Atch_1_to_Amd_1_QandAs_0001.pdf

PDF 48 KB Posted

Attached to
Replace Visitor Center HVACs-Cumberland Island NS
Solicitation number
140P5424Q0040
Issued by

About this file

This document is a Questions and Answers (Q&A) attachment related to a federal solicitation for replacing heating, ventilating, and air conditioning (HVAC) systems at the Cumberland Island National Seashore visitor center.

The key details are:

  • The solicitation is for a contractor to replace 4 HVAC systems at the visitor center, with a 45-day performance period.
  • The Q&A addresses questions about the size and refrigerant of the existing air handler, and confirms that an alternate refrigerant such as R-454B would be considered. It also states that reputable, name brand HVAC units such as Lennox, York, or Carrier are required.
  • The federal contract opportunity has a solicitation number of 140P5424Q0040, is a total small business set-aside, and the award will be a firm fixed price purchase order based on best value, considering price, proposed equipment, experience, past performance, and completion time.

View the file

Other files

File Type Posted
Sol_140P5424Q0040_Amd_0001.pdf PDF
Atch_1_SOW.pdf PDF
Atch_2_Required_Form.pdf PDF
Sol_140P5424Q0040.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

140P5424Q0040 Amendment 1 Attachment 1

Page 1 of 1 Page

Question #1: Can you please confirm how many tons are the air handler? During the site visit there was limited access to view the air handler located in the downstairs elevator closet. It was secured with a lock and no one had access to open the closet.

Answer: 2 tons – the unit only cools the elevator shaft, I’m not sure why it was installed in there nor why the unit is of the size unless the equipment room gets extremely hot

Question #2: Can you please confirm if an alternate refrigerant can be used other than 410a?

Answer: The most environmentally friendly refrigerants that have been in use in light commercial and residential systems for at least 5 years and is readily available will receive higher consideration than units with older refrigerants such as r410a since the EPA is phasing out r410a. For example, R-454B would receive greater consideration.

Question #3: Can you please confirm if there are any specific band preferences regarding the units?

Answer: If you are referring to “dead-band” which should be + or – 1 degree f. If you are inquiring of “brand” preferences, the units must be reputable, name brand, top of the line units such as Lennox, York, Carrier, among others.

Note: Any answers or clarifications that add to or change any information currently in the statement of work (SOW) will be incorporated before award. Acknowledgement of these answers demonstrates offeror’s receipt of updated info.