This document summarizes a pre-bid site inspection tour and question and answer session for a federal contract opportunity to replace the water system at Kelly Island Campground. The Bureau of Land Management is soliciting bids to remove existing water piping west of the main roadway, replace the water line from the well to the pump house, and install new water distribution piping to provide water to RV and tent campsites. Bidders must complete work within 180 days of receiving notice to proceed. The contractor will be responsible for coordinating water shutdowns, conducting chlorine flushes and bacteria testing on sections as work is finished, installing utility marking tape to indicate piping locations, and identifying all subsurface utilities. The pre-bid meeting provided an opportunity for contractors to inspect the site and have their questions answered in order to develop responsive bids for this project to upgrade Kelly Island's water infrastructure by the specified deadline.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Form 1510-56 (December 1985)

UNITED STATES

DEPARTMENT OF THE INTERIOR

BUREAU OF LAND MANAGEMENT

SITE INSPECTION TOUR / PREBID CONFERENCE RECORD

1. Solicitation No. :140L2623R0007 4. Meeting Place: KELLY ISLAND CAMPGROUND (PROJECT LOCATION)

2. Title: KELLY ISLAND WATER SYSTEM REPALCEMENT 5. Conducted by: JERRY BURROWS & NEAL KIRKPATRICK

3. Date and Time: 05/24/2023, 2:00 P.M.

7. Attended By: (Attach Separate Sheet, if Necessary)

Name and Firm Address (include zip code) Phone No.

(include area code)

TRACY SCOTT

IDAHO AGG.

2245 N LANDMARK CIRCLE IDAHO FALLS, ID 83404 208-360-1940

JUSTIN GRIMMETT

ATS WELDING & MECHANICAL

550 W. PACIFIC STREET BLACKFOOT, ID 83221 208-970-6277

BLAKE C FORD

BFC DIVERSIFIED

724 E. 81ST N. IDAHO FALLS, ID 83401 208-520-6429

8. Questions asked and responses given: (Use Reverse if necessary)

Q1: What is the existing well depth?

A1: 320’ total depth.

Q2: Is power to remain?

A2: Yes, power is to remain.

Q3: Are the water lines to be abandoned in place?

A3: Correction to onsite answer. No, Drawing Sheet C102 Demolition Plan – “Remove all existing piping west of the main roadway”.

Q4: Is the water line from the well to the pump house being replaced?

A4: Yes, Drawing Sheet C103 Site Improvement Plan.

Q5: Is the existing pump, well piping and pitless adapter being replaced?

A5: No, Drawing Sheet C104 Camp Host Site Plan, note 11.

Q6: Are any of the buildings being demolished?

A6: None of the buildings are to be demolished.

Q7: Is the water system run as a loop.

A7: Yes, on the East side and No on the West side, refer to Drawing Sheet C103 Site Improvement Plan.

Q8: Will the site remain open to campers during the work?

A8: Yes. Contractor shall coordinate with the Government to shutdown sections of the site for the safety of the public and Contractor/Subcontractors.

Q9: Will chlorine flush and bacteria testing be required on each section as it is completed?

A9: Refer to Specifications Section 331415 – Site Water Distribution Piping 3.10 Cleaning for all cleaning and disinfecting requirements.

Q10: Will water shut off need to be coordinated with camp host site receiving water?

A10: Yes, the Contractor will coordinate with the camp host and Government to shut off the camp host water.

Q11: Are the water lines and hydrants precisely located/detailed/dimensioned with offsets on the drawings?

A11: No. Drawings show general locations. Government will stake hydrant locations prior to start of work.

Q12: Is the water system blown out at the end of the season?

A12: Yes.

Q13: Will air traps and specific section blowout be required?

A13: Refer to Drawing Sheet C103 Site Improvement Plan for all in line water structures/controls.

Q14: Does each hydrant require a shutoff valve or curb stop for isolation?

A14: Refer to Drawing Sheets C103 & C501 Typ. 2 for all in line water controls and hydrant details.

Q15: Is the contractor required to identify all subsurface piping/lines/utilities?

A15: Yes, Drawing Sheet C001 General Note 5.

Q16: Will water be required at the tent sites, or just the RV sites?

A16: Refer to Drawing Sheet C103 Site Improvement Plan for the proposed layout of the new water.

Q17: Will the contractor be required to submit as-built drawings or place locator tape/ribbon, to indicating actual location of new piping?

A17: Refer to Specifications Section 017839 – Project Record Documents for required drawings. Yes, you will need to install utility marking tape, refer to Drawing

Sheet C501 Typ. 1.

Q19: What is the project start date and timeframe.

A19: 180 days from notice to proceed.

Q20: Will any permitting through the State or County be required?

A20: No. Project site is on Federal land and all permitting will be accomplished through the BLM.

Q21: Is power running to each site?

A21: No. Only the camp host site has power.

Q22: Is the return line running adjacent to the road?

A22: Refer to Drawing Sheet C103 Site Improvement Plan for water line locations. Trees are not to be removed.

Q23: Who should we talk to about Davis-Bacon Wages and payment?

A23: Contact the solicitation Contracting Officer for any questions regarding pay.

Q24: Will the new concrete pad and the existing host site pad be connected? Will it be dimensioned or staked?

A24: No, refer to Drawing Sheet C104 Camp Host Site Plan for new concrete pad location and dimensions.

Q25: Is the day-use area concrete slab and shade shelter location precisely located/detailed/dimensioned with offsets on the drawings?

A25: No, the day use shade shelter and slab will be staked by the Government before the start of work.

Q26: Is there a septic leach/drain field to be concerned about?

A26: No. All septic is captured in concrete vaults.

Q27: Will a concrete walkway to the shade shelter be part of the work?

A27: No.

Q28: Is high ground water level expected to interfere with work?

A28: There is a chance of ground water interference.

9. Was a complete site inspection made? Yes No. (If “No,” explain)

-YES

By (Name) Title Date

JERRY BURROWS CIVIL ENGINEER 05/24/2023