A06_NATR_304927A_100__CDs_Liepers_Fork_HVAC_Reno_Dwgs_COMBINED.pdf
PDF 6 MB Posted
- Attached to
- HVAC LF MAINT. REPLACE
- Solicitation number
- 140P5224R0003
About this file
This document contains a set of construction drawings and specifications for the replacement of the HVAC system at the Leiper's Fork District Facility along the Natchez Trace Parkway. The drawings include floor plans, reflected ceiling plans, HVAC schedules and details. The project scope involves the design and replacement of the existing HVAC systems serving the facility. The applicable codes are the 2012 and 2018 editions of various building and mechanical codes with Tennessee amendments. Key details include the existing building area of 11,220 square feet, an existing occupancy type of mixed B, S-1 and F-1, and the existing building being sprinklered.
The related federal contract opportunity is for the HVAC repair and replacement work at the Leiper's Fork District Office facility. This is a firm fixed price commercial item solicitation with a NAICS code of 238220. The evaluation factors are cost, technical approach, and relevant experience. Bidders must provide references demonstrating applicable experience. Proposals are due electronically to the Contracting Officer by the closing date specified in the solicitation.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sol_140P5224R0003.pdf | ||
| A06_NATR_LF_mechanical_dwgs.pdf | ||
| B03_DBA_Williamson_County.pdf | ||
| SOW_-_NATR_LF_HVAC_Statement_of_Work.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
International Building Code (IBC):
2012 Edition, with Tennessee Amendments
International Fuel Gas Code (IFGC):
2018 Edition, with Tennessee Amendments
National Electrical Code (NEC):
2017 Edition, with Tennessee Amendments
International Fire Code (IFC):
2012 Edition, with Tennessee Amendments
International Energy Conservation Code (IECC):
2012 Edition, with Tennessee Amendments
International Plumbing Code (IPC):
2012 Edition, with Tennessee Amendments
NFPA 101 - Life Safety Code:
2012 Edition, with Tennessee Amendments
International Mechanical Code (IMC):
2012 edition, with Tennessee Amendments
Rules and regulations of the Safety Fire Commissioner for the state minimum fire safety standards - 120-3-3:
EXISTING 2-STORY
LEIPER'S FORK RANGERS
STATION FACILITY
EXISTING STORAGE
BUILDING
CONSTRUCTION
STAGING AREA
LIMITS OF
CONSTRUCTION
NARRATIVE DESCRIPTION OF PROJECT:
The project is to complete the design and replacement of the HVAC systems that serve the Leiper’s Fork District Facility, along the Natchez Trace Parkway.
Architectural drawings of existing facility are shown for reference only. See MECH & ELEC drawings for graphic description of project scope.
APPLICABLE CODES:
PROJECT STATISTICS:
PROJECT SITE:
LEIPER'S FORK DISTRICT FACILITY
LE
IP
ERS
CREEK R
D
N A
TC
H
EZ
T
RA
C
E
PK
W Y
PINEWOOD RD
N U
M B
E R
SHEET NAME S
H
E E
T N
U M
B E
R
C U
R R
E N
T R
E V
D
A T
E
C U
R R
E N
T R
E V
N
O
01 GENERAL
G1 COVER SHEET 1
02 ARCHITECTURAL
A1 FLOOR PLANS 2
A2 REFLECTED CEILING PLANS 3
03 MECHANICAL
M1 GENERAL NOTES & LEGENDS 4
M2 HVAC - FLOOR PLAN - DEMO 5
M3 HVAC - FLOOR PLAN - NEW WORK 6
M4 HVAC - PART PLANS 7
M5 HVAC DETAILS 8
M6 HAVC SCHEDULES 9
04 ELECTRICAL
E1 ELECTRICAL NOTES & DETAILS 10
E2 ELECTRICAL RISER DIAGRAM & PANEL SCHEDULES 11
E3 FLOOR PLAN - ELECTRICAL 12
E4 ELECTRICAL SPECIFICATIONS 13
A/E FIRM
PRIME/ARCH:
TITLE OF PROJECT
NAME OF PARK
REGION COUNTY STATE
UNITED STATES
DEPARTMENT OF THE INTERIOR
NATIONAL PARK SERVICE
DENVER SERVICE CENTER
Mark Sheet REVISION InitialDate
Houser Walker Architecture Atlanta, GA
VICINITY MAP
SHEET
DRAWING NO.
PKG.
NO.
OF
LEIPER'S FORK
LEIPER'S FORK DISTRICT
FACILITY HVAC REPLACEMENT
100% CONSTRUCTION DRAWINGS
SOUTHEAST US TENNESSEEWILLIAMSON
MECHANICAL:
Johnson Spellman & Associates Inc.
Peachtree Corners, GA
ELECTRICAL:
Westside Engineering Atlanta, GA
AREA:
Existing Building Area: 11,220 sf Project Scope Area: na
HEIGHT:
Existing:
Height: 32 ft Stories: 2
Proposed:
Height: No change Stories: No change
OCCUPANCY:
Existing:
Occupancy Type: Mixed B, S-1, F-1
Proposed: No change
CONSTRUCTION:
Existing Type: III B Proposed Type: No change
SPRINKLERED:
Existing: Yes Proposed: No change
PARKING:
Existing: 19 spaces Proposed: No change
SITE PLAN1 0 4040 80
SCALE OF FEET
UP UP
411 SF
BREAK/TRAINING
150 SF
DIST. RANGER
297 SF
SHARED OFFICE
196 SF
MAINTENANCE
71 SF
STORAGE
42 SF
TELE-ELEC
785 SF
WOOD SHOP
118 SF
FURNACE
55 SF
VALVE
1,430 SF
WASH / LIFT /
SERVICE
660 SF
WELDING
927 SF
FIRE BAY
1,144 SF
WAREHOUSE
304 SF
RANGERS
153 SF
MEN
127 SF
WOMEN
CHASE
1,343 SF
STORAGE
306 SF
MECH
OPEN TO
VEHICLE BAY
BELOW
C O
R R
ID
O
R B
E
LO
W EXISTING ASPHALT
SHINGLE ROOF
BELOW
EXISTING ASPHALT
SHINGLE ROOF
BELOW
EXISTING ASPHALT
SHINGLE ROOF
BELOW
EXISTING ASPHALT
SHINGLE ROOF
BELOW
3" / 12" 3" / 12"
EXISTING OPENING
FOR MAKE-UP AIR
LOUVER & DAMPER
EXISTING OPENINGS
FOR OUTSIDE AIR
LOUVER & DAMPER
LEVEL 1 - EXISTING FLOOR PLAN1 LEVEL 2 - EXISTING FLOOR PLAN2
0 88 16
SCALE OF FEET
GENERAL NOTE:
1. See Mechanical & Electrical drawings for new scope
SHEET
1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com
TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM
Houser Walker Architecture
DATE:
TECH. REVIEW:
PKG.
NO.
OF05/05/23
A1Contact: Hank Houser
FLOOR PLANS
LEIPER'S FORK DISTRICT FACILITY HVAC REPLACEMENT
HWA
10' - 5"
8' - 0"
8' - 0"
8' - 0" 8' - 0"
10' - 5"
10' - 5"
20' - 6"12' - 0" 12' - 0" 12' - 0"
8' - 0"
20' - 6"
8' - 0"
BREAK/TRAINING
DIST. RANGER
SHARED OFFICE
MAINTENANCE
STORAGE
TELE-ELEC
WOOD SHOP
FURNACE
VALVE
WASH / LIFT /
SERVICE
WELDING FIRE BAY
WAREHOUSE
RANGERS
MEN
WOMEN
VARIES
7' - 6"
7' - 6"
12' - 0"
VARIES
3" / 12"
3" / 12"
7' - 6"
7' - 6"
NEW INDUSTRIAL
FANS ABOVE,
SEE MECH
8' - 6"
8' - 6"
20' - 6"
STORAGE
MECH
OPEN TO
VEHICLE BAY
BELOW
NEW INDUSTRIAL
FANS ABOVE,
SEE MECH
C O
R R
ID
O
R B
E
LO
W
CEILING LEGEND
- EXISTING 2X4 ACT
- EXISTING GYP BD CEILING
SHEET
1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com
TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM
Houser Walker Architecture
DATE:
TECH. REVIEW:
PKG.
NO.
OF05/05/23
A2Contact: Hank Houser
REFLECTED CEILING PLANS
LEIPER'S FORK DISTRICT FACILITY HVAC REPLACEMENT
HWA
LEVEL 1 - REFLECTED CEILING PLAN1 LEVEL 2 - REFLECTED CEILING PLAN2
GENERAL NOTES:
1. All existing ceilings to remain.
2. See mechanical & electrical drawings for new scope.
3. Patch and repaint ceilings where required at new mechanical & electrical work areas.
4. For mechanical penetrations at roof see SMACNA detail figure 4-20.
Patch & repair asphalt shingle roofing as needed.
