ATTACHMENT_No__4__Electrical_Power_Load_Analysis_(EPLA)_0001.pdf

PDF 159 KB Posted

Attached to
Main Electrical Switchboard for R/V Gladys Reese Federal contract opportunity
Solicitation number
1305M325Q0225
Issued by
Department of Commerce National Oceanic and Atmospheric Administration

About this file

This document is an electrical load calculation spreadsheet for the Gladys Reese EPLA (Electrical Power Load Analysis) for a marine vessel, prepared by engineers Michael Loboda and Ian Lawson. The spreadsheet details electrical demand loads across six different operating conditions: summer cruising, winter cruising, summer functional general, summer functional camera array, winter functional general, and winter functional trap video. The analysis covers multiple electrical panels including ACP (HVAC 440V Panel), ELP (Engineering Lighting Panel), MLP (Compartment Lighting & Receptacles Panel), MNL (Mission Lighting Panel), MPP (Mission Power 440V Panel), and others, with comprehensive load factor calculations for various equipment such as pumps, compressors, fans, lighting, receptacles, and specialized marine equipment. The total demand load ranges from 82.6 kW to 158.7 kW across different operating conditions, with load factors varying by equipment type and operational mode, and calculations performed in accordance with IEEE, PRG, and NFPA standards.

View the file

Other files for this federal contract opportunity

Other files attached to Main Electrical Switchboard for R/V Gladys Reese, newest first.
File Type Posted
Sol_1305M325Q0225_Amd_0003.pdf PDF
Sol_1305M325Q0225_Amd_0002.pdf PDF
Sol_1305M325Q0225_Amd_0001.pdf PDF
ATTACHMENT_No__5__Engine_Performance_Curve_and_Specifications_0001.pdf PDF
ATTACHMENT_No__3__One-line_Drawing_of_Vessel_s_Existing_Electrical_System_0001.pdf PDF
1305M325Q0225_Attachments_1-2.pdf PDF
Sol_1305M325Q0225.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

KEY: NEW LOAD

CALCULATIONS BY: Michael Loboda, PE CUSTOM LOAD FACTOR

Ian Lawson, PE CLIENT-ESTIMATED

REVISION: - 3/20/2025 SEE NOTE 3

OPERATING CONDITION:

TOTAL DEMAND LOAD, KW (KVA @ 0.8PF): 82.6 (103.3) 95.9 (119.8) 145.5 (181.8) 158.7 (198.3) 128.4 (160.5) 120.8 (151) TOTAL 208/120V DEMAND LOAD, KW (KVA @ 0.8PF): 32.4 (40.5) 32.4 (40.5) 38.5 (48.2) 38.5 (48.2) 36.8 (46) 38.1 (47.6)

TOTAL DEMAND LOAD [NEW LOADS ONLY], KW (KVA @ 0.8PF): 22.6 (28.2) 28.2 (35.2) 85.3 (106.6) 90.9 (113.6) 68.2 (85.2) 53.0 (66.2) TOTAL 208/120V DEMAND LOAD [NEW LOADS ONLY], KW (KVA @ 0.8PF): 15.1 (18.9) 15.1 (18.9) 21.2 (26.4) 21.2 (26.4) 19.4 (24.3) 20.7 (25.9)

KW EACH KW TOTAL L.F. KW L.F. KW L.F. KW L.F. KW L.F. KW L.F. KW

1S-4P (1) 1 7.93 7.93 0.5 3.96 0.5 3.96 0.5 3.96 0.5 3.96 0.5 3.96 0.5 3.96 1S-4P (1) 1 4.02 4.02 0.1 0.40 0.1 0.40 0.1 0.40 0.1 0.40 0.1 0.40 0.1 0.40 1S-4P (1) 1 11.18 11.18 0.1 1.12 0.1 1.12 0.1 1.12 0.1 1.12 0.1 1.12 0.1 1.12 1S-4P (1) 1 3.73 3.73 0.1 0.37 0.1 0.37 0.1 0.37 0.1 0.37 0.1 0.37 0.1 0.37 1S-4P (1) 1 11.18 11.18 0.1 1.12 0.1 1.12 0.1 1.12 0.1 1.12 0.1 1.12 0.1 1.12 1S-4P (1) 1 3.73 3.73 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 1S-4P (1) 1 5.59 5.59 0.9 5.03 0.9 5.03 0.9 5.03 0.9 5.03 0.9 5.03 0.9 5.03 1S-4P (2) 1 5.59 5.59 0.9 5.03 0.9 5.03 0.9 5.03 0.9 5.03 0.9 5.03 0.9 5.03 1S-4P (2) 1 11.18 11.18 0.1 1.12 0.1 1.12 0.1 1.12 0.1 1.12 0.1 1.12 0.1 1.12 1S-4P (2) 1 3.73 3.73 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 1S-4P (2) 1 7.93 7.93 0.5 3.96 0.5 3.96 0.5 3.96 0.5 3.96 0.5 3.96 0.5 3.96 1S-4P (2) 1 4.02 4.02 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 1S-4P (2) 1 0.75 0.75 0.3 0.23 0.3 0.23 0.3 0.23 0.3 0.23 0.3 0.23 0.3 0.23 1S-4P (2) 1S-4P (2) 1 0.75 0.75 0.9 0.68 0.9 0.68 0.9 0.68 0.9 0.68 0.9 0.68 0.9 0.68 1S-4P (2) 1S-4P (2)

