B08_ATCH_1_STATEMENT_OF_WORK_A-C_updated_4-5-24.pdf

PDF 83 KB Posted

Attached to
Replace A/C with Two 2-ton Split A/Cs IAW SOW Federal contract opportunity
Solicitation number
140G0124Q0131
Issued by
Department of the Interior US Geological Survey Office of Acquisitions and Grants

About this file

This document is a Statement of Work (SOW) for the replacement of the current air conditioner in a server room with two 2-ton split unit air conditioners. The key requirements include:

The contractor shall furnish and install two new 2-ton ductless split computer room air conditioning (CRAC) systems, including condensing units on the roof, evaporator blower units on the wall, refrigerant lines, electrical connections, digital thermostats, and condensate pumps. The existing Liebert A/C unit must be removed and disposed of properly. The work must be completed between 04/21/2024 and 04/30/2024.

This requirement is being competed as a small business set-aside under NAICS code 238220. An RFQ will be issued on or about 04/05/2024 with quotes due by 04/10/2024. The anticipated award date is 04/15/2025. A site visit is scheduled for 04/09/2024. Offerors must be registered in SAM.gov to be eligible for award.

View the file

Other files for this federal contract opportunity

Other files attached to Replace A/C with Two 2-ton Split A/Cs IAW SOW, newest first.
File Type Posted
Sol_140G0124Q0131_Amd_0001.pdf PDF
B08_ATCH_3_WAGE_DET_SCA___2015-4143_REV_26_12-26-23.pdf PDF
Sol_140G0124Q0131.pdf PDF
B08_ATCH_2_SPECIFICATIONS.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Work Statement

Server Room A/C Replacement

Furnish and install new two 2-ton ductless split Computer Room A/C systems.

The systems' condensing units will be installed on the roof of the building on 2 support stands. The systems' evaporator blower units will be installed on the wall of the room. One insulated copper line set will be installed between the two units up through the existing duct chase. Electrical circuits with outdoor disconnects and separate connections between indoor and outdoor units will be provided by the owner's electrical contractor. Each unit will be controlled by one wall mounted digital thermostat.

One condensate pump will be installed on each unit and will expel all condensate to the nearest domestic drain. Each system will include one Low Ambient control on the system for year-round operation. All roof penetrations will be put into pitch boxes and sealed. The units will be started and tested for proper operation

Remove existing Liebert A/C and dispose in accordance with federal, state, and local regulations.

wnru c:b-ef>v.J a.a tv-.e_cle_d M VLUd..a_c{

Urgent need for a new server room ac as our current unit is not currently working unless filled with freon on a regular basis.

The contractor is responsible for getting the new AC units in place on the roof. The USGS does not have the equipment necessary to get the AC unit up there.