140L6221Q0016
AMENDMENT: 0005
QUESTIONS AND ANSWERS
1. Are dimensions interior or exterior?
Exterior
2. How far is the new sub-panel to the new prefabricated storage locker?
From the power pole to the storage locker is approximately 164 feet
3. What type of permits are required for your local jurisdiction?
Follow the National Electrical Codes by a licensed electrician. permits None it is on Government Property.
4. 2.3 States a minimum of 38deg. 2.6 states a minimum of 50 deg. Which is required? Bid Schedule state 1 Each 12,286 BTU Heater.
The heaters have to maintain a minimum of 50 degrees in the winter.
5. States Vertical Sump walls are to be two-hour fire rated. Other sections state four hour.
As per section 2.2 states “Four hour rated fire wall construction for the entire prefabricated storage locker including but not limited to walls, roof, and vertical walls of sump.” The building shall have a four-hour fire rating while the sump have a two hour fire rating. This is correct as the specification state. The building should have two different fire ratings.
6. States 10’ Long on Back Wall but the dimensions are 15’.
The building length must be 15 feet. Section 1.1.1 “Regardless of make, model, or manufacturer the prefabricated storage locker shall, at a minimum meet the following requirement features and requirements.”
7. Teal is a licensed manufacture in California where the buildings are fabricated. Is a copy of the California License acceptable?
What License are you refereeing to? If it is a construction license for building? The building can be manufactured in California.