2__Attachment_1_-_General_Requirement___Specification.pdf
PDF 328 KB Posted
- Attached to
- FWS - MAKAH NFH-HVAC DUCTLESS SYSTEM QTRS 2-4
- Solicitation number
- 140FC326Q0010
About this file
This document is a General Requirement & Specification for the procurement and installation of a ductless mini-split heat pump system. The specification requires contractors to furnish and install a factory-new 37MHRAQ12AA3 Comfort Series Single Zone Mini Split Heat Pump with R454B refrigerant, paired with an indoor unit (model 45MHHAQ12XC3). The system must deliver a nominal cooling and heating capacity of 12,000 BTUs and meet minimum efficiency ratings of 21.40 SEER2, 10.80 EER2, and 9.20 HSPF2. All equipment must be new, unused, current production, and meet or exceed the stated specifications; no substitutions are permitted without prior written government approval.
The specification mandates compliance with federal, state, and local codes including DOE efficiency standards, EPA refrigerant regulations, and the National Electrical Code. The contractor must provide all labor, materials, equipment, and supervision necessary for complete installation, including refrigerant line sets, condensation drain piping, electrical components, and outdoor equipment pads. Systems must operate on 208–230V electrical service, be UL or ETL listed, and include factory-installed safety features such as thermostatic or electronic expansion valves, pressure safety switches, and compressor overload protection. Equipment must include minimum 10-year manufacturer parts and compressor warranties plus 1-year labor warranty. Upon completion, the contractor shall deliver the system in fully operational condition with comprehensive documentation including installation manuals, wiring diagrams, commissioning procedures, warranty certificates, and operations and maintenance manuals, with delivery on an FOB destination basis to the government-specified facility.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sol_140FC326Q0010.pdf | ||
| 1__Statement_of_Work_(SOW)_Makah_National_Fish_Hatchery_(Ductless_HVACs).pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
General Requirement & Specification
Specification – 37MHRAQ12AA3 Comfort Series Single Zone Mini Split Heat
Pump w/R454B Refrigerant Heat Pump (Meet or Exceed)
1. General Requirements The contractor shall furnish all labor, materials, equipment, supervision, and incidentals necessary to provide and install factory-new ductless mini-split heat pump systems in accordance with this specification. All equipment shall be new, unused, and of current production.
All work and materials shall comply with applicable federal, state, and local codes, including but not limited to:
• U.S. Department of Energy (DOE) efficiency standards
• Environmental Protection Agency (EPA) refrigerant regulations
• National Electrical Code (NEC)
• Manufacturer installation requirements
Equipment provided shall meet or exceed the specifications identified herein. No substitutions shall be made without prior written approval from the Government.
2. Equipment Specification (Basis of Design – Meet or Exceed)
Outdoor Unit:
37MHRAQ12AA3 Comfort Series Single-
Zone Ductless Mini-Split Heat Pump
Refrigerant: R454B
Indoor Unit (Air Handler):
Product number 45MHHAQ12XC3
3. Performance Requirements Each ductless heat pump system shall meet or exceed the following minimum performance criteria:
Cooling / Heating Capacity
• Nominal Capacity: 12,000 BTUs
Efficiency Ratings
• Minimum 21.40 SEER2
• Minimum 10.80 EER2
• Minimum 9.20 HSPF2
Warranty
• Minimum 10-Year Manufacturer Parts Warranty
• Minimum 10-Year Compressor Warranty
• Minimum 1-Year Labor Warranty
4. Refrigerant & Environmental Compliance
• Systems shall operate using R454B refrigerant, a non-ozone-depleting refrigerant with reduced global warming potential (GWP).
• All components shall comply with the latest EPA SNAP (Significant New Alternatives
Policy) requirements.
• Systems shall support compliance with future federal refrigerant regulations if applicable.
5. Construction & Durability
• Cabinets shall be constructed of galvanized steel with corrosion-resistant coatings.
• Exterior surfaces shall have powder-coated or baked enamel finishes suitable for harsh environmental conditions.
• Condenser coils shall be copper tube/aluminum fin or microchannel design, protected against physical and environmental damage.
• Units shall include service access panels for compressor, controls, and major components.
6. Controls and Safety Features (Bluetooth Capabilities) Systems shall be equipped with factory-installed safety and control features, including:
• Thermostatic Expansion Valve (TXV) or Electronic Expansion Valve (EEV)
• High- and low-pressure safety switches
• Compressor overload protection
• Standardized wiring terminals
Systems shall be BACnet or Modbus compatible, if required by the Government.
7. Electrical Requirements
• Units shall operate on 208–230V electrical service, model-specific.
• Contractor shall provide all required electrical components, including:
▪ Electrical whip
▪ Disconnects
▪ Required electrical circuits via licensed electrician
• All equipment shall be UL or ETL listed for safety and performance compliance.
8. Installation Materials The contractor shall furnish and install all materials necessary for a complete and functional system, including but not limited to:
• Refrigerant line sets
• Line hide / protective coverings
• PVC condensation drain piping
• Outdoor equipment pads
• Electrical whip and associated wiring
9. Delivery and Documentation
• Equipment shall be delivered FOB destination to the Government-specified facility.
• Contractor shall provide the following documentation upon completion:
• Manufacturer installation manuals
• Electrical wiring diagrams
• Startup and commissioning procedures
• Warranty certificates
• Operations & Maintenance (O&M) manuals
10. Final Condition All systems shall be installed, tested, and left in fully operational condition. The contractor shall demonstrate system operation to the Government or designated tenant representative. Work areas shall be left clean and free of debris.