This is a Statement of Work (SOW) for preventive maintenance services on Heating, Ventilation, and Air Conditioning (HVAC) control systems and components at two National Weather Service locations in Vermont.
The work encompasses quarterly preventive maintenance services, supplemented by semi-annual and annual maintenance checks across two sites: the Burlington National Weather Service Weather Forecast Office (1200 Airport Drive, South Burlington, VT) and the Vermont National Guard Base Radar Data Acquisition (RDA) Site at Camp Johnson (30 Mount Mansfield Avenue, Colchester, VT). The contractor must furnish all labor, materials, equipment, and supplies to service and maintain air handlers, electronic duct heaters, condensing units, humidifier systems, heat pumps, variable air volume boxes, dampers, louvers, exhaust fans, control system sensors, transmitters, differential pressure switches, and related components. The HVAC system operates continuously 24/7/365. Contractor technicians must be Liebert manufacturer-qualified and licensed, qualified, and experienced in servicing mechanical and automated environmental control systems. All work and materials must meet or exceed industry standards and equipment manufacturer specifications. Contractor personnel must comply with OSHA requirements, provide Safety Data Sheets for materials upon request, execute lock-out tag-out procedures, sign in/out at facility reception desks, and maintain comprehensive written maintenance records documenting all work performed, pressures, temperatures, voltages, fluid levels, and test results. Site 1 equipment includes four Liebert units (two Model PX029DH1AD09B7 and two Model DSO225A units). Site 2 equipment includes three BARD units. Deficiencies identified during inspections must be corrected within five working days of government notification. The Government Point of Contact will be provided upon contract award.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATEMENT OF WORK
1. PURPOSE
The National Weather Service (NWS) Weather Forecast Office (WFO) located in South Burlington, VT, requires preventive maintenance services for all Heating, Ventilation, and Air Conditioning (HVAC) control system and components.
2. PLACES OF PERFORMANCE
The Contractor shall perform services at the following two (2) locations:
SITE 1: Burlington National Weather Service, Weather Forecast Office Burlington International Airport 1200 Airport Drive South Burlington, Vermont 05403-6028
SITE 2: Vermont National Guard Base, Radar Data Acquisition (RDA) Site Camp Johnson 30 Mount Mansfield Avenue Colchester, Vermont 05446-3012
3. SCOPE OF WORK
The Contractor shall furnish all labor, material, equipment, and incidentals to provide preventive maintenance on HVAC equipment, controls, and components, including air handlers, electronic duct heaters, condensing units, humidifier system, heat pumps, variable air volume (VAV) boxes, dampers and louvers, exhaust fans, control system sensors, transmitters, differential pressure switches, and other components. The HVAC system operates constantly 24/7/365 and preventive maintenance is required to enable HVAC system function, and to mitigate system downtime and additional repair costs. Preventive maintenance services shall be performed on a quarterly basis. In addition, the Contractor shall perform Semi-Annual and Annual Preventive Maintenance Service and checks.
The Contractor shall ensure all HVAC equipment is serviced and maintained including, but not limited to, the following: air handler units, electronic duct heaters, all condensing units, humidifier system, heat pumps, dampers and louvers, all exhaust fans, control system including sensors, transmitters, differential pressure switches and all other components, and package units located in the Radar Data Acquisition (RDA) building and the Transmitter Power Maintenance Shelter (TPMS) building.
The Contractor shall provide parts and materials that are required in the course of providing preventive maintenance services listed in the any specific equipment manufacturers checklists or as listed in the Statement of Work.
The Contractor will have five (5) working days after date of notification by the Government to correct any/all deficiencies.
Service for troubleshooting or diagnosing issues related to emergency or non-scheduled repairs is not covered under this preventive maintenance contract and will be addressed through a separate purchasing process. The Contractor may or may not be contacted to provide any of these services.
4. CONTRACTOR QUALIFICATIONS
The Contractor’s technicians and personnel performing the work on the Liebert HVAC units shall be Liebert manufacturer-qualified.
The Contractor’s technicians and personnel performing the work shall be licensed, qualified, and experienced in repairing and servicing mechanical and automated environmental control systems software and equipment.