0 88 16
SCALE OF FEET
ROOF DETAIL @ MECH PENETRATIONS3
H
C
T
T
S
TM
HVAC LEGEND & ABBREVIATIONS HVAC LEGEND & ABBREVIATIONS
SYMBOL DESCRIPTION
BALANCING VALVE
CHECK VALVE
SOLENOID VALVE
GLOBE VALVE
THREE WAY MODULATING MOTORIZED CONTROL VALVE
TWO WAY MODULATING MOTORIZED CONTROL VALVE
BALL VALVE
PRESSURE REDUCING VALVE
RELIEF VALVE
AUTOMATIC AIR VENT
MANUAL AIR VENT
THERMOMETER
PRESSURE GAUGE
DRIP LEG
TEST PLUG
THERMOMETER WELL
GAUGE COCK
STRAINER
SIGHT GLASS
SYMBOL DESCRIPTION
PIPING OR EQUIPMENT TO BE REMOVED
PIPE FLOW ARROW
CHILLED WATER RETURNCHWR
GRADE ARROW-INDICATES RISE OR DROP IN DUCT OR PIPEUP DNOR
CHILLED WATER SUPPLYCHWS
CONDENSER WATER RETURNCWR
CONDENSER WATER SUPPLYCWS
HOT WATER RETURNHWR
HOT WATER SUPPLYHWS
CONDENSATE DRAINC
LOW PRESSURE STEAM (PRESSURE SHOWN)LPS (5#)
MEDIUM PRESSURE STEAM (PRESSURE SHOWN)MPS (65#)
HIGH PRESSURE STEAM (PRESSURE SHOWN)HPS (125#)
LOW PRESSURE STEAM CONDENSATELPC
LOW PRESSURE STEAM CONDENSATEMPC
LOW PRESSURE STEAM CONDENSATEHPC
PUMPED STEAM CONDENSATEP
VENTV
REFRIGERANT LIQUIDRL
REFRIGERANT SUCTIONRS
STEAM TRAP
HUMIDITY SENSOR
TEMPERATURE SENSOR
SWITCH
TIMER
CARBON DIOXIDE SENSOR
THERMOSTAT
CONNECT TO EXISTING
EXTENT OF DEMO
HVAC LEGEND & ABBREVIATIONS
SYMBOL DESCRIPTION
RECTANGULAR AIR DUCT - FIRST DIMENSION IS SIDE SHOWN00x00
DUCT TRANSITION, RECTANGULAR TO ROUND OR OVAL
ROUND DUCT (A"∅) OR FLAT OVAL (AxB)
FIRE DAMPER (FD)
AIR DUCT FLEXIBLE CONNECTOR
DUCTWORK TO BE REMOVED
SUPPLY OR OUTSIDE AIR RECTANGULAR DUCT RISE OR DROP
RETURN AIR RECTANGULAR DUCT RISE OR DROPOR
OR
SMOKE DAMPER (SD)
COMBINATION FIRE/SMOKE DAMPER (FSD)
SQUARE ELBOW WITH TURNING VANES
DUCT TRANSITION, RECTANGULAR TO RECTANGULAR
FLEX DUCT AT DIFFUSER
DUCT-MOUNTED STATIC PRESSURE SENSOR (DM-SPS)
MANUAL VOLUME DAMPER (MD)
OR
CONCENTRIC REDUCER
PIPE UNION
PIPE RISE [DOUBLE LINE/SINGLE LINE]
PIPE DROP [DOUBLE LINE/SINGLE LINE]
CAP ON END OF LINE
GATE VALVE
BUTTERFLY VALVE
LINED DUCTWORK, DIMENSIONS ARE OUTER METAL TO OUTER METAL
SMOKE DETECTOR (SDT)
BACKDRAFT DAMPER (BDD)
OR EXHAUST AIR RECTANGULAR DUCT RISE OR DROP
ECCENTRIC REDUCER FLAT SIDE ON BOTTOM OR FLAT SIDE ON TOP
MOTOR OPERATED DAMPER (SAME SIZE AS DUCT UNLESS OTHERWISE NOTED) (MOD)
AIR FLOW SENSOR (AFS)
MECHANICAL - GENERAL NOTES
1. EXISTING EQUIPMENT, DUCTWORK AND PIPING TO REMAIN, UNLESS NOTED TO BE REMOVED.
2. VERIFY LOCATIONS OF EXISTING PIPING, DUCTWORK AND EQUIPMENT PRIOR TO BEGINNING WORK.
3. PROVIDE INSULATED FLEXIBLE DUCT TO DIFFUSER SAME SIZE AS DIFFUSER NECK SIZE WITH SPIN-IN AND SINGLE BLADE DAMPER AT DIFFUSER TAKE-OFF.
4. RUNOUTS TO DIFFUSERS SHALL BE SAME SIZE AS DIFFUSER NECK, UNLESS OTHERWISE NOTED.
5. ALL EXISTING EQUIPMENT, DUCTWORK AND PIPING IS SHOWN LIGHT DASHED, DEMO WORK IS BOLD DOTTED, AND NEW WORK IS BOLD SOLID.
6. ROUTE DUCTWORK AS TIGHT TO STRUCTURE AS POSSIBLE, UNLESS OTHERWISE NOTED.
7. MAXIMUM FLEXIBLE DUCT RUNOUT TO BE FIVE FEET. USE GALVANIZED STEEL DUCT FOR INDIVIDUAL RUNOUTS OVER FIVE FEET.
8. BALANCE AIR DISTRIBUTION SYSTEMS AS NOTED.
9. UNLESS OTHERWISE NOTED, WALL MOUNTED THERMOSTATS AND SENSORS SHALL BE MOUNTED AT 4'-0" AFF. COORDINATE FINAL DEVICE LOCATIONS AND HEIGHTS WITH
ARCHITECT AND ARCHITECTURAL DRAWINS PRIOR TO INSTALLATION.
10. COORDINATE ALL LAY-IN CEILING DIFFUSERS WITH ARCHITECTURAL REFLECTED CEILING PLAN.
11. PROTECT ALL MATERIALS AND EQUIPMENT FROM DAMAGE.
12. CONTRACTOR SHALL PAINT ALL DUCTWORK VISIBLE THROUGH SUPPLY AND RETURN AIR OPENINGS AND GRILLES FLAT BLACK.
13. CONTRACTOR TO COORDINATE FIRE DAMPER HOURLY RATINGS WITH GENERAL CONTRACTOR AND ARCHITECTURAL DRAWINGS.
14. COORDINATE ALL MANUAL VOLUME DAMPERS TO BE LOCATED IN AN ACCESSIBLE LOCATION.
15. SEE SPECIFICATIONS REGARDING DUCTWORK CLEANLINESS AND DUCT PROTECTION DURING CONSTRUCTION.
16. CONTRACTOR SHALL COORDINATE LOCATION AND QUANTITY OF ALL MANUAL DAMPERS, MOTORIZED DAMPERS, FILTER RACKS, SMOKE DETECTORS, ETC WITH CONTROL
SCHEMATIC DRAWINGS.
17. FLEXIBLE DUCTWORK SHALL NOT BE INSTALLED ABOVE INACESSIBLE CEILINGS.
18. FLEXIBLE DUCTWORK SHALL NOT BE INSTALLED IN RETURN OR EXHAUST AIR SYSTEMS UNLESS OTHERWISE NOTED.
19. ALL PIPING RUNOUTS TO EQUIPMENT SHALL BE 3/4" UNLESS OTHERWISE NOTED.
20. EQUIPMENT ABOVE ACESSIBLE CEILINGS SHALL BE LOCATED WITH BOTTOM OF UNIT ACESSIBLE FROM THE CEILING LEVEL, NOT TO EXCEED 24" ABOVE THE CEILING.
21. ALL RETURN GRILLES SHALL BE TYPE R-1 UNLESS OTHERWISE NOTED.
22. NO FIELD PENETRATIONS OF AIR HANDLING UNIT CASINGS ARE PERMITTED. NO CONDUITS, PIPES, OR DEVICES SHALL BE ATTACHED TO THE CASING WITH SCREWS, BOLTS,OR OTHER ATTACHMENT METHODS THAT REQUIRE PIERCING OF THE CASING. ACCEPTABLE ATTACHMENT METHOD IS USE OF PERFORATED BASE STUDS (MCMASTER CARR PART #97590A315 OR EQUAL) BONDED TO THE OUTER UNIT CASING WITH EPOXY (GRAINGER PART # 3XH44 OR EQUAL).
SHEET
1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com
TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM
Houser Walker Architecture
DATE:
TECH. REVIEW:
PKG.
NO.
OF
M1Contact: Hank Houser
GENERAL NOTES & LEGENDS
SCHEMATIC DESIGN
JSA
HWA25
Rectangle
HWA25
Snapshot
HWA25
Snapshot
1 1 1
6 8
EXISTING 8x8 DUCT
TO BE REMOVED
EXIST. VACUUM
DUCT TO REMAIN
EXIST. VACUUM
DUCT TO REMAIN
EXIST. VACUUM
DUCT TO REMAIN
5 5
SHEET
1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com
TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM
Houser Walker Architecture
DATE:
TECH. REVIEW:
PKG.
NO.
OF
M2Contact: Hank Houser
HVAC - FLOOR PLAN - DEMO
SCHEMATIC DESIGN
JSA
4 4 8 16 1/8" = 1'-0"
FEETSCALE
SCALE: 1/8" = 1'-0"1 1ST FLOOR PLAN - DEMO
4 4 8 16
1/8" = 1'-0"
FEETSCALE
SCALE: 1/8" = 1'-0"2 2ND FLOOR PLAN - DEMO
GENERAL NOTES - HVAC
Key Name General Notes - HVAC
1 SEE SHEET M-001 FOR HVAC GENERAL NOTES.
KEY NOTES #
1. EXISTING UNIT HEATER TO BE REMOVED. REMOVE EXISTING GAS PIPING TO
NEAREST SHUT-OFF.
2. EXISTING AIR HANDLER UNIT TO BE REMOVED.
3. EXISTING MIXING AIR UNIT TO BE REMOVED.
4. EXISTING EXHAUST FAN TO REMAIN.
5. EXISTING OUTSIDE AIR LOUVER TO BE REMOVED
6. EXISTING DUCT FURNACE TO BE REMOVED
7. EXISTING EXHAUST FAN TO BE REMOVED.
8. EXISTING OUTDOOR CONDENSING UNIT TO BE REMOVED.
9. EXISTING DUST COLLECTOR TO BE REMOVED.
HWA25
Rectangle
HWA25
Snapshot
UH-6
UH-5
UH-4 UH-3 UH-2
UH-1
T
T
T
T T
T
T
BREAK/TRAINING
DIST. RANGER
SHARED OFFICE
MAINTENANCE
STORAGE
TELE-ELEC
WOOD SHOP
FURNACE
VALVE
WASH / LIFT / SERVICE
WELDING
FIRE BAY
WAREHOUSE
RANGERS
MEN
WOMEN
CHASE
AHU-1
CU-1
DFU-1
EF-1
EF-2
EF-3
8" ø
8" ø
4'-0"
S-1
12x12 EXHAUST DUCT
UP TO NEW EF-6
WELDING HOOD
EXHAUST DUCT
UP TO NEW EF-5
EXISTING EXHAUST
DUCT UP TO NEW EF-4
DSSC
10"ø
TYP.2
EXIST.
8"ø
EXIST.
16x10
EXIST.
20x14
EXIST.
14X8
EXIST.
14X8
EXIST.
12" Ø
EXIST.
8"ø
EXIST.
10"ø
EXIST.
14x12
EXIST.
20x14 x1 x1
20x12 x1
30x14 x8 x1
30x14
30x14 12x12 x1 x1
24x18
14x6
14x4
12x4 x1 x1 x1
14x12
EXIST.
8"ø
EXIST.
6x6
EXIST.
6"ø
EXIST.
6"ø
EXIST.
18x12
TYP.6
EXIST.
T
M4
TO MUA-1
TO AHU-1
H
DC-1
EXIST. VACUUM
DUCT TO REMAIN
FITNESS AREA
MECH
OPEN TO VEHICLE BAY BELOW
HVLS-1 HVLS-2
10"ø
E-1
DSSA-1
4'-0"
S-1
MUA-1
EF-4
UP TO EF-7
DSSA-2
4'-0"
S-1
EXISTING LV-2, MOTORIZED
DAMPER TO BE REPLACED
EXISTING L1
EXISTING 12x4 EXHAUST
DUCT UP INTO ATTIC
THEN HORIZONTAL (TYP.3)
12x12 R-2 RETURNING AIR
HIGH IN CORRIDOR SPACE
EXISTING LV-2, MOTORIZED
DAMPER TO BE REPLACED
SHEET
1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com
TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM
Houser Walker Architecture
DATE:
TECH. REVIEW:
PKG.
