This document contains questions and answers related to solicitation number 140A2323Q0639 from the Department of the Interior Bureau of Indian Affairs Bureau of Indian Education for a kitchen hood and fire suppression system at the Crazy Horse Indian School. The solicitation is for brand new work requiring the installation of two type I kitchen hoods. Drawings of the work area and information on a recent kitchen floor project can be provided. While fire dampers are not required for the hoods, a structural evaluation of the roof should be included in the curb design. The existing kitchen equipment layout must be maintained.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Questions & Answers for 140A2323Q0639 – Kitchen Hood & Fire Suppression System – Crazy Horse Indian School
Q1: Do you have a drawing for the area we are working in?
A1: Drawings are posted
Q3: We would like to know if this is a brand new contract OR if there is (was) an incumbent performing these services.
If not brand new, could you please provide the current / previous contract number?
A3: This is a brand new contract.
Q4: Can you confirm that this bid is due on Labor Day?
A4: Yes, will extend.
Q5: Will makeup air be included in the design and construction?
A5: No
Q6: Does cooling need to be added to the makeup air unit?
A6: No, cooling will not be added to the makeup air unit.
Q7: Can you end any information on the recent kitchen floor project as we will need to perform patching?
A7: The flooring was provided by Fischers Flooring of Rapid City, DS.
Q8: Are there plans for the school that can be shared?
A8: Yes
Q9: We do not typically see a requirement for fire dampers on exhausts, can you clarify the
SOW?
A9: Fire dampers are not required for kitchen hoods. This requirement will be removed from the
SOW
Q10: The exhaust fans on the roof, is there a structural evaluation that needs done?
A10: Yes, a structural evaluation should be made as part of the roof curb design.
Q11: Is it possible to re-arrange the equipment under the hoods to be (1) type one hood and (1) type 2hood? Cooking/frying on one side and ovens/steamer on the other side?
A11: The cooking staff prefer the existing kitchen equipment arrangement as is. Unfortunately, we will need to install 2 type I hoods to accommodate.