The Contractor shall ensure that all work and materials supplied meet or exceed industry standards and equipment manufacturer's specifications.
5. DESCRIPTION OF WORK
The Contractor shall provide preventive maintenance services including all of the tasks in the following checklists.
SITE 1: Burlington National Weather Service, Weather Forecast Office
Checklist: Heat pumps and air conditioner condensing units routine operating inspection and quarterly maintenance � Install gauges and check refrigerant pressures.
� Check and tighten all electrical connections.
� Check bearings and compressor for proper lubrication.
� Check compressor voltage and running amps.
� Check all safety/operating controls; calibrate as necessary.
� Check thermostats; calibrate as necessary.
� Check super heat temperature.
� Check sub cooling temperature.
� Check condition of condenser coils; clean twice per year.
� Check condition of blower wheels and drive belts; re-tension, clean and replace as necessary.
� Check temperature differences across the condenser and evaporator coils.
� Leak-test refrigerant circuits.
� Advise the Government Point of Contact of any deficiencies noted during the above inspections and make recommendations as to the correction of same.
Checklist: Fans and Air Handling Units Quarterly Routine Operating Inspection and Maintenance, except as noted � Check belts and sheaves.
� Inspect and / or tighten all nuts and bolts if needed.
� Check motor mounts and vibration pads; check for excessive vibration or noise. Check motor operating conditions.
� Inspect electrical connections and conductors annually.
� Lubricate and adjust associated dampers, motors and linkage annually.
� Check all fan operations and clean fan blades semi-annually or as needed.
� Inspect condensate drain pans and piping to ensure proper drainage; clean drains and drain pans annually or as needed.
� Change pleated filters quarterly; change bag filters annually or sooner if necessary.
� Check heating and cooling coils.
� Clean external surfaces as required.
� Inspect for leaks.
� Check belts and supply/replace if applicable. Check fan belt tension and adjust as required.
� Lubricate fan and motor bearings per manufacturer's recommendation. Check and tighten locking collars and bolts.
� Inspect operating and safety controls.
� Check motor operating conditions.
� Check coils.
� Check all operating conditions and adjust as required.
� Advise the Government Point of Contact of any deficiencies noted during the above inspections and make recommendations as to the correction of same.
Checklist: Self-Contained Package Units Routine Operating Inspection and Maintenance Semi-annual, except as noted � Check operating controls for proper functioning; calibrate as necessary.
� Check safety controls for proper operation and adjust as necessary.
� Inspect condition of evaporator coils.
� Check condition of unit air filters. Supply and change semi-annually or as needed.
� Inspect fan belts and supply replacements as necessary. Check fan belt tension and adjust as required.
� Check fan motor bearings for proper lubrication per manufacturer's recommendations. Check and tighten locking collar bolts.
� Inspect condensate drain pans and piping to ensure proper drainage; clean annually or as necessary.
� Check compressor oil pressure and level.
� Check compressor amperage draw with ammeter.
� Check compressor motor windings with meg ohm meter annually.
� Install pressure gauges and check refrigerant pressures.
� Inspect refrigerant piping and fittings for leaks.
� In the beginning of the heating season check operation of heating section.
� Advise the Government Point of Contact of any deficiencies noted during the above inspections and make recommendations as to the correction of same.
Checklist: Annual Preventive Maintenance Services � Check vessel connections for leaks.
� Check condenser and receiver relief valves for leaks.
� Check refrigeration systems and piping for problems.
� Calibrate pressure gauges and thermometers.
� Check safety controls for proper settings and operation.
� Check and tighten electrical connections.
� Megger-test compressors to determine integrity of motor windings.
� Change oil filters and clean if applicable / when required.
� Take oil sample for laboratory analysis if applicable / when required.
� Check oil heaters and controls if applicable / when required.
� Remove condenser heads and brush/clean tubes when required.
� Inspect condensers for signs of corrosion.
� Check evaporator coils, clean as required.
� Clean inlet vanes/linkage and inlet guide vane (IGV) ring.
� Verify proper operation of inlet vane assembly.
