About this file

This is a Lighting Plan for the Richard S. Bolt Visitor Center, dated November 5, 2025, in Phase NA. The plan provides detailed specifications for the exhibit lighting system to be installed throughout the visitor center.

The lighting design includes 23 eight-foot tracks installed at 10 feet above floor level (AFF), with a total of 120 fixture heads. Each track accommodates 8 fixtures operating at 9 watts per LED fixture, generating 72 watts per 8-foot track and requiring 1 amp per track. Additional components specified include one theatrical projector light (Wavelight WVL-F or equal), one ceiling array of LEDs for the tent canopy, and 8 inset spot lights. The system incorporates ceiling quad boxes to power the light tracks and a wall quad (positioned at 120" AFF) to power lighting in the exhibit ceiling. All exhibit lighting operates on a separate circuit. Lighting in the scenic tent and LED lighting in the exhibit ceiling will be installed by the fabricator. The plan notes that locations and power must be coordinated with the architectural package, and that junction boxes should be positioned at the ceiling with power run from there to the tracks. The document includes overall plan drawings at 3/32" scale and detailed dimensional measurements for track placement and layout throughout the facility.

View the file

Other files

File Type Posted
Past_Performance_Survey.docx DOCX document
B03_-_Service_Contract_Act_WD_2015-4517.pdf PDF
Sol_140FF027Q0028.pdf PDF
B08_-_SOW_-_Ceiling_OutletsV2.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT NAME

Richard S. Bolt Visitor Center 01.03 /Users/davidoberrieth/Desktop/OKEF/2025_11_4-OKEF.vwx

Lighting PlanDATEPHASE

NA 11/5/25

Overall Plan Scale: 3/32" = 1'-0"1

1/ 8"

0 1 2 3 4 FT

lighting in Scenic tent installed by fabricator

1/ 2"

39"

261 5/16"

284 3/8"

311 3/8"

1/

213 1/4"

36"

127 9/16"

146 9/16"

101 7/8"

55 1/4"

9/

/1 6"14

1/

8"

/1 6"

/4

5/

/1

6"

9/

43 1/2"

LED lighting in exhibit ceiling installed by fabricator

1/ 2" wall outlet @ 120" AFF to power lights in exhibit ceiling

Lighting Notes:

23 - 8 foot tracks @ 10 foot AFF

120 - fixture heads

1 - theatrical projector light Wavelight WVL-F or equal

1 - Ceiling array of LED's for Tent Canopy

8 - Inset spot lights ceiling quad boxes to power light tracks

Wall Quad to power Lighting in exhibit ceiling tracks connected

LED

ceiling array

Locations and power to be coordinated with architectural package.

Only exhibit lights shown here.

ALL EXHIBIT LIGHTING ON SEPARATE CIRCUIT

8 fixtures per track @ 9watts per LED fixture 72watts per 8' track = 1 amp per track hmcda Text Box These are all overhead tracks and (1) projector. The junction boxes should be at the ceiling and we will run our power from there to the track.