B08_140L6326Q0026_-_Attachment_05_-_Drawings_V2_0002.pdf
PDF 2 MB Posted
- Attached to
- CCSC AV RECEPTACLES INSTALL
- Solicitation number
- 140L6326Q0026
About this file
This is a design document and electrical power plan for AV (audiovisual) electrical outlets at a Bureau of Land Management facility in Anchorage, Alaska. The project is titled "CCSC AV Electrical Outlets" and was designed by Design Alaska, with Elizabeth Johnston serving as the design representative. The Bureau of Land Management is the owners' representative and authority having jurisdiction, with Curtis Fortenberry listed as the primary point of contact.
The electrical power plan (E100) details the installation and distribution of power to two main panels serving multiple rooms within the facility. Panel A is a 100-amp, three-phase panel operating at 208Y/120V serving various rooms with receptacles, lighting, heat tape, and equipment loads totaling 25,242 VA of connected load and 70.7 amperes of demand load. Panel B is similarly configured and serves additional spaces including classrooms, storage, and multipurpose rooms with a total connected load of 28,500 VA and 90.5 amperes of demand load. The document includes detailed circuit schedules showing specific load assignments, breaker trip ratings, circuit numbers, and load types (receptacles, lighting, continuous/non-continuous equipment, motors, and spare circuits). Specific notes address installation requirements such as flexible metal conduit routing, surface-mounted panel mounting, paint-to-match finishes, and requirements to verify and update circuit directory information in accordance with NEC 408.4(A). The design is based on NEC 2023 code standards and was issued on June 18, 2024.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CIRCLE
PRUDHOE
FAIRBANKS
BERING
SEA
PACIFIC
ANCHORAGE
HOMER
KODIAK
SEWARD
KOTZEBUE
NOME
U N
IT
ED
S
TA
TE
S
R U
S S
I A
NENANA
TANANA
ARCTIC
BAY
WHITEHORSE YT.
HAINES JCT.
OCEAN
CORDOVA
VALDEZ
SITKA
JUNEAU
EAGLE
TOK
GLENNALLEN
POLE
NORTH DAWSON Y.T.
C
AN
AD
A
ST
AT
ES
U
N
IT
ED
CIRCLE
OCEAN
BARROWARCTIC
HAINES
GENERAL SYMBOLS ALASKA MAP VICINITY MAP PROJECT TEAM
ANCHORAGE, ALASKA
CCSC AV ELECTRICAL OUTLETS
BUREAU OF LAND MANAGEMENT
OWNERS REPRESENTATIVE
BUREAU OF LAND MANAGEMENT
POINT OF CONTACT: CURTIS FORTENBERRY
222 UNIVERSITY AVE
FAIRBANKS, AK 99709
907 474-2206 cfortenb@blm.gov
DESIGN REPRESENTATIVE
DESIGN ALASKA
POINT OF CONTACT: ELIZABETH JOHNSTON
601 COLLEGE ROAD
FAIRBANKS, AK 99701
907 452-1241 elizabeth@designalaska.com
PROJECT
LOCATION
SEE DISCIPLINES FOR SPECIFIC SYMBOLS
ELECTRICAL
E100 ELECTRICAL POWER PLAN
NUMBER
NAME
SHEET LOCATION
SCALE
TRUE NORTH
PLAN NORTH
GRID LINE
REVISION
ROOM NAME
ROOM NUMBER
G001
VIEW NAME
1/8"=1'-0"
ROOM
NAME
A
CODE SUMMARY
GOVERNING CODES
NEC 2023
AUTHORITY HAVING JURISDICTION
BUREAU OF LAND MANAGEMENT
GENERAL
T100 GENERAL INFORMATION
6/18/2024 9:56 AM 902401 T-001.DWG6/18/2024 9:56 AM 902401 T-001.DWG
902401
18 JUN 2024
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
CCSC AV
ELECTRICAL
OUTLETS
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
T100
SEW
ETJ
GENERAL
INFORMATION
6/18/2024 9:55 AM 902401-E100.DWG
902401
18 JUN 2024
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
CCSC AV
ELECTRICAL
OUTLETS
E100
SEW
ETJ
ELECTRIC POWER
PLAN
ROOM 116 PLAN1
E100 1/8" = 1'
ROOM 128 PLAN2
E100 1/8" = 1'
QUAD RECEPTACLE
DUPLEX RECEPTACLE
PANELBOARD: SURFACE MOUNTED
NOTE KEY - INDICATES NOTES APPLICABLE ON EACH SHEET
CONCEALED CONDUIT (NOTE A BELOW)
EXPOSED CONDUIT (NOTE A BELOW)
UNLESS OTHERWISE NOTED
FLEXIBLE CONDUIT
UON
NOTES:
GENERAL: ALL BRANCH CIRCUITS #12 CONDUCTORS IN 3/4" C
MIN. TO 20 AMP CIRCUIT BREAKER (TYPICAL) UON
e.g. A-2,4 (4 #10, 1/2" C.) INDICATES CIRCUIT
NUMBERS 2 AND 4 IN PANEL "A" FEEDS TO EQUIPMENT WITH 4
#10 AWG WIRES RUN IN 1/2" DIA. CONDUIT. SEE NOTE C BELOW.
