This document is a Questions and Answers (Q&A) Amendment 3 for the Bears Bluff NFH Underground Communications Line Replacement project (Solicitation # 140FGA25Q0063). The Q&A provides technical specifications and clarifications for the fiber optic communication line installation, including requirements for duct size (minimum 1.25-inch non-metallic), fiber type (6 strand OM4 multimode), and termination (LC connectors).
Key additional details include a 24-inch minimum burial depth for conduit, with potential deeper installation to avoid underground utilities, and the requirement for handholes within 50 feet of each building. The Fish and Wildlife Service (FWS) will provide the network switches. No specific brand requirements exist for materials, and no permitting is needed since the work is on private property. The document includes four reference images showing the start and end points of the communication line installation, including interior equipment rooms and exterior building views.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140FGA25Q0063_Amd_0003.pdf | ||
| Sol_140FGA25Q0063_Amd_0002.pdf | ||
| Sol_140FGA25Q0063_Amd_0001.pdf | ||
| Provisions___Clauses_Amendment_1_0001.pdf | ||
| Sol_140FGA25Q0063.pdf | ||
| Price_Schedule.pdf | ||
| SOW.pdf | ||
| DOL_Wage_Determination.pdf | ||
| Notice_to_Offerors.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Questions & Answers - Amendment 3
Bears Bluff NFH Replace Underground Communications Line
Solicitation # 140FGA25Q0063 Questions and Answers
1. What is the duct size that they are requiring to be installed?
Response: Minimum size: 1.25-inch.
2. Who is the manufacturer of the fiber that is required?
Response: To be determined by contractor.
3. What is the strand count and type of multimode fiber that is required?
Response: 6 strand OM4.
4. What type of fiber terminations are required? Ex. LC, SC, / APC, UPC, splice cassettes or mechanical connectors?
Response: LC connectors.
5. Conduit Buried depth (24” or more)?
Response: 24-inch minimum, may need to go deeper in some areas to avoid underground water pipes, etc.
6. Do we need to add Handhole for future splicing or termination?
Response: Handholes within 50-ft of each building. Locations to be determined by the representative on site. Contractor may choose to put an additional handhole in middle of run.
7. Material Standard (Conduit, Fiber, Patch cord, Termination Box)– Any Specific brand?
Response: 1.25” (min) non-metallic conduit, OM4 multimode fiber, fiber handoff from tray/termination must be LC configuration, no specific brands.
8. Permitting – It’s private property so do we need to get the permit?
Response: No permitting required.
9. Existing Photos of start and end point to buy the required material?
Response: Images below.
• The first image is the end point inside.
• The second image is the end point outside.
• The third image is the start point inside.
• The fourth image is the start point inside.
10. Will FWS be providing the switches?
Response: Yes.