� Inspect fan motor control.
� Clean condensate pans.
� Tighten set screws on fan assembly locking collar and torque locking collar per manufacturer's specs.
� Advise the Government Point of Contact of any mechanical or electrical discrepancies that would affect unit operation along with recommendations for correction.
Quarterly Inspection, except as noted: Variable Frequency Drive (VFD) Supply Air Handler and Econoflex Adjustable Speed Drive (ASD) Controller � Check belts and sheaves.
� Tighten all nuts and bolts.
� Check fan mounts and vibration pads; check for excessive vibration or noise. Check fan operating conditions.
� Inspect electrical connections and conductors annually.
� Lubricate and adjust associated dampers, fan and linkage annually.
� Check all fan operations.
� Inspect charcoal filters if applicable / when required.
� Supply and change charcoal filters annually or sooner if necessary if applicable / when required.
� Clean external surfaces as required.
� Inspect for leaks.
� Check belts and supply and/or replace as necessary. Check fan belt tension and adjust as required.
� Lubricate fan and motor bearings per manufacturer's recommendation. Check and tighten locking collars and bolts.
� Inspect operating and safety controls.
� Check motor operating conditions.
� Check and clean fan blades as required semi-annually.
� Check all operating conditions and adjust as required.
� Check all operational modes on VFD controller if applicable / when required.
� Inspect electrical connections on VFD controller if applicable / when required.
� Advise the Government Point of Contact of any deficiencies noted during the above inspections and make recommendations as to the correction of same.
Control System Maintenance | Quarterly Preventive Maintenance � Check and adjust all control loops.
� Inspect all controllers and verify proper system operation.
� Verify incoming AC power and note proper voltages, check for transformer degradation and report.
� Ensure all wiring and terminations are secure.
� Check all electronic board seating.
� Check data and power cabling for pinching, cracking, tears or breaks and report unusual conditions.
� Check diagnostic Light Emitting Diodes (LEDs), fuses and surge transient protection devices where applicable. Report unusual conditions.
� Troubleshoot minor operational problems relating to controls with the Government Point of
Contact and make recommendations.
Semi-Annual Preventive Maintenance � Verify power supply voltages and record.
� Ensure proper cabinet grounding.
� Review system performance with the Government Point of Contact and discuss recommendations and/or changes as required.
� Inspect cables, electrical connections, computer and system peripherals and clean computer as required.
� Diagnostic testing; examining, calibrating, adjusting and cleaning of control devices as required.
� Perform quarterly tasks.
� Advise the Government Point of Contact of any deficiencies noted during the above inspections; make recommendations as to the correction of same.
Annual Preventive Maintenance � Check and calibrate sensors as required.
� Review control loops and adjust as necessary.
� Evaluate all input/output points for proper operation and report any deficiencies.
� Inspect interior surfaces and components of the panel enclosures and associated field equipment and clean as required for proper operation.
� Ensure all monitoring devices and plug-in components are securely in place, note any deficiency for review.
� Perform quarterly and semi-annual tasks.
� Meet with the Government Point of Contact to discuss system needs, operational deficiencies and system enhancements.
Additional Requirements | Maintenance Records � The Contractor shall supply and maintain written records of maintenance and repairs on site.
� Note and report any mechanical, electrical or control system discrepancies that would affect equipment operations.
� Document all preventive maintenance work done, all pertinent pressures, temperatures, voltages, fluid levels and test results.
� The report shall contain any uncorrected deficiencies noted at inspection.
Qualifications and Standards � The Contractor’s technicians and personnel tasked with service and repairs shall be licensed, qualified, and skilled to repair and service the specific mechanical and automated environmental control systems software and equipment on site.
� The Contractor shall ensure that all work and materials supplied will meet or exceed industry standards and equipment manufacturer's specifications.
Safety Data Sheets (SDS) � Provide to the Government Point of Contact upon request for supplies and materials used by the Contractor.
Safety | Lock-Out Tag-Out � Advise the Government Point of Contact prior to starting maintenance procedures.
� Disconnect power supply; Tag unit as "Out of Service" as per Occupational Safety and
Health Act (OSHA) requirements.