A. NO. OF WIRES (IF OTHER THAN 2) INDICATED BY NO. OF SLASHES
( = TWO "HOT" WIRES AND TWO NEUTRAL WIRES).
B. HOME-RUN DESIGNATION: "A" = PANELBOARD NOTATION,
"-2,4" = CIRCUIT NUMBERS.
C. INSTALL AN INSULATED EQUIPMENT GROUNDING
CONDUCTOR IN ALL FEEDER AND BRANCH CIRCUIT CONDUITS
SIZED IN ACCORDANCE WITH NEC REQUIREMENTS.
PANEL 'A'
CKT
P TRIP LOAD SERVED LOAD
TYPE
LOAD
(VA)
BU
S
LOAD
(VA)
LOAD
TYPE LOAD SERVED TRIP P CKT
NO.NO.
1 1 20 REC RM 117 R 720 A 360 R NORTH REC FLOOR RM 118 20 1 2
3 1 20 EAST WALL REC RM 117 R 720 B 360 R SOUTH REC FLOOR RM 118 20 1 4
5 1 20 REC RM 117 R 720 C 720 R EAST REC RM 118 20 1 6
7 1 20 (R) EAST REC RM 116 R 1,260 A 540 R WEST REC RM 118 20 1 8
9 1 20 NORTH REC RM 116 R 1,080 B 360 R SOUTH REC FLOOR RM 116 20 1 10
11 1 20 WEST REC RM 116 R 900 C 360 R MID REC FLOOR RM 116 20 1 12
13 1 20 MICROWAVE RM 103 E 400 A 360 R NORTH REC FLOOR RM 116 20 1 14
15 1 20 REFRIGERATOR RM 103 E 1,000 B 720 R REC RM 101 20 1 16
17 1 20 DISPOSAL RM 103 E 1,000 C 720 R REC RM 102, 105 20 1 18
19 1 20 WEST REC RM 103 R 360 A 180 R REC RM 106 20 1 20
21 1 20 EAST REC RM 103 R 360 B 1,000 R REC RM 109 20 1 22
23 1 20 DISHWASHER RM 103 E 1,000 C 900 R REC RM 107, 108 20 1 24
25 1 20 REC RM 104 R 1,080 A 1,536 L LTS RM 111, 114, 115 20 1 26
27 1 20 LTS RM 113 L 256 B 853 L LTS RM 101, 102, 103, 104, 105 20 1 28
29 1 20 (R) REC RM 116 PROJECTOR R 360 C 780 L LIGHTING LARGE FAN ROOM 20 1 30
31 1 20 SPARE S 0 A 0 S SPARE 20 1 32
33 1 20 REC WEST PARKING R 180 B 940 L EXTERIOR EGRESS LTS 20 1 34
35 1 20 LTS RM 116 L 1,237 C 1,920 L ACCESSIBLE PARKING LTS 20 1 36
37 -- -- SPACE S 0 A 0 S SPARE 50 2 38
39 -- -- SPACE S 0 B 0 S " " 40
41 -- -- SPACE S 0 C 0 S SPACE -- -- 42
MAIN: 225 AMPS MLO PHASE A: 6,796 VA 56.6 A CONNECTED: 25,242 VA NOTES:
FED FROM
MDP-3 100A/3P TYPE: 208Y/120 V 3 PH, 4 W. PHASE B: 7,829 VA 65.2 A AMPS: 70.1 A
AIC: 10,000 RMS SYMM. AMPS PHASE C: 10,617 VA 88.4 A VOLTAGE: 208 V
N.E.C. FEEDER CALCULATIONS: (VA) (A) LOAD TYPE:
LIGHTING 9,403 VA 26.1 A L = LIGHTING (LOAD X 125%)
RECEPTACLES 12,160 VA 33.8 A R = RECEPTACLES (NEC 220.44)
EQUIPMENT (CONTINUOUS) 0 VA 0.0 A C = EQUIPMENT (CONTINUOUS) X 125%
EQUIPMENT (NON-CONTINUOUS) 3,400 VA 9.4 A E = EQUIPMENT (NON-CONTINUOUS) X 100%
MOTORS 500 VA 1.4 A M = MOTORS (LOAD + 25% OF LARGEST MOTOR)
TOTAL DEMAND LOAD 25,463 VA 70.7 A F = FEEDERS
MOUNTING SPECIAL REQUIREMENTS: S = SPARE OR SPACE LOCATION
SURFACE SEE SPECIFIC NOTE 4 RM 106
PANEL 'B'
CKT
P TRIP LOAD SERVED LOAD
TYPE
LOAD
(VA)
BU
S
LOAD
(VA)
LOAD
TYPE LOAD SERVED TRIP P CKT
NO.NO.
