Questions and Answers (Q&A’s)

12/08/2020

The SOW reads that the contractor shall test run the 40hp pump for proper operation.

1) Can you confirm if a procedure for proper pump operation will be provided and/or what is the contractor to confirm?

Answer: No proper pump operation will be provided. The contractor is to confirm that when the pump is turned on to its operating position no debris from the sump is sucked up into the pump.

2) Can you confirm that the pump can be started and stopped at the building on site?

Answer: Yes, the pump can be started and stopped at the building site.