A06_NATR_304927A_100__CDs_Liepers_Fork_HVAC_Reno_Dwgs_COMBINED.pdf

PDF 6 MB Posted

Attached to
HVAC LF MAINT. REPLACE
Solicitation number
140P5224R0003
Issued by

About this file

This document contains a set of construction drawings and specifications for the replacement of the HVAC system at the Leiper's Fork District Facility along the Natchez Trace Parkway. The drawings include floor plans, reflected ceiling plans, HVAC schedules and details. The project scope involves the design and replacement of the existing HVAC systems serving the facility. The applicable codes are the 2012 and 2018 editions of various building and mechanical codes with Tennessee amendments. Key details include the existing building area of 11,220 square feet, an existing occupancy type of mixed B, S-1 and F-1, and the existing building being sprinklered.

The related federal contract opportunity is for the HVAC repair and replacement work at the Leiper's Fork District Office facility. This is a firm fixed price commercial item solicitation with a NAICS code of 238220. The evaluation factors are cost, technical approach, and relevant experience. Bidders must provide references demonstrating applicable experience. Proposals are due electronically to the Contracting Officer by the closing date specified in the solicitation.

View the file

Other files

File Type Posted
Sol_140P5224R0003.pdf PDF
A06_NATR_LF_mechanical_dwgs.pdf PDF
B03_DBA_Williamson_County.pdf PDF
SOW_-_NATR_LF_HVAC_Statement_of_Work.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

International Building Code (IBC):

2012 Edition, with Tennessee Amendments

International Fuel Gas Code (IFGC):

2018 Edition, with Tennessee Amendments

National Electrical Code (NEC):

2017 Edition, with Tennessee Amendments

International Fire Code (IFC):

2012 Edition, with Tennessee Amendments

International Energy Conservation Code (IECC):

2012 Edition, with Tennessee Amendments

International Plumbing Code (IPC):

2012 Edition, with Tennessee Amendments

NFPA 101 - Life Safety Code:

2012 Edition, with Tennessee Amendments

International Mechanical Code (IMC):

2012 edition, with Tennessee Amendments

Rules and regulations of the Safety Fire Commissioner for the state minimum fire safety standards - 120-3-3:

EXISTING 2-STORY

LEIPER'S FORK RANGERS

STATION FACILITY

EXISTING STORAGE

BUILDING

CONSTRUCTION

STAGING AREA

LIMITS OF

CONSTRUCTION

NARRATIVE DESCRIPTION OF PROJECT:

The project is to complete the design and replacement of the HVAC systems that serve the Leiper’s Fork District Facility, along the Natchez Trace Parkway.

Architectural drawings of existing facility are shown for reference only. See MECH & ELEC drawings for graphic description of project scope.

APPLICABLE CODES:

PROJECT STATISTICS:

PROJECT SITE:

LEIPER'S FORK DISTRICT FACILITY

LE

IP

ERS

CREEK R

D

N A

TC

H

EZ

T

RA

C

E

PK

W Y

PINEWOOD RD

N U

M B

E R

SHEET NAME S

H

E E

T N

U M

B E

R

C U

R R

E N

T R

E V

D

A T

E

C U

R R

E N

T R

E V

N

O

01 GENERAL

G1 COVER SHEET 1

02 ARCHITECTURAL

A1 FLOOR PLANS 2

A2 REFLECTED CEILING PLANS 3

03 MECHANICAL

M1 GENERAL NOTES & LEGENDS 4

M2 HVAC - FLOOR PLAN - DEMO 5

M3 HVAC - FLOOR PLAN - NEW WORK 6

M4 HVAC - PART PLANS 7

M5 HVAC DETAILS 8

M6 HAVC SCHEDULES 9

04 ELECTRICAL

E1 ELECTRICAL NOTES & DETAILS 10

E2 ELECTRICAL RISER DIAGRAM & PANEL SCHEDULES 11

E3 FLOOR PLAN - ELECTRICAL 12

E4 ELECTRICAL SPECIFICATIONS 13

A/E FIRM

PRIME/ARCH:

TITLE OF PROJECT

NAME OF PARK

REGION COUNTY STATE

UNITED STATES

DEPARTMENT OF THE INTERIOR

NATIONAL PARK SERVICE

DENVER SERVICE CENTER

Mark Sheet REVISION InitialDate

Houser Walker Architecture Atlanta, GA

VICINITY MAP

SHEET

DRAWING NO.

PKG.

NO.

OF

LEIPER'S FORK

LEIPER'S FORK DISTRICT

FACILITY HVAC REPLACEMENT

100% CONSTRUCTION DRAWINGS

SOUTHEAST US TENNESSEEWILLIAMSON

MECHANICAL:

Johnson Spellman & Associates Inc.

Peachtree Corners, GA

ELECTRICAL:

Westside Engineering Atlanta, GA

AREA:

Existing Building Area: 11,220 sf Project Scope Area: na

HEIGHT:

Existing:

Height: 32 ft Stories: 2

Proposed:

Height: No change Stories: No change

OCCUPANCY:

Existing:

Occupancy Type: Mixed B, S-1, F-1

Proposed: No change

CONSTRUCTION:

Existing Type: III B Proposed Type: No change

SPRINKLERED:

Existing: Yes Proposed: No change

PARKING:

Existing: 19 spaces Proposed: No change

SITE PLAN1 0 4040 80

SCALE OF FEET

UP UP

411 SF

BREAK/TRAINING

150 SF

DIST. RANGER

297 SF

SHARED OFFICE

196 SF

MAINTENANCE

71 SF

STORAGE

42 SF

TELE-ELEC

785 SF

WOOD SHOP

118 SF

FURNACE

55 SF

VALVE

1,430 SF

WASH / LIFT /

SERVICE

660 SF

WELDING

927 SF

FIRE BAY

1,144 SF

WAREHOUSE

304 SF

RANGERS

153 SF

MEN

127 SF

WOMEN

CHASE

1,343 SF

STORAGE

306 SF

MECH

OPEN TO

VEHICLE BAY

BELOW

C O

R R

ID

O

R B

E

LO

W EXISTING ASPHALT

SHINGLE ROOF

BELOW

EXISTING ASPHALT

SHINGLE ROOF

BELOW

EXISTING ASPHALT

SHINGLE ROOF

BELOW

EXISTING ASPHALT

SHINGLE ROOF

BELOW

3" / 12" 3" / 12"

EXISTING OPENING

FOR MAKE-UP AIR

LOUVER & DAMPER

EXISTING OPENINGS

FOR OUTSIDE AIR

LOUVER & DAMPER

LEVEL 1 - EXISTING FLOOR PLAN1 LEVEL 2 - EXISTING FLOOR PLAN2

0 88 16

SCALE OF FEET

GENERAL NOTE:

1. See Mechanical & Electrical drawings for new scope

SHEET

1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com

TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM

Houser Walker Architecture

DATE:

TECH. REVIEW:

PKG.

NO.

OF05/05/23

A1Contact: Hank Houser

FLOOR PLANS

LEIPER'S FORK DISTRICT FACILITY HVAC REPLACEMENT

HWA

10' - 5"

8' - 0"

8' - 0"

8' - 0" 8' - 0"

10' - 5"

10' - 5"

20' - 6"12' - 0" 12' - 0" 12' - 0"

8' - 0"

20' - 6"

8' - 0"

BREAK/TRAINING

DIST. RANGER

SHARED OFFICE

MAINTENANCE

STORAGE

TELE-ELEC

WOOD SHOP

FURNACE

VALVE

WASH / LIFT /

SERVICE

WELDING FIRE BAY

WAREHOUSE

RANGERS

MEN

WOMEN

VARIES

7' - 6"

7' - 6"

12' - 0"

VARIES

3" / 12"

3" / 12"

7' - 6"

7' - 6"

NEW INDUSTRIAL

FANS ABOVE,

SEE MECH

8' - 6"

8' - 6"

20' - 6"

STORAGE

MECH

OPEN TO

VEHICLE BAY

BELOW

NEW INDUSTRIAL

FANS ABOVE,

SEE MECH

C O

R R

ID

O

R B

E

LO

W

CEILING LEGEND

- EXISTING 2X4 ACT

- EXISTING GYP BD CEILING

SHEET

1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com

TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM

Houser Walker Architecture

DATE:

TECH. REVIEW:

PKG.

NO.

OF05/05/23

A2Contact: Hank Houser

REFLECTED CEILING PLANS

LEIPER'S FORK DISTRICT FACILITY HVAC REPLACEMENT

HWA

LEVEL 1 - REFLECTED CEILING PLAN1 LEVEL 2 - REFLECTED CEILING PLAN2

GENERAL NOTES:

1. All existing ceilings to remain.

2. See mechanical & electrical drawings for new scope.

3. Patch and repaint ceilings where required at new mechanical & electrical work areas.

4. For mechanical penetrations at roof see SMACNA detail figure 4-20.

Patch & repair asphalt shingle roofing as needed.

0 88 16

SCALE OF FEET

ROOF DETAIL @ MECH PENETRATIONS3

H

C

T

T

S

TM

HVAC LEGEND & ABBREVIATIONS HVAC LEGEND & ABBREVIATIONS

SYMBOL DESCRIPTION

BALANCING VALVE

CHECK VALVE

SOLENOID VALVE

GLOBE VALVE

THREE WAY MODULATING MOTORIZED CONTROL VALVE

TWO WAY MODULATING MOTORIZED CONTROL VALVE

BALL VALVE

PRESSURE REDUCING VALVE

RELIEF VALVE

AUTOMATIC AIR VENT

MANUAL AIR VENT

THERMOMETER

PRESSURE GAUGE

DRIP LEG

TEST PLUG

THERMOMETER WELL

GAUGE COCK

STRAINER

SIGHT GLASS

SYMBOL DESCRIPTION

PIPING OR EQUIPMENT TO BE REMOVED

PIPE FLOW ARROW

CHILLED WATER RETURNCHWR

GRADE ARROW-INDICATES RISE OR DROP IN DUCT OR PIPEUP DNOR

CHILLED WATER SUPPLYCHWS

CONDENSER WATER RETURNCWR

CONDENSER WATER SUPPLYCWS

HOT WATER RETURNHWR

HOT WATER SUPPLYHWS

CONDENSATE DRAINC

LOW PRESSURE STEAM (PRESSURE SHOWN)LPS (5#)

MEDIUM PRESSURE STEAM (PRESSURE SHOWN)MPS (65#)

HIGH PRESSURE STEAM (PRESSURE SHOWN)HPS (125#)