1 1 20 REC FLOOR RM 128 R 360 A 540 R MULTI-OUT RM 128 20 1 2
3 1 20 HEAT TAPE C 1,920 B 540 R MULTI-OUT RM 128 20 1 4
5 1 20 RM 129 FAN & CURTAIN E 720 C 540 R MULTI-OUT RM 128 20 1 6
7 1 20 MULTI-OUT RM 128 R 720 A 1,920 C HEAT TAPE 20 1 8
9 1 20 REC RM 128 R 540 B 720 R REC RM 127 20 1 10
11 1 20 REC RM 122, 125 R 720 C 720 R REC RM 126 20 1 12
13 1 20 REC RM 123, 124 R 720 A 1,174 L LTS RM 117 20 1 14
15 1 20 LTS RM 120, 121, 124, L 562 B 1,110 L LTS RM 119 20 1 16
17 1 20 LTS 122, 123 , 125 L 912 C 540 L LTS SMALL FAN ROOM 20 1 18
19 1 20 CENTRAL LTS RM 128 L 925 A 789 L LTS RM 126, 127 20 1 20
21 1 20 EAST LTS RM 128 L 1,537 B 360 R REC RM 131 20 1 22
23 1 20 WEST LTS RM 128 L 600 C 555 C LTS RM 118, HEAT TAPE 20 1 24
25 3 20 SPARE S 0 A 1,920 C HEAT TAPE 20 1 26
27 " " S 0 B 180 R (R) REC RM 128 PROJECTOR 20 1 28
29 " " S 0 C 1,664 E RM 123 HAND DRYER 20 2 30
31 2 20 RM 122 HAND DRYER E 1,664 A 1,664 E " " 32
33 " " E 1,664 B 0 S SPACE -- -- 34
35 -- -- SPACE S 0 C 0 S SPACE -- -- 36
37 -- -- SPACE S 0 A 0 S SPACE -- -- 38
39 -- -- SPACE S 0 B 0 S SPACE -- -- 40
41 -- -- SPACE S 0 C 0 S SPACE -- -- 42
MAIN: 225 AMPS MLO PHASE A: 12,396 VA 103.2 A CONNECTED: 28,500 VA NOTES:
FED FROM
MDP-4 100A/3P TYPE: 208Y/120 V 3 PH, 4 W. PHASE B: 9,133 VA 76.1 A AMPS: 79.1 A
AIC: 10,000 RMS SYMM. AMPS PHASE C: 6,971 VA 58.0 A VOLTAGE: 208 V
N.E.C. FEEDER CALCULATIONS: (VA) (A) LOAD TYPE:
LIGHTING 10,186 VA 28.3 A L = LIGHTING (LOAD X 125%)
RECEPTACLES 6,660 VA 18.5 A R = RECEPTACLES (NEC 220.44)
EQUIPMENT (CONTINUOUS) 7,894 VA 21.9 A C = EQUIPMENT (CONTINUOUS) X 125%
EQUIPMENT (NON-CONTINUOUS) 7,376 VA 20.5 A E = EQUIPMENT (NON-CONTINUOUS) X 100%
MOTORS 500 VA 1.4 A M = MOTORS (LOAD + 25% OF LARGEST MOTOR)
TOTAL DEMAND LOAD 32,616 VA 90.5 A F = FEEDERS
MOUNTING SPECIAL REQUIREMENTS: S = SPARE OR SPACE LOCATION
SURFACE SEE SPECIFIC NOTE 4 RM 126
PROVIDE FLEXIBLE METAL CONDUIT TO PANEL 'B'
EXTEND POWER FROM EXISTING RECEPTACLE BELOW, INSTALL ON LEFT OF STUD
(OPPOSITE EXISTING COMM BOX)
ROUTE ALONG EXISTING TRIM OR MULTI-OUTLET ASSEMBLY, PAINT TO MATCH
ADJACENT CEILING OR WALL
PROVIDE TYPED PANEL DIRECTORY. TRACE AND VERIFY CIRCUITS AND UPDATE
"LOAD SERVED" INFORMATION IN ACCORDANCE WITH NEC 408.4(A)
ROOM 116 CONDUIT DETAIL4
E100 NO SCALE
ROOM 116 CONDUIT AND RECEPTACLE DETAIL5
E100 NO SCALE
E100
E100
ROOM 128 RECEPTACLE DETAIL3
E100 NO SCALE
PANEL 'A'
PANEL 'B'
E100
+108"
A-29
B-28
RM
MULTI-PURPOSE
STORAGE
CLASSROOM
STORAGE
CLASSROOM
REVISED(R)
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
REG IS T ER ED P R O F E S S IO NA L ENGINEER
Elizabeth T.B. Johnston
No. EE12945 18-Jun-2024 etj Image
| Sheets and Views |
| 902401 T-001-Layout1 |
| 902401-E100-Layout1 |
| elizabeth@designalaska.com | |
| 2024-06-20T08:46:21-0800 | |
| Elizabeth T.B. Johnston, PE | |
| I am the author of this document |
File details come from the government source that posted it. Updated .