This document is a Chilled Water Distribution Schematic drawing for Independence National Historical Park in Philadelphia, Pennsylvania. The detailed engineering schematic shows the layout of chilled water piping infrastructure across multiple city blocks, including specific locations like the Liberty Bell Center, Independence Hall, Second Bank, Chemical Heritage Museum, and Merchants' Exchange. The drawing includes multiple manholes (numbered #2-#17), pipe sizes, and directional indicators for 4", 6", and 8" chilled water lines. Notes on the drawing provide additional technical guidance, such as referencing future piping details, chilled water flow rates, and instructions for connecting to existing building controllers and infrastructure.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Questions_and_Answers_0003.docx | DOCX document | |
| Sol_140P4225Q0038_Amd_0003.pdf | ||
| Sol_140P4225Q0038_Amd_0002.pdf | ||
| Manhole_Photos_0002.pdf | ||
| Sol_140P4225Q0038_Amd_0001.pdf | ||
| Questions_and_Answers_0001.docx | DOCX document | |
| Wage_Determination_WD_15-4233_Rev_33.pdf | ||
| Sol_140P4225Q0038.pdf | ||
| Price_Schedule.docx | DOCX document | |
| PWS_-_CW_Loop_Piping_Video-UT_Inspection_R1.doc | DOC document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AutoCAD SHX Text
CONGRESS HALL
AutoCAD SHX Text
INDEPENDENCE HALL
AutoCAD SHX Text
OLD CITY HALL
AutoCAD SHX Text
APS MUSEUM
AutoCAD SHX Text
EAST WING
AutoCAD SHX Text
WEST WING
AutoCAD SHX Text
MANHOLE #17
AutoCAD SHX Text
MANHOLE #16
AutoCAD SHX Text
6" CHWS/R
AutoCAD SHX Text
SECOND BANK
AutoCAD SHX Text
4" CHWS/R
AutoCAD SHX Text
MANHOLE #13
AutoCAD SHX Text
6" CHWS/R
AutoCAD SHX Text #343
AutoCAD SHX Text #341
AutoCAD SHX Text #339
AutoCAD SHX Text #325
AutoCAD SHX Text #315
AutoCAD SHX Text #313
AutoCAD SHX Text #311
AutoCAD SHX Text
309-325 WALNUT ST HOUSES
AutoCAD SHX Text
6" CHWS/R
AutoCAD SHX Text
2" CHWS/R
AutoCAD SHX Text
MANHOLE #10
AutoCAD SHX Text
8" CHWS/R
AutoCAD SHX Text
MANHOLE #11
AutoCAD SHX Text
4" CHWS/R
AutoCAD SHX Text
MANHOLE #12
AutoCAD SHX Text
NEW HALL
AutoCAD SHX Text
CHEMICAL HERITAGE FOUNDATION 315
AutoCAD SHX Text
MANHOLE #7
AutoCAD SHX Text
MANHOLE #8
AutoCAD SHX Text
MANHOLE #9
AutoCAD SHX Text
6" CHWS/R
AutoCAD SHX Text
6" CHWS/R
AutoCAD SHX Text
CARPENTER'S HALL
AutoCAD SHX Text
FIRST BANK
AutoCAD SHX Text
2" CHWS/R
AutoCAD SHX Text
MANHOLE #6
AutoCAD SHX Text
MANHOLE #5
AutoCAD SHX Text
MERCHANT'S EXCHANGE
AutoCAD SHX Text
CITY TAVERN
AutoCAD SHX Text
CENTRAL CHILLER PLANT BUILDING
AutoCAD SHX Text
MANHOLE #2
AutoCAD SHX Text
MANHOLE #1
AutoCAD SHX Text
MANHOLE #3
AutoCAD SHX Text
8" CHWS
AutoCAD SHX Text
3" CHWS/R
AutoCAD SHX Text
4" CHWS/R
AutoCAD SHX Text
8" CHWS/R
AutoCAD SHX Text
WALNUT STREET
AutoCAD SHX Text
CHESTNUT STREET
AutoCAD SHX Text
S 6TH STREET
AutoCAD SHX Text
S 5TH STREET
AutoCAD SHX Text
S 4TH STREET
AutoCAD SHX Text
S 3RD STREET
AutoCAD SHX Text
6" CHWS/R
AutoCAD SHX Text
6" CHWS/R
AutoCAD SHX Text
FRANKLIN COURT MUSEUM
AutoCAD SHX Text
LIBERTY BELL CENTER
AutoCAD SHX Text 4" CHWS / CHWR (Approx 330')
AutoCAD SHX Text
TONS
AutoCAD SHX Text
GPM
AutoCAD SHX Text 112.5
AutoCAD SHX Text
AutoCAD SHX Text
