This is a design document and electrical power plan for AV (audiovisual) electrical outlets at a Bureau of Land Management facility in Anchorage, Alaska. The project is titled "CCSC AV Electrical Outlets" and was designed by Design Alaska, with Elizabeth Johnston serving as the design representative. The Bureau of Land Management is the owners' representative and authority having jurisdiction, with Curtis Fortenberry listed as the primary point of contact.

The electrical power plan (E100) details the installation and distribution of power to two main panels serving multiple rooms within the facility. Panel A is a 100-amp, three-phase panel operating at 208Y/120V serving various rooms with receptacles, lighting, heat tape, and equipment loads totaling 25,242 VA of connected load and 70.7 amperes of demand load. Panel B is similarly configured and serves additional spaces including classrooms, storage, and multipurpose rooms with a total connected load of 28,500 VA and 90.5 amperes of demand load. The document includes detailed circuit schedules showing specific load assignments, breaker trip ratings, circuit numbers, and load types (receptacles, lighting, continuous/non-continuous equipment, motors, and spare circuits). Specific notes address installation requirements such as flexible metal conduit routing, surface-mounted panel mounting, paint-to-match finishes, and requirements to verify and update circuit directory information in accordance with NEC 408.4(A). The design is based on NEC 2023 code standards and was issued on June 18, 2024.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CIRCLE

PRUDHOE

FAIRBANKS

BERING

SEA

PACIFIC

ANCHORAGE

HOMER

KODIAK

SEWARD

KOTZEBUE

NOME

U N

IT

ED

S

TA

TE

S

R U

S S

I A

NENANA

TANANA

ARCTIC

BAY

WHITEHORSE YT.

HAINES JCT.

OCEAN

CORDOVA

VALDEZ

SITKA

JUNEAU

EAGLE

TOK

GLENNALLEN

POLE

NORTH DAWSON Y.T.

C

AN

AD

A

ST

AT

ES

U

N

IT

ED

CIRCLE

OCEAN

BARROWARCTIC

HAINES

GENERAL SYMBOLS ALASKA MAP VICINITY MAP PROJECT TEAM

ANCHORAGE, ALASKA

CCSC AV ELECTRICAL OUTLETS

BUREAU OF LAND MANAGEMENT

OWNERS REPRESENTATIVE

BUREAU OF LAND MANAGEMENT

POINT OF CONTACT: CURTIS FORTENBERRY

222 UNIVERSITY AVE

FAIRBANKS, AK 99709

907 474-2206 cfortenb@blm.gov

DESIGN REPRESENTATIVE

DESIGN ALASKA

POINT OF CONTACT: ELIZABETH JOHNSTON

601 COLLEGE ROAD

FAIRBANKS, AK 99701

907 452-1241 elizabeth@designalaska.com

PROJECT

LOCATION

SEE DISCIPLINES FOR SPECIFIC SYMBOLS

ELECTRICAL

E100 ELECTRICAL POWER PLAN

NUMBER

NAME

SHEET LOCATION

SCALE

TRUE NORTH

PLAN NORTH

GRID LINE

REVISION

ROOM NAME

ROOM NUMBER

G001

VIEW NAME

1/8"=1'-0"