Health and Safety Regulations The Contractor must comply with all applicable Local, State and Federal laws governing the health and safety of its employees, including all regulations promulgated under the OSHA. Such compliance shall include, but is not be limited to, ensuring that all employees are properly trained for the work to be performed and have been supplied with all necessary protective and safety equipment
Visitor Sign-in The Contractor’s employees/subcontractor must sign in/sign out at the Weather Forecast Office Reception Desk when arriving/leaving.
Maintenance Manuals The Contractor may ask the Government Point of Contact to review a maintenance manual. If maintenance manuals are not available, the Contractor shall contact the equipment manufacturer for their preventive maintenance program requirements and keep a copy for the office.
Codes and Standards The Contractor shall follow and ensure compliance with the latest effective publication or applicable codes and ordinances of local governing agencies and of the following standards, codes, etc., as they apply to the work of this Statement of Work.
� American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHREA) � National Building Code (BOCA) � Factory Mutual Engineering Association (FM) � Underwriters' Laboratories, Inc. (UL) � National Electrical Code (NFPA 70-99), National Electrical Safety Code (ANSI C2) and the NECA Standard of Installation or Local standards, whichever is the more stringent NEC (2002) will be followed, as applicable.
� American Society of Mechanical Engineers (ASME) Air Conditioning and Refrigeration Institute (ARI) Air Movement and Control Association (AMCA) � American Gas Association (AGA) � American National Standards Institute (ANSI) American Society for Testing and Materials (ASTM) Electrical Testing Laboratories (ETL) � International Mechanical Code (IMC) 1996 � Air Movement and Control Association (AMCA) � Contractor shall follow all Federal, State and Local Codes to include Department of Transportation, (OSHA) � Occupational Safety and Health regulations (e.g. 29 CFR 1910, 1926).
� OSHA General Industry Safety and Health Standards (29 CFR 1910); OSHA Construction Industry Standards (29 CFR 1926). (Single copies of these regulations are available from the local OSHA Area Offices and are also sold by the Superintendent of Documents, US.
Government Printing Office, Washington, DC 20402).
� Environmental Protection Agency (EPA) Final Rule (40 CFR, Part 761) dated July 17, 1985.
Materials The Contractor shall provide all parts necessary to complete the preventive maintenance activities specified herein and ensure that the parts are new, of good quality and warrantied according to the manufacturer. Materials requiring a SDS shall be reviewed by the Government Point of Contact prior to usage at least five (5) working days prior to usage. Products found to have certain health hazards to employees shall not be used.
Equipment located at Site 1 - Burlington National Weather Service, Weather Forecast Office, Burlington International Airport
� Liebert Model PX029DH1AD09B7 Serial number: Y22F002765 � Liebert Model DSO225A Serial number: N22DT2A014 � Liebert Model PX029DH1AD09B7 Serial number: Y22F002626 � Liebert Model DSO225A Serial number: N22DT2A024
SITE 2: Vermont National Guard Base, Radar Data Acquisition (RDA) Site, Camp Johnson
Heat Pumps and Air Conditioner (A/C) Condensing Units Quarterly Routine Operating Inspection and Maintenance, Except as Noted � Install gauges and check refrigerant pressures.
� Check and tighten all electrical connections.
� Check bearings and compressor for proper lubrication.
� Check compressor voltage and running amps.
� Check all safety/operating controls; calibrate as necessary.
� Check thermostats; calibrate as necessary.
� Check super heat temperature.
� Check sub cooling temperature.
� Check condition of condenser coils; clean twice per year.
� Check condition of blower wheels and drive belts; re-tension, clean and replace as necessary.
� Check temperature differences across the condenser and evaporator coils.
� Leak test refrigerant circuits.
� Advise the Government Point of Contact of any deficiencies noted during the above inspections; make recommendations as to the correction of same.
Fans and Air Handling Units Quarterly Routine Operating Inspection and Maintenance, except as noted � Check belts and sheaves.
� Tighten all nuts and bolts.
� Check motor mounts and vibration pads; check for excessive vibration or noise. Check motor operating conditions.