TONS
AutoCAD SHX Text
GPM
AutoCAD SHX Text 182.5
AutoCAD SHX Text
AutoCAD SHX Text
LIBRARY OF AMERICAN PHILOSOPHICAL SOCIETY
AutoCAD SHX Text
TONS
AutoCAD SHX Text
GPM
AutoCAD SHX Text 70.0
AutoCAD SHX Text
AutoCAD SHX Text
TONS
AutoCAD SHX Text
GPM
AutoCAD SHX Text 0.0
AutoCAD SHX Text 0.0
AutoCAD SHX Text
SERVICE CAPPED
AutoCAD SHX Text
TONS
AutoCAD SHX Text
GPM
AutoCAD SHX Text 0.0
AutoCAD SHX Text 0.0
AutoCAD SHX Text
PEMBERTON HOUSE
AutoCAD SHX Text
TONS
AutoCAD SHX Text
GPM
AutoCAD SHX Text 46.0
AutoCAD SHX Text 59.0
AutoCAD SHX Text
MARKET STREET HOUSES
AutoCAD SHX Text #309
AutoCAD SHX Text
TONS
AutoCAD SHX Text
GPM
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
TONS
AutoCAD SHX Text
GPM
AutoCAD SHX Text 91.5
AutoCAD SHX Text
AutoCAD SHX Text
TONS
AutoCAD SHX Text
GPM
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CURRENT
AutoCAD SHX Text
3" CHWS/R
AutoCAD SHX Text
TONS
AutoCAD SHX Text
GPM
AutoCAD SHX Text 50.0
AutoCAD SHX Text 63.0
AutoCAD SHX Text
8" CHWR
AutoCAD SHX Text
OLD VISITOR CENTER BEING "DEMOLISHED" (NIC)
AutoCAD SHX Text
TONS
AutoCAD SHX Text
GPM
AutoCAD SHX Text 10.0
AutoCAD SHX Text
AutoCAD SHX Text
3" CHWS/R
AutoCAD SHX Text
TONS
AutoCAD SHX Text
GPM
AutoCAD SHX Text 25.0
AutoCAD SHX Text 32.0
AutoCAD SHX Text
TONS
AutoCAD SHX Text
GPM
AutoCAD SHX Text 78.0
AutoCAD SHX Text 99.0
AutoCAD SHX Text
6" CHWS/R
AutoCAD SHX Text
6" CHWS/R
AutoCAD SHX Text
8" CHWS/R
AutoCAD SHX Text
8" CHWS/R
AutoCAD SHX Text
MANHOLE #4
AutoCAD SHX Text
8" CHWS/R
AutoCAD SHX Text
3" CHWS/R
AutoCAD SHX Text
AutoCAD SHX Text
TONS
AutoCAD SHX Text
GPM
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DPT-3, 3-WAY VALVE NEED 2-WAY
AutoCAD SHX Text
DPT-4 5' DIFFERENTIAL PRESSURE
AutoCAD SHX Text
DPT-7
AutoCAD SHX Text
DPT-5,8
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
AutoCAD SHX Text
CHILLED WATER
AutoCAD SHX Text
DISTRIBUTION SCHEMATIC
AutoCAD SHX Text
AutoCAD SHX Text 113190A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
R.KAUL
AutoCAD SHX Text
E.WHITE
AutoCAD SHX Text
D.KAHN
AutoCAD SHX Text 06-28-13
AutoCAD SHX Text
INDEPENDENCE HALL NATIONAL PARK
AutoCAD SHX Text
CENTRAL CHILLER PLANT UPGRADES
AutoCAD SHX Text 186711
AutoCAD SHX Text M2.00
AutoCAD SHX Text 6/20/13 10:42 EWHITE R18 H:\JOBS18\18683\INDE\180619\DRAWINGS\MECH\M200 CHILLED WTR DISTR.DWG
AutoCAD SHX Text
KEY NOTES
AutoCAD SHX Text
1. SEE SHEET M1.01 FOR THE PROJECTED FUTURE CHILLED WATER FLOW RATES. 2. THE CHILLED WATER FLOW RATES SHOWN ARE BASED ON A CWS TEMPERATURE OF 39 DEG. F AND A CWR TEMP OF 58 DEG. F. 3. SEE SPECIFICATIONS 230913 FOR DPT PIPING DETAIL.
AutoCAD SHX Text
SHEET NOTES
AutoCAD SHX Text
AutoCAD SHX Text
%%UCHILLED WATER DISTRIBUTION SCHEMATIC
AutoCAD SHX Text M2.00
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text PROVIDE NEW DIFF. PRESS. TRANSMITTER DPT-3 AND CONNECT TO EXISTING CONTROLLER IN THE BUILDING. PROVIDE NEW DIFF. PRESS TRANSMITTER DPT-4 AND CONNECT TO EXISTING CONTROLLER IN THE BUILDING. PROVIDE NEW DIFF PRESS TRANSMITTER DPT-5 & DPT-8 AND CONNECT TO EXISTING CONTROLLER IN THE BUILDING. PROVIDE NEW DIFF PRESS TRANSMITTER DPT-7 AND CONNECT TO EXISTING CONTROLLER IN THE BUILDING.