B08_Solicitation_(Attachment_12_-_Questions_and_Answers)_0002.docx
DOCX document 17 KB Posted
- Attached to
- HSTR, Repair Truman Farm Home Foundation
- Solicitation number
- 140P6024B0006
About this file
This document appears to be a Questions and Answers document related to the federal contract opportunity "HSTR, Repair Truman Farm Home Foundation" (Solicitation Number: 140P6024B0006). The contract is being awarded by the Department of the Interior National Park Service Midwest Region.
The key details summarized from the Questions and Answers document include information about the property, such as the location of the power meter, the status of lead paint abatement, the condition of the brick foundation, and the requirement to contact the utility company to remove the gas meter. The document also provides clarification on the scope of work, including details on the plaster and paint repair work, as well as addressing questions related to the chimneys and the need to address any lead-based paint issues. Lastly, the document addresses several bid-related questions, such as the extent of exterior wood surface painting and the requirement for crack monitors.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Truman Farm Foundation Contract – Question List June 18, 2024
1. Is power meter on the pole on North side of property the only one?
Yes; no meter on/in house.
2. What is the scope of interior finishes work, plaster, etc.? Kitchen/dining room?
The rooms having work done to plaster are indicated in the solicitation; kitchen and dining room are not included in contract.
3. What is the status of lead paint abatement?
Interior spaces have been tested. Lead paint remains in some areas. Kitchen and Dining Room work will be completed in separate contract in the future. Areas where wall/window work is required should be tested and properly treated per Project Specifications, Section 01 7400, Lead Paint Abatement.
4. Is the north wall of the second floor hallway in scope for demo?
No, only the east wall.
5. When was the roof replaced last?
6. Does the front brick foundation have a footing?
Brick foundation (original to 1894) on front portion of the house has no footing; adding the footings in identified locations is part of the solicitation.
7. Where is the access for the crawlspace?
Per the solicitation there is to be a trap door placed in the front sitting room (NW) floor.
8. Was there previous tuckpointing work in the attic chimneys?
Yes, in 1997.
9. 100 amp panel in basement- will this be upgraded as part of the scope?
Upgrading the panel is not part of the scope.
10. Can we get back inside the house if needed?
Yes, by appointment only.
Submitted questions:
11. There is a requirement to contact Spire and have them remove the existing gas meter and line beyond the excavation. One that line is removed past the point of excavation, can it be abandoned in place?
Yes
12. There is a requirement for blower fans to be used for exhausting humidity through the chimneys. Keynote 122 p13/60 in the plans. Oftentimes old chimneys fill up with debris over the years. Can the government confirm that these chimneys are clear of debris and will function in this capacity?
The chimney in the Sitting Room (NW corner) was cleaned out my NPS staff around 2012; Parlor (SW corner) has not been cleaned out. Both likely have some level of debris.
13. On page 18/60 in the plans, Keynote 140 09 0300 REPAIR HISTORIC PLASTER WITH IN-KIND PATCHES. PAINT TO MATCH ADJACENT SURFACE. All the walls in that stairwell have wallpaper on them. Can you provide a more precise description of the work you want us to do there? Where do we start and stop, what materials need to be used, etc.?
The wallpaper dates to the early 1980s and will be fully removed and walls painted in a later project. Patches can be made to the area where repairs are indicated. Remove as much wallpaper as needed to make the plaster repairs.
14. Where on the project do you anticipate us needing to address lead paint abatement?
See #3; Previous work indicates that the east upstairs wall did not have plaster replaced. See previous LBP reports and plaster schedule from 1984 work. If not previously tested, assume lead paint. Basement stone is not painted, however window on North wall does have LBP.
15. Chimney repointing, only inside the attic spaces, where accessible? This is more of a clarification – nothing above roof line, correct?
See 01 2700 Repointing chimneys; primary work is in attic, however contractor should determine whether any repointing is needed on exterior portions.
16. Bid Additive 3, Scrape, prime and paint exterior wood surfaces. Is this the home in its entirety?
No, just areas of work, those that are peeling, or appear to only have one coat of paint.
17. Crack monitors – Will NPS provide replacement monitors for reinstallation?
Contractor will supply the crack monitors.