ROOM

NAME

A

CODE SUMMARY

GOVERNING CODES

NEC 2023

AUTHORITY HAVING JURISDICTION

BUREAU OF LAND MANAGEMENT

GENERAL

T100 GENERAL INFORMATION

6/18/2024 9:56 AM 902401 T-001.DWG6/18/2024 9:56 AM 902401 T-001.DWG

902401

18 JUN 2024

COMM. NUMBER

ISSUE DATE

DESIGNED BY

DRAWN BY

1"0" SCALE

601 College Road Fairbanks AK 99701 907.452.1241

Architects SurveyorsEngineers

AECC511 designalaska.com

CCSC AV

ELECTRICAL

OUTLETS

U.S. DEPARTMENT OF THE INTERIOR

BUREAU OF LAND MANAGEMENT

NATIONAL SYSTEM OF PUBLIC LANDS

T100

SEW

ETJ

GENERAL

INFORMATION

6/18/2024 9:55 AM 902401-E100.DWG

902401

18 JUN 2024

COMM. NUMBER

ISSUE DATE

DESIGNED BY

DRAWN BY

1"0" SCALE

601 College Road Fairbanks AK 99701 907.452.1241

Architects SurveyorsEngineers

AECC511 designalaska.com

CCSC AV

ELECTRICAL

OUTLETS

E100

SEW

ETJ

ELECTRIC POWER

PLAN

ROOM 116 PLAN1

E100 1/8" = 1'

ROOM 128 PLAN2

E100 1/8" = 1'

QUAD RECEPTACLE

DUPLEX RECEPTACLE

PANELBOARD: SURFACE MOUNTED

NOTE KEY - INDICATES NOTES APPLICABLE ON EACH SHEET

CONCEALED CONDUIT (NOTE A BELOW)

EXPOSED CONDUIT (NOTE A BELOW)

UNLESS OTHERWISE NOTED

FLEXIBLE CONDUIT

UON

NOTES:

GENERAL: ALL BRANCH CIRCUITS #12 CONDUCTORS IN 3/4" C

MIN. TO 20 AMP CIRCUIT BREAKER (TYPICAL) UON

e.g. A-2,4 (4 #10, 1/2" C.) INDICATES CIRCUIT

NUMBERS 2 AND 4 IN PANEL "A" FEEDS TO EQUIPMENT WITH 4

#10 AWG WIRES RUN IN 1/2" DIA. CONDUIT. SEE NOTE C BELOW.

A. NO. OF WIRES (IF OTHER THAN 2) INDICATED BY NO. OF SLASHES

( = TWO "HOT" WIRES AND TWO NEUTRAL WIRES).

B. HOME-RUN DESIGNATION: "A" = PANELBOARD NOTATION,

"-2,4" = CIRCUIT NUMBERS.

C. INSTALL AN INSULATED EQUIPMENT GROUNDING

CONDUCTOR IN ALL FEEDER AND BRANCH CIRCUIT CONDUITS

SIZED IN ACCORDANCE WITH NEC REQUIREMENTS.

PANEL 'A'

CKT

P TRIP LOAD SERVED LOAD

TYPE

LOAD

(VA)

BU

S

LOAD

(VA)

LOAD

TYPE LOAD SERVED TRIP P CKT

NO.NO.

