B09_Attachment_8_Q_and_A_Amendment_001_0001.docx

DOCX document 17 KB Posted

Attached to
CERC Admin Building (A3) Flume Electrical Upgrade Federal contract opportunity
Solicitation number
140G0122Q0059
Issued by
Department of the Interior US Geological Survey Office of Acquisitions and Grants

View the file

Other files for this federal contract opportunity

Other files attached to CERC Admin Building (A3) Flume Electrical Upgrade, newest first.
File Type Posted
Sol_140G0122Q0059_Amd_0001.pdf PDF
B08_Attachment_5_Form_DI-137_Release_of_Claims.pdf PDF
B08_Attachment_6_Payroll_WH-347.pdf PDF
B08_Attachment_3_WD_MO20210036_dtd_25_Feb_2022.pdf PDF
B08_Attachment_1_SOW_CERC_A3_Flume_Electrical_Upgrade.docx DOCX document
B08_Attachment_7_Statement_and_Acknowledgement_of_Subcontractor_SF1413-13e.pdf PDF
Sol_140G0122Q0059.pdf PDF
B08_Attachment_4_Payment_Bond_SF25A-16d.pdf PDF
B08_Attachment_2_SOW_Pictures.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

140G0122Q0059 Amendment 001 Questions and Answers

1) Is there a One Line diagram?

a. There is not.

2) Have the shutdown days been identified?

a. They have not, just need the correct amount of notice to coordinate the shut-down (5 days)

3) How many days would that be?

a. I do not have the answer to that, it would depend on the contractor. (no more than 24 hrs at a time)

4) Would the contractor be responsible for a generator to ensure all items are still working during the transition?

a. Yes

5) Is the new panel MCB or MLO?

a. MCB

6) Will the new panel require breakers fill?

a. Yes

7) Will the new transformer require primary & secondary voltage?

a. Yes Delta 3 phase 240 main, WYE 3 phase 480 secondary

8) What is the KVA for the transformer?

a. The transformer must support a 200-amp load

9) Will the transformer require a wall mount kit?

a. Yes

10) Can we still set up a site visit to come and view the project details?

a. Contact Corey McClanahan, cmcclanahan@usgs.gov, (573) 875-5399 at least 3 business days prior to the revised closing date for the solicitation.

11) Is an electrical license from another state acceptable?

a. The Office of Statewide Electrical Contractors in Missouri stated that the Missouri state license is an optional license and is not a requirement. Please see Missouri Statue 324.915 for work exempt from statutory requirements. If you do not hold a statewide license, you will need to contact the local political subdivisions (city or county in Missouri) for more information.