1S-2P 1S-2P 1S-2P

GLADYS REESE EPLA

DIRTY OIL TRANSFER PUMP

BILGE / FIRE PUMP

ENGINE RM SUPPLY FAN #2

FEEDER: ENGINEERING LIGHTING PANEL (ELP)

FEEDER: MISSION LIGHTING PANEL (MNL)

FEEDER: HVAC 440V PANEL (ACP)

FEEDER: MISSION POWER 440V PANEL (MPP)

FEEDER: COMPARTMENT LIGHTING & RECEPTACLES PANEL (MLP)

FEEDER: 208/120V SWBD - VIA XFMR (1S-2P)

STEERING PUMP #1

STEERING PUMP #2

FUEL OIL TRANSFER PUMP

SUMMER CRUISING

SUMMER FUNCTIONAL:

CAMERA ARRAY

WINTER FUNCTIONAL:

TRAP VIDEO

FIRE/ BALLAST PUMP

WINTER CRUISING

ENGINE RM SUPPLY FAN #1

AIR COMPRESSOR #1

SEWAGE PUMP #1

AIR COMPRESSOR #2

SEWAGE PUMP #2

FWD MACHINERY SPACE VENT FAN

POTABLE WATER PRESSURE SET

PARENT

PANEL

DESCRIPTION QTY

CONNECTED LOAD DEMAND LOAD

General Notes:

1. Calculations below are per IEEE Std 45.1 & 45.3, PRG.E2-06, & NFPA 70.

2. Load Factors are per DDS 310-1, Appendix A unless noted as Custom.

3. Certain existing panels are modeled as a single load for simplicity. Connected load shown is representative, accounting for L.F.

See loads on MLP Parent Panel See loads on ELP Parent Panel See loads on MNL Parent Panel

See loads on ACP Parent Panel See loads on MPP Parent Panel

See loads on 1S-2P Parent Panel

SUMMER FUNCTIONAL:

GENERAL

WINTER FUNCTIONAL:

GENERAL

Ian Lawson, PE CLIENT-ESTIMATED

REVISION: - 3/20/2025 SEE NOTE 3

OPERATING CONDITION:

TOTAL DEMAND LOAD, KW (KVA @ 0.8PF): 82.6 (103.3) 95.9 (119.8) 145.5 (181.8) 158.7 (198.3) 128.4 (160.5) 120.8 (151) TOTAL 208/120V DEMAND LOAD, KW (KVA @ 0.8PF): 32.4 (40.5) 32.4 (40.5) 38.5 (48.2) 38.5 (48.2) 36.8 (46) 38.1 (47.6)

TOTAL DEMAND LOAD [NEW LOADS ONLY], KW (KVA @ 0.8PF): 22.6 (28.2) 28.2 (35.2) 85.3 (106.6) 90.9 (113.6) 68.2 (85.2) 53.0 (66.2) TOTAL 208/120V DEMAND LOAD [NEW LOADS ONLY], KW (KVA @ 0.8PF): 15.1 (18.9) 15.1 (18.9) 21.2 (26.4) 21.2 (26.4) 19.4 (24.3) 20.7 (25.9)

KW EACH KW TOTAL L.F. KW L.F. KW L.F. KW L.F. KW L.F. KW L.F. KW

GLADYS REESE EPLA

STEERING PUMP #1

SUMMER CRUISING

SUMMER FUNCTIONAL:

CAMERA ARRAY

WINTER FUNCTIONAL:

TRAP VIDEO

WINTER CRUISING

PARENT

PANEL

DESCRIPTION QTY

CONNECTED LOAD DEMAND LOAD

General Notes:

1. Calculations below are per IEEE Std 45.1 & 45.3, PRG.E2-06, & NFPA 70.

2. Load Factors are per DDS 310-1, Appendix A unless noted as Custom.

3. Certain existing panels are modeled as a single load for simplicity. Connected load shown is representative, accounting for L.F.