LOW PRESSURE STEAM CONDENSATELPC

LOW PRESSURE STEAM CONDENSATEMPC

LOW PRESSURE STEAM CONDENSATEHPC

PUMPED STEAM CONDENSATEP

VENTV

REFRIGERANT LIQUIDRL

REFRIGERANT SUCTIONRS

STEAM TRAP

HUMIDITY SENSOR

TEMPERATURE SENSOR

SWITCH

TIMER

CARBON DIOXIDE SENSOR

THERMOSTAT

CONNECT TO EXISTING

EXTENT OF DEMO

HVAC LEGEND & ABBREVIATIONS

SYMBOL DESCRIPTION

RECTANGULAR AIR DUCT - FIRST DIMENSION IS SIDE SHOWN00x00

DUCT TRANSITION, RECTANGULAR TO ROUND OR OVAL

ROUND DUCT (A"∅) OR FLAT OVAL (AxB)

FIRE DAMPER (FD)

AIR DUCT FLEXIBLE CONNECTOR

DUCTWORK TO BE REMOVED

SUPPLY OR OUTSIDE AIR RECTANGULAR DUCT RISE OR DROP

RETURN AIR RECTANGULAR DUCT RISE OR DROPOR

OR

SMOKE DAMPER (SD)

COMBINATION FIRE/SMOKE DAMPER (FSD)

SQUARE ELBOW WITH TURNING VANES

DUCT TRANSITION, RECTANGULAR TO RECTANGULAR

FLEX DUCT AT DIFFUSER

DUCT-MOUNTED STATIC PRESSURE SENSOR (DM-SPS)

MANUAL VOLUME DAMPER (MD)

OR

CONCENTRIC REDUCER

PIPE UNION

PIPE RISE [DOUBLE LINE/SINGLE LINE]

PIPE DROP [DOUBLE LINE/SINGLE LINE]

CAP ON END OF LINE

GATE VALVE

BUTTERFLY VALVE

LINED DUCTWORK, DIMENSIONS ARE OUTER METAL TO OUTER METAL

SMOKE DETECTOR (SDT)

BACKDRAFT DAMPER (BDD)

OR EXHAUST AIR RECTANGULAR DUCT RISE OR DROP

ECCENTRIC REDUCER FLAT SIDE ON BOTTOM OR FLAT SIDE ON TOP

MOTOR OPERATED DAMPER (SAME SIZE AS DUCT UNLESS OTHERWISE NOTED) (MOD)

AIR FLOW SENSOR (AFS)

MECHANICAL - GENERAL NOTES

1. EXISTING EQUIPMENT, DUCTWORK AND PIPING TO REMAIN, UNLESS NOTED TO BE REMOVED.

2. VERIFY LOCATIONS OF EXISTING PIPING, DUCTWORK AND EQUIPMENT PRIOR TO BEGINNING WORK.

3. PROVIDE INSULATED FLEXIBLE DUCT TO DIFFUSER SAME SIZE AS DIFFUSER NECK SIZE WITH SPIN-IN AND SINGLE BLADE DAMPER AT DIFFUSER TAKE-OFF.

4. RUNOUTS TO DIFFUSERS SHALL BE SAME SIZE AS DIFFUSER NECK, UNLESS OTHERWISE NOTED.

5. ALL EXISTING EQUIPMENT, DUCTWORK AND PIPING IS SHOWN LIGHT DASHED, DEMO WORK IS BOLD DOTTED, AND NEW WORK IS BOLD SOLID.

6. ROUTE DUCTWORK AS TIGHT TO STRUCTURE AS POSSIBLE, UNLESS OTHERWISE NOTED.

7. MAXIMUM FLEXIBLE DUCT RUNOUT TO BE FIVE FEET. USE GALVANIZED STEEL DUCT FOR INDIVIDUAL RUNOUTS OVER FIVE FEET.

8. BALANCE AIR DISTRIBUTION SYSTEMS AS NOTED.

9. UNLESS OTHERWISE NOTED, WALL MOUNTED THERMOSTATS AND SENSORS SHALL BE MOUNTED AT 4'-0" AFF. COORDINATE FINAL DEVICE LOCATIONS AND HEIGHTS WITH

ARCHITECT AND ARCHITECTURAL DRAWINS PRIOR TO INSTALLATION.

10. COORDINATE ALL LAY-IN CEILING DIFFUSERS WITH ARCHITECTURAL REFLECTED CEILING PLAN.

11. PROTECT ALL MATERIALS AND EQUIPMENT FROM DAMAGE.

12. CONTRACTOR SHALL PAINT ALL DUCTWORK VISIBLE THROUGH SUPPLY AND RETURN AIR OPENINGS AND GRILLES FLAT BLACK.

13. CONTRACTOR TO COORDINATE FIRE DAMPER HOURLY RATINGS WITH GENERAL CONTRACTOR AND ARCHITECTURAL DRAWINGS.

14. COORDINATE ALL MANUAL VOLUME DAMPERS TO BE LOCATED IN AN ACCESSIBLE LOCATION.

15. SEE SPECIFICATIONS REGARDING DUCTWORK CLEANLINESS AND DUCT PROTECTION DURING CONSTRUCTION.

16. CONTRACTOR SHALL COORDINATE LOCATION AND QUANTITY OF ALL MANUAL DAMPERS, MOTORIZED DAMPERS, FILTER RACKS, SMOKE DETECTORS, ETC WITH CONTROL

SCHEMATIC DRAWINGS.

17. FLEXIBLE DUCTWORK SHALL NOT BE INSTALLED ABOVE INACESSIBLE CEILINGS.

18. FLEXIBLE DUCTWORK SHALL NOT BE INSTALLED IN RETURN OR EXHAUST AIR SYSTEMS UNLESS OTHERWISE NOTED.

19. ALL PIPING RUNOUTS TO EQUIPMENT SHALL BE 3/4" UNLESS OTHERWISE NOTED.

20. EQUIPMENT ABOVE ACESSIBLE CEILINGS SHALL BE LOCATED WITH BOTTOM OF UNIT ACESSIBLE FROM THE CEILING LEVEL, NOT TO EXCEED 24" ABOVE THE CEILING.

21. ALL RETURN GRILLES SHALL BE TYPE R-1 UNLESS OTHERWISE NOTED.

22. NO FIELD PENETRATIONS OF AIR HANDLING UNIT CASINGS ARE PERMITTED. NO CONDUITS, PIPES, OR DEVICES SHALL BE ATTACHED TO THE CASING WITH SCREWS, BOLTS,OR OTHER ATTACHMENT METHODS THAT REQUIRE PIERCING OF THE CASING. ACCEPTABLE ATTACHMENT METHOD IS USE OF PERFORATED BASE STUDS (MCMASTER CARR PART #97590A315 OR EQUAL) BONDED TO THE OUTER UNIT CASING WITH EPOXY (GRAINGER PART # 3XH44 OR EQUAL).

SHEET

1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com

TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM

Houser Walker Architecture

DATE:

TECH. REVIEW:

PKG.

NO.

OF

M1Contact: Hank Houser

GENERAL NOTES & LEGENDS

SCHEMATIC DESIGN

JSA

HWA25

Rectangle

HWA25

Snapshot

HWA25

Snapshot

1 1 1

6 8

EXISTING 8x8 DUCT

TO BE REMOVED

EXIST. VACUUM

DUCT TO REMAIN

EXIST. VACUUM

DUCT TO REMAIN

EXIST. VACUUM

DUCT TO REMAIN

5 5

SHEET

1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com

TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM

Houser Walker Architecture

DATE:

TECH. REVIEW:

PKG.

NO.

OF

M2Contact: Hank Houser

HVAC - FLOOR PLAN - DEMO

SCHEMATIC DESIGN

JSA

4 4 8 16 1/8" = 1'-0"

FEETSCALE

SCALE: 1/8" = 1'-0"1 1ST FLOOR PLAN - DEMO

4 4 8 16

1/8" = 1'-0"

FEETSCALE

SCALE: 1/8" = 1'-0"2 2ND FLOOR PLAN - DEMO

GENERAL NOTES - HVAC

Key Name General Notes - HVAC

1 SEE SHEET M-001 FOR HVAC GENERAL NOTES.

KEY NOTES #

1. EXISTING UNIT HEATER TO BE REMOVED. REMOVE EXISTING GAS PIPING TO

NEAREST SHUT-OFF.

2. EXISTING AIR HANDLER UNIT TO BE REMOVED.

3. EXISTING MIXING AIR UNIT TO BE REMOVED.

4. EXISTING EXHAUST FAN TO REMAIN.

5. EXISTING OUTSIDE AIR LOUVER TO BE REMOVED

6. EXISTING DUCT FURNACE TO BE REMOVED

7. EXISTING EXHAUST FAN TO BE REMOVED.

8. EXISTING OUTDOOR CONDENSING UNIT TO BE REMOVED.

9. EXISTING DUST COLLECTOR TO BE REMOVED.

HWA25

Rectangle

HWA25

Snapshot

UH-6

UH-5

UH-4 UH-3 UH-2

UH-1

T

T

T

T T

T

T

BREAK/TRAINING

DIST. RANGER

SHARED OFFICE

MAINTENANCE

STORAGE

TELE-ELEC

WOOD SHOP

FURNACE

VALVE

WASH / LIFT / SERVICE

WELDING

FIRE BAY

WAREHOUSE

RANGERS

MEN

WOMEN

CHASE

AHU-1

CU-1

DFU-1

EF-1

EF-2

EF-3

8" ø

8" ø

4'-0"

S-1

12x12 EXHAUST DUCT

UP TO NEW EF-6

WELDING HOOD

EXHAUST DUCT

UP TO NEW EF-5

EXISTING EXHAUST

DUCT UP TO NEW EF-4

DSSC

10"ø

TYP.2

EXIST.

8"ø

EXIST.

16x10

EXIST.

20x14

EXIST.

14X8

EXIST.

14X8

EXIST.

12" Ø

EXIST.

8"ø

EXIST.

10"ø

EXIST.

14x12

EXIST.

20x14 x1 x1

20x12 x1

30x14 x8 x1

30x14

30x14 12x12 x1 x1

24x18

14x6

14x4

12x4 x1 x1 x1

14x12

EXIST.

8"ø

EXIST.

6x6

EXIST.

6"ø

EXIST.

6"ø

EXIST.

18x12

TYP.6

EXIST.

T

M4

TO MUA-1

TO AHU-1

H

DC-1

EXIST. VACUUM

DUCT TO REMAIN

FITNESS AREA

MECH

OPEN TO VEHICLE BAY BELOW

HVLS-1 HVLS-2

10"ø

E-1

DSSA-1

4'-0"

S-1

MUA-1

EF-4

UP TO EF-7

DSSA-2

4'-0"

S-1

EXISTING LV-2, MOTORIZED

DAMPER TO BE REPLACED

EXISTING L1

EXISTING 12x4 EXHAUST

DUCT UP INTO ATTIC

THEN HORIZONTAL (TYP.3)

12x12 R-2 RETURNING AIR

HIGH IN CORRIDOR SPACE

EXISTING LV-2, MOTORIZED

DAMPER TO BE REPLACED

SHEET

1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com

TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM

Houser Walker Architecture

DATE:

TECH. REVIEW:

PKG.

NO.