� Inspect electrical connections and conductors annually.
� Lubricate and adjust associated dampers, motors and linkage annually.
� Check all fan operations.
� Inspect condensate drain pans and piping to ensure proper drainage; clean drains and drain pans annually or as needed.
� Change pleated filters quarterly; change bag filters (if applicable) annually or sooner if necessary.
� Check heating and cooling coils.
� Clean external surfaces as required.
� Inspect for leaks.
� Check belts and supply/replace as necessary. Check fan belt tension and adjust as required.
� Lubricate fan and motor bearings per manufacturer's recommendation � Check and tighten locking collars and bolts.
� Inspect operating and safety controls.
� Check motor operating conditions.
� Check and clean fan blades as required semi-annually.
� Check coils.
� Check all operating conditions and adjust as required.
� Advise the Government Point of Contact of any deficiencies noted during the above inspections; make recommendations as to the correction of same.
Self-contained Package Units Semi-Annual Routine Operating Inspection and Maintenance, except as noted � Check operating controls for proper functioning; calibrate as necessary.
� Check safety controls for proper operation; adjust as necessary.
� Inspect condition of evaporator coils.
� Check condition of unit air filters. Supply and change as required or semi-annually.
� Inspect fan belts and supply/replace as necessary. Check fan belt tension and adjust as required.
� Check fan motor bearings for proper lubrication per manufacturer's recommendations.
� Check and tighten locking collar bolts.
� Inspect condensate drain pans and piping to ensure proper drainage; clean annually or as necessary.
� Check compressor oil pressure and level if applicable / when required.
� Check compressor amperage draw with ammeter.
� Check compressor motor windings with meg ohm meter annually.
� Install pressure gauges and check refrigerant pressures.
� Inspect refrigerant piping and fittings for leaks.
� In the beginning of the heating season, check operation of heating section.
� Advise the Government Point of Contact of any deficiencies noted during the above inspections; make recommendations as to the correction of same
Annual Preventive Maintenance Service � Check vessel connections for leaks.
� Check condenser and receiver relief valves for leaks.
� Check refrigeration systems and piping for problems.
� Calibrate pressure gauges and thermometers.
� Check safety controls for proper settings and operation.
� Check and tighten electrical connections.
� Check megger compressors to determine integrity of motor windings.
� Change oil filters and clean strainers if applicable / when required.
� Take oil sample for laboratory analysis if applicable / when required.
� Check oil heaters and controls.
� Remove condenser heads and brush/clean tubes when required.
� Inspect condensers for signs of corrosion.
� Check evaporator coils, clean as required.
� Clean inlet vanes/linkage and IGV ring if applicable / when required.
� Verify proper operation of inlet vane assembly if applicable / when required.
� Inspect fan motor control.
� Clean condensate pans.
� Tighten set screws on fan assembly locking collar and torque locking collar per manufacturer's specs if applicable / when required.
� Note and report any mechanical or electrical discrepancies that would affect unit operation along with recommendations for correction.
CONTROL SYSTEM MAINTENANCE
Quarterly Preventive Maintenance � Check and adjust all control loops.
� Inspect all controllers and verify proper system operation.
� Verify incoming AC power and note proper voltages, check for transformer degradation and report.
� Ensure all wiring and terminations are secure.
� Check all electronic board seating if applicable / when required.
� Check data/power cabling for pinching, cracking, tears or breaks and report unusual conditions.
� Check diagnostic LEDs, fuses and surge transient protection devices where applicable.
Report unusual conditions.
� Troubleshoot minor operational problems relating to controls with Government Point of Contact; make recommendations.
Semi-annual Preventive Maintenance � Verify power supply voltages and record.
� Ensure proper cabinet grounding.
� Review system performance with Government Point of Contact and discuss recommendations and/or changes as required.
� Inspect cables, electrical connections, computer and system peripherals, and clean as required.
� Diagnostic testing; examining, calibrating, adjusting and cleaning of control devices as required.
� Perform quarterly tasks.
� Advise the Government Point of Contact of any deficiencies noted during the above inspections; make recommendations as to the correction of same.