SUMMER FUNCTIONAL:

GENERAL

WINTER FUNCTIONAL:

GENERAL

ACP 1 0.87 0.87 0.7 0.61 0.7 0.61 0.7 0.61 0.7 0.61 0.7 0.61 0.7 0.61

ACP 1 25.00 25.00 0.0 0.00 0.7 17.50 0.0 0.00 0.7 17.50 0.0 0.00 0.7 17.50

ACP 1 9.00 9.00 0.5 4.50 0.5 4.50 0.5 4.50 0.5 4.50 0.5 4.50 0.5 4.50

ACP 1 12.00 12.00 0.4 4.80 0.4 4.80 0.4 4.80 0.4 4.80 0.4 4.80 0.4 4.80

ACP 1 7.06 7.06 0.7 4.94 0.0 0.00 0.7 4.94 0.0 0.00 0.7 4.94 0.0 0.00

ACP 1 7.06 7.06 0.7 4.94 0.0 0.00 0.7 4.94 0.0 0.00 0.7 4.94 0.0 0.00

ACP 1 10.00 10.00 0.7 7.00 0.0 0.00 0.7 7.00 0.0 0.00 0.7 7.00 0.0 0.00

ACP 1 14.00 14.00 0.0 0.00 0.9 12.60 0.0 0.00 0.9 12.60 0.0 0.00 0.9 12.60

ACP 1 0.55 0.55 0.7 0.39 0.7 0.39 0.7 0.39 0.7 0.39 0.7 0.39 0.7 0.39

ELP 1 1.00 1.00 0.2 0.20 0.2 0.20 0.2 0.20 0.2 0.20 0.2 0.20 0.2 0.20

ELP 1 0.20 0.20 0.0 0.00 0.0 0.00 0.7 0.14 0.7 0.14 0.7 0.14 0.7 0.14

ELP 1 1.00 1.00 0.2 0.20 0.2 0.20 0.2 0.20 0.2 0.20 0.2 0.20 0.2 0.20

ELP 1 1.00 1.00 0.2 0.20 0.2 0.20 0.2 0.20 0.2 0.20 0.2 0.20 0.2 0.20

ELP 1 0.50 0.50 0.9 0.45 0.9 0.45 0.9 0.45 0.9 0.45 0.9 0.45 0.9 0.45

ELP 1 0.10 0.10 0.1 0.01 0.1 0.01 0.1 0.01 0.1 0.01 0.1 0.01 0.1 0.01

ELP 1 0.50 0.50 0.6 0.30 0.6 0.30 0.6 0.30 0.6 0.30 0.6 0.30 0.6 0.30

ELP 1 1.00 1.00 0.2 0.20 0.2 0.20 0.2 0.20 0.2 0.20 0.2 0.20 0.2 0.20

ELP 1 0.50 0.50 0.9 0.45 0.9 0.45 0.9 0.45 0.9 0.45 0.9 0.45 0.9 0.45

ELP 1 0.20 0.20 0.9 0.18 0.9 0.18 0.9 0.18 0.9 0.18 0.9 0.18 0.9 0.18

ELP 1 0.50 0.50 0.9 0.45 0.9 0.45 0.9 0.45 0.9 0.45 0.9 0.45 0.9 0.45

ELP 1 0.20 0.20 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00

ELP 1 0.50 0.50 0.2 0.10 0.2 0.10 0.2 0.10 0.2 0.10 0.2 0.10 0.2 0.10

ELP 1 0.50 0.50 0.2 0.10 0.2 0.10 0.2 0.10 0.2 0.10 0.2 0.10 0.2 0.10

ELP 1 0.50 0.50 0.2 0.10 0.2 0.10 0.2 0.10 0.2 0.10 0.2 0.10 0.2 0.10

ELP 1 0.10 0.10 0.9 0.09 0.9 0.09 0.9 0.09 0.9 0.09 0.9 0.09 0.9 0.09

MLP

MLP 1 4.67 4.67 0.6 2.80 0.6 2.80 0.6 2.80 0.6 2.80 0.6 2.80 0.6 2.80

MLP 1 10.83 10.83 0.6 6.50 0.6 6.50 0.6 6.50 0.6 6.50 0.6 6.50 0.6 6.50

PLP 1 2.22 2.22 0.9 2.00 0.9 2.00 0.9 2.00 0.9 2.00 0.9 2.00 0.9 2.00