NO.
OF
M3Contact: Hank Houser
HVAC - FLOOR PLAN - NEW
WORK
SCHEMATIC DESIGN
JSA
4 4 8 16 1/8" = 1'-0"
FEETSCALE
SCALE: 1/8" = 1'-0"1 1ST FLOOR PLAN - NEW WORK
4 4 8 16
1/8" = 1'-0"
FEETSCALE
SCALE: 1/8" = 1'-0"2 2ND FLOOR PLAN - NEW WORK
GENERAL NOTES - HVAC
Key Name General Notes - HVAC
1 SEE SHEET M-001 FOR HVAC GENERAL NOTES.
KEY NOTES #
1. SLOT DIFFUSER SERVING FITNESS AREA ON FLOOR ABOVE,
HWA25
Rectangle
HWA25
Snapshot
12x12
15x1830x14
30x14 x3
AHU-1
M4
M4
24x12
LV-3
AHU-1
15x18
EXISTING DUCTWORK
NEW 12x12 DUCTWORK CONNECTING
INTO EXISTING DUCT
DFU-1
12x12
NEW DUCTWORK CONNECTING NEW
AHU-1 INTO EXISTING DUCTWORK
NEW DUCTWORK CONNECTING NEW
AHU-1 INTO EXISTING DUCTWORK
LEVEL 1
0"
LEVEL 2
12' - 8"
LEVEL 1
0'-0"
LEVEL 2
12'-8"
M4
12x12
24x12
LV-3
18x15
14x30
DFU-1
AHU-1
6x6
EXIST.
LEVEL 1
0"
LEVEL 2
12' - 8"
LEVEL 1
0'-0"
LEVEL 2
12'-8"
M4
15x18
12x12
6x6
EXIST.
30x
AHU-1
DFU-1
NEW 12x12 DUCTWORK CONNECTING
TO EXISTING DUCTWORK
SHEET
1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com
TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM
Houser Walker Architecture
DATE:
TECH. REVIEW:
PKG.
NO.
OF
M4Contact: Hank Houser
HVAC - PART PLANS
SCHEMATIC DESIGN
Author
1 1 2 4 5 1/2" = 1'-0"
FEETSCALE
SCALE: 1/2" = 1'-0"4 MECHANICAL PART PLAN
SCALE: NO SCALE1 MECHANICAL PERSPECTIVE
1 1 2 4 5 1/2" = 1'-0"
FEETSCALE
SCALE: 1/2" = 1'-0"2 MECHANlCAL SECTION VIEW
1 1 2 4 5 1/2" = 1'-0"
FEETSCALE
SCALE: 1/2" = 1'-0"3 MECHANICAL SECTION VIEW
HWA25
Rectangle
HWA25
Snapshot
3'
MI
N.
DOWN DRAFT
PROOF CAP
FLASH AND
COUNTER FLASH
ROOF
REUSE EXISTING EXHAUST
NEW PIPE TO CONNECT
UNIT HEATER TO EXISTING
CEILING PENETRATION
REUSE EXISTING OR
SIMILAR ATTACHMENT
NEW UNIT HEATER
REUSE EXISTING EXHAUST
DOWN DRAFT
PROOF CAP
INSULATED
DOUBLE WALL
FLUE (SEE
SPECIFICATIONS)
MANUFACTURER'S VENTILATED ROOF
THIMBLE
ROOF
MAINTAIN
MANUFACTURER'S
MINIMUM CLEARANCE
FROM COMBUSTIBLES
MINIMUM 3'
ABOVE HIGHEST
POINT ON ROOF
WITHIN 10'
1'-6"
FLEXIBLE COUPLING
DIRT LEG
FLANGED JOINT OR UNION TO
PERMIT PIPING DISASSEMBLY
FOR BURSTING DISC
SERVICING
CAP HANDTIGHT TO
PERMIT CLEANOUT
5" REFRIGERANT RELIEF VENTED TO THE
OUTSIDE OF BUILDING SEE SHEET M11.2 FOR
CONTINUATION
PIPING CONNECTION TO RUPTURE DISK FLANGE
AND ALL PIPING TO OUTDOORS PROVIDED BY
CONTRACTOR
NON-FRAGMENTING COMPOSITE
MATERIAL RUPTURE DISK
RELIEF
CONNECTION
LINED RETURN AIR
TRANSFER DUCT, SIZE
(LINER TO LINER) AS
NOTED ON DRAWING.
INTERIOR WALL
OPEN END
DUCT HIGH IN CORRIDOR
NOTES:
1. TRANSFER AIR DUCT MAY BE INSTALLED IN HORIZONTAL OR VERTICAL ARRANGEMENT. IF
INSTALLED IN HORIZONTAL ARRANGEMENT THE OPEN ENDS OF DUCT SHALL BE POINTED UP.
SHEET
1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com
TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM
Houser Walker Architecture
DATE:
TECH. REVIEW:
PKG.
NO.
OF
M5Contact: Hank Houser
HVAC DETAILS
SCHEMATIC DESIGN
JSA
SCALE: NO SCALE1 GAS UNIT HEATER INSTALLATION
SCALE: NO SCALE3 GAS FLUE CAP DIAGRAM
SCALE: NO SCALE4 REFRIGERANT VENT PIPING
SCALE: NO SCALE2 LINED TRANSFER DETAIL
HWA25
Rectangle
HWA25
Snapshot
SHEET
1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com
TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM
Houser Walker Architecture
DATE:
TECH. REVIEW:
PKG.
NO.
OF
M6Contact: Hank Houser
HVAC SCHEDULES
SCHEMATIC DESIGN
JSA
AIR HANDLING UNIT SCHEDULE
MARK SERVES
FAN COOLING COIL FILTERS OUTSIDE AIR
VOLTAGE REMARKSCFM MIN.
CFM ESP HP RPM TYPE EAT DB/WB LAT DB/WB CAPACITY (MBH)
TOTAL/SENS. TYPE MIN. CFM MAX. CFM
AHU-1 OFFICE 4000 2690 2.3 2.25 1800 DIRECT DRIVE 74°F/62°F 55°F/53°F 108/85 MERV 8 200 600 208V/3ph (1),(2),(3),(4),(5),(6),(7), (8),(9)
GENERAL
1. AMBIENT DESIGN CONDITIONS: SUMMER 94°F DB / 74°F WB, WINTER 10°F. SUMMER RETURN 77°F DB / 64° WB, WINTER RETURN 65°F DB/ 30%RH.
2. PROVIDE DIRECT DRIVE PLNEUM SUPPLY FAN WITH VFD OR ECM MOTOR.
3. PROVIDE FIELD MOUNTED SMOKE DETECTOR AT SUPPLY DISCHARGE.
4. PROVIDE SINGLE POINT POWER CONNECTION WITH FACTORY BREAKER/DISCONNECT.
5. PROVIDE ECONOMIZER PACKAGE WITH POWERED EXHAUST.
6. PROVIDE UV LIGHTS AT DOWNSTREAM SIDE OF COOLING COIL, FACTORY WIRED AND POWERED. PROVIDE CONTACT FOR AMP DRAW OUTPUT.
7. PROVIDE UNIT WITH VERTICAL DISCHARGE DUCT CONNECTION
8. MODULATING HOT GAS RE-HEAT.
9. PROVIDE INVERTER SCROLL COMPRESSOR ON LEAD CIRCUIT.
GAS UNIT HEATER SCHEDULE
MARK TYPE LOCATION
CAPACITY
INPUT/OUTPUT
(MBH)
CFM FAN MOTOR VOLTAGE DESIGN BASIS REMARKS
GUH-1 GAS FIRED
UNIT HEATER SHOP 1,2 105 / 87 1,700 3/4 120V REZNOR UBZ 100 1, 2, 3
GUH-2 GAS FIRED
UNIT HEATER FIRE BAYS 45 / 37 630 1/16 120V REZNOR UDX 45 1, 2, 3
GUH-3 GAS FIRED
UNIT HEATER FIRE BAYS 45 / 37 630 1/16 120V REZNOR UDX 45 1, 2, 3
GUH-4 GAS FIRED
UNIT HEATER WELDING BAY 105 / 87 1,700 3/4 120V REZNOR UBZ 100 1, 2, 3
GUH-5 GAS FIRED
UNIT HEATER WASH/LIFT/SERVICE 120 / 100 2,000 3/4 120V REZNOR UBZ 125 1, 2, 3
GUH-6 GAS FIRED
UNIT HEATER WAREHOUSE 45 / 37 630 1/16 120V REZNOR UDX 45 1, 2, 3
NOTES:
1. PROVIDE GAS FIRED UNIT HEATER WITH DUCTED COMBUSTION AIR, DUCTED FLUE, 100% SHUT-OFF WITH CONTINUOUS RETRY, POWER EXHAUSTER WITH MOISTURE RESISTANT BURNER
ENCLOSURE, DUAL PRESSURE SWITCHES, TRANFORMER AND GAS CONTROLS.
2. PROVIDE WIRED PROGRAMMABLE WALL THERMOSTAT POWERED FROM HEATER. (PROVIDE TRANSFORMER WITH HEATER AS REQURIED) PROVIDE VENTED LOCKBOX FOR THERMOSTAT.
3. DUCT (INSULATED) BOTH FLUE AND COMBUSTION AIR TO WALL TERMINAL- PROVIDE FLUE AND COMBUSTION TERMINATION ACCESSORIES FROM MANUFACTURER. VERIFY TOTAL
COMBINED VENT AND COMBUSTION AIR INTAKE LENGTHS WITH MANUFACTURER.
FAN SCHEDULE
MARK LOCATION TYPE DIAMETER ELECTRICAL DESIGN BASIS REMARKSHP VOLTAGE
HVLS-1 VEHICLE BAY 8 AIRFOIL
BLADE 10' 1 120V/1ph BIG ASS FANS
ESSENCE 1, 2
HVLS-2 VEHICLE BAY 8 AIRFOIL
BLADE 10' 1 120V/1ph BIG ASS FANS
ESSENCE 1, 2
NOTES:
1. PROVIVDE FAN WITH RAPID MOUNT INDUSTRIAL I-BEAM HARDWARE KIT, AND DROP LENGTH SIZED/TRIMMED TO FIT.
2. PROVIDE FAN WITH LOW VOLTAGE WALL MOUNTED TOUCHSCREEN REMOTE (1 PER FAN) AND TRANSFORMER IF NECESSARY TO POWER
FROM FAN.