OF

M3Contact: Hank Houser

HVAC - FLOOR PLAN - NEW

WORK

SCHEMATIC DESIGN

JSA

4 4 8 16 1/8" = 1'-0"

FEETSCALE

SCALE: 1/8" = 1'-0"1 1ST FLOOR PLAN - NEW WORK

4 4 8 16

1/8" = 1'-0"

FEETSCALE

SCALE: 1/8" = 1'-0"2 2ND FLOOR PLAN - NEW WORK

GENERAL NOTES - HVAC

Key Name General Notes - HVAC

1 SEE SHEET M-001 FOR HVAC GENERAL NOTES.

KEY NOTES #

1. SLOT DIFFUSER SERVING FITNESS AREA ON FLOOR ABOVE,

HWA25

Rectangle

HWA25

Snapshot

12x12

15x1830x14

30x14 x3

AHU-1

M4

M4

24x12

LV-3

AHU-1

15x18

EXISTING DUCTWORK

NEW 12x12 DUCTWORK CONNECTING

INTO EXISTING DUCT

DFU-1

12x12

NEW DUCTWORK CONNECTING NEW

AHU-1 INTO EXISTING DUCTWORK

NEW DUCTWORK CONNECTING NEW

AHU-1 INTO EXISTING DUCTWORK

LEVEL 1

0"

LEVEL 2

12' - 8"

LEVEL 1

0'-0"

LEVEL 2

12'-8"

M4

12x12

24x12

LV-3

18x15

14x30

DFU-1

AHU-1

6x6

EXIST.

LEVEL 1

0"

LEVEL 2

12' - 8"

LEVEL 1

0'-0"

LEVEL 2

12'-8"

M4

15x18

12x12

6x6

EXIST.

30x

AHU-1

DFU-1

NEW 12x12 DUCTWORK CONNECTING

TO EXISTING DUCTWORK

SHEET

1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com

TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM

Houser Walker Architecture

DATE:

TECH. REVIEW:

PKG.

NO.

OF

M4Contact: Hank Houser

HVAC - PART PLANS

SCHEMATIC DESIGN

Author

1 1 2 4 5 1/2" = 1'-0"

FEETSCALE

SCALE: 1/2" = 1'-0"4 MECHANICAL PART PLAN

SCALE: NO SCALE1 MECHANICAL PERSPECTIVE

1 1 2 4 5 1/2" = 1'-0"

FEETSCALE

SCALE: 1/2" = 1'-0"2 MECHANlCAL SECTION VIEW

1 1 2 4 5 1/2" = 1'-0"

FEETSCALE

SCALE: 1/2" = 1'-0"3 MECHANICAL SECTION VIEW

HWA25

Rectangle

HWA25

Snapshot

3'

MI

N.

DOWN DRAFT

PROOF CAP

FLASH AND

COUNTER FLASH

ROOF

REUSE EXISTING EXHAUST

NEW PIPE TO CONNECT

UNIT HEATER TO EXISTING

CEILING PENETRATION

REUSE EXISTING OR

SIMILAR ATTACHMENT

NEW UNIT HEATER

REUSE EXISTING EXHAUST

DOWN DRAFT

PROOF CAP

INSULATED

DOUBLE WALL

FLUE (SEE

SPECIFICATIONS)

MANUFACTURER'S VENTILATED ROOF

THIMBLE

ROOF

MAINTAIN

MANUFACTURER'S

MINIMUM CLEARANCE

FROM COMBUSTIBLES

MINIMUM 3'

ABOVE HIGHEST

POINT ON ROOF

WITHIN 10'

1'-6"

FLEXIBLE COUPLING

DIRT LEG

FLANGED JOINT OR UNION TO

PERMIT PIPING DISASSEMBLY

FOR BURSTING DISC

SERVICING

CAP HANDTIGHT TO

PERMIT CLEANOUT

5" REFRIGERANT RELIEF VENTED TO THE

OUTSIDE OF BUILDING SEE SHEET M11.2 FOR

CONTINUATION

PIPING CONNECTION TO RUPTURE DISK FLANGE

AND ALL PIPING TO OUTDOORS PROVIDED BY

CONTRACTOR

NON-FRAGMENTING COMPOSITE

MATERIAL RUPTURE DISK

RELIEF

CONNECTION

LINED RETURN AIR

TRANSFER DUCT, SIZE

(LINER TO LINER) AS

NOTED ON DRAWING.

INTERIOR WALL

OPEN END

DUCT HIGH IN CORRIDOR

NOTES:

1. TRANSFER AIR DUCT MAY BE INSTALLED IN HORIZONTAL OR VERTICAL ARRANGEMENT. IF

INSTALLED IN HORIZONTAL ARRANGEMENT THE OPEN ENDS OF DUCT SHALL BE POINTED UP.

SHEET

1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com

TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM

Houser Walker Architecture

DATE:

TECH. REVIEW:

PKG.

NO.

OF

M5Contact: Hank Houser

HVAC DETAILS

SCHEMATIC DESIGN

JSA

SCALE: NO SCALE1 GAS UNIT HEATER INSTALLATION

SCALE: NO SCALE3 GAS FLUE CAP DIAGRAM

SCALE: NO SCALE4 REFRIGERANT VENT PIPING

SCALE: NO SCALE2 LINED TRANSFER DETAIL

HWA25

Rectangle

HWA25

Snapshot

SHEET

1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com

TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM

Houser Walker Architecture

DATE:

TECH. REVIEW:

PKG.

NO.

OF

M6Contact: Hank Houser

HVAC SCHEDULES

SCHEMATIC DESIGN

JSA

AIR HANDLING UNIT SCHEDULE

MARK SERVES

FAN COOLING COIL FILTERS OUTSIDE AIR

VOLTAGE REMARKSCFM MIN.

CFM ESP HP RPM TYPE EAT DB/WB LAT DB/WB CAPACITY (MBH)

TOTAL/SENS. TYPE MIN. CFM MAX. CFM

AHU-1 OFFICE 4000 2690 2.3 2.25 1800 DIRECT DRIVE 74°F/62°F 55°F/53°F 108/85 MERV 8 200 600 208V/3ph (1),(2),(3),(4),(5),(6),(7), (8),(9)

GENERAL

1. AMBIENT DESIGN CONDITIONS: SUMMER 94°F DB / 74°F WB, WINTER 10°F. SUMMER RETURN 77°F DB / 64° WB, WINTER RETURN 65°F DB/ 30%RH.

2. PROVIDE DIRECT DRIVE PLNEUM SUPPLY FAN WITH VFD OR ECM MOTOR.

3. PROVIDE FIELD MOUNTED SMOKE DETECTOR AT SUPPLY DISCHARGE.

4. PROVIDE SINGLE POINT POWER CONNECTION WITH FACTORY BREAKER/DISCONNECT.

5. PROVIDE ECONOMIZER PACKAGE WITH POWERED EXHAUST.

6. PROVIDE UV LIGHTS AT DOWNSTREAM SIDE OF COOLING COIL, FACTORY WIRED AND POWERED. PROVIDE CONTACT FOR AMP DRAW OUTPUT.

7. PROVIDE UNIT WITH VERTICAL DISCHARGE DUCT CONNECTION

8. MODULATING HOT GAS RE-HEAT.

9. PROVIDE INVERTER SCROLL COMPRESSOR ON LEAD CIRCUIT.

GAS UNIT HEATER SCHEDULE

MARK TYPE LOCATION

CAPACITY

INPUT/OUTPUT

(MBH)

CFM FAN MOTOR VOLTAGE DESIGN BASIS REMARKS

GUH-1 GAS FIRED

UNIT HEATER SHOP 1,2 105 / 87 1,700 3/4 120V REZNOR UBZ 100 1, 2, 3

GUH-2 GAS FIRED

UNIT HEATER FIRE BAYS 45 / 37 630 1/16 120V REZNOR UDX 45 1, 2, 3

GUH-3 GAS FIRED

UNIT HEATER FIRE BAYS 45 / 37 630 1/16 120V REZNOR UDX 45 1, 2, 3

GUH-4 GAS FIRED

UNIT HEATER WELDING BAY 105 / 87 1,700 3/4 120V REZNOR UBZ 100 1, 2, 3

GUH-5 GAS FIRED

UNIT HEATER WASH/LIFT/SERVICE 120 / 100 2,000 3/4 120V REZNOR UBZ 125 1, 2, 3

GUH-6 GAS FIRED

UNIT HEATER WAREHOUSE 45 / 37 630 1/16 120V REZNOR UDX 45 1, 2, 3

NOTES:

1. PROVIDE GAS FIRED UNIT HEATER WITH DUCTED COMBUSTION AIR, DUCTED FLUE, 100% SHUT-OFF WITH CONTINUOUS RETRY, POWER EXHAUSTER WITH MOISTURE RESISTANT BURNER

ENCLOSURE, DUAL PRESSURE SWITCHES, TRANFORMER AND GAS CONTROLS.

2. PROVIDE WIRED PROGRAMMABLE WALL THERMOSTAT POWERED FROM HEATER. (PROVIDE TRANSFORMER WITH HEATER AS REQURIED) PROVIDE VENTED LOCKBOX FOR THERMOSTAT.

3. DUCT (INSULATED) BOTH FLUE AND COMBUSTION AIR TO WALL TERMINAL- PROVIDE FLUE AND COMBUSTION TERMINATION ACCESSORIES FROM MANUFACTURER. VERIFY TOTAL

COMBINED VENT AND COMBUSTION AIR INTAKE LENGTHS WITH MANUFACTURER.

FAN SCHEDULE

MARK LOCATION TYPE DIAMETER ELECTRICAL DESIGN BASIS REMARKSHP VOLTAGE

HVLS-1 VEHICLE BAY 8 AIRFOIL

BLADE 10' 1 120V/1ph BIG ASS FANS

ESSENCE 1, 2

HVLS-2 VEHICLE BAY 8 AIRFOIL

BLADE 10' 1 120V/1ph BIG ASS FANS

ESSENCE 1, 2

NOTES:

1. PROVIVDE FAN WITH RAPID MOUNT INDUSTRIAL I-BEAM HARDWARE KIT, AND DROP LENGTH SIZED/TRIMMED TO FIT.

2. PROVIDE FAN WITH LOW VOLTAGE WALL MOUNTED TOUCHSCREEN REMOTE (1 PER FAN) AND TRANSFORMER IF NECESSARY TO POWER

FROM FAN.