PLP 1 4.83 4.83 0.6 2.90 0.6 2.90 0.6 2.90 0.6 2.90 0.6 2.90 0.6 2.90

A/C COMPRESSOR #1

MISSION SPACE A/C

BATTERY CHARGER #3 (STBD)

WATER HEATER

FEEDER: FOCSLE LIGHTING PANEL (FLP)

FEEDER: PILOTHOUSE LIGHTING PANEL (PLP)

FEEDER: ELECTRONICS PANEL (EP)

AIR HANDLER #1 HEATER STRIP

MISSION SPACE VENT FAN CONTROLLER - VIA XFMR

A/C COMPRESSOR #2

ALARM PANEL

PASSAGEWAY RECEPTACLES

STBD ENGINE RM LIGHTS

AIR HANDLER FAN MOTOR

COMPARTMENT LIGHTING & RECEPTACLES PANEL - OTHER LOADS

PILOTHOUSE LIGHTING PANEL - OTHER LOADS

BATTERY CHARGER #1

GALLEY RANGE

RUDDER ANGLE INDICATOR

SPARE SHAFT TACHOMETERS

BATTERY CHARGER #2 (PORT)

BOW THRUSTER CHARGER

MISSION SPACE HEATER

STBD ENGINE RM RECEPTACLES

FWD MACHINERY LIGHTS

EMERGENCY STOPS

PASSAGEWAY LIGHTS

PORT ENGINE RM RECEPTACLES

PORT ENGINE RM LIGHTS

SHAFT TACHOMETERS

See loads on PLP Parent Panel

Ian Lawson, PE CLIENT-ESTIMATED

REVISION: - 3/20/2025 SEE NOTE 3

OPERATING CONDITION:

TOTAL DEMAND LOAD, KW (KVA @ 0.8PF): 82.6 (103.3) 95.9 (119.8) 145.5 (181.8) 158.7 (198.3) 128.4 (160.5) 120.8 (151) TOTAL 208/120V DEMAND LOAD, KW (KVA @ 0.8PF): 32.4 (40.5) 32.4 (40.5) 38.5 (48.2) 38.5 (48.2) 36.8 (46) 38.1 (47.6)

TOTAL DEMAND LOAD [NEW LOADS ONLY], KW (KVA @ 0.8PF): 22.6 (28.2) 28.2 (35.2) 85.3 (106.6) 90.9 (113.6) 68.2 (85.2) 53.0 (66.2) TOTAL 208/120V DEMAND LOAD [NEW LOADS ONLY], KW (KVA @ 0.8PF): 15.1 (18.9) 15.1 (18.9) 21.2 (26.4) 21.2 (26.4) 19.4 (24.3) 20.7 (25.9)

KW EACH KW TOTAL L.F. KW L.F. KW L.F. KW L.F. KW L.F. KW L.F. KW

GLADYS REESE EPLA

STEERING PUMP #1

SUMMER CRUISING

SUMMER FUNCTIONAL:

CAMERA ARRAY

WINTER FUNCTIONAL:

TRAP VIDEO

WINTER CRUISING

PARENT

PANEL

DESCRIPTION QTY

CONNECTED LOAD DEMAND LOAD

General Notes:

1. Calculations below are per IEEE Std 45.1 & 45.3, PRG.E2-06, & NFPA 70.

2. Load Factors are per DDS 310-1, Appendix A unless noted as Custom.

3. Certain existing panels are modeled as a single load for simplicity. Connected load shown is representative, accounting for L.F.