EXHAUST FAN SCHEDULE
MARK SERVES TYPE DRIVE TYPE CFM ESP HP VOLTAGE DESIGN BASIS REMARKS
EF-1 WOMENS RESTROOM CEILING DIRECT
DRIVE 150 0.385 128 W 115V/1ph GREENHECK SP-B150 1
EF-2 CHASE CEILING DIRECT
DRIVE 75 0.240 20 W 115V/1ph GREENHECK SP-B110 1
EF-3 MENS RESTROOM CEILING DIRECT
DRIVE 150 0.385 128 W 115V/1ph GREENHECK SP-B150 1
EF-4 WASH/LIFT/SERVICE INLINE DIRECT
DRIVE 2900 0.4 1 208V/3ph GREENHECK SQ-140 1
EF-5 WELDING HOOD INLINE DIRECT
DRIVE 2100 0.4 3/4 208V/3ph GREENHECK SQ-130 1
EF-6 WELDING BAY UPBLAST ROOF
EXHAUSTER
DIRECT
DRIVE 660 0.2 1/15 115V/1ph GREENHECK CUE-090-D 1
EF-7 FITNESS AREA INLINE DIRECT
DRIVE 200 0.4 1/10 115V/1ph GREENHECK SQ-80 1
NOTES:
1. DIRECT DRIVE
2. BACKDRAFT DAMPER
3. ROOF CURB, BACKDRAFT DAMPER, AND ALUMINUM BIRDSCREEN.
4. PROVIDE FACTORY MOUNTED DISCONNECT SWITCH
FAN CONTROL TYPE:
WS WALL MOUNTED SWITCH
DDC DDC CONTROL
TS DDC THERMOSTAT
LS INTERLOCKED TO ROOM LIGHT SWITCH
GAS DUCT FURNACE SCHEDULE
MARK SERVES INPUT MBH VOLTAGE DESIGN BASIS REMARK
DFU-1 OFFICES 125 115V/1ph REZNOR EEDU
MAKE-UP AIR UNIT SCHEDULE
MARK SERVED BY INPUT MBH OUTPUT MBH CFM ESP FILTER 2" THROWAWAY MOTOR HP VOLTAGE/PHASE DESIGN BASIS MUA-1 SERVES 300 240 2550 0.6 (2) 20x20 (2) 20x25 1 208V/3ph REZNOR SCE 300
DUCTLESS SPLIT SYSTEM SCHEDULE
MARK SERVED BY SERVES TYPE CFM
COOLING
TOTAL/SENSIB
LE (BTUH)
HEATING
TOTAL MAX
(BTUH)
VOLTAGE DESIGN BASIS REMARKS
DSSA-1 DSSC-1 FITNESS AREA - 119 HIGH WALL 400 208V/1ph DSSA-2 DSSC-1 FITNESS AREA - 119 HIGH WALL 400 208V/1ph
NOTES:
1. COOLING CAPACITIES AT 75°F DB/64°F WB ENTERING AIR TEMPERATURE, 95°F AMBIENT.
2. PROVIDE MATCHING OUTDOOR CONDENSING UNIT (TAGGED CU-#) TO PROVIDE CAPACITIES AS SCHEDULED; VOLTAGE OF OUTDOOR UNIT TO BE 208V/1PH
3. PROVIDE LOW AMBIENT WIND BAFFLE FOR OPERATION DOWN TO 0°F.
4. WARRANTY SHALL INCLUDE 5-YEAR COMPRESSOR INCLUDING LABOR AND 5-YEAR REFRIGERATION LEAK WARRANTY INCLUDING LABOR.
5. INDOOR UNIT IS POWERED BY OUTDOOR UNIT. ELECTRICAL DATA IS FOR BOTH COMPONENTS, CONNECTIONS TO OUTDOOR UNIT.
LOUVER SCHEDULE
MARK FUNCTION WIDTH HEIGHT MATERIAL BASIS OF DESIGN REMARKS
LV-1 MAKE-UP AIR
INTAKE 60" 48" EXISTING EXISTING TO REMAIN --
LV-2 MAKE-UP AIR
INTAKE 48" 36" EXISTING EXISTING TO REMAIN 3
LV-3 OUTSIDE AIR
INTAKE 24" 12" ALUMINUM GREENHECK ESD 1, 2
LV-4 COMBUSTION
AIR 18" 12" EXISTING EXISTING TO REMAIN --
GRILLE, REGISTER & DIFFUSER SCHEDULE
MARK DESCRIPTION DIFFUSER
SIZE NECK SIZE MOUNTING
TYPE DAMPER FINISH DESIGN BASIS
S-1
EXTRUDED ALUMINUM "PENCIL PROOF" LINEAR BAR
GRILLE, 7/32" BARS, 7/16" SPACING CONCEALED
MOUNTING, 30° DEFLECTION.
48" LONG
SLOTS AS NOTED SURFACE /
EXPOSED
CABLE-OPERATED DAMPER,
ADJUSTABLE THROUGH SLOT
FACE
FLAT BLACK INTERIOR WITH
WHITE FACE/BORDER TITUS CT-PP-3
R-1 FULL FACE 1/2"x1/2"x1/2" ALUMINUM EGG CRATE GRILLE, CORE ONLY, FRAMELESS 24x24 AS NOTED LAY-IN
CEILING NO WHITE TITUS 50F
R-2
STEEL SIDE WALL RETURN GRILLE, 3/4" BLADE
SPACING, FLANGE FRAME, 35 DEGREE OFFSET
BLADES, BLADES PARALLEL TO LONG DIMENSION.
TITUS 350RL.
AS NOTED
SAME
SIZE AS
DIFFUSER
WALL
MOUNTED NO WHITE TITUS 350RL
E-1 1/2"x1/2"x1/2" ALUMINUM EGG CRATE GRILLE, DUCT
CONNECTION AS NOTED
SAME
SIZE AS
DIFFUSER
SURFACE /
EXPOSED O.B. DAMPER WHITE TITUS 50F
NOTES:
1. PROVIDE LOUVER WITH EXTENDED SILL, GALVINIZED BIRDSCREEN AND ANODIZED FINISH (FINAL COLOR SELECTED BY ARCHITECT).
2. LOUVER SHALL HAVE A MINIMUM FREE AREA OF 50%.
3. MOTORIZED DAMPER TO BE REPLACED.
DUST COLLECTOR SCHEDULE
MARK SERVICE CFM ESP RPM FAN HP SHAKER HP VOLTAGE BASIS OF DESIGN REMARKS
DC-1 SHOP 1, 2 2700 7 3450 7.5 .750 208V/3ph AMERICAN AIR FILTER SILENCER AND WEATHERPROOF
MOTOR COVER
HWA25
Rectangle
HWA25
Snapshot
05/05/23
Contact: Hank Houser
LEIPER'S FORK DISTRICT FACILITY HVAC REPLACEMENT
W W E S T S I D E
E N G I N E E R I N G
200 Galleria Pkwy Suite 1150
Atlanta, GA 30339 cesslinger@westside-engineering.com
404-965-1287 tel 404-601-9859 fax
WE # 22486
SHEET
1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com
TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM
Houser Walker Architects
DATE:
TECH. REVIEW:
PKG.
NO.
OF
E1
ELECTRICAL NOTES
AND DETAILS
HWA
AutoCAD SHX Text ELECTRICAL CIRCUIT RUN IN CONDUIT AND CIRCUIT HOMERUN TO PANELBOARD (PANEL AND CIRCUIT DESIGNATION AS INDICATED). AS A MINIMUM CONDITION, EACH SINGLE PHASE CIRCUIT SHALL HAVE ONE #12 PHASE CONDUCTOR, ONE #12 NEUTRAL CONDUCTOR, AND ONE #12 GROUNDING CONDUCTOR (PLUS ONE INSULATED, ISOLATED GROUNDING CONDUCTOR WHEN SERVING ISOLATED GROUND TYPE DEVICES) IN 1/2" CONDUIT. PROVIDE ADDITIONAL PHASE CONDUCTORS AS REQUIRED FOR "MULTIPLE PHASED" ELECTRICAL LOADS. PROVIDE ADDITIONAL "SWITCH LEG" CONDUCTORS TO PROVIDE THE LIGHT FIXTURE CONTROL INDICATED. MULTIPLE SINGLE PHASE CONDUCTORS SHALL BE GROUPED TOGETHER IN A COMMON CONDUIT IN ACCORDANCE WITH THE NEC AND AT THE CONTRACTOR'S DISCRETION. MULTIPLE SINGLE PHASE CONDUCTORS SERVING ISOLATED GROUND RECEPTACLES SHALL NOT SHARE COMMON NEUTRALS. NEUTRAL AND GROUNDING CONDUCTORS SHALL BE SHARED AS ALLOWED BY THE NEC. BRANCH CIRCUIT CONDUCTORS IN CONDUIT SHALL BE RUN CONCEALED IN WALLS AND/OR ABOVE CEILINGS, IN/OR BELOW FLOORS, EXCEPT IN EXPOSED CONSTRUCTION AREAS. FLUORESCENT LIGHTING CIRCUITS SERVING SWITCHED FIXTURES WITH EMERGENCY BATTERY BACK-UP SHALL CONTAIN ONE UNSWITCHED CONDUCTOR. FLUORESCENT DIMMING CIRCUITS SERVING DIMMING BALLASTS SHALL BE PROVIDED WITH WIRING AS REQUIRED BY BALLAST MANUFACTURER. MULTIPLE PHASE LIGHTING CIRCUITS SERVING DIMMED LOADS SHALL NOT SHARE COMMON NEUTRALS.
AutoCAD SHX Text
PROVIDE FIRE STOPPING AT CONDUIT PENETRATIONS PER UL.
AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING FIRE STOPPING AT ALL WALL, FLOOR AND CEILING PENETRATIONS WHERE CONDUIT PENETRATIONS OCCUR.
AutoCAD SHX Text PRIOR TO ANY EXCAVATION, CONTRACTOR SHALL HAVE ALL EXISTING UNDERGROUND UTILITIES LOCATED.
AutoCAD SHX Text TELEPHONE/TELEVISION BACKBOARD, 4' X 4' X 3/4" THICK EXTERIOR GRADE PLYWOOD. MOUNT VERTICALLY WITH BOTTOM OF PLYWOOD 6" A.F.F., U.O.N.
AutoCAD SHX Text TELEVISION OUTLET 18" A.F.F., U.O.N. SINGLE GANG BOX WITH DEVICE PLATE. PROVIDE 3/4" (UON) CONDUIT WITH PULLWIRE FROM OUTLET TO ABOVE ACCESSIBLE CEILING.
AutoCAD SHX Text TELEPHONE OUTLET 18" A.F.F., U.O.N. DOUBLE GANG BOX WITH DEVICE PLATE. PROVIDE 3/4" (UON) CONDUIT WITH PULLWIRE FROM OUTLET TO ABOVE ACCESSIBLE CEILING. PROVIDE WITH SINGLE GANG ADAPTER.
AutoCAD SHX Text TELEPHONE/DATA OUTLET 18" A.F.F., U.O.N. DOUBLE GANG BOX WITH DEVICE PLATE. PROVIDE 1" (UON) CONDUIT WITH PULLWIRE FROM OUTLET TO ABOVE ACCESSIBLE CEILING. PROVIDE WITH SINGLE GANG ADAPTER.