EXHAUST FAN SCHEDULE

MARK SERVES TYPE DRIVE TYPE CFM ESP HP VOLTAGE DESIGN BASIS REMARKS

EF-1 WOMENS RESTROOM CEILING DIRECT

DRIVE 150 0.385 128 W 115V/1ph GREENHECK SP-B150 1

EF-2 CHASE CEILING DIRECT

DRIVE 75 0.240 20 W 115V/1ph GREENHECK SP-B110 1

EF-3 MENS RESTROOM CEILING DIRECT

DRIVE 150 0.385 128 W 115V/1ph GREENHECK SP-B150 1

EF-4 WASH/LIFT/SERVICE INLINE DIRECT

DRIVE 2900 0.4 1 208V/3ph GREENHECK SQ-140 1

EF-5 WELDING HOOD INLINE DIRECT

DRIVE 2100 0.4 3/4 208V/3ph GREENHECK SQ-130 1

EF-6 WELDING BAY UPBLAST ROOF

EXHAUSTER

DIRECT

DRIVE 660 0.2 1/15 115V/1ph GREENHECK CUE-090-D 1

EF-7 FITNESS AREA INLINE DIRECT

DRIVE 200 0.4 1/10 115V/1ph GREENHECK SQ-80 1

NOTES:

1. DIRECT DRIVE

2. BACKDRAFT DAMPER

3. ROOF CURB, BACKDRAFT DAMPER, AND ALUMINUM BIRDSCREEN.

4. PROVIDE FACTORY MOUNTED DISCONNECT SWITCH

FAN CONTROL TYPE:

WS WALL MOUNTED SWITCH

DDC DDC CONTROL

TS DDC THERMOSTAT

LS INTERLOCKED TO ROOM LIGHT SWITCH

GAS DUCT FURNACE SCHEDULE

MARK SERVES INPUT MBH VOLTAGE DESIGN BASIS REMARK

DFU-1 OFFICES 125 115V/1ph REZNOR EEDU

MAKE-UP AIR UNIT SCHEDULE

MARK SERVED BY INPUT MBH OUTPUT MBH CFM ESP FILTER 2" THROWAWAY MOTOR HP VOLTAGE/PHASE DESIGN BASIS MUA-1 SERVES 300 240 2550 0.6 (2) 20x20 (2) 20x25 1 208V/3ph REZNOR SCE 300

DUCTLESS SPLIT SYSTEM SCHEDULE

MARK SERVED BY SERVES TYPE CFM

COOLING

TOTAL/SENSIB

LE (BTUH)

HEATING

TOTAL MAX

(BTUH)

VOLTAGE DESIGN BASIS REMARKS

DSSA-1 DSSC-1 FITNESS AREA - 119 HIGH WALL 400 208V/1ph DSSA-2 DSSC-1 FITNESS AREA - 119 HIGH WALL 400 208V/1ph

NOTES:

1. COOLING CAPACITIES AT 75°F DB/64°F WB ENTERING AIR TEMPERATURE, 95°F AMBIENT.

2. PROVIDE MATCHING OUTDOOR CONDENSING UNIT (TAGGED CU-#) TO PROVIDE CAPACITIES AS SCHEDULED; VOLTAGE OF OUTDOOR UNIT TO BE 208V/1PH

3. PROVIDE LOW AMBIENT WIND BAFFLE FOR OPERATION DOWN TO 0°F.

4. WARRANTY SHALL INCLUDE 5-YEAR COMPRESSOR INCLUDING LABOR AND 5-YEAR REFRIGERATION LEAK WARRANTY INCLUDING LABOR.

5. INDOOR UNIT IS POWERED BY OUTDOOR UNIT. ELECTRICAL DATA IS FOR BOTH COMPONENTS, CONNECTIONS TO OUTDOOR UNIT.

LOUVER SCHEDULE

MARK FUNCTION WIDTH HEIGHT MATERIAL BASIS OF DESIGN REMARKS

LV-1 MAKE-UP AIR

INTAKE 60" 48" EXISTING EXISTING TO REMAIN --

LV-2 MAKE-UP AIR

INTAKE 48" 36" EXISTING EXISTING TO REMAIN 3

LV-3 OUTSIDE AIR

INTAKE 24" 12" ALUMINUM GREENHECK ESD 1, 2

LV-4 COMBUSTION

AIR 18" 12" EXISTING EXISTING TO REMAIN --

GRILLE, REGISTER & DIFFUSER SCHEDULE

MARK DESCRIPTION DIFFUSER

SIZE NECK SIZE MOUNTING

TYPE DAMPER FINISH DESIGN BASIS

S-1

EXTRUDED ALUMINUM "PENCIL PROOF" LINEAR BAR

GRILLE, 7/32" BARS, 7/16" SPACING CONCEALED

MOUNTING, 30° DEFLECTION.

48" LONG

SLOTS AS NOTED SURFACE /

EXPOSED

CABLE-OPERATED DAMPER,

ADJUSTABLE THROUGH SLOT

FACE

FLAT BLACK INTERIOR WITH

WHITE FACE/BORDER TITUS CT-PP-3

R-1 FULL FACE 1/2"x1/2"x1/2" ALUMINUM EGG CRATE GRILLE, CORE ONLY, FRAMELESS 24x24 AS NOTED LAY-IN

CEILING NO WHITE TITUS 50F

R-2

STEEL SIDE WALL RETURN GRILLE, 3/4" BLADE

SPACING, FLANGE FRAME, 35 DEGREE OFFSET

BLADES, BLADES PARALLEL TO LONG DIMENSION.

TITUS 350RL.

AS NOTED

SAME

SIZE AS

DIFFUSER

WALL

MOUNTED NO WHITE TITUS 350RL

E-1 1/2"x1/2"x1/2" ALUMINUM EGG CRATE GRILLE, DUCT

CONNECTION AS NOTED

SAME

SIZE AS

DIFFUSER

SURFACE /

EXPOSED O.B. DAMPER WHITE TITUS 50F

NOTES:

1. PROVIDE LOUVER WITH EXTENDED SILL, GALVINIZED BIRDSCREEN AND ANODIZED FINISH (FINAL COLOR SELECTED BY ARCHITECT).

2. LOUVER SHALL HAVE A MINIMUM FREE AREA OF 50%.

3. MOTORIZED DAMPER TO BE REPLACED.

DUST COLLECTOR SCHEDULE

MARK SERVICE CFM ESP RPM FAN HP SHAKER HP VOLTAGE BASIS OF DESIGN REMARKS

DC-1 SHOP 1, 2 2700 7 3450 7.5 .750 208V/3ph AMERICAN AIR FILTER SILENCER AND WEATHERPROOF

MOTOR COVER

HWA25

Rectangle

HWA25

Snapshot

05/05/23

Contact: Hank Houser

LEIPER'S FORK DISTRICT FACILITY HVAC REPLACEMENT

W W E S T S I D E

E N G I N E E R I N G

200 Galleria Pkwy Suite 1150

Atlanta, GA 30339 cesslinger@westside-engineering.com

404-965-1287 tel 404-601-9859 fax

WE # 22486

SHEET

1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com

TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM

Houser Walker Architects

DATE:

TECH. REVIEW:

PKG.

NO.

OF

E1

ELECTRICAL NOTES

AND DETAILS

HWA

AutoCAD SHX Text ELECTRICAL CIRCUIT RUN IN CONDUIT AND CIRCUIT HOMERUN TO PANELBOARD (PANEL AND CIRCUIT DESIGNATION AS INDICATED). AS A MINIMUM CONDITION, EACH SINGLE PHASE CIRCUIT SHALL HAVE ONE #12 PHASE CONDUCTOR, ONE #12 NEUTRAL CONDUCTOR, AND ONE #12 GROUNDING CONDUCTOR (PLUS ONE INSULATED, ISOLATED GROUNDING CONDUCTOR WHEN SERVING ISOLATED GROUND TYPE DEVICES) IN 1/2" CONDUIT. PROVIDE ADDITIONAL PHASE CONDUCTORS AS REQUIRED FOR "MULTIPLE PHASED" ELECTRICAL LOADS. PROVIDE ADDITIONAL "SWITCH LEG" CONDUCTORS TO PROVIDE THE LIGHT FIXTURE CONTROL INDICATED. MULTIPLE SINGLE PHASE CONDUCTORS SHALL BE GROUPED TOGETHER IN A COMMON CONDUIT IN ACCORDANCE WITH THE NEC AND AT THE CONTRACTOR'S DISCRETION. MULTIPLE SINGLE PHASE CONDUCTORS SERVING ISOLATED GROUND RECEPTACLES SHALL NOT SHARE COMMON NEUTRALS. NEUTRAL AND GROUNDING CONDUCTORS SHALL BE SHARED AS ALLOWED BY THE NEC. BRANCH CIRCUIT CONDUCTORS IN CONDUIT SHALL BE RUN CONCEALED IN WALLS AND/OR ABOVE CEILINGS, IN/OR BELOW FLOORS, EXCEPT IN EXPOSED CONSTRUCTION AREAS. FLUORESCENT LIGHTING CIRCUITS SERVING SWITCHED FIXTURES WITH EMERGENCY BATTERY BACK-UP SHALL CONTAIN ONE UNSWITCHED CONDUCTOR. FLUORESCENT DIMMING CIRCUITS SERVING DIMMING BALLASTS SHALL BE PROVIDED WITH WIRING AS REQUIRED BY BALLAST MANUFACTURER. MULTIPLE PHASE LIGHTING CIRCUITS SERVING DIMMED LOADS SHALL NOT SHARE COMMON NEUTRALS.

AutoCAD SHX Text

PROVIDE FIRE STOPPING AT CONDUIT PENETRATIONS PER UL.

AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING FIRE STOPPING AT ALL WALL, FLOOR AND CEILING PENETRATIONS WHERE CONDUIT PENETRATIONS OCCUR.

AutoCAD SHX Text PRIOR TO ANY EXCAVATION, CONTRACTOR SHALL HAVE ALL EXISTING UNDERGROUND UTILITIES LOCATED.

AutoCAD SHX Text TELEPHONE/TELEVISION BACKBOARD, 4' X 4' X 3/4" THICK EXTERIOR GRADE PLYWOOD. MOUNT VERTICALLY WITH BOTTOM OF PLYWOOD 6" A.F.F., U.O.N.

AutoCAD SHX Text TELEVISION OUTLET 18" A.F.F., U.O.N. SINGLE GANG BOX WITH DEVICE PLATE. PROVIDE 3/4" (UON) CONDUIT WITH PULLWIRE FROM OUTLET TO ABOVE ACCESSIBLE CEILING.

AutoCAD SHX Text TELEPHONE OUTLET 18" A.F.F., U.O.N. DOUBLE GANG BOX WITH DEVICE PLATE. PROVIDE 3/4" (UON) CONDUIT WITH PULLWIRE FROM OUTLET TO ABOVE ACCESSIBLE CEILING. PROVIDE WITH SINGLE GANG ADAPTER.

AutoCAD SHX Text TELEPHONE/DATA OUTLET 18" A.F.F., U.O.N. DOUBLE GANG BOX WITH DEVICE PLATE. PROVIDE 1" (UON) CONDUIT WITH PULLWIRE FROM OUTLET TO ABOVE ACCESSIBLE CEILING. PROVIDE WITH SINGLE GANG ADAPTER.

AutoCAD SHX Text

KEYNOTE.