SUMMER FUNCTIONAL:

GENERAL

WINTER FUNCTIONAL:

GENERAL

MNL 1 6.00 6.00 0.5 3.00 0.5 3.00 0.5 3.00 0.5 3.00 0.5 3.00 0.5 3.00

MNL 1 2.30 2.30 0.0 0.00 0.0 0.00 0.3 0.69 0.3 0.69 0.3 0.69 0.3 0.69

MNL 5 0.24 1.20 0.7 0.84 0.7 0.84 0.7 0.84 0.7 0.84 0.7 0.84 0.7 0.84

MNL 6 0.24 1.44 0.7 1.01 0.7 1.01 0.7 1.01 0.7 1.01 0.7 1.01 0.7 1.01

MNL 1 0.42 0.42 0.0 0.00 0.0 0.00 0.6 0.25 0.6 0.25 0.0 0.00 0.6 0.25

MNL 1 0.84 0.84 0.0 0.00 0.0 0.00 0.5 0.42 0.5 0.42 0.0 0.00 0.0 0.00

MNL 1 4.00 4.00 0.0 0.00 0.0 0.00 0.9 3.60 0.9 3.60 0.9 3.60 0.9 3.60

MNL 1 3.50 3.50 0.0 0.00 0.0 0.00 0.3 1.05 0.3 1.05 0.0 0.00 0.3 1.05

MNL 6 0.24 1.44 0.7 1.01 0.7 1.01 0.7 1.01 0.7 1.01 0.7 1.01 0.7 1.01

MNL 6 0.24 1.44 0.7 1.01 0.7 1.01 0.7 1.01 0.7 1.01 0.7 1.01 0.7 1.01

MNL 1 5.00 5.00 0.7 3.50 0.7 3.50 0.7 3.50 0.7 3.50 0.7 3.50 0.7 3.50

MNL 1 4.80 4.80 0.9 4.32 0.9 4.32 0.9 4.32 0.9 4.32 0.9 4.32 0.9 4.32

MNL 1 0.75 0.75 0.6 0.45 0.6 0.45 0.6 0.45 0.6 0.45 0.6 0.45 0.6 0.45

MNL 1 0.03 0.03 0.0 0.00 0.0 0.00 0.2 0.01 0.2 0.01 0.0 0.00 0.0 0.00

MPP 1 0.75 0.75 0.1 0.08 0.1 0.08 0.1 0.08 0.1 0.08 0.1 0.08 0.1 0.08

MPP 1 1.60 1.60 0.0 0.00 0.0 0.00 0.1 0.16 0.1 0.16 0.1 0.16 0.1 0.16

MPP 1 18.65 18.65 0.0 0.00 0.0 0.00 0.5 9.33 0.5 9.33 0.5 9.33 0.0 0.00

MPP 1 7.50 7.50 0.0 0.00 0.0 0.00 0.5 3.75 0.5 3.75 0.5 3.75 0.5 3.75

MPP 1 3.73 3.73 0.0 0.00 0.0 0.00 0.5 1.87 0.5 1.87 0.5 1.87 0.5 1.87

MPP 1 22.37 22.37 0.0 0.00 0.0 0.00 0.6 13.42 0.6 13.42 0.0 0.00 0.6 13.42

MPP 1 9.60 9.60 0.0 0.00 0.0 0.00 0.4 3.84 0.4 3.84 0.4 3.84 0.0 0.00

MPP 1 37.29 37.29 0.0 0.00 0.0 0.00 0.6 22.37 0.6 22.37 0.6 22.37 0.0 0.00

MPP 1 4.80 4.80 0.0 0.00 0.0 0.00 0.4 1.92 0.4 1.92 0.0 0.00 0.0 0.00

MISSION HPU

UNCONTAMINATED SEA WATER PUMP

CHEM LAB FWD / WET LAB 120V DUPLEX RECEPTACLES - NEMA 5-20

CTD WINCH

A-FRAME HPU

CRANE

LAB SPACE UPS 208V (240V RATED) RECEPTACLE - NEMA 6-50

LAB SPACE LIGHTING

WALK-IN FREEZER

ICE MAKER 208V RECEPTACLE - NEMA 6-20

FLOODLIGHTS

ACOUSTIC ARRAY UPS

FUME HOOD

WET LAB WATER HEATER

ULTRA LOW TEMP FREEZER

CUFES

WET LAB 120V RECEPTACLES - NEMA 5-20

COMPUTER LAB OUTBOARD 120V DUPLEX RECEPTACLES - NEMA 5-20

RAW WATER WASH DOWN PUMP

MULTI WINCH

120V DECK RECEPTACLE - NEMA 5-50 - VIA XFMR

240V DECK RECEPTACLE - NEMA 6-50 - VIA XFMR

COMPUTER LAB INBOARD 120V DUPLEX RECEPTACLES - NEMA 5-20