AutoCAD SHX Text
KEYNOTE.
AutoCAD SHX Text
STARTER
AutoCAD SHX Text
MOTOR CONNECTION, WITH INTEGRAL DISCONNECTING MEANS.
AutoCAD SHX Text
MOTOR RATED SWITCH. MOUNT WITHIN SIGHT OF EQUIPMENT.
AutoCAD SHX Text DISCONNECT SWITCH, 240 OR 600 VOLTS AS REQUIRED. AMPS, POLES AND FUSING AS NOTED, NEMA 1, U.O.N.
AutoCAD SHX Text
JUNCTION BOX.
AutoCAD SHX Text
PANELBOARD / LOAD CENTER
AutoCAD SHX Text RECEPTACLE/TELEPHONE/DATA OUTLETS, FLUSH MOUNT IN FLUSH MOUNTED FLOOR BOX WITH RUBBER OR THERMOPLASTIC CARPET COVER PLATE. PROVIDE NUMBER AND TYPE OF DEVICES PER PLANS. COORDINATE DEPTH OF FLOOR BOX WITH SLAB DEPTH. COORDINATE EXACT LOCATION WITH ARCHITECT. PROVIDE 3/4" CONDUIT WITH CONDUCTORS INDICATED FOR SERVICE TO RECEPTACLE OUTLET. PROVIDE (1) 1-1/4" CONDUIT WITH PULLWIRE FROM EACH SPECIAL SYSTEMS OUTLET TO ABOVE NEAREST ACCESSIBLE CEILING FOR SPECIAL SYSTEM WIRING BY OTHERS.
AutoCAD SHX Text
SPECIAL RECEPTACLE, AMPERAGE, AND VOLTAGE AS INDICATED, 18" AFF, UON.
AutoCAD SHX Text DUPLEX GROUNDING TYPE RECEPTACLE, 20A, 125 VOLT, NEMA 5-20R. MOUNT HORIZONTALLY 6" A.F.F. FOR WATER COOLER.
AutoCAD SHX Text DUPLEX GROUND FAULT INTERRUPTER TYPE RECEPTACLE, MOUNT HORIZONTALLY 18" A.F.F., U.O.N., IN CAST OUTLET BOX WITH GASKET DEVICE COVER.
AutoCAD SHX Text DUPLEX GROUND FAULT INTERRUPTER TYPE RECEPTACLE, 20A, 125 VOLT, NEMA 5-20R, 18" A.F.F., U.O.N.
AutoCAD SHX Text
DUPLEX GROUNDING TYPE RECEPTACLE, 20A, 125 VOLT, NEMA 5-20R, 18" A.F.F., U.O.N..
AutoCAD SHX Text
ELECTRICAL LEGEND
AutoCAD SHX Text
%%UFIRE PROOFING NOTES:
AutoCAD SHX Text
DEVICE PLATE NOTE
AutoCAD SHX Text
UTILITY NOTES:
AutoCAD SHX Text
1. 2.
AutoCAD SHX Text 1.
AutoCAD SHX Text
MCB
AutoCAD SHX Text
MLO
AutoCAD SHX Text
NTS
AutoCAD SHX Text
PNL
AutoCAD SHX Text
SN
AutoCAD SHX Text U.O.N.
AutoCAD SHX Text
WP
AutoCAD SHX Text V
AutoCAD SHX Text W
AutoCAD SHX Text P
AutoCAD SHX Text A.F.F.
AutoCAD SHX Text A.F.G.
AutoCAD SHX Text
GFI
AutoCAD SHX Text
KVA
AutoCAD SHX Text
KW
AutoCAD SHX Text
BFG
AutoCAD SHX Text
ABBREVIATIONS
AutoCAD SHX Text C
AutoCAD SHX Text F
AutoCAD SHX Text G
AutoCAD SHX Text A
AutoCAD SHX Text
TV
AutoCAD SHX Text J
AutoCAD SHX Text S
AutoCAD SHX Text
SPECIAL SYSTEMS
AutoCAD SHX Text
AutoCAD SHX Text M
AutoCAD SHX Text A-1
AutoCAD SHX Text
EWC
AutoCAD SHX Text
GFI
AutoCAD SHX Text
WP
AutoCAD SHX Text
POWER
AutoCAD SHX Text
- KILOWATT
AutoCAD SHX Text
- MAIN CIRCUIT BREAKER
AutoCAD SHX Text
- UNLESS OTHERWISE NOTED
AutoCAD SHX Text
- MAIN LUG ONLY
AutoCAD SHX Text
- NOT TO SCALE
AutoCAD SHX Text
- SOLID NEUTRAL
AutoCAD SHX Text
- WEATHERPROOF/GFI
AutoCAD SHX Text
- VOLTS
AutoCAD SHX Text
- WIRE
AutoCAD SHX Text
- PANEL
AutoCAD SHX Text
- POLE
AutoCAD SHX Text
- ABOVE FINISHED FLOOR
AutoCAD SHX Text
- ABOVE FINISHED GRADE
AutoCAD SHX Text
- BELOW FINISHED GRADE
AutoCAD SHX Text
- GROUND FAULT CIRCUIT INTERRUPTING
AutoCAD SHX Text
- AMPERES
AutoCAD SHX Text
- CONDUIT
AutoCAD SHX Text
- GROUND
AutoCAD SHX Text
- KILO VOLT AMP
AutoCAD SHX Text
- FUSE
AutoCAD SHX Text ALL COVERPLATES SHALL BE NYLON WITH FINISH TO BE SELECTED BY ARCHITECT. ALL DEVICES (SWITCHES, RECEPTACLES, ETC) SHALL BE FINISH BY ARCHITECT (UON). COORDINATE WITH ARCHITECTURAL PLANS.
AutoCAD SHX Text
(2) DUPLEX GROUNDING TYPE RECEPTACLES IN COMMON BOX, 20A, 125 VOLT, NEMA 5-20R, 18" A.F.F, U.O.N
AutoCAD SHX Text
ETR
AutoCAD SHX Text
- EXISTING TO REMAIN
AutoCAD SHX Text H
AutoCAD SHX Text
- HORIZONTALLY MOUNTED DEVICE.
AutoCAD SHX Text
HAZARDOUS LOCATIONS
AutoCAD SHX Text ENSURE THAT ALL CIRCUITRY, DEVICES, CONNECTIONS, AND WIRING LOCATED IN HAZARDOUS LOCATIONS COMPLY WITH NEC CODE. COORDINATE EXACT LOCATIONS AND EQUIPMENT WITH ARCHITECT/OWNER PRIOR TO ROUGH-IN.
AutoCAD SHX Text EXISTING LIGHTING FIXTURE BALLASTS AND FLUORESCENT LAMPS MAY CONTAIN PCB'S. DISPOSE OF BALLASTS AND LAMPS IN ACCORDANCE WITH EPA.
AutoCAD SHX Text ANY ELECTRICAL OUTAGES REQUIRED BY THE WORK SHALL BE COORDINATED WITH OWNER'S REPRESENTATIVE AND CONFIRMED IN WRITING. ANY OUTAGE SHALL NOT BE SCHEDULED DURING NORMAL BUSINESS HOURS OR DURING FACILITY FUNCTIONS AND ALL COSTS FOR OVERTIME SHALL BE INCLUDED IN THE BID.
AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL TRACE ALL CIRCUITS IN EXISTING PANELS TO REMAIN AFFECTED BY DEMOLITION. TAG ALL UNUSED CIRCUIT BREAKERS AS "SPARE" AND TIGHTEN ALL CONNECTIONS. PROVIDE NEW TYPED DIRECTORY PROTECTED BY PLASTIC AND PLACE IN COVER OF PANELS CONSISTENT WITH NEW CONSTRUCTION.
AutoCAD SHX Text CONDUITS MAY BE ABANDONED IN FLOOR AND WALLS ONLY. ELECTRICAL CONTRACTOR SHALL REMOVE ALL WIRING FROM ABANDONED CONDUITS, DISCONNECT FROM ALL POWER SOURCES AND PROVIDE BLANK PLATES ON ALL ABANDONED OUTLETS. CUT OFF ABANDONED CONDUITS 1" BELOW FINISHED FLOOR AND GROUT FLUSH. ABANDONED CONDUIT SHALL BE CAPPED AT BOTH ENDS.
AutoCAD SHX Text REMOVE ALL CONDUIT, WIRE, BOXES AND FASTENING DEVICES AS REQUIRED TO AVOID ANY INTERFERENCE WITH NEW INSTALLATION.
AutoCAD SHX Text SEE MECHANICAL DRAWING FOR HEATERS, EXHAUST FANS, ETC., WHICH MUST BE DISCONNECTED BY THE ELECTRICAL CONTRACTOR FOR REMOVAL OR ABANDONMENT BY MECHANICAL CONTRACTOR. ELECTRICAL CONTRACTOR SHALL REMOVE ALL STARTERS, DISCONNECT SWITCHES AND ASSOCIATED CONDUIT AND WIRING.
AutoCAD SHX Text ALL REMOVED COMPUTER EQUIPMENT SHALL BE TURNED OVER TO OWNER UNLESS DIRECTED TO DO OTHERWISE.
AutoCAD SHX Text IT SHALL BE THE ELECTRICAL CONTRACTORS RESPONSIBILITY TO PROTECT AND RETAIN POWER TO ALL EXISTING ACTIVE EQUIPMENT TO REMAIN. THIS INCLUDES RE-ROUTING OF EXISTING CIRCUITING EFFECTED BY DEMOLITION.
AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL VISIT AND EXAMINE THE SITE PRIOR TO CONSTRUCTION TO ASCERTAIN THE EXISTING CONDITIONS AND LIMITS OF DEMOLITION AND CONSTRUCTION.
AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL REMOVE ALL ASSOCIATED WIRING, CONDUIT, SURFACE RACEWAY, ETC. FOR DEVICES/LOADS BEING REMOVED. ITEMS REMOVED SHALL BECOME PROPERTY OF THE ELECTRICAL CONTRACTOR (UON) AND SHALL BE REMOVED FROM THE SITE. ITEMS REMOVED SHALL NOT BE STORED AT THE SITE. UNDER NO CONDITIONS SHALL ITEMS REMOVED BE USED IN THE NEW CONSTRUCTION.
AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL REMOVE DEVICES ON WALLS TO BE REMOVED AND AS DIRECTED BY ARCHITECT.
AutoCAD SHX Text HOLES LEFT BY REMOVAL OF ELECTRICAL DEVICES, PANELS, ETC. SHALL BE PATCHED IN EXISTING WALLS TO REMAIN. REFER TO ARCHITECTURAL DRAWINGS.
AutoCAD SHX Text 12.
AutoCAD SHX Text 11.
AutoCAD SHX Text 10.