AutoCAD SHX Text

STARTER

AutoCAD SHX Text

MOTOR CONNECTION, WITH INTEGRAL DISCONNECTING MEANS.

AutoCAD SHX Text

MOTOR RATED SWITCH. MOUNT WITHIN SIGHT OF EQUIPMENT.

AutoCAD SHX Text DISCONNECT SWITCH, 240 OR 600 VOLTS AS REQUIRED. AMPS, POLES AND FUSING AS NOTED, NEMA 1, U.O.N.

AutoCAD SHX Text

JUNCTION BOX.

AutoCAD SHX Text

PANELBOARD / LOAD CENTER

AutoCAD SHX Text RECEPTACLE/TELEPHONE/DATA OUTLETS, FLUSH MOUNT IN FLUSH MOUNTED FLOOR BOX WITH RUBBER OR THERMOPLASTIC CARPET COVER PLATE. PROVIDE NUMBER AND TYPE OF DEVICES PER PLANS. COORDINATE DEPTH OF FLOOR BOX WITH SLAB DEPTH. COORDINATE EXACT LOCATION WITH ARCHITECT. PROVIDE 3/4" CONDUIT WITH CONDUCTORS INDICATED FOR SERVICE TO RECEPTACLE OUTLET. PROVIDE (1) 1-1/4" CONDUIT WITH PULLWIRE FROM EACH SPECIAL SYSTEMS OUTLET TO ABOVE NEAREST ACCESSIBLE CEILING FOR SPECIAL SYSTEM WIRING BY OTHERS.

AutoCAD SHX Text

SPECIAL RECEPTACLE, AMPERAGE, AND VOLTAGE AS INDICATED, 18" AFF, UON.

AutoCAD SHX Text DUPLEX GROUNDING TYPE RECEPTACLE, 20A, 125 VOLT, NEMA 5-20R. MOUNT HORIZONTALLY 6" A.F.F. FOR WATER COOLER.

AutoCAD SHX Text DUPLEX GROUND FAULT INTERRUPTER TYPE RECEPTACLE, MOUNT HORIZONTALLY 18" A.F.F., U.O.N., IN CAST OUTLET BOX WITH GASKET DEVICE COVER.

AutoCAD SHX Text DUPLEX GROUND FAULT INTERRUPTER TYPE RECEPTACLE, 20A, 125 VOLT, NEMA 5-20R, 18" A.F.F., U.O.N.

AutoCAD SHX Text

DUPLEX GROUNDING TYPE RECEPTACLE, 20A, 125 VOLT, NEMA 5-20R, 18" A.F.F., U.O.N..

AutoCAD SHX Text

ELECTRICAL LEGEND

AutoCAD SHX Text

%%UFIRE PROOFING NOTES:

AutoCAD SHX Text

DEVICE PLATE NOTE

AutoCAD SHX Text

UTILITY NOTES:

AutoCAD SHX Text

1. 2.

AutoCAD SHX Text 1.

AutoCAD SHX Text

MCB

AutoCAD SHX Text

MLO

AutoCAD SHX Text

NTS

AutoCAD SHX Text

PNL

AutoCAD SHX Text

SN

AutoCAD SHX Text U.O.N.

AutoCAD SHX Text

WP

AutoCAD SHX Text V

AutoCAD SHX Text W

AutoCAD SHX Text P

AutoCAD SHX Text A.F.F.

AutoCAD SHX Text A.F.G.

AutoCAD SHX Text

GFI

AutoCAD SHX Text

KVA

AutoCAD SHX Text

KW

AutoCAD SHX Text

BFG

AutoCAD SHX Text

ABBREVIATIONS

AutoCAD SHX Text C

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text A

AutoCAD SHX Text

TV

AutoCAD SHX Text J

AutoCAD SHX Text S

AutoCAD SHX Text

SPECIAL SYSTEMS

AutoCAD SHX Text

AutoCAD SHX Text M

AutoCAD SHX Text A-1

AutoCAD SHX Text

EWC

AutoCAD SHX Text

GFI

AutoCAD SHX Text

WP

AutoCAD SHX Text

POWER

AutoCAD SHX Text

- KILOWATT

AutoCAD SHX Text

- MAIN CIRCUIT BREAKER

AutoCAD SHX Text

- UNLESS OTHERWISE NOTED

AutoCAD SHX Text

- MAIN LUG ONLY

AutoCAD SHX Text

- NOT TO SCALE

AutoCAD SHX Text

- SOLID NEUTRAL

AutoCAD SHX Text

- WEATHERPROOF/GFI

AutoCAD SHX Text

- VOLTS

AutoCAD SHX Text

- WIRE

AutoCAD SHX Text

- PANEL

AutoCAD SHX Text

- POLE

AutoCAD SHX Text

- ABOVE FINISHED FLOOR

AutoCAD SHX Text

- ABOVE FINISHED GRADE

AutoCAD SHX Text

- BELOW FINISHED GRADE

AutoCAD SHX Text

- GROUND FAULT CIRCUIT INTERRUPTING

AutoCAD SHX Text

- AMPERES

AutoCAD SHX Text

- CONDUIT

AutoCAD SHX Text

- GROUND

AutoCAD SHX Text

- KILO VOLT AMP

AutoCAD SHX Text

- FUSE

AutoCAD SHX Text ALL COVERPLATES SHALL BE NYLON WITH FINISH TO BE SELECTED BY ARCHITECT. ALL DEVICES (SWITCHES, RECEPTACLES, ETC) SHALL BE FINISH BY ARCHITECT (UON). COORDINATE WITH ARCHITECTURAL PLANS.

AutoCAD SHX Text

(2) DUPLEX GROUNDING TYPE RECEPTACLES IN COMMON BOX, 20A, 125 VOLT, NEMA 5-20R, 18" A.F.F, U.O.N

AutoCAD SHX Text

ETR

AutoCAD SHX Text

- EXISTING TO REMAIN

AutoCAD SHX Text H

AutoCAD SHX Text

- HORIZONTALLY MOUNTED DEVICE.

AutoCAD SHX Text

HAZARDOUS LOCATIONS

AutoCAD SHX Text ENSURE THAT ALL CIRCUITRY, DEVICES, CONNECTIONS, AND WIRING LOCATED IN HAZARDOUS LOCATIONS COMPLY WITH NEC CODE. COORDINATE EXACT LOCATIONS AND EQUIPMENT WITH ARCHITECT/OWNER PRIOR TO ROUGH-IN.

AutoCAD SHX Text EXISTING LIGHTING FIXTURE BALLASTS AND FLUORESCENT LAMPS MAY CONTAIN PCB'S. DISPOSE OF BALLASTS AND LAMPS IN ACCORDANCE WITH EPA.

AutoCAD SHX Text ANY ELECTRICAL OUTAGES REQUIRED BY THE WORK SHALL BE COORDINATED WITH OWNER'S REPRESENTATIVE AND CONFIRMED IN WRITING. ANY OUTAGE SHALL NOT BE SCHEDULED DURING NORMAL BUSINESS HOURS OR DURING FACILITY FUNCTIONS AND ALL COSTS FOR OVERTIME SHALL BE INCLUDED IN THE BID.

AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL TRACE ALL CIRCUITS IN EXISTING PANELS TO REMAIN AFFECTED BY DEMOLITION. TAG ALL UNUSED CIRCUIT BREAKERS AS "SPARE" AND TIGHTEN ALL CONNECTIONS. PROVIDE NEW TYPED DIRECTORY PROTECTED BY PLASTIC AND PLACE IN COVER OF PANELS CONSISTENT WITH NEW CONSTRUCTION.

AutoCAD SHX Text CONDUITS MAY BE ABANDONED IN FLOOR AND WALLS ONLY. ELECTRICAL CONTRACTOR SHALL REMOVE ALL WIRING FROM ABANDONED CONDUITS, DISCONNECT FROM ALL POWER SOURCES AND PROVIDE BLANK PLATES ON ALL ABANDONED OUTLETS. CUT OFF ABANDONED CONDUITS 1" BELOW FINISHED FLOOR AND GROUT FLUSH. ABANDONED CONDUIT SHALL BE CAPPED AT BOTH ENDS.

AutoCAD SHX Text REMOVE ALL CONDUIT, WIRE, BOXES AND FASTENING DEVICES AS REQUIRED TO AVOID ANY INTERFERENCE WITH NEW INSTALLATION.

AutoCAD SHX Text SEE MECHANICAL DRAWING FOR HEATERS, EXHAUST FANS, ETC., WHICH MUST BE DISCONNECTED BY THE ELECTRICAL CONTRACTOR FOR REMOVAL OR ABANDONMENT BY MECHANICAL CONTRACTOR. ELECTRICAL CONTRACTOR SHALL REMOVE ALL STARTERS, DISCONNECT SWITCHES AND ASSOCIATED CONDUIT AND WIRING.

AutoCAD SHX Text ALL REMOVED COMPUTER EQUIPMENT SHALL BE TURNED OVER TO OWNER UNLESS DIRECTED TO DO OTHERWISE.

AutoCAD SHX Text IT SHALL BE THE ELECTRICAL CONTRACTORS RESPONSIBILITY TO PROTECT AND RETAIN POWER TO ALL EXISTING ACTIVE EQUIPMENT TO REMAIN. THIS INCLUDES RE-ROUTING OF EXISTING CIRCUITING EFFECTED BY DEMOLITION.

AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL VISIT AND EXAMINE THE SITE PRIOR TO CONSTRUCTION TO ASCERTAIN THE EXISTING CONDITIONS AND LIMITS OF DEMOLITION AND CONSTRUCTION.

AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL REMOVE ALL ASSOCIATED WIRING, CONDUIT, SURFACE RACEWAY, ETC. FOR DEVICES/LOADS BEING REMOVED. ITEMS REMOVED SHALL BECOME PROPERTY OF THE ELECTRICAL CONTRACTOR (UON) AND SHALL BE REMOVED FROM THE SITE. ITEMS REMOVED SHALL NOT BE STORED AT THE SITE. UNDER NO CONDITIONS SHALL ITEMS REMOVED BE USED IN THE NEW CONSTRUCTION.

AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL REMOVE DEVICES ON WALLS TO BE REMOVED AND AS DIRECTED BY ARCHITECT.

AutoCAD SHX Text HOLES LEFT BY REMOVAL OF ELECTRICAL DEVICES, PANELS, ETC. SHALL BE PATCHED IN EXISTING WALLS TO REMAIN. REFER TO ARCHITECTURAL DRAWINGS.

AutoCAD SHX Text 12.

AutoCAD SHX Text 11.

AutoCAD SHX Text 10.

AutoCAD SHX Text 9.

AutoCAD SHX Text 8.

AutoCAD SHX Text 7.

AutoCAD SHX Text 4.

AutoCAD SHX Text 5.

AutoCAD SHX Text 6.

AutoCAD SHX Text 3.

AutoCAD SHX Text 1.

AutoCAD SHX Text 2.