Annual Preventive Maintenance � Check and calibrate sensors as required.
� Review control loops and adjust as necessary.
� Evaluate all input/output points for proper operation and report any deficiencies.
� Inspect interior surfaces and components of the panel enclosures and associated field equipment and clean as required for proper operation. Ensure all monitoring devices and plug-in components are securely in place, note any deficiency for review.
� Perform quarterly and semi-annual tasks.
� Meet with Government Point of Contact to discuss system needs, operational deficiencies and system enhancements.
Maintenance Records � The Contractor shall supply and maintain written records of maintenance and repairs on site.
� Note and report any mechanical, electrical or control system discrepancies that would affect equipment operations.
� Document all preventive maintenance work done, all pertinent pressures, temperatures, voltages, fluid levels and test results.
� The report shall contain any uncorrected deficiencies noted at inspection.
Safety Data Sheets (SDS) � Provide to the Government Point of Contact upon request for supplies and materials used by the Contractor.
Safety | Lock-Out Tag-Out � Advise the Government Point of Contact prior to starting maintenance procedures.
� Disconnect power supply; Tag unit as "Out of Service" as per Occupational Safety and
Health Act (OSHA) requirements.
Health and Safety Regulations The Contractor must comply with all applicable Local, State and Federal laws governing the health and safety of its employees, including all regulations promulgated under the OSHA. Such compliance shall include, but is not be limited to, ensuring that all employees are properly trained for the work to be performed and have been supplied with all necessary protective and safety equipment
Visitor Sign-in The Contractor’s employees/subcontractor must be escorted by a National Weather Service employee from the main gate at Camp Johnson, to the RDA and back anytime that the contractor is on site at the RDA. Any contractor/subcontractor employee may also be subject to a background check and random vehicle inspection when entering the site.
Maintenance Manuals The Contractor may ask the Government Point of Contact to review the Government’s maintenance manual. If maintenance manuals are not available, the Contractor shall contact the equipment manufacturer for their preventive maintenance program requirements and keep a copy for the office.
Codes and Standards Latest effective publication or applicable codes and ordinances of local governing agencies and of the following standards, codes, etc., as they apply.
� American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHREA) � National Building Code (BOCA) � Factory Mutual Engineering Association (FM) � Underwriters' Laboratories, Inc. (UL) � National Electrical Code (NFPA 70-99), National Electrical Safety Code (ANSI C2) and the NECA Standard of Installation or Local standards, whichever is the more stringent NEC (2002) will be followed, as applicable.
� American Society of Mechanical Engineers (ASME) Air Conditioning and Refrigeration Institute (ARI) Air Movement and Control Association (AMCA) � American Gas Association, (AGA) � American National Standards Institute (ANSI) American Society for Testing and Materials (ASTM) Electrical Testing Laboratories (ETL) � International Mechanical Code (IMC) 1996
� Air Movement and Control Association (AMCA) � Contractor shall follow all Federal, State and Local Codes to include Department of Transportation, (OSHA) � Occupational Safety and Health regulations (e.g. 29 CFR 1910, 1926).
OSHA General Industry Safety and Health Standards (29 CFR 1910); OSHA Construction Industry Standards (29 CFR 1926). (Single copies of these regulations are available from the local OSHA Area Offices and are also sold by the Superintendent of Documents, US.
Government Printing Office, Washington � Environmental Protection Agency (EPA) Final Rule (40 CFR, Part 761) dated July 17, 1985.
Materials The Contractor shall provide all parts necessary to complete the preventive maintenance activities specified herein and ensure that the parts are new, of good quality and warrantied according to the manufacturer. Materials requiring a SDS shall be reviewed by the Government Point of Contact prior to usage at least five (5) working days prior to usage. Products found to have certain health hazards to employees shall not be used.
Equipment located at Site 2 - Vermont National Guard Base, RDA Site, Ethan Allen Army National Guard Facility (Camp Johnson) � BARD Serial # 310H143135544-02 � BARD Serial # 404K193683019-02 � BARD Serial # 404K193683016-02
6. GOVERNMENT POINT OF CONTACT