AutoCAD SHX Text 9.
AutoCAD SHX Text 8.
AutoCAD SHX Text 7.
AutoCAD SHX Text 4.
AutoCAD SHX Text 5.
AutoCAD SHX Text 6.
AutoCAD SHX Text 3.
AutoCAD SHX Text 1.
AutoCAD SHX Text 2.
AutoCAD SHX Text
GENERAL ELECTRICAL DEMOLITION NOTES
AutoCAD SHX Text 9.
AutoCAD SHX Text COORDINATE MOUNTING OF ALL EXTERIOR DISCONNECT WITH ARCHITECTURAL ELEVATIONS. IF NOT INDICATED ON ARCHITECTURAL ELEVATIONS, REQUEST ELEVATIONS OF DISCONNECT SWITCHES FROM ARCHITECT IN WRITING PRIOR TO ROUGH-IN.
AutoCAD SHX Text ALIGN VERTICALLY AND HORIZONTALLY ALL LIGHT SWITCHES, THERMOSTATS, FIRE ALARM PULL STATIONS, ETC. ALL THESE ITEMS SHALL BE CLUSTERED WHERE POSSIBLE. COORDINATE EXACT REQUIREMENTS WITH ARCHITECT.
AutoCAD SHX Text THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING OUTLET BOX INSTALLATION WITH WALL FINISH (GYPSUM FURRING, TILE, ETC). THE CONTRACTOR SHALL PROVIDE AND INSTALL ANY EXTENSION RINGS NECESSARY TO ACCOMMODATE WALL FINISHES.
AutoCAD SHX Text THE CONTRACTOR SHALL USE CARE WHEN CUTTING OPENINGS FOR OUTLET BOXES IN CMU WALLS. OUTLET BOXES SHALL BE INSTALLED IN CMU WALLS SECURELY WITH EPOXY.
AutoCAD SHX Text PRIOR TO ROUGH-IN FOR ALL LIGHTING SWITCHES, VERIFY ALL DOOR SWINGS WITH ARCHITECTURAL PLANS.
AutoCAD SHX Text FOR EXACT LOCATION OF ALL EXTERIOR LIGHTING FIXTURES MOUNTED ON EXTERIOR OF BUILDING, ARCHITECTURAL ELEVATIONS SHALL GOVERN
AutoCAD SHX Text ALL MOUNTING HEIGHT DIMENSIONS ARE TO THE CENTER OF THE OUTLET BOX UNLESS OTHERWISE NOTED.
AutoCAD SHX Text PRIOR TO ROUGH-IN, CONTRACTOR SHALL COORDINATE EXACT LOCATION OF ALL WIRING DEVICE WITH ARCHITECTURAL ELEVATION TO AVOID CONFLICTS WITH CASEWORK, COUNTER TOPS, DOOR SWINGS, ETC. WHERE CONFLICTS OCCURS, CONTRACTOR SHALL CONTACT THE ARCHITECT IN WRITING FOR RESOLUTION.
AutoCAD SHX Text FOR EXACT LOCATION OF EQUIPMENT MOUNTED IN SUSPENDED CEILINGS. SUCH AS LIGHTING FIXTURES, AND SMOKE DETECTORS, SEE ARCHITECTURAL REFLECTED CEILING PLANS. ARCHITECTURAL REFLECTED PLAN SHALL GOVERN FINAL LOCATION.
AutoCAD SHX Text 5.
AutoCAD SHX Text 8.
AutoCAD SHX Text 6.
AutoCAD SHX Text 7.
AutoCAD SHX Text 3.
AutoCAD SHX Text 4.
AutoCAD SHX Text 2.
AutoCAD SHX Text 1.
AutoCAD SHX Text 9.
AutoCAD SHX Text COORDINATE MOUNTING OF ALL EXTERIOR DISCONNECT WITH ARCHITECTURAL ELEVATIONS. IF NOT INDICATED ON ARCHITECTURAL ELEVATIONS, REQUEST ELEVATIONS OF DISCONNECT SWITCHES FROM ARCHITECT IN WRITING PRIOR TO ROUGH-IN.
AutoCAD SHX Text THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING OUTLET BOX INSTALLATION WITH WALL FINISH (GYPSUM FURRING, TILE, ETC). THE CONTRACTOR SHALL PROVIDE AND INSTALL ANY EXTENSION RINGS NECESSARY TO ACCOMMODATE WALL FINISHES.
AutoCAD SHX Text THE CONTRACTOR SHALL USE CARE WHEN CUTTING OPENINGS FOR OUTLET BOXES IN CMU WALLS. OUTLET BOXES SHALL BE INSTALLED IN CMU WALLS SECURELY WITH EPOXY.
AutoCAD SHX Text PRIOR TO ROUGH-IN FOR ALL LIGHTING SWITCHES, VERIFY ALL DOOR SWINGS WITH ARCHITECTURAL PLANS.
AutoCAD SHX Text FOR EXACT LOCATION OF ALL EXTERIOR LIGHTING FIXTURES MOUNTED ON EXTERIOR OF BUILDING, ARCHITECTURAL ELEVATIONS SHALL GOVERN
AutoCAD SHX Text ALL MOUNTING HEIGHT DIMENSIONS ARE TO THE CENTER OF THE OUTLET BOX UNLESS OTHERWISE NOTED.
AutoCAD SHX Text PRIOR TO ROUGH-IN, CONTRACTOR SHALL COORDINATE EXACT LOCATION OF ALL WIRING DEVICE WITH ARCHITECTURAL ELEVATION TO AVOID CONFLICTS WITH CASEWORK, COUNTER TOPS, DOOR SWINGS, ETC. WHERE CONFLICTS OCCURS, CONTRACTOR SHALL CONTACT THE ARCHITECT IN WRITING FOR RESOLUTION.
AutoCAD SHX Text FOR EXACT LOCATION OF EQUIPMENT MOUNTED IN SUSPENDED CEILINGS. SUCH AS LIGHTING FIXTURES, AND SMOKE DETECTORS, SEE ARCHITECTURAL REFLECTED CEILING PLANS. ARCHITECTURAL REFLECTED PLAN SHALL GOVERN FINAL LOCATION.
AutoCAD SHX Text 5.
AutoCAD SHX Text 8.
AutoCAD SHX Text 6.
AutoCAD SHX Text 7.
AutoCAD SHX Text 3.
AutoCAD SHX Text 4.
AutoCAD SHX Text 2.
AutoCAD SHX Text 1.
AutoCAD SHX Text
GENERAL ELECTRICAL NOTES
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text V
AutoCAD SHX Text
FIRE ALARM PULL STATION. WALL MOUNT AT 48" A.F.F.
AutoCAD SHX Text
FIRE ALARM SYSTEMS
AutoCAD SHX Text FIRE ALARM STROBE. WALL MOUNT 80" TO BOTTOM OF OUTLET BOX, A.F.F. OR 6" BELOW CEILING IN COMPLIANCE WITH ADA REQUIREMENTS.
AutoCAD SHX Text
FIRE ALARM SMOKE DETECTOR, PHOTOELECTRIC TYPE.
AutoCAD SHX Text
FIRE ALARM HEAT DETECTOR.
AutoCAD SHX Text F
AutoCAD SHX Text S
AutoCAD SHX Text FIRE ALARM SPEAKER/STROBE. MOUNT IN CEILING IN COMPLIANCE WITH ADA REQUIREMENTS.CEILING IN COMPLIANCE WITH ADA REQUIREMENTS.
AutoCAD SHX Text D
AutoCAD SHX Text
FIRE ALARM DUCT SMOKE DETECTOR.
AutoCAD SHX Text S
AutoCAD SHX Text FIRE ALARM SPEAKER. WALL MOUNT 80" A.F.F. TO BOTTOM OF OUTLET BOX, A.F.F. OR 6" BELOW CEILING IN COMPLIANCE WITH ADA REQUIREMENTS.
AutoCAD SHX Text
FIRE ALARM DOOR HOLD OPEN DEVICE
AutoCAD SHX Text H
06/09/23
LEIPER'S FORK DISTRICT FACILITY HVAC REPLACEMENT
0 88 16
SCALE OF FEET
W W E S T S I D E
E N G I N E E R I N G
200 Galleria Pkwy Suite 1150
Atlanta, GA 30339 cesslinger@westside-engineering.com
404-965-1287 tel 404-601-9859 fax
WE # 22486
SHEET
1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com
TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM
Houser Walker Architects
DATE:
TECH. REVIEW:
PKG.
NO.
OF
PARTIAL EXISTING ELECTRICAL RISER DIAGRAM1
EQUIPMENT NAMEPLATE DETAIL3
E2
ELECTRICAL RISER
DIAGRAM AND PANEL
SCHEDULES 11
HWA
AutoCAD SHX Text
208Y/120V, 3ɸ, 4W + G NORMAL PANELBOARD 225 A, MLO, 14000 SCCR FED FROM DH1A-3
AutoCAD SHX Text
EQUIPMENT DESIGNATION
AutoCAD SHX Text
ELECTRICAL CHARACTERISTICS (VOLTAGE, PHASE, NUMBER OF WIRES + GROUND)
AutoCAD SHX Text
POWER SUPPLY SYSTEM (NORMAL, EMERGENCY, STANDBY)
AutoCAD SHX Text EQUIPMENT RATINGS (MAIN RATING, MLO OR MCB [PANELBOARDS, SWITCHBOARDS, AND SWITCH GEAR], FUSED OR UNFUSED [SWITCHES], MINIMUM SCCR)
AutoCAD SHX Text
SOURCE (EQUIPMENT NAME AND FEEDER NUMBER)
AutoCAD SHX Text NAMEPLATE BACKGROUND COLORS SHALL BE BLACK FOR NORMAL POWER SUPPLY SYSTEMS, RED FOR LEGALLY REQUIRED EMERGENCY POWER SUPPLY SYSTEMS, AND YELLOW FOR OPTIONAL STANDBY POWER SUPPLY SYSTEMS.
AutoCAD SHX Text
BH1A
AutoCAD SHX Text T
AutoCAD SHX Text EXISTING PAD MOUNTED UTILITY TRANSFORMER. COORDINATE POTENTIAL UPGRADE WITH POWER COMPANY
AutoCAD SHX Text
EXISTING PANEL 'P2' 225A MLO 208/120V 3PH, 4W
AutoCAD SHX Text
EXISTING 400A-3P ENCLOSED CIRCUIT BREAKER TO REMAIN.
AutoCAD SHX Text
%%UKEY NOTES
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING SERVICE TROUGH TO REMAIN
AutoCAD SHX Text
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING GROUND TO REMAIN
AutoCAD SHX Text
EXISTING PANEL 'P1' 225A MLO 208/120V 3PH, 4W
AutoCAD SHX Text
EXISTING PANEL 'L2' 125A MLO 208/120V 3PH, 4W
AutoCAD SHX Text
EXISTING PANEL 'L1' 225A MLO 208/120V 3PH, 4W
AutoCAD SHX Text
EXISTING FEEDERS TO REMAIN
AutoCAD SHX Text EXISTING PANEL TO REMAIN. PROVIDE CIRCUIT BREAKERS AS REQUIRED. CIRCUIT BREAKERS ARE EXISTING, UON. FIELD VERIFY EXACT REQUIREMENTS.