AutoCAD SHX Text

GENERAL ELECTRICAL DEMOLITION NOTES

AutoCAD SHX Text 9.

AutoCAD SHX Text COORDINATE MOUNTING OF ALL EXTERIOR DISCONNECT WITH ARCHITECTURAL ELEVATIONS. IF NOT INDICATED ON ARCHITECTURAL ELEVATIONS, REQUEST ELEVATIONS OF DISCONNECT SWITCHES FROM ARCHITECT IN WRITING PRIOR TO ROUGH-IN.

AutoCAD SHX Text ALIGN VERTICALLY AND HORIZONTALLY ALL LIGHT SWITCHES, THERMOSTATS, FIRE ALARM PULL STATIONS, ETC. ALL THESE ITEMS SHALL BE CLUSTERED WHERE POSSIBLE. COORDINATE EXACT REQUIREMENTS WITH ARCHITECT.

AutoCAD SHX Text THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING OUTLET BOX INSTALLATION WITH WALL FINISH (GYPSUM FURRING, TILE, ETC). THE CONTRACTOR SHALL PROVIDE AND INSTALL ANY EXTENSION RINGS NECESSARY TO ACCOMMODATE WALL FINISHES.

AutoCAD SHX Text THE CONTRACTOR SHALL USE CARE WHEN CUTTING OPENINGS FOR OUTLET BOXES IN CMU WALLS. OUTLET BOXES SHALL BE INSTALLED IN CMU WALLS SECURELY WITH EPOXY.

AutoCAD SHX Text PRIOR TO ROUGH-IN FOR ALL LIGHTING SWITCHES, VERIFY ALL DOOR SWINGS WITH ARCHITECTURAL PLANS.

AutoCAD SHX Text FOR EXACT LOCATION OF ALL EXTERIOR LIGHTING FIXTURES MOUNTED ON EXTERIOR OF BUILDING, ARCHITECTURAL ELEVATIONS SHALL GOVERN

AutoCAD SHX Text ALL MOUNTING HEIGHT DIMENSIONS ARE TO THE CENTER OF THE OUTLET BOX UNLESS OTHERWISE NOTED.

AutoCAD SHX Text PRIOR TO ROUGH-IN, CONTRACTOR SHALL COORDINATE EXACT LOCATION OF ALL WIRING DEVICE WITH ARCHITECTURAL ELEVATION TO AVOID CONFLICTS WITH CASEWORK, COUNTER TOPS, DOOR SWINGS, ETC. WHERE CONFLICTS OCCURS, CONTRACTOR SHALL CONTACT THE ARCHITECT IN WRITING FOR RESOLUTION.

AutoCAD SHX Text FOR EXACT LOCATION OF EQUIPMENT MOUNTED IN SUSPENDED CEILINGS. SUCH AS LIGHTING FIXTURES, AND SMOKE DETECTORS, SEE ARCHITECTURAL REFLECTED CEILING PLANS. ARCHITECTURAL REFLECTED PLAN SHALL GOVERN FINAL LOCATION.

AutoCAD SHX Text 5.

AutoCAD SHX Text 8.

AutoCAD SHX Text 6.

AutoCAD SHX Text 7.

AutoCAD SHX Text 3.

AutoCAD SHX Text 4.

AutoCAD SHX Text 2.

AutoCAD SHX Text 1.

AutoCAD SHX Text 9.

AutoCAD SHX Text COORDINATE MOUNTING OF ALL EXTERIOR DISCONNECT WITH ARCHITECTURAL ELEVATIONS. IF NOT INDICATED ON ARCHITECTURAL ELEVATIONS, REQUEST ELEVATIONS OF DISCONNECT SWITCHES FROM ARCHITECT IN WRITING PRIOR TO ROUGH-IN.

AutoCAD SHX Text THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING OUTLET BOX INSTALLATION WITH WALL FINISH (GYPSUM FURRING, TILE, ETC). THE CONTRACTOR SHALL PROVIDE AND INSTALL ANY EXTENSION RINGS NECESSARY TO ACCOMMODATE WALL FINISHES.

AutoCAD SHX Text THE CONTRACTOR SHALL USE CARE WHEN CUTTING OPENINGS FOR OUTLET BOXES IN CMU WALLS. OUTLET BOXES SHALL BE INSTALLED IN CMU WALLS SECURELY WITH EPOXY.

AutoCAD SHX Text PRIOR TO ROUGH-IN FOR ALL LIGHTING SWITCHES, VERIFY ALL DOOR SWINGS WITH ARCHITECTURAL PLANS.

AutoCAD SHX Text FOR EXACT LOCATION OF ALL EXTERIOR LIGHTING FIXTURES MOUNTED ON EXTERIOR OF BUILDING, ARCHITECTURAL ELEVATIONS SHALL GOVERN

AutoCAD SHX Text ALL MOUNTING HEIGHT DIMENSIONS ARE TO THE CENTER OF THE OUTLET BOX UNLESS OTHERWISE NOTED.

AutoCAD SHX Text PRIOR TO ROUGH-IN, CONTRACTOR SHALL COORDINATE EXACT LOCATION OF ALL WIRING DEVICE WITH ARCHITECTURAL ELEVATION TO AVOID CONFLICTS WITH CASEWORK, COUNTER TOPS, DOOR SWINGS, ETC. WHERE CONFLICTS OCCURS, CONTRACTOR SHALL CONTACT THE ARCHITECT IN WRITING FOR RESOLUTION.

AutoCAD SHX Text FOR EXACT LOCATION OF EQUIPMENT MOUNTED IN SUSPENDED CEILINGS. SUCH AS LIGHTING FIXTURES, AND SMOKE DETECTORS, SEE ARCHITECTURAL REFLECTED CEILING PLANS. ARCHITECTURAL REFLECTED PLAN SHALL GOVERN FINAL LOCATION.

AutoCAD SHX Text 5.

AutoCAD SHX Text 8.

AutoCAD SHX Text 6.

AutoCAD SHX Text 7.

AutoCAD SHX Text 3.

AutoCAD SHX Text 4.

AutoCAD SHX Text 2.

AutoCAD SHX Text 1.

AutoCAD SHX Text

GENERAL ELECTRICAL NOTES

AutoCAD SHX Text H

AutoCAD SHX Text S

AutoCAD SHX Text V

AutoCAD SHX Text

FIRE ALARM PULL STATION. WALL MOUNT AT 48" A.F.F.

AutoCAD SHX Text

FIRE ALARM SYSTEMS

AutoCAD SHX Text FIRE ALARM STROBE. WALL MOUNT 80" TO BOTTOM OF OUTLET BOX, A.F.F. OR 6" BELOW CEILING IN COMPLIANCE WITH ADA REQUIREMENTS.

AutoCAD SHX Text

FIRE ALARM SMOKE DETECTOR, PHOTOELECTRIC TYPE.

AutoCAD SHX Text

FIRE ALARM HEAT DETECTOR.

AutoCAD SHX Text F

AutoCAD SHX Text S

AutoCAD SHX Text FIRE ALARM SPEAKER/STROBE. MOUNT IN CEILING IN COMPLIANCE WITH ADA REQUIREMENTS.CEILING IN COMPLIANCE WITH ADA REQUIREMENTS.

AutoCAD SHX Text D

AutoCAD SHX Text

FIRE ALARM DUCT SMOKE DETECTOR.

AutoCAD SHX Text S

AutoCAD SHX Text FIRE ALARM SPEAKER. WALL MOUNT 80" A.F.F. TO BOTTOM OF OUTLET BOX, A.F.F. OR 6" BELOW CEILING IN COMPLIANCE WITH ADA REQUIREMENTS.

AutoCAD SHX Text

FIRE ALARM DOOR HOLD OPEN DEVICE

AutoCAD SHX Text H

06/09/23

LEIPER'S FORK DISTRICT FACILITY HVAC REPLACEMENT

0 88 16

SCALE OF FEET

W W E S T S I D E

E N G I N E E R I N G

200 Galleria Pkwy Suite 1150

Atlanta, GA 30339 cesslinger@westside-engineering.com

404-965-1287 tel 404-601-9859 fax

WE # 22486

SHEET

1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com

TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM

Houser Walker Architects

DATE:

TECH. REVIEW:

PKG.

NO.

OF

PARTIAL EXISTING ELECTRICAL RISER DIAGRAM1

EQUIPMENT NAMEPLATE DETAIL3

E2

ELECTRICAL RISER

DIAGRAM AND PANEL

SCHEDULES 11

HWA

AutoCAD SHX Text

208Y/120V, 3ɸ, 4W + G NORMAL PANELBOARD 225 A, MLO, 14000 SCCR FED FROM DH1A-3

AutoCAD SHX Text

EQUIPMENT DESIGNATION

AutoCAD SHX Text

ELECTRICAL CHARACTERISTICS (VOLTAGE, PHASE, NUMBER OF WIRES + GROUND)

AutoCAD SHX Text

POWER SUPPLY SYSTEM (NORMAL, EMERGENCY, STANDBY)

AutoCAD SHX Text EQUIPMENT RATINGS (MAIN RATING, MLO OR MCB [PANELBOARDS, SWITCHBOARDS, AND SWITCH GEAR], FUSED OR UNFUSED [SWITCHES], MINIMUM SCCR)

AutoCAD SHX Text

SOURCE (EQUIPMENT NAME AND FEEDER NUMBER)

AutoCAD SHX Text NAMEPLATE BACKGROUND COLORS SHALL BE BLACK FOR NORMAL POWER SUPPLY SYSTEMS, RED FOR LEGALLY REQUIRED EMERGENCY POWER SUPPLY SYSTEMS, AND YELLOW FOR OPTIONAL STANDBY POWER SUPPLY SYSTEMS.

AutoCAD SHX Text

BH1A

AutoCAD SHX Text T

AutoCAD SHX Text EXISTING PAD MOUNTED UTILITY TRANSFORMER. COORDINATE POTENTIAL UPGRADE WITH POWER COMPANY

AutoCAD SHX Text

EXISTING PANEL 'P2' 225A MLO 208/120V 3PH, 4W

AutoCAD SHX Text

EXISTING 400A-3P ENCLOSED CIRCUIT BREAKER TO REMAIN.

AutoCAD SHX Text

%%UKEY NOTES

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EXISTING SERVICE TROUGH TO REMAIN

AutoCAD SHX Text

AutoCAD SHX Text M

AutoCAD SHX Text

AutoCAD SHX Text

EXISTING GROUND TO REMAIN

AutoCAD SHX Text

EXISTING PANEL 'P1' 225A MLO 208/120V 3PH, 4W

AutoCAD SHX Text

EXISTING PANEL 'L2' 125A MLO 208/120V 3PH, 4W

AutoCAD SHX Text

EXISTING PANEL 'L1' 225A MLO 208/120V 3PH, 4W

AutoCAD SHX Text

EXISTING FEEDERS TO REMAIN

AutoCAD SHX Text EXISTING PANEL TO REMAIN. PROVIDE CIRCUIT BREAKERS AS REQUIRED. CIRCUIT BREAKERS ARE EXISTING, UON. FIELD VERIFY EXACT REQUIREMENTS.