1 1 20 REC RM 117 R 720 A 360 R NORTH REC FLOOR RM 118 20 1 2

3 1 20 EAST WALL REC RM 117 R 720 B 360 R SOUTH REC FLOOR RM 118 20 1 4

5 1 20 REC RM 117 R 720 C 720 R EAST REC RM 118 20 1 6

7 1 20 (R) EAST REC RM 116 R 1,260 A 540 R WEST REC RM 118 20 1 8

9 1 20 NORTH REC RM 116 R 1,080 B 360 R SOUTH REC FLOOR RM 116 20 1 10

11 1 20 WEST REC RM 116 R 900 C 360 R MID REC FLOOR RM 116 20 1 12

13 1 20 MICROWAVE RM 103 E 400 A 360 R NORTH REC FLOOR RM 116 20 1 14

15 1 20 REFRIGERATOR RM 103 E 1,000 B 720 R REC RM 101 20 1 16

17 1 20 DISPOSAL RM 103 E 1,000 C 720 R REC RM 102, 105 20 1 18

19 1 20 WEST REC RM 103 R 360 A 180 R REC RM 106 20 1 20

21 1 20 EAST REC RM 103 R 360 B 1,000 R REC RM 109 20 1 22

23 1 20 DISHWASHER RM 103 E 1,000 C 900 R REC RM 107, 108 20 1 24

25 1 20 REC RM 104 R 1,080 A 1,536 L LTS RM 111, 114, 115 20 1 26

27 1 20 LTS RM 113 L 256 B 853 L LTS RM 101, 102, 103, 104, 105 20 1 28

29 1 20 (R) REC RM 116 PROJECTOR R 360 C 780 L LIGHTING LARGE FAN ROOM 20 1 30

31 1 20 SPARE S 0 A 0 S SPARE 20 1 32

33 1 20 REC WEST PARKING R 180 B 940 L EXTERIOR EGRESS LTS 20 1 34

35 1 20 LTS RM 116 L 1,237 C 1,920 L ACCESSIBLE PARKING LTS 20 1 36

37 -- -- SPACE S 0 A 0 S SPARE 50 2 38

39 -- -- SPACE S 0 B 0 S " " 40

41 -- -- SPACE S 0 C 0 S SPACE -- -- 42

MAIN: 225 AMPS MLO PHASE A: 6,796 VA 56.6 A CONNECTED: 25,242 VA NOTES:

FED FROM

MDP-3 100A/3P TYPE: 208Y/120 V 3 PH, 4 W. PHASE B: 7,829 VA 65.2 A AMPS: 70.1 A

AIC: 10,000 RMS SYMM. AMPS PHASE C: 10,617 VA 88.4 A VOLTAGE: 208 V

N.E.C. FEEDER CALCULATIONS: (VA) (A) LOAD TYPE:

LIGHTING 9,403 VA 26.1 A L = LIGHTING (LOAD X 125%)

RECEPTACLES 12,160 VA 33.8 A R = RECEPTACLES (NEC 220.44)

EQUIPMENT (CONTINUOUS) 0 VA 0.0 A C = EQUIPMENT (CONTINUOUS) X 125%

EQUIPMENT (NON-CONTINUOUS) 3,400 VA 9.4 A E = EQUIPMENT (NON-CONTINUOUS) X 100%

MOTORS 500 VA 1.4 A M = MOTORS (LOAD + 25% OF LARGEST MOTOR)

TOTAL DEMAND LOAD 25,463 VA 70.7 A F = FEEDERS

MOUNTING SPECIAL REQUIREMENTS: S = SPARE OR SPACE LOCATION

SURFACE SEE SPECIFIC NOTE 4 RM 106

PANEL 'B'

CKT

P TRIP LOAD SERVED LOAD

TYPE

LOAD

(VA)

BU

S

LOAD

(VA)

LOAD

TYPE LOAD SERVED TRIP P CKT

NO.NO.