AutoCAD SHX Text
PROVIDE NEW CIRCUIT BREAKER IN EXISTING PANEL TO ACCOMMODATE NEW LOAD.
AutoCAD SHX Text
GENERAL NOTES:
AutoCAD SHX Text
1. ELECTRICAL CONTRACTOR SHALL TRACE ALL CIRCUITS IN EXISTING ELECTRICAL CONTRACTOR SHALL TRACE ALL CIRCUITS IN EXISTING PANELS TO REMAIN AFFECTED BY DEMOLITION. TAG AND TURN OFF ALL UNUSED CIRCUIT BREAKERS AND LABEL AS "SPARE" AND TIGHTEN ALL CONNECTIONS. PROVIDE NEW TYPED DIRECTORY PROTECTED BY PLASTIC AND PLACE IN COVER OF PANELS CONSISTENT WITH NEW CONSTRUCTION.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
UP
BREAK/TRAINING
DIST. RANGER
SHARED OFFICE
MAINTENANCE
STORAGE
TELE-ELEC
WOOD SHOP
FURNACE
VALVE
WASH / LIFT /
SERVICE
WELDING FIRE BAYWAREHOUSE
RANGERS
MEN
WOMEN
CHASE
UP
05/05/23
Contact: Hank Houser
LEIPER'S FORK DISTRICT FACILITY HVAC REPLACEMENT
0 88 16
SCALE OF FEET
W W E S T S I D E
E N G I N E E R I N G
200 Galleria Pkwy Suite 1150
Atlanta, GA 30339 cesslinger@westside-engineering.com
404-965-1287 tel 404-601-9859 fax
WE # 22486
SHEET
1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com
TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM
Houser Walker Architects
DATE:
TECH. REVIEW:
PKG.
NO.
OF
1 LEVEL 1 FLOOR PLAN - ELECTRICAL
E3
FLOOR PLAN -
ELECTRICAL
2 LEVEL 2 FLOOR PLAN - ELECTRICAL
HWA
AutoCAD SHX Text
KEYNOTES:
AutoCAD SHX Text PROVIDE CONNECTION TO OVERHEAD FAN. COORDINATE EXACT CONNECTION REQUIREMENTS WITH MECHANICAL DRAWINGS PRIOR TO ROUGH-IN.
AutoCAD SHX Text
AutoCAD SHX Text PROVIDE CONNECTION FROM CONTROLS TO OVERHEAD FAN ABOVE. COORDINATE EXACT CONNECTION REQUIREMENTS WITH MECHANICAL DRAWINGS PRIOR TO ROUGH-IN.
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text M
AutoCAD SHX Text S
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text L2-32
AutoCAD SHX Text L2-34
AutoCAD SHX Text
EF-4
AutoCAD SHX Text DISCONNECT EXISTING EXHAUST FAN AND PROVIDE CONNECTION TO NEW EXHAUST FAN INSTALLED. RE-USE EXISTING DISCONNECT SWITCH AND CIRCUITRY TO FURTHEST EXTENT POSSIBLE. EXTEND EXISTING CIRCUITRY AS REQUIRED.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CU-1
AutoCAD SHX Text
DSSC
AutoCAD SHX Text PROVIDE CONNECTION TO ASSOCIATED CONDENSING UNIT VIA 2#12, 1#12G, 3/4"C. AS RECOMMENDED BY MANUFACTURER.
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
DSSA-1
AutoCAD SHX Text
AutoCAD SHX Text
EF-7 (ON ROOF)
AutoCAD SHX Text S
AutoCAD SHX Text M
AutoCAD SHX Text
WP
AutoCAD SHX Text
MAU-1
AutoCAD SHX Text
30/3/NF
AutoCAD SHX Text
GUH-2
AutoCAD SHX Text
GUH-3
AutoCAD SHX Text
30/2/15AF
AutoCAD SHX Text
30/2/15AF
AutoCAD SHX Text
GUH-4
AutoCAD SHX Text
30/2/20AF
AutoCAD SHX Text P1-26
AutoCAD SHX Text 2#10, 1#10G, 3/4"C.
AutoCAD SHX Text
GUH-1
AutoCAD SHX Text
30/2/NF
AutoCAD SHX Text P1-30
AutoCAD SHX Text
GUH-5
AutoCAD SHX Text
30/2/20AF
AutoCAD SHX Text
GUH-6
AutoCAD SHX Text
30/2/15AF
AutoCAD SHX Text P1-28
AutoCAD SHX Text 2#10, 1#10G, 3/4"C.
AutoCAD SHX Text
DFU-1
AutoCAD SHX Text DISCONNECT EXISTING DUCT FURNACE AND PROVIDE CONNECTION TO NEW DUCT FURNACE INSTALLED. RE-USE EXISTING DISCONNECT SWITCH AND CIRCUITRY TO FURTHEST EXTENT POSSIBLE. EXTEND EXISTING CIRCUITRY AS REQUIRED.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text DISCONNECT EXISTING AIR HANDLING UNIT AND PROVIDE CONNECTION TO NEW AIR HANDLING UNIT INSTALLED. RE-USE EXISTING DISCONNECT SWITCH AND CIRCUITRY TO FURTHEST EXTENT POSSIBLE. EXTEND EXISTING CIRCUITRY AS REQUIRED.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EF-5
AutoCAD SHX Text P1-8,10,12
AutoCAD SHX Text
EF-6
AutoCAD SHX Text S
AutoCAD SHX Text M
AutoCAD SHX Text PROVIDE CONNECTION TO NEAREST AVAILABLE UNSWITCHED 120V-1PH CIRCUIT WITH ADEQUATE CAPACITY.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
DSSA-2
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text DISCONNECT EXISTING DUCT COLLECTOR UNIT AND PROVIDE CONNECTION TO NEW UNIT AS REQUIRED. RE-USE EXISTING CIRCUITRY TO FURTHEST EXTENT POSSIBLE.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EF-3
AutoCAD SHX Text
AutoCAD SHX Text
EF-2
AutoCAD SHX Text
AutoCAD SHX Text
EF-1
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PROVIDE CONNECTION TO AIR HANDLING UNIT CONTROLS.
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text L2-36
AutoCAD SHX Text
AutoCAD SHX Text
30/2/NF
L2-40,42 3#10, 1#10G, 3/4"C.
05/05/23
LEIPER'S FORK DISTRICT FACILITY HVAC REPLACEMENT
W W E S T S I D E
E N G I N E E R I N G
200 Galleria Pkwy Suite 1150
Atlanta, GA 30339 cesslinger@westside-engineering.com
404-965-1287 tel 404-601-9859 fax
WE # 22486
SHEET
1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com
TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM
Houser Walker Architects
DATE:
TECH. REVIEW:
PKG.
NO.
OF
E4
ELECTRICAL
SPECIFICATIONS
HWA
AutoCAD SHX Text
MISCELLANEOUS:
AutoCAD SHX Text
1. SELECT, SIZE, AND ASSEMBLE FOUNDATIONS, SUPPORTS, AND FASTENERS.
AutoCAD SHX Text
2. FASTENINGS FOR SECURING CONDUIT RUNS, LIGHT APPARATUS.
AutoCAD SHX Text
* TOGGLE BOLTS ON HOLLOW TILE OR CONCRETE BLOCKS
AutoCAD SHX Text
MASONRY.
AutoCAD SHX Text
BY THE OWNER'S REPRESENTATIVE.
AutoCAD SHX Text
PERMANENT NAMEPLATES FOR EQUIPMENT IDENTIFICATION.
AutoCAD SHX Text
REFRIGERATED SPACES OR OUTDOOR AREAS,TO PREVENT CIRCULATION OF AIR.
AutoCAD SHX Text
EACH TYPE PENETRATION.
AutoCAD SHX Text
TELEPHONE SYSTEM ROUGH-IN:
AutoCAD SHX Text
CONDUCTORS, AND MISCELLANEOUS MATERIALS OR DEVICES.
AutoCAD SHX Text
* BOLTS, BEAM CLAMPS, OR DRIVEN OR WELDED STUDS ON STEEL WORK
AutoCAD SHX Text
* STEEL ANCHORS OF THE SELF-DRILLING OR NON-DRILLING TYPES ON SOLID CONCRETE OR
AutoCAD SHX Text
* POWER DRIVEN STUDS MAY BE USED ON STEEL AND SOLID CONCRETE WHERE ACCEPTED
AutoCAD SHX Text
3. MAJOR COMPONENTS OF THE DISTRIBUTION SYSTEM SUCH AS THE PANELBOARD SHALL HAVE
AutoCAD SHX Text
4. SEAL CONDUITS ROUTED BETWEEN SPACES OF DIFFERENT AMBIENT TEMPERATURES, SUCH AS
AutoCAD SHX Text
5. INSTALL RACEWAY OR CABLE, ETC. THAT PENETRATES A FIRE BARRIER, WITH MATERIALS AND
AutoCAD SHX Text METHODS APPROVED FOR APPLICATION BY BUILDING OFFICIALS. IDENTIFY EACH FIRE BARRIER
AutoCAD SHX Text FROM THE ARCHITECTURAL PLANS, AND FOR SECURE APPROVAL OF MATERIALS AND METHODS FOR
AutoCAD SHX Text
1. CONTACT THE TELEPHONE CO., COORDINATE THE WORK TO MAKE THE INSTALLATION READY FOR
AutoCAD SHX Text THE TELEPHONE COMPANY, INCLUDING CABINETS, RACEWAYS AND PULL WIRES, RACEWAY SYSTEM
AutoCAD SHX Text
BOXES, DEDICATED ELECTRICAL BRANCH CIRCUITS AND RECEPTACLES, DEDICATED GROUNDING
AutoCAD SHX Text
2. PROVIDE COMPLETE ENCLOSED RACEWAYS WITH MEASURED PULL CORDS FOR FUTURE USE BY
AutoCAD SHX Text OTHERS. PROVIDE A 3/4" PVC CONDUIT FROM EACH MAIN CABINET OR BACKBOARD LOCATION TO
AutoCAD SHX Text
NEAREST ACCESSIBLE, GROUNDED, METAL COLD WATER PIPE, AND A #6 SOLID COPPER
AutoCAD SHX Text
CONDUCTOR BONDED TO THE WATER PIPE AND COILED FOR USE IN GROUNDING EQUIPMENT.
AutoCAD SHX Text
8. SIZE RACEWAYS TO ACCOMMODATE THE ENCLOSED CONDUCTORS.
AutoCAD SHX Text
AND AT LOW POINTS IN RACEWAY RUNS.
AutoCAD SHX Text
EQUIPMENT.
AutoCAD SHX Text
ROUTE RACEWAYS TO AVOID 'TRAPPING' WHERE PRACTICABLE.
AutoCAD SHX Text
ENCLOSURES AND BOXES:
AutoCAD SHX Text
SURFACE MOUNTED DEVICES.
AutoCAD SHX Text
DEVICES:
AutoCAD SHX Text
2. ENCLOSURES:
AutoCAD SHX Text
NECESSARY TO MEET CU. IN. CAPACITY REQUIRED BY CODE.
AutoCAD SHX Text
FEATURES TO SUIT CODE REQUIREMENTS.
AutoCAD SHX Text
ARROW HART.
AutoCAD SHX Text
ARROW HART.
AutoCAD SHX Text
'COMM. SPEC. GRADE' SERIES, LUTRON OR LITHONIA.
AutoCAD SHX Text
SUBMITTALS:
AutoCAD SHX Text
DISTRIBUTION EQUIPMENT:
AutoCAD SHX Text
* SERVICE & DISTRIBUTION EQUIPMENT
AutoCAD SHX Text
* PROTECTIVE DEVICES
AutoCAD SHX Text
* LIGHTING FIXTURES AND LAMPS
AutoCAD SHX Text
* WIRING DEVICES AND COVER PLATES
AutoCAD SHX Text
SIEMENS-ALLIS ITE PRODUCTS, EATON/CUTLER HAMMER.
AutoCAD SHX Text
'SQUARE D' I-LINE DEVICES.
AutoCAD SHX Text
CIRCUIT DIRECTORY CARD USING A TYPEWRITER.
AutoCAD SHX Text
'NEMA-3R' ENCLOSED TYPE WITH LOCKING HASP.
AutoCAD SHX Text
SIDE OF THE CABINET.
AutoCAD SHX Text
CONDUCTORS:
AutoCAD SHX Text
VAC OR 600VAC AS FOLLOWS:
AutoCAD SHX Text
INCANDESCENT LIGHTING.
AutoCAD SHX Text
1. SUBMIT SHOP DRAWINGS & PRODUCT INFORMATION FOR THE FOLLOWING:
AutoCAD SHX Text
1. DISTRIBUTION EQUIPMENT; RATED FOR 240 OR 600 VAC, 60 HZ, FAULT CURRENT INTERRUPTING
AutoCAD SHX Text CAPACITY AS INDICATED, IN AMPERES, RMS, SYMMETRICAL, BUT NOT LESS THAN 10,000 AMPS, WITH
AutoCAD SHX Text SOLID NEUTRAL GROUND (S/N); ABB/GENERAL ELECTRIC (ABB-G.E.), SCHNEIDER ELECTRIC/SQUARE-D, AutoCAD SHX Text
2. DISTRIBUTION EQUIPMENT USING CIRCUIT BREAKER TYPE PROTECTIVE DEVICES; BOLTED-ON OR
AutoCAD SHX Text
3. PANELBOARDS; FACTORY ASSEMBLED, MINIMUM WIDTH OF 20 INCHES, A MINIMUM DEPTH OF 5-3/4
AutoCAD SHX Text INCHES, AND MINIMUM MAINS RATED 100 AMPERES, WITH POLE 'SPACES'; BUSSED AND READY FOR
AutoCAD SHX Text INSTALLATION OF PROTECTIVE DEVICES. CABINETS; FULL SIZED SINGLE DOORS WITH CHROMIUM
AutoCAD SHX Text PLATED COMBINATION CYLINDER LOCK AND CATCH AND TWO KEYS. "ABB/GENERAL ELECTRIC" OR
AutoCAD SHX Text EQUAL: TYPE "NLAB" W/ Q-LINE BRANCH CIRCUIT BREAKERS; TYPE "NHB" WITH E-FRAME BREAKERS.
AutoCAD SHX Text
4. PANELBOARD MAINS; COPPER OR ALUMINUM WITH BRANCH CONNECTIONS IN VERTICALLY
AutoCAD SHX Text
DISTRIBUTED CONSECUTIVE PHASE SEQUENCE SUCH THAT ONE OR MULTIPLE POLE BREAKERS
AutoCAD SHX Text
CAN BE MOUNTED IN ANY POSITION. SOLID NEUTRAL BUS; WITH A FEEDER LUG AND WITH A
AutoCAD SHX Text
SEPARATE SET-SCREW TERMINAL FOR EACH BRANCH CIRCUIT POLE.
AutoCAD SHX Text
5. PANELBOARD MOUNTING; TOP OF ENCLOSURE 78 INCHES ABOVE THE FINISHED FLOOR/GRADE, WITH
AutoCAD SHX Text
THE BOTTOM OF THE CABINET NOT CLOSER THAN 6 INCHES TO THE FLOOR/GRADE, PROPERLY
AutoCAD SHX Text
ALIGNED AND SUPPORTED INDEPENDENTLY OF THE CONNECTING RACEWAYS. COMPLETE INSIDE
AutoCAD SHX Text
6. DISCONNECT SWITCHES; 'HEAVY-DUTY' RATED WITH QUICK-MAKE AND QUICK-BREAK MECHANISMS.
AutoCAD SHX Text
PROVIDE GROUND LUGS AND CODE REQUIRED ACCESSORIES. SWITCHES LOCATED OUTSIDE;
AutoCAD SHX Text
7. PROVIDE AN ENCLOSED SWITCH FOR ELECTRICALLY SERVED EQUIPMENT. PROVIDE SWITCHES &
AutoCAD SHX Text
FUSES, INCLUDING HEATER ELEMENTS, RATED PER THE CHARACTERISTICS AND NAMEPLATE
AutoCAD SHX Text
RATINGS OF EQUIPMENT IN ACCORDANCE WITH CODE REQUIREMENTS, MANUFACTURER'S
AutoCAD SHX Text
RECOMMENDATIONS AND CHARTS. PROVIDE SWITCHES WITH CODE REQUIRED ACCESSORIES.
AutoCAD SHX Text
8. FUSED SWITCHES IN BRANCH CIRCUITS; NON-RENEWABLE CARTRIDGE FUSES RATED 250 OR 300
AutoCAD SHX Text
* SIZES 1 - 200 AMPS: DUAL ELEMENT, CURRENT LIMITING FUSES, CLASS 'RK-1', OR 'RK-5', AutoCAD SHX Text
SELECTED TO PROVIDE STARTING AND LIMIT LET-THRU CURRENT.
AutoCAD SHX Text
* OTHER RATINGS, SIZES OR SPECIAL APPLICATIONS AS INDICATED.
AutoCAD SHX Text
9. STATIONARY FRACTIONAL HORSEPOWER MOTORS NOT PROVIDED WITH INTEGRAL MOTOR RUNNING
AutoCAD SHX Text
OVERLOAD PROTECTION, OR INHERENTLY PROTECTED BY DESIGN; SWITCHED BY A FRACTIONAL
AutoCAD SHX Text
HORSEPOWER STARTER PROVIDING SUPPLEMENTARY PROTECTION.
AutoCAD SHX Text
10. STARTERS AND DISCONNECT SWITCHES; ENCLOSED QUICK-MAKE AND QUICK-BREAK MECHANISMS.
AutoCAD SHX Text
11. BRANCH CIRCUIT BREAKERS; MOLDED CASE, AUTOMATIC TRIPPING TYPE, BOLT-ON OR I-LINE
AutoCAD SHX Text
CONSTRUCTION, MINIMUM FRAME SIZE OF 100 AMPS AND A MINIMUM TRIP SIZE OF 15 AMPS,
AutoCAD SHX Text CALIBRATED FOR 40oC. PROVIDE SUITABLE TYPE BREAKERS SERVING HIGH INRUSH CIRCUITS FOR
AutoCAD SHX Text
12. GROUP SINGLE-POLE BREAKERS USED FOR MULTI-WIRE CIRCUITS CONSECUTIVELY ON THE SAME
AutoCAD SHX Text
1. CONDUCTORS; SOFT DRAWN, ANNEALED COPPER WITH CONDUCTIVITY OF NOT LESS THAN 98
AutoCAD SHX Text
LIGHTING:
AutoCAD SHX Text
BY LEVITON, 'COMM. SPEC. GRADE', HUBBELL OR ARROW HART.
AutoCAD SHX Text
DEVICES AND COVER PLATE FINISHES; AS INDICATED BY THE PLANS.
AutoCAD SHX Text
CONTRACT DOCUMENTS. WHERE NO CRI IS SCHEDULE, CRI SHALL BE 80 OR GREATER.
AutoCAD SHX Text
GROUNDING:
AutoCAD SHX Text
GROUNDING PATH TO THE POWER SERVICE DISCONNECT SWITCH.
AutoCAD SHX Text
EXTENT.
AutoCAD SHX Text
CONDUCTORS INDICATED.
AutoCAD SHX Text
TESTING:
AutoCAD SHX Text
THE POINT OF SERVICE ONLY.
AutoCAD SHX Text
OPERATION OF MATERIALS.
AutoCAD SHX Text
'ASTM' STANDARDS.
AutoCAD SHX Text
4. CONDUCTORS;
AutoCAD SHX Text
THE PLANS.
AutoCAD SHX Text
THE SAME ELECTRICAL TERMINAL POSITION
AutoCAD SHX Text VOLTS, WITH 75oC OR 90oC INSULATION AS FOLLOWS:
AutoCAD SHX Text
RACEWAYS:
AutoCAD SHX Text
EXPOSED.
AutoCAD SHX Text
ON GRADE, OF 'THW', 'THWN' OR 'XHHW'.
AutoCAD SHX Text
OR OTHER APPROVED TYPE.
AutoCAD SHX Text
A SUITABLE HIGH TEMPERATURE RATING.
AutoCAD SHX Text
3. RACEWAYS IN ORDINARY LOCATIONS:
AutoCAD SHX Text
ELECTRICAL METALLIC TUBING (EMT) OR MC CABLE.
AutoCAD SHX Text
BE PERMITTED TO BE USED IN NON-ACCESSIBLE AREAS.
AutoCAD SHX Text
B. BRANCH CONDUCTORS RATED FOR:
AutoCAD SHX Text
CONDUIT OR FLEXIBLE METALLIC TUBING.
AutoCAD SHX Text
LOCATION OR FEEDER (OR SUB-FEEDER..
AutoCAD SHX Text
* 1/2-INCH; GENERAL.
AutoCAD SHX Text
MORE THAN (3) CONDUCTORS.
AutoCAD SHX Text
2. CONDUCTOR SIZE NUMBERS; AMERICAN WIRE GAUGE (AWG. SYSTEM, STANDARD TRADE SIZES.
AutoCAD SHX Text
3. CONDUCTORS; COLOR CODED PER…