AutoCAD SHX Text

PROVIDE NEW CIRCUIT BREAKER IN EXISTING PANEL TO ACCOMMODATE NEW LOAD.

AutoCAD SHX Text

GENERAL NOTES:

AutoCAD SHX Text

1. ELECTRICAL CONTRACTOR SHALL TRACE ALL CIRCUITS IN EXISTING ELECTRICAL CONTRACTOR SHALL TRACE ALL CIRCUITS IN EXISTING PANELS TO REMAIN AFFECTED BY DEMOLITION. TAG AND TURN OFF ALL UNUSED CIRCUIT BREAKERS AND LABEL AS "SPARE" AND TIGHTEN ALL CONNECTIONS. PROVIDE NEW TYPED DIRECTORY PROTECTED BY PLASTIC AND PLACE IN COVER OF PANELS CONSISTENT WITH NEW CONSTRUCTION.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

UP

BREAK/TRAINING

DIST. RANGER

SHARED OFFICE

MAINTENANCE

STORAGE

TELE-ELEC

WOOD SHOP

FURNACE

VALVE

WASH / LIFT /

SERVICE

WELDING FIRE BAYWAREHOUSE

RANGERS

MEN

WOMEN

CHASE

UP

05/05/23

Contact: Hank Houser

LEIPER'S FORK DISTRICT FACILITY HVAC REPLACEMENT

0 88 16

SCALE OF FEET

W W E S T S I D E

E N G I N E E R I N G

200 Galleria Pkwy Suite 1150

Atlanta, GA 30339 cesslinger@westside-engineering.com

404-965-1287 tel 404-601-9859 fax

WE # 22486

SHEET

1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com

TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM

Houser Walker Architects

DATE:

TECH. REVIEW:

PKG.

NO.

OF

1 LEVEL 1 FLOOR PLAN - ELECTRICAL

E3

FLOOR PLAN -

ELECTRICAL

2 LEVEL 2 FLOOR PLAN - ELECTRICAL

HWA

AutoCAD SHX Text

KEYNOTES:

AutoCAD SHX Text PROVIDE CONNECTION TO OVERHEAD FAN. COORDINATE EXACT CONNECTION REQUIREMENTS WITH MECHANICAL DRAWINGS PRIOR TO ROUGH-IN.

AutoCAD SHX Text

AutoCAD SHX Text PROVIDE CONNECTION FROM CONTROLS TO OVERHEAD FAN ABOVE. COORDINATE EXACT CONNECTION REQUIREMENTS WITH MECHANICAL DRAWINGS PRIOR TO ROUGH-IN.

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text M

AutoCAD SHX Text S

AutoCAD SHX Text M

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text L2-32

AutoCAD SHX Text L2-34

AutoCAD SHX Text

EF-4

AutoCAD SHX Text DISCONNECT EXISTING EXHAUST FAN AND PROVIDE CONNECTION TO NEW EXHAUST FAN INSTALLED. RE-USE EXISTING DISCONNECT SWITCH AND CIRCUITRY TO FURTHEST EXTENT POSSIBLE. EXTEND EXISTING CIRCUITRY AS REQUIRED.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

CU-1

AutoCAD SHX Text

DSSC

AutoCAD SHX Text PROVIDE CONNECTION TO ASSOCIATED CONDENSING UNIT VIA 2#12, 1#12G, 3/4"C. AS RECOMMENDED BY MANUFACTURER.

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

DSSA-1

AutoCAD SHX Text

AutoCAD SHX Text

EF-7 (ON ROOF)

AutoCAD SHX Text S

AutoCAD SHX Text M

AutoCAD SHX Text

WP

AutoCAD SHX Text

MAU-1

AutoCAD SHX Text

30/3/NF

AutoCAD SHX Text

GUH-2

AutoCAD SHX Text

GUH-3

AutoCAD SHX Text

30/2/15AF

AutoCAD SHX Text

30/2/15AF

AutoCAD SHX Text

GUH-4

AutoCAD SHX Text

30/2/20AF

AutoCAD SHX Text P1-26

AutoCAD SHX Text 2#10, 1#10G, 3/4"C.

AutoCAD SHX Text

GUH-1

AutoCAD SHX Text

30/2/NF

AutoCAD SHX Text P1-30

AutoCAD SHX Text

GUH-5

AutoCAD SHX Text

30/2/20AF

AutoCAD SHX Text

GUH-6

AutoCAD SHX Text

30/2/15AF

AutoCAD SHX Text P1-28

AutoCAD SHX Text 2#10, 1#10G, 3/4"C.

AutoCAD SHX Text

DFU-1

AutoCAD SHX Text DISCONNECT EXISTING DUCT FURNACE AND PROVIDE CONNECTION TO NEW DUCT FURNACE INSTALLED. RE-USE EXISTING DISCONNECT SWITCH AND CIRCUITRY TO FURTHEST EXTENT POSSIBLE. EXTEND EXISTING CIRCUITRY AS REQUIRED.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text DISCONNECT EXISTING AIR HANDLING UNIT AND PROVIDE CONNECTION TO NEW AIR HANDLING UNIT INSTALLED. RE-USE EXISTING DISCONNECT SWITCH AND CIRCUITRY TO FURTHEST EXTENT POSSIBLE. EXTEND EXISTING CIRCUITRY AS REQUIRED.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EF-5

AutoCAD SHX Text P1-8,10,12

AutoCAD SHX Text

EF-6

AutoCAD SHX Text S

AutoCAD SHX Text M

AutoCAD SHX Text PROVIDE CONNECTION TO NEAREST AVAILABLE UNSWITCHED 120V-1PH CIRCUIT WITH ADEQUATE CAPACITY.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

DSSA-2

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text DISCONNECT EXISTING DUCT COLLECTOR UNIT AND PROVIDE CONNECTION TO NEW UNIT AS REQUIRED. RE-USE EXISTING CIRCUITRY TO FURTHEST EXTENT POSSIBLE.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EF-3

AutoCAD SHX Text

AutoCAD SHX Text

EF-2

AutoCAD SHX Text

AutoCAD SHX Text

EF-1

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

PROVIDE CONNECTION TO AIR HANDLING UNIT CONTROLS.

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text

AutoCAD SHX Text L2-36

AutoCAD SHX Text

AutoCAD SHX Text

30/2/NF

L2-40,42 3#10, 1#10G, 3/4"C.

05/05/23

LEIPER'S FORK DISTRICT FACILITY HVAC REPLACEMENT

W W E S T S I D E

E N G I N E E R I N G

200 Galleria Pkwy Suite 1150

Atlanta, GA 30339 cesslinger@westside-engineering.com

404-965-1287 tel 404-601-9859 fax

WE # 22486

SHEET

1819 Peachtree Road, NE Suite 102 Atlanta, GA 30309 404.633.4264 houserwalker.com

TITLE OF SHEET DRAWING NO.SUB SHEET NO.DESIGNED:A/E FIRM

Houser Walker Architects

DATE:

TECH. REVIEW:

PKG.

NO.

OF

E4

ELECTRICAL

SPECIFICATIONS

HWA

AutoCAD SHX Text

MISCELLANEOUS:

AutoCAD SHX Text

1. SELECT, SIZE, AND ASSEMBLE FOUNDATIONS, SUPPORTS, AND FASTENERS.

AutoCAD SHX Text

2. FASTENINGS FOR SECURING CONDUIT RUNS, LIGHT APPARATUS.

AutoCAD SHX Text

* TOGGLE BOLTS ON HOLLOW TILE OR CONCRETE BLOCKS

AutoCAD SHX Text

MASONRY.

AutoCAD SHX Text

BY THE OWNER'S REPRESENTATIVE.

AutoCAD SHX Text

PERMANENT NAMEPLATES FOR EQUIPMENT IDENTIFICATION.

AutoCAD SHX Text

REFRIGERATED SPACES OR OUTDOOR AREAS,TO PREVENT CIRCULATION OF AIR.

AutoCAD SHX Text

EACH TYPE PENETRATION.

AutoCAD SHX Text

TELEPHONE SYSTEM ROUGH-IN:

AutoCAD SHX Text

CONDUCTORS, AND MISCELLANEOUS MATERIALS OR DEVICES.

AutoCAD SHX Text

* BOLTS, BEAM CLAMPS, OR DRIVEN OR WELDED STUDS ON STEEL WORK

AutoCAD SHX Text

* STEEL ANCHORS OF THE SELF-DRILLING OR NON-DRILLING TYPES ON SOLID CONCRETE OR

AutoCAD SHX Text

* POWER DRIVEN STUDS MAY BE USED ON STEEL AND SOLID CONCRETE WHERE ACCEPTED

AutoCAD SHX Text

3. MAJOR COMPONENTS OF THE DISTRIBUTION SYSTEM SUCH AS THE PANELBOARD SHALL HAVE

AutoCAD SHX Text

4. SEAL CONDUITS ROUTED BETWEEN SPACES OF DIFFERENT AMBIENT TEMPERATURES, SUCH AS

AutoCAD SHX Text

5. INSTALL RACEWAY OR CABLE, ETC. THAT PENETRATES A FIRE BARRIER, WITH MATERIALS AND

AutoCAD SHX Text METHODS APPROVED FOR APPLICATION BY BUILDING OFFICIALS. IDENTIFY EACH FIRE BARRIER

AutoCAD SHX Text FROM THE ARCHITECTURAL PLANS, AND FOR SECURE APPROVAL OF MATERIALS AND METHODS FOR

AutoCAD SHX Text

1. CONTACT THE TELEPHONE CO., COORDINATE THE WORK TO MAKE THE INSTALLATION READY FOR

AutoCAD SHX Text THE TELEPHONE COMPANY, INCLUDING CABINETS, RACEWAYS AND PULL WIRES, RACEWAY SYSTEM

AutoCAD SHX Text

BOXES, DEDICATED ELECTRICAL BRANCH CIRCUITS AND RECEPTACLES, DEDICATED GROUNDING

AutoCAD SHX Text

2. PROVIDE COMPLETE ENCLOSED RACEWAYS WITH MEASURED PULL CORDS FOR FUTURE USE BY

AutoCAD SHX Text OTHERS. PROVIDE A 3/4" PVC CONDUIT FROM EACH MAIN CABINET OR BACKBOARD LOCATION TO

AutoCAD SHX Text

NEAREST ACCESSIBLE, GROUNDED, METAL COLD WATER PIPE, AND A #6 SOLID COPPER

AutoCAD SHX Text

CONDUCTOR BONDED TO THE WATER PIPE AND COILED FOR USE IN GROUNDING EQUIPMENT.

