This document is a Questions and Answers (Q&A) amendment related to Solicitation 140G0124Q0183 for the removal and replacement of a walk-in cooler at the USGS Eastern Ecological Science Center (EESC) Fish Health Lab (FHL).

The key details are:

  • The contractor will not be responsible for replacing the existing chart recorder, as it will not be used.
  • The installation of an internal ramp inside the new walk-in cooler to accommodate wheeled shelving and carts is acceptable.
  • The USGS does not require an audio/visual alarm system for the walk-in cooler, only temperature monitoring.
  • A 36" x 76" door with a 12" x 12" view window for the walk-in cooler is acceptable, even though the specifications called for a 34" x 76" door.
  • The USGS prefers the outdoor condensing unit to be installed at ground level, rather than on the roof, due to difficulties with roof access and penetration.

View the file

Other files

File Type Posted
Sol_140G0124Q0183_Amd_0002.pdf PDF
B09_Attachment_4_Q___A_Amd_002_0002.docx DOCX document
Sol_140G0124Q0183_Amd_0001.pdf PDF
B08_Attachment_2_WD_WV20240037.pdf PDF
Sol_140G0124Q0183.pdf PDF
B08_Attachment_1_Existing_Site_Conditions.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

140G0124Q0183 Amendment 001 Q&A

1. Regarding the Chart Recorder panel, will the contractor or the USGS staff be responsible for replacing the chart recorder? Does the USGS plan to re-use the chart recorder?

a. Will not be used

2. I am incorporating an Internal ramp inside the new walk-in cooler to allow for wheeled shelving, hand carts, etc. to enter the cooler. Is this acceptable?

a. Yes

3. Does the USGS want an Audio / Visual alarm system for the walk-in cooler?

a. No, just temp reading

4. The specs identify a 34" x 76" door, the minimum dimension for a walk-in cooler door with a 12" x 12" view window is 36" x 76". Would a 36" x 76" door with a view window acceptable?

a. Yes

5. We are proposing to install an air-cooled outdoor condensing unit on the roof of the building or at ground level for the walk-in cooler. This was recommended by the manufacturer. Is there a preference?

a. Roof access is concrete and prefer not to penetrate the roof - access for ground will be difficult also.

File details come from the government source that posted it. Updated .