13_-_Plan_Sheets_1.pdf
PDF 6 MB Posted
- Attached to
- FPCM-LAC-I001104-M047-CS/ Complete Roof System
- Solicitation number
- 0000039915
- Issued by
- Los Angeles County, California
About this file
Summary of Plan Sheets for California State Prison Los Angeles County Roof Replacement Project
This is a comprehensive set of architectural and engineering plan sheets for Phase 1 of a roof replacement project at California State Prison, Los Angeles County (CDCR), located at 44750 60th Street, West Lancaster, California 93536. The project involves replacing roofs on 18 typical 270-housing unit buildings (Buildings 331–345, 348–349, and 3410) with an 80 mil, fully-adhered Class A, UL 790 PVC roofing system over 1/2-inch protection board and 6-inch minimum rigid insulation. The scope of work includes demolition of existing built-up roofing systems, repair and patching of metal deck substrates, removal and reinstallation of mechanical units, exhaust fans, water heaters, and associated roof penetrations, as well as installation of new metal coping, flashing, scuppers, guard rails, roof hatches, walk pads, parapet extensions, and condensate and plumbing systems. The project document is dated August 31, 2023, with Office of the State Fire Marshal approval granted on October 10, 2023, for fire and panic code compliance only, with final approval subject to field inspection. Project number 5843.10 is managed by Hibserayamauchi Architects, Inc., with structural engineering by a registered California state engineer and mechanical/plumbing design by Turley Mechanical Engineering Group, Inc., with electrical design by M. Neilsen Engineering.
The plan sheets include detailed demolition and remodel keynotes, general construction notes requiring all debris removal in compliance with local, state, and federal codes, protection of building and utilities during work, repair of damaged areas to match existing finishes, and coordination with plant operations and the head of maintenance. Gas line reconnections must be inspected and tested per CPC 1213, CMC 1303, and NFPA 54. All existing mechanical units, including AHUs, exhaust fans, and a 250-gallon water heater, are to be temporarily removed, labeled, stored, and protected for reinstallation in working order, with verification meetings scheduled before and after work completion. Roof drainage calculations are provided based on a 2-inch per hour rainfall rate per CPC standards, with equivalent areas ranging from 200 to 2,200 square feet, requiring 3-inch roof drains or 10-inch by 4-inch scupper openings. Electrical work includes disconnection and reconnection of HVAC circuits, conduit replacement, and installation of new weatherproof GFCI receptacles. Wind uplift design zones are identified with field values of 60 PSF (field), 75 PSF (perimeter), and 105 PSF (corners), with a safety factor of 2 included.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 13_-_Plan_Specs.pdf | ||
| 12_-_FPCM-LAC-I001104-M047-CS.pdf | ||
| 13_-_Plan_Sheets_2.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
12'-0" 13'-0" 13'-0" 13'-0" 13'-0"13'-0" 13'-0"13'-0"5'-8" 13'-0"11'-2"
DN
3 1 1.8 2 6 4 5 7 8 9 1110
B.4
A
B
D
C
J
E
F
G
H
K
K.8
L
M
1 111.8 2 3 4 5 6 7 8 9 10 5.7 7.3
A
B
B.7
D
E.7
G.3
J
K.7
L
M
134'-2"
1'-4"
2'-2"
(E
S L O
P E
/4
(E) SLOPE
1/4" : 1'-0"
(E
S L O
P E
/4
(E
S L O
P E
/4
(E
S L O
P E
/4
(E
S L O
P E
/4
( E
S L O
P E
/4
RIDGE
D04
TYP
D01
TYP
D01
TYP
D01
TYP
D01
TYP
D02
TYP
D01
D15
D14
D17
D01
TYP
D02
TYP
D03
D09
D14
D10
TYP
D07
TYP
D13
TYP
D18
D05
D07
TYP
D05
TYP
D05
D05
D19
D10
TYP
D06
TYP
D06
TYP
D16
D14
D13
TYP
D13
TYP
D04
TYP
D08
TYP
D08
TYP
D04
TYP
D21
D11
TYP
D11
TYP
D11
TYP
D12
D12
D14
D02
TYP
D07
TYP
D14
D18
(E) SCUPPER AT HIGHER ROOF TO BE REMOVED.
GENERAL NOTES
1. ALL CONSTRUCTION DEBRIS GENERATED IN THE COURSE OF THIS PROJECT SHALL
BE REMOVED AND DISPOSED OF IN COMPLIANCE WITH ALL LOCAL, STATE AND
FEDERAL CODES AND REGULATIONS.
2. REPAIR/REPLACE ANY DAMAGED UTILITIES DURING THE COURSE OF WORK.
3. PROTECT BUILDING FROM DAMAGE WHICH MAY OCCUR FROM DEMOLITION, DUST,
WATER, ADVERSE WEATHER, ETC.
4. CONTRACTOR TO PATCH AND REPAIR ALL AREAS DAMAGED BY, OR INCIDENTAL TO
DEMOLITION AND/OR NEW WORK TO MATCH ADJACENT FINISHES UNLESS
OTHERWISE NOTED.
5. REPLACE ALL (E) CONDUIT & PIPE SUPPORTS ON ROOF W/ (N) HARD PIPE SUPPORT
BLOCK. SED & SMD.
6. REMOVE (E) CONDUIT OR PIPE IN CONFLICT WITH THE INSTALLATION OF (N) WORK.
REINSTALL AFTER COMPLETION OF (N)WORK.
7. REMOVE ALL (E) MECHANICAL UNITS, VENTS, AND FANS AS REQUIRED TO PERFORM
ROOFING AND FLASHING WORK. STORE AND PROTECT UNITS FOR REINSTALL TO
WORKING ORDER. SCHEDULE MEETING WITH HEAD OF MAINTENANCE AND
CONTRACTOR TO VERIFY WORKING ORDER OF HVAC SYSTEM PRIOR TO WORK AND
ONCE WORK IS COMPLETE.
8. PROTECT ELECTRICAL BOXES.
9. ALL INFORMATION SHOWN ON THE DRAWING RELATIVE TO (E) CONDITIONS IS GIVEN
AS THE BEST PRESENT KNOWLEDGE . WHERE ACTUAL CONDITIONS CONFLICT WITH
THE DRAWING, THEY SHALL BE REPORTED TO THE ARCHITECT SO THAT THE
CORRECTIONS/CLARIFICATIONS CAN BE PROVIDED.
10. ALL DIMENSIONS ARE TO BE VERIFIED IN FIELD.
11. COORDINATE WITH PLANT OPS BEFORE AND AFTER SHUTTING OFF ANY UTILITIES.
12. ANY GAS LINES THAT HAVE BEEN DISCONNECTED AND RECONNECTED, SHALL BE
INSPECTED AND TESTED FOR LEAKAGE IN ACCORDANCE WITH CPC 1213, CMC 1303
AND NFPA 54.
13.PAINT ALL (N) TRIMS AND FLASHING TO MATCH (E) COLOR.
14.ALL FIRE RETARDANT TREATED WOOD SHALL BE INSPECTED PRIOR TO COVERING.
MATERIAL SHALL BEAR A LABEL THAT INDICATES ITS LISTING.
EQUIPMENT LEGