. Steady-State Frequency Operational Bandwidth: 0.5 percent of rated frequency, from no load to full load.
4. Steady-State Frequency Stability: When system is operating at any constant load within the rated load, there shall be no random speed variations outside the steady-state operational band and no hunting or surging of speed.
5. Transient Frequency Performance: Less than 5 percent variation for 50 percent step-load increase or decrease. Frequency shall recover and remain within the steady-state operating band within five seconds.
6. Output Waveform: At no load, harmonic content measured line to line or line to neutral shall not exceed 5 percent total and 3 percent for single harmonics. Telephone influence factor, determined according to NEMA MG 1, shall not exceed 50 percent.
7. Sustained Short-Circuit Current: For a three-phase, bolted short circuit at system output terminals, system shall supply a minimum of 250 percent of rated full-load current for not less than 10 seconds and then clear the fault automatically, withou...
8. Start Time: Comply with NFPA 110, Type 10, system requirements.<DELETE SENTENCE>
2.4 ENGINE
A. Fuel: Natural gas.
B. Rated Engine Speed: 3600 rpm.
C. Lubrication System: Engine or skid mounted.
1. Filter and Strainer: Rated to remove 90 percent of particles 5 micrometers and smaller while passing full flow.
2. Thermostatic Control Valve: Control flow in system to maintain optimum oil temperature. Unit shall be capable of full flow and is designed to be fail-safe.
3. Crankcase Drain: Arranged for complete gravity drainage to an easily removable container with no disassembly and without use of pumps, siphons, special tools, or appliances.
D. Cooling System: Closed loop, liquid cooled, with radiator factory mounted on engine generator mounting frame and integral engine-driven coolant pump.
1. Coolant: Solution of 50 percent ethylene-glycol-based antifreeze and 50 percent water, with anticorrosion additives as recommended by engine manufacturer.
2. Size of Radiator: Adequate to contain expansion of total system coolant, from cold start to 110 percent load condition.
3. Temperature Control: Self-contained, thermostatic-control valve modulates coolant flow automatically to maintain optimum constant coolant temperature as recommended by engine manufacturer.
4. Coolant Hose: Flexible assembly with inside surface of nonporous rubber and outer covering of aging-, UV-, and abrasion-resistant fabric.
a. Rating: 50-psig (345-kPa) maximum working pressure with coolant at 180 deg F (82 deg C), and non-collapsible under vacuum.
b. End Fittings: Flanges or steel pipe nipples with clamps to suit piping and equipment connections.
E. Muffler/Silencer: Critical type, sized as recommended by engine manufacturer and selected with exhaust piping system to not exceed engine manufacturer's engine backpressure requirements.
1. Minimum sound attenuation of 25 dB at 500 Hz.
2. Sound level measured at a distance of 25 feet (8 m) from exhaust discharge after installation is complete shall be 79 dBA or less.
F. Air-Intake Filter: Standard-duty, engine-mounted air cleaner with replaceable dry-filter element and "blocked filter" indicator.
G. Starting System: 12-V electric, with negative ground.
1. Components: Sized so they are not damaged during a full engine-cranking cycle, with ambient temperature at maximum specified in "Performance Requirements" Article.
2. Cranking Motor: Heavy-duty unit that automatically engages and releases from engine flywheel without binding.
3. Battery: Lead acid, with capacity within ambient temperature range specified in "Performance Requirements" Article to provide specified cranking cycle at least three times without recharging.
4. Battery Cable: Size as recommended by engine manufacturer for cable length indicated. Include required interconnecting conductors and connection accessories.
5. Battery Compartment: Factory fabricated of metal with acid-resistant finish and thermal insulation. Thermostatically controlled heater shall be arranged to maintain battery above 50 deg F (10 deg C) regardless of external ambient temperature within...
6. Battery Stand: Factory-fabricated, two-tier metal with acid-resistant finish designed to hold the quantity of battery cells required and to maintain the arrangement to minimize lengths of battery interconnections.
7. Battery-Charging Alternator: Factory mounted on engine with solid-state voltage regulation and 30-A minimum continuous rating.
8. Battery Charger: Current-limiting, automatic-equalizing and float-charging type designed for lead-acid batteries. Unit shall comply with UL 1236 and include the following features:
a. Operation: Equalizing-charging rate of 2 A shall be initiated automatically after battery has lost charge until an adjustable equalizing voltage is achieved at battery terminals. Unit shall then be automatically switched to a lower float-charging m...
b. Automatic Temperature Compensation: Adjust float and equalize voltages for variations in ambient temperature from minus 40 to 140 deg F (minus 40 to plus 60 deg C) to prevent overcharging at high temperatures and undercharging at low temperatures.
c. Automatic Voltage Regulation: Maintain constant output voltage regardless of input voltage variations up to plus or minus 10 percent.
d. Ammeter and Voltmeter: Flush mounted in door. Meters shall indicate charging rates.
9. Accessories:
a. Cold Weather Kit.
b. Base Plug Kit
2.5 GASEOUS FUEL SYSTEM
A. Natural Gas Piping: Comply with requirements in Section 231123 "Facility Natural Gas Piping."
B. Gas Train: Comply with NFPA 37.
C. Engine Fuel System:
1. Natural Gas, Vapor-Withdrawal System:
a. Carburetor.
b. Secondary Gas Regulators: One for each fuel type, with atmospheric vents piped to building exterior.
c. Fuel-Shutoff Solenoid Valves: NRTL-listed, normally closed, safety shutoff valves; one for each fuel source.
2. Fuel Filters: One for each fuel type.
3. Manual Fuel Shutoff Valves: One for each fuel type.
4. Flexible Fuel Connectors: Minimum one for each fuel connection.
2.6 CONTROL AND MONITORING
A. Automatic Starting System Sequence of Operation: When mode-selector switch on the control and monitoring panel is in the automatic position, remote-control contacts in one or more separate automatic transfer switches initiate starting and stopping ...
B. Manual Starting System Sequence of Operation: Switching On-Off switch on the generator control panel to the on position starts engine generator. The off position of same switch initiates engine generator shutdown. When engine generator is running, ...
C. Provide minimum run-time control set for 15 minutes, with override only by operation of a remote emergency-stop switch.
D. Comply with UL 508A.
E. Configuration: Operating and safety indications, protective devices, basic system controls, and engine gages shall be grouped in a common control and monitoring panel mounted on the engine generator. Mounting method shall isolate the control panel ...
F. Control and Monitoring Panel:
1. Digital controller with integrated LCD display, controls, and microprocessor, capable of local and remote control, monitoring, and programming, with battery backup.
2. Instruments: Located on the control and monitoring panel and viewable during operation.
a. Engine lubricating-oil pressure.
b. Engine-coolant temperature.
c. DC voltmeter (alternator battery charging).
d. Running-time meter.
e. AC ammeter, for each phase.
f. AC frequency meter.
g. Generator-voltage adjusting rheostat.
3. Controls and Protective Devices: Controls, shutdown devices, and common visual alarm indication as required by NFPA 110 for Level 2 system,<DELETE PORITON OF SENTENCE> including the following:
a. Cranking control equipment.
b. Run-Off-Auto switch.
c. Overcrank alarm.<DELETE>
d. Overcrank shutdown device.
e. High engine temperature. <DELETE>
f. High engine temperature shutdown device.
g. Overspeed alarm. <DELETE>
h. Overspeed shutdown device.
i. Coolant high-temperature alarm. <DELETE>
j. Coolant high-temperature shutdown device.
k. EPS load indicator. <DELETE>
l. Contacts for local and remote common alarm. <DELETE>
2.7 GENERATOR OVERCURRENT AND FAULT PROTECTION
A. Overcurrent protective devices for the entire EPSS shall be coordinated to optimize selective tripping when a short circuit occurs. Coordination of protective devices shall consider both utility and EPSS as the voltage source.
1. Overcurrent protective devices for the EPSS shall be accessible only to authorized personnel.
B. Generator Circuit Breaker: Molded-case, thermal-magnetic type; 100 percent rated; complying with UL 489.
1. Tripping Characteristic: Designed specifically for generator protection.
2. Trip Rating: Matched to generator output rating.
3. Shunt Trip: Connected to trip breaker when engine generator is shut down by other protective devices.
4. Mounting: Adjacent to, or integrated with, control and monitoring panel.
2.8 GENERATOR, EXCITER, AND VOLTAGE REGULATOR
A. Comply with NEMA MG 1.
B. Drive: Generator shaft shall be directly connected to engine shaft. Exciter shall be rotated integrally with generator rotor.
C. Electrical Insulation: Class H.
D. Stator-Winding Leads: Brought out to terminal box to permit future reconnection for other voltages if required. Provide 12-lead alternator.
E. Range: Provide limited range of output voltage by adjusting the excitation level.
F. Construction shall prevent mechanical, electrical, and thermal damage due to vibration, overspeed up to 125 percent of rating, and heat during operation at 110 percent of rated capacity.
G. Voltage Regulator: Solid-state type, separate from exciter, providing automatic voltage regulation<ADD TO SENTENCE> performance. as specified and as required by NFPA 110.<DELETE PORTION OF SENTENCE>
1. Maintain voltage within 5 percent on one step, full load.<DELETE>
2. Provide anti-hunt provision to stabilize voltage.<DELETE>
3. Maintain frequency within 25 percent and stabilize at rated frequency within five seconds.<DELETE>
2.9 SOURCE QUALITY CONTROL
A. Prototype Testing: Factory test engine generator using same engine model, constructed of identical or equivalent components and equipped with identical or equivalent accessories.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Interruption of Existing Electrical Service: Do not interrupt electrical service to facilities occupied by Owner or others unless permitted under the following conditions and then only after arranging to provide temporary electrical service accordi...
1. Notify COR no fewer than Five working days in advance of proposed interruption of electrical service.
B. Comply with packaged engine generator manufacturers' written installation and alignment instructions and with NFPA110<DELETE PORTION OF SENTENCE>.
C. Equipment Mounting:
1. Install packaged engine generators on cast-in-place concrete equipment bases.
2. Coordinate size and location of concrete bases for packaged engine generators. Cast anchor-bolt inserts into bases. Concrete, reinforcement, and formwork requirements are specified with concrete.
D. Install packaged engine generator to provide access, without removing connections or accessories, for periodic maintenance.
E. Gaseous Fuel Piping:
1. Natural gas piping, valves, and specialties for gas distribution are specified in Section 231123 "Facility Natural Gas Piping."

F. Electrical Wiring: Install electrical devices furnished by equipment manufacturers but not specified to be factory mounted.

3.2 CONNECTIONS
A. Piping installation requirements are specified in other Sections. Drawings indicate general arrangement of piping and specialties.
B. Connect fuel piping adjacent to packaged engine generator to allow service and maintenance.
C. Gaseous Fuel Connections:
1. Connect fuel piping to engines with a ball valve and union and flexible connector.
2. Install manual shutoff valve in a remote location to isolate gaseous fuel supply to the generator.

D. Balance single-phase loads to obtain a maximum of 10 percent unbalance between any two phases.

3.3 IDENTIFICATION
A. Install a sign indicating the generator neutral is bonded to the main service neutral at the main service location.
3.4 FIELD QUALITY CONTROL
A. Manufacturer's Field Service: Engage a factory-authorized service representative to test and inspect components, assemblies, and equipment installations, including connections.
B. Tests and Inspections:
1. Perform tests recommended by manufacturer and each visual and mechanical inspection and electrical and mechanical test listed in first two subparagraphs below, as specified in NETA ATS. Certify compliance with test parameters.
a. Visual and Mechanical Inspection:
1) Compare equipment nameplate data with Drawings and the Specifications.
2) Inspect physical and mechanical condition.
3) Inspect anchorage, alignment, and grounding.
4) Verify that the unit is clean.
b. Electrical and Mechanical Tests:
1) Perform insulation-resistance tests according to IEEE 43.
a) Machines Larger Than 200 hp (150 kW): Test duration shall be 10 minutes. Calculate polarization index.
b) Machines 200 hp (150 kW) or Less: Test duration shall be one minute. Calculate the dielectric-absorption ratio.
2) Test protective relay devices.
3) Verify phase rotation, phasing, and synchronized operation as required by the application.
4) Functionally test engine shutdown for low oil pressure, overtemperature, overspeed, and other protection features as applicable.
5) Conduct performance test according to NFPA 110.<DELETE>
6) Verify correct functioning of the governor and regulator.
2. NFPA 110 Acceptance Tests: Perform tests required by NFPA 110 that are additional to those specified here including, but not limited to, single-step full-load pickup test.<DELETE>
3. Battery-Charger Tests: Verify specified rates of charge for both equalizing and float-charging conditions.
4. System Integrity Tests: Methodically verify proper installation, connection, and integrity of each element of engine generator system before and during system operation. Check for air, exhaust, and fluid leaks.
5. Voltage and Frequency Transient Stability Tests: Use recording oscilloscope to measure voltage and frequency transients for 50 and 100 percent step-load increases and decreases, and verify that performance is as specified.
6. Harmonic-Content Tests: Measure harmonic content of output voltage at 25 and 100 percent of rated linear load. Verify that harmonic content is within specified limits.
C. Coordinate tests with tests for transfer switches and run them concurrently.
D. Test instruments shall have been calibrated within the past 12 months, traceable to NIST Calibration Services, and adequate for making positive observation of test results. Make calibration records available for examination on request.
E. Leak Test: After installation, charge exhaust, coolant, and fuel systems and test for leaks. Repair leaks and retest until no leaks exist.
F. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation for generator and associated equipment.
G. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.
H. Remove and replace malfunctioning units and retest and reinspect as specified above.
I. Retest: Correct deficiencies identified by tests and observations, and retest until specified requirements are met.
J. Report results of tests and inspections in writing. Record adjustable relay settings and measured insulation resistances, time delays, and other values and observations. Attach a label or tag to each tested component indicating satisfactory complet...
3.5 DEMONSTRATION
A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain packaged engine generators.