AutoCAD SHX Text

8. SIZE RACEWAYS TO ACCOMMODATE THE ENCLOSED CONDUCTORS.

AutoCAD SHX Text

AND AT LOW POINTS IN RACEWAY RUNS.

AutoCAD SHX Text

EQUIPMENT.

AutoCAD SHX Text

ROUTE RACEWAYS TO AVOID 'TRAPPING' WHERE PRACTICABLE.

AutoCAD SHX Text

ENCLOSURES AND BOXES:

AutoCAD SHX Text

SURFACE MOUNTED DEVICES.

AutoCAD SHX Text

DEVICES:

AutoCAD SHX Text

2. ENCLOSURES:

AutoCAD SHX Text

NECESSARY TO MEET CU. IN. CAPACITY REQUIRED BY CODE.

AutoCAD SHX Text

FEATURES TO SUIT CODE REQUIREMENTS.

AutoCAD SHX Text

ARROW HART.

AutoCAD SHX Text

ARROW HART.

AutoCAD SHX Text

'COMM. SPEC. GRADE' SERIES, LUTRON OR LITHONIA.

AutoCAD SHX Text

SUBMITTALS:

AutoCAD SHX Text

DISTRIBUTION EQUIPMENT:

AutoCAD SHX Text

* SERVICE & DISTRIBUTION EQUIPMENT

AutoCAD SHX Text

* PROTECTIVE DEVICES

AutoCAD SHX Text

* LIGHTING FIXTURES AND LAMPS

AutoCAD SHX Text

* WIRING DEVICES AND COVER PLATES

AutoCAD SHX Text

SIEMENS-ALLIS ITE PRODUCTS, EATON/CUTLER HAMMER.

AutoCAD SHX Text

'SQUARE D' I-LINE DEVICES.

AutoCAD SHX Text

CIRCUIT DIRECTORY CARD USING A TYPEWRITER.

AutoCAD SHX Text

'NEMA-3R' ENCLOSED TYPE WITH LOCKING HASP.

AutoCAD SHX Text

SIDE OF THE CABINET.

AutoCAD SHX Text

CONDUCTORS:

AutoCAD SHX Text

VAC OR 600VAC AS FOLLOWS:

AutoCAD SHX Text

INCANDESCENT LIGHTING.

AutoCAD SHX Text

1. SUBMIT SHOP DRAWINGS & PRODUCT INFORMATION FOR THE FOLLOWING:

AutoCAD SHX Text

1. DISTRIBUTION EQUIPMENT; RATED FOR 240 OR 600 VAC, 60 HZ, FAULT CURRENT INTERRUPTING

AutoCAD SHX Text CAPACITY AS INDICATED, IN AMPERES, RMS, SYMMETRICAL, BUT NOT LESS THAN 10,000 AMPS, WITH

AutoCAD SHX Text SOLID NEUTRAL GROUND (S/N); ABB/GENERAL ELECTRIC (ABB-G.E.), SCHNEIDER ELECTRIC/SQUARE-D, AutoCAD SHX Text

2. DISTRIBUTION EQUIPMENT USING CIRCUIT BREAKER TYPE PROTECTIVE DEVICES; BOLTED-ON OR

AutoCAD SHX Text

3. PANELBOARDS; FACTORY ASSEMBLED, MINIMUM WIDTH OF 20 INCHES, A MINIMUM DEPTH OF 5-3/4

AutoCAD SHX Text INCHES, AND MINIMUM MAINS RATED 100 AMPERES, WITH POLE 'SPACES'; BUSSED AND READY FOR

AutoCAD SHX Text INSTALLATION OF PROTECTIVE DEVICES. CABINETS; FULL SIZED SINGLE DOORS WITH CHROMIUM

AutoCAD SHX Text PLATED COMBINATION CYLINDER LOCK AND CATCH AND TWO KEYS. "ABB/GENERAL ELECTRIC" OR

AutoCAD SHX Text EQUAL: TYPE "NLAB" W/ Q-LINE BRANCH CIRCUIT BREAKERS; TYPE "NHB" WITH E-FRAME BREAKERS.

AutoCAD SHX Text

4. PANELBOARD MAINS; COPPER OR ALUMINUM WITH BRANCH CONNECTIONS IN VERTICALLY

AutoCAD SHX Text

DISTRIBUTED CONSECUTIVE PHASE SEQUENCE SUCH THAT ONE OR MULTIPLE POLE BREAKERS

AutoCAD SHX Text

CAN BE MOUNTED IN ANY POSITION. SOLID NEUTRAL BUS; WITH A FEEDER LUG AND WITH A

AutoCAD SHX Text

SEPARATE SET-SCREW TERMINAL FOR EACH BRANCH CIRCUIT POLE.

AutoCAD SHX Text

5. PANELBOARD MOUNTING; TOP OF ENCLOSURE 78 INCHES ABOVE THE FINISHED FLOOR/GRADE, WITH

AutoCAD SHX Text

THE BOTTOM OF THE CABINET NOT CLOSER THAN 6 INCHES TO THE FLOOR/GRADE, PROPERLY

AutoCAD SHX Text

ALIGNED AND SUPPORTED INDEPENDENTLY OF THE CONNECTING RACEWAYS. COMPLETE INSIDE

AutoCAD SHX Text

6. DISCONNECT SWITCHES; 'HEAVY-DUTY' RATED WITH QUICK-MAKE AND QUICK-BREAK MECHANISMS.

AutoCAD SHX Text

PROVIDE GROUND LUGS AND CODE REQUIRED ACCESSORIES. SWITCHES LOCATED OUTSIDE;

AutoCAD SHX Text

7. PROVIDE AN ENCLOSED SWITCH FOR ELECTRICALLY SERVED EQUIPMENT. PROVIDE SWITCHES &

AutoCAD SHX Text

FUSES, INCLUDING HEATER ELEMENTS, RATED PER THE CHARACTERISTICS AND NAMEPLATE

AutoCAD SHX Text

RATINGS OF EQUIPMENT IN ACCORDANCE WITH CODE REQUIREMENTS, MANUFACTURER'S

AutoCAD SHX Text

RECOMMENDATIONS AND CHARTS. PROVIDE SWITCHES WITH CODE REQUIRED ACCESSORIES.

AutoCAD SHX Text

8. FUSED SWITCHES IN BRANCH CIRCUITS; NON-RENEWABLE CARTRIDGE FUSES RATED 250 OR 300

AutoCAD SHX Text

* SIZES 1 - 200 AMPS: DUAL ELEMENT, CURRENT LIMITING FUSES, CLASS 'RK-1', OR 'RK-5', AutoCAD SHX Text

SELECTED TO PROVIDE STARTING AND LIMIT LET-THRU CURRENT.

AutoCAD SHX Text

* OTHER RATINGS, SIZES OR SPECIAL APPLICATIONS AS INDICATED.

AutoCAD SHX Text

9. STATIONARY FRACTIONAL HORSEPOWER MOTORS NOT PROVIDED WITH INTEGRAL MOTOR RUNNING

AutoCAD SHX Text

OVERLOAD PROTECTION, OR INHERENTLY PROTECTED BY DESIGN; SWITCHED BY A FRACTIONAL

AutoCAD SHX Text

HORSEPOWER STARTER PROVIDING SUPPLEMENTARY PROTECTION.

AutoCAD SHX Text

10. STARTERS AND DISCONNECT SWITCHES; ENCLOSED QUICK-MAKE AND QUICK-BREAK MECHANISMS.

AutoCAD SHX Text

11. BRANCH CIRCUIT BREAKERS; MOLDED CASE, AUTOMATIC TRIPPING TYPE, BOLT-ON OR I-LINE

AutoCAD SHX Text

CONSTRUCTION, MINIMUM FRAME SIZE OF 100 AMPS AND A MINIMUM TRIP SIZE OF 15 AMPS,

AutoCAD SHX Text CALIBRATED FOR 40oC. PROVIDE SUITABLE TYPE BREAKERS SERVING HIGH INRUSH CIRCUITS FOR

AutoCAD SHX Text

12. GROUP SINGLE-POLE BREAKERS USED FOR MULTI-WIRE CIRCUITS CONSECUTIVELY ON THE SAME

AutoCAD SHX Text

1. CONDUCTORS; SOFT DRAWN, ANNEALED COPPER WITH CONDUCTIVITY OF NOT LESS THAN 98

AutoCAD SHX Text

LIGHTING:

AutoCAD SHX Text

BY LEVITON, 'COMM. SPEC. GRADE', HUBBELL OR ARROW HART.

AutoCAD SHX Text

DEVICES AND COVER PLATE FINISHES; AS INDICATED BY THE PLANS.

AutoCAD SHX Text

CONTRACT DOCUMENTS. WHERE NO CRI IS SCHEDULE, CRI SHALL BE 80 OR GREATER.

AutoCAD SHX Text

GROUNDING:

AutoCAD SHX Text

GROUNDING PATH TO THE POWER SERVICE DISCONNECT SWITCH.

AutoCAD SHX Text

EXTENT.

AutoCAD SHX Text

CONDUCTORS INDICATED.

AutoCAD SHX Text

TESTING:

AutoCAD SHX Text

THE POINT OF SERVICE ONLY.

AutoCAD SHX Text

OPERATION OF MATERIALS.

AutoCAD SHX Text

'ASTM' STANDARDS.

AutoCAD SHX Text

4. CONDUCTORS;

AutoCAD SHX Text

THE PLANS.

AutoCAD SHX Text

THE SAME ELECTRICAL TERMINAL POSITION

AutoCAD SHX Text VOLTS, WITH 75oC OR 90oC INSULATION AS FOLLOWS:

AutoCAD SHX Text

RACEWAYS:

AutoCAD SHX Text

EXPOSED.

AutoCAD SHX Text

ON GRADE, OF 'THW', 'THWN' OR 'XHHW'.

AutoCAD SHX Text

OR OTHER APPROVED TYPE.

AutoCAD SHX Text

A SUITABLE HIGH TEMPERATURE RATING.

AutoCAD SHX Text

3. RACEWAYS IN ORDINARY LOCATIONS:

AutoCAD SHX Text

ELECTRICAL METALLIC TUBING (EMT) OR MC CABLE.

AutoCAD SHX Text

BE PERMITTED TO BE USED IN NON-ACCESSIBLE AREAS.

AutoCAD SHX Text

B. BRANCH CONDUCTORS RATED FOR:

AutoCAD SHX Text

CONDUIT OR FLEXIBLE METALLIC TUBING.

AutoCAD SHX Text

LOCATION OR FEEDER (OR SUB-FEEDER..

AutoCAD SHX Text

* 1/2-INCH; GENERAL.

AutoCAD SHX Text

MORE THAN (3) CONDUCTORS.

AutoCAD SHX Text

2. CONDUCTOR SIZE NUMBERS; AMERICAN WIRE GAUGE (AWG. SYSTEM, STANDARD TRADE SIZES.

AutoCAD SHX Text

3. CONDUCTORS; COLOR CODED PER…