1 1 20 REC FLOOR RM 128 R 360 A 540 R MULTI-OUT RM 128 20 1 2

3 1 20 HEAT TAPE C 1,920 B 540 R MULTI-OUT RM 128 20 1 4

5 1 20 RM 129 FAN & CURTAIN E 720 C 540 R MULTI-OUT RM 128 20 1 6

7 1 20 MULTI-OUT RM 128 R 720 A 1,920 C HEAT TAPE 20 1 8

9 1 20 REC RM 128 R 540 B 720 R REC RM 127 20 1 10

11 1 20 REC RM 122, 125 R 720 C 720 R REC RM 126 20 1 12

13 1 20 REC RM 123, 124 R 720 A 1,174 L LTS RM 117 20 1 14

15 1 20 LTS RM 120, 121, 124, L 562 B 1,110 L LTS RM 119 20 1 16

17 1 20 LTS 122, 123 , 125 L 912 C 540 L LTS SMALL FAN ROOM 20 1 18

19 1 20 CENTRAL LTS RM 128 L 925 A 789 L LTS RM 126, 127 20 1 20

21 1 20 EAST LTS RM 128 L 1,537 B 360 R REC RM 131 20 1 22

23 1 20 WEST LTS RM 128 L 600 C 555 C LTS RM 118, HEAT TAPE 20 1 24

25 3 20 SPARE S 0 A 1,920 C HEAT TAPE 20 1 26

27 " " S 0 B 180 R (R) REC RM 128 PROJECTOR 20 1 28

29 " " S 0 C 1,664 E RM 123 HAND DRYER 20 2 30

31 2 20 RM 122 HAND DRYER E 1,664 A 1,664 E " " 32

33 " " E 1,664 B 0 S SPACE -- -- 34

35 -- -- SPACE S 0 C 0 S SPACE -- -- 36

37 -- -- SPACE S 0 A 0 S SPACE -- -- 38

39 -- -- SPACE S 0 B 0 S SPACE -- -- 40

41 -- -- SPACE S 0 C 0 S SPACE -- -- 42

MAIN: 225 AMPS MLO PHASE A: 12,396 VA 103.2 A CONNECTED: 28,500 VA NOTES:

FED FROM

MDP-4 100A/3P TYPE: 208Y/120 V 3 PH, 4 W. PHASE B: 9,133 VA 76.1 A AMPS: 79.1 A

AIC: 10,000 RMS SYMM. AMPS PHASE C: 6,971 VA 58.0 A VOLTAGE: 208 V

N.E.C. FEEDER CALCULATIONS: (VA) (A) LOAD TYPE:

LIGHTING 10,186 VA 28.3 A L = LIGHTING (LOAD X 125%)

RECEPTACLES 6,660 VA 18.5 A R = RECEPTACLES (NEC 220.44)

EQUIPMENT (CONTINUOUS) 7,894 VA 21.9 A C = EQUIPMENT (CONTINUOUS) X 125%

EQUIPMENT (NON-CONTINUOUS) 7,376 VA 20.5 A E = EQUIPMENT (NON-CONTINUOUS) X 100%

MOTORS 500 VA 1.4 A M = MOTORS (LOAD + 25% OF LARGEST MOTOR)

TOTAL DEMAND LOAD 32,616 VA 90.5 A F = FEEDERS

MOUNTING SPECIAL REQUIREMENTS: S = SPARE OR SPACE LOCATION

SURFACE SEE SPECIFIC NOTE 4 RM 126

PROVIDE FLEXIBLE METAL CONDUIT TO PANEL 'B'

EXTEND POWER FROM EXISTING RECEPTACLE BELOW, INSTALL ON LEFT OF STUD

(OPPOSITE EXISTING COMM BOX)

ROUTE ALONG EXISTING TRIM OR MULTI-OUTLET ASSEMBLY, PAINT TO MATCH

ADJACENT CEILING OR WALL

PROVIDE TYPED PANEL DIRECTORY. TRACE AND VERIFY CIRCUITS AND UPDATE

"LOAD SERVED" INFORMATION IN ACCORDANCE WITH NEC 408.4(A)

ROOM 116 CONDUIT DETAIL4

E100 NO SCALE

ROOM 116 CONDUIT AND RECEPTACLE DETAIL5

E100 NO SCALE

E100

E100

ROOM 128 RECEPTACLE DETAIL3

E100 NO SCALE

PANEL 'A'

PANEL 'B'

E100

+108"

A-29

B-28

RM

MULTI-PURPOSE

STORAGE

CLASSROOM

STORAGE

CLASSROOM

REVISED(R)

U.S. DEPARTMENT OF THE INTERIOR

BUREAU OF LAND MANAGEMENT

NATIONAL SYSTEM OF PUBLIC LANDS

REG IS T ER ED P R O F E S S IO NA L ENGINEER

Elizabeth T.B. Johnston

No. EE12945 18-Jun-2024 etj Image

Sheets and Views
902401 T-001-Layout1
902401-E100-Layout1
elizabeth@designalaska.com
2024-06-20T08:46:21-0800
Elizabeth T.B. Johnston, PE