140P4225Q0053_QnA_0001.pdf
PDF 68 KB Posted
- Attached to
- Annual Fire Protection Inspection and Testing Serv Federal contract opportunity
- Solicitation number
- 140P4225Q0053
About this file
This document is a Questions and Answers (Q&A) file for Solicitation #140P4225Q0053 for COLO Fire Protection Inspection and Testing Services. The solicitation covers fire protection system inspections across multiple locations, including Collections, Hamilton, Cole Digges, Yorktown Visitor Center, Jamestown Maintenance, Neck-o-land, Jamestown Research Center, Jamestown Visitor Center, and Glasshouse. The Q&A reveals that this is a new requirement with no incumbent contractor, and no estimated contract value is available.
Key technical requirements include NICET level III certification for water-based system inspections, as specified in the Statement of Work. The document indicates multiple fire protection systems will be inspected, including intrusion systems, FM200 systems, and various devices such as backflow devices, fire alarms, sprinkler pumps, extinguishers, and emergency lights. Potential bidders are directed to review the Solicitation and Statement of Work for detailed special requirements and system specifications.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P4225Q0053_Amd_0001.pdf | ||
| Sol_140P4225Q0053.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Solicitation #140P4225Q0053 COLO Fire Protection Inspection and Testing Services
Questions and Answers
8/12/25
Q1. Are the previous years’ inspection reports available?
A1. No, previous inspections do not align with the systems involved in this requirement
Q2. Is a system count summary available? Is a breakdown of devices per building available?
A2. No, we do not have system component counts available.
Q3. Are previous inspection reports available for: Fire Alarm, Sprinkler Pumps, Backflows, Extinguishers, and/or Emergency Lights?
A3. No, we do not have system component counts available, however appendix A shows the number of intrusion, FM200, etc. The Statement of Work does outline the types of systems in each building. There are 2 backflow devices at Collections, 2 at Hamilton, 2 at Cole Digges, 3 at Yorktown Visitor Center, 2 at Jamestown Maintenance, 1 at Neck-o-land, 2 at Jamestown Research Center, 2 at Jamestown Visitor Center, and 2 at Glasshouse.
Q4. What special requirements will be required in order to perform the inspections and maintenance?
A4. Please review the Solicitation and Statement of Work.
Q5. Is the project a new requirement or is there an incumbent contractor currently performing these services? If there are incumbent vendor(s), can you provide the contract details?
A5. No, this is a new requirement
Q6. Is an estimated contract value available?
A6. No
Q7. Is NICET level III mandatory for inspection and testing of water-based systems?
A7. Yes, NICET level III is required where stated in the Statement of Work and Solicitation.
File details come from the government source that posted it. Updated .