This document is an amendment to a solicitation (140P1524Q0069) for SCADA System Maintenance at Lees Ferry, Glen Canyon National Recreation Area (GLCA). The purpose of the amendment is to post responses to questions received and confirm that the hour and date for receipt of offers remains the same.

The solicitation is an emergency requirement with no period of performance currently listed. Offerors must include a service date with their quote. The SCADA system uses Allen Bradley CompactLogix PLCs, FactoryTalk View Site Edition software, and a redundant pair of HMI systems consisting of a Windows 7 PC and a graphical interface panel. The government has access to system drawings, O&M manuals, and backup/documented PLC and HMI code. Any required parts or components would be procured under the contract.

View the file

Other files for this federal contract opportunity

Other files attached to GLCA SCADA System Maintenance, newest first.
File Type Posted
Sol_140P1524Q0069.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

(x)

140P1524Q0069 x x copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted ; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGEMENT TO BE

RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR

OFFER. If by virtue of this amendment you desire to change an offer already submitted , such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

x

PIA

Flagstaff AZ 86001-2694 1824 S Thompson St, Ste 200 NPS, IMR - Arizona MABO

07/25/20240001

13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS. IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

12. ACCOUNTING AND APPROPRIATION DATA (If required) is not extended.is extended, Items 8 and 15, and returning

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended , by one of the following methods: (a) By completing

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

FACILITY CODE CODE

10B. DATED (SEE ITEM 13)

10A. MODIFICATION OF CONTRACT/ORDER NO.

9B. DATED (SEE ITEM 11)

9A. AMENDMENT OF SOLICITATION NO.

CODE

8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)

7. ADMINISTERED BY (If other than Item 6)CODE 6. ISSUED BY

PAGE OF PAGES

4. REQUISITION/PURCHASE REQ. NO.3. EFFECTIVE DATE2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO. (If applicable)

1. CONTRACT ID CODE

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

07/17/2024

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority) appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

E. IMPORTANT: Contractor is not is required to sign this document and return __________________ copies to the issuing office.

ORDER NO. IN ITEM 10A.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

The purpose of this amendment, 0001, is to:

1. Post responses to questions received

2. The hour and date for receipt of offers remains the same

This is an emergency requirement. There is no period of performance currently listed.

Offerors must include a service date with their quote.

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)15A. NAME AND TITLE OF SIGNER (Type or print)

15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 15B. CONTRACTOR/OFFEROR 16C. DATE SIGNED

(Signature of person authorized to sign) (Signature of Contracting Officer)

Rebecca Myers

STANDARD FORM 30 (REV. 11/2016)

Prescribed by GSA FAR (48 CFR) 53.243

Previous edition unusable

Except as provided herein, all terms and conditions of the document referenced in Item 9 A or 10A, as heretofore changed, remains unchanged and in full force and effect .

United States Department of the Interior

NATIONAL PARK SERVICE

CONTRACTING OPERATIONS - CENTRAL

1849 C Street NW Washington, DC 20240

General: No other solicitation clauses or dates change with this Amendment.

Contracting Officer: Rebecca Myers, rebecca_myres@nps.gov

Solicitation #: 140P1524Q0069

Amendment #: 01

GLCA SCADA System Maintenance

Questions and Government Responses listed below:

QUESTIONS:

Question # Question Answer/Response

1. What type of HMI software you are using for this

SCADA system ?

Software is A -B Rockwell.

FactoryTalk View Site Edition

2. What is being controlled at the water treatment plant?

Right now, the plant is running half manually (intake pumps, chem -feed, flow pump on contact basin). Then entire plant is supposed to be run by the SCADA software controls at HMI 1 and 2. From the intake pumps to the CL17 machine.

3. Do you happen to know the brand of PLCs and the SCADA/HMI software being used?

Allen Bradley CompactLogix PLCs

HMI-1 Windows 7 on personal

PC

HMI-2 graphical interface (RIO-

200) panel

4. Do you have any drawings/documents/O&M manuals on your current system?

Yes, we have located drawings and o&m manuals.

5. What SCADA software(s) are you using? SCADA FactoryTalk View Site Edition

6. What hardware manufacturer is the SCADA software running on?

Personal PC (Dell), running windows 7

7. When was this system installed originally?

Plant was built and put into operation in 2016, February.

8. Do you have backups/copies of any/all SCADA/PLC/HMI/OIT code?

According to our 100% design Technical Specifications, Yes.

9. Is this code documented in a concise manner (i.e.

english)?

English and assuming yes, a concise manner.

10. Do you have any documentation/drawings for the network?

No

11. What is your policy on outside laptops/hardware entering your facility?

No policy, outside laptops hardware are ok to be brought in.

12. Is there a "maintenance" laptop/computer at the facility to utilize in the event outside hardware can't be used or the software licensing isn't readily available?

Yes

13. Obviously any parts needed can't be determined from your RFP. How will billing be handled in the event there are components that need to be replaced?

The service would fall under the contract and any supplies would be bought via credit card up to our allowable amount for goods.

14. What SCADA/HMI system is it running? GE iFIX?

AVEVA/Wonderware InTouch?

AVEVA/Wonderware System Platform? Ignition?

FactoryTalk View? VTSCADA? Etc

HMI1 is Windows 7 on Personal PC (Dell), HMI2 graphical interface (RIO-200) panel

15. Is this a redundant pair? Or single system?

redundant pair, yes.

16. Is it running on physical machines or virtualized systems such as VMware, HyperV, Nutanix etc?

physical machines.

17. Based on the SOW, when NPS refers to "would not operate correctly," does this mean that the OS and SCADA system loads, but the operations and functions are not as expected? Or does Operating System or SCADA system not run/can't load?

Both.

File details come from the government source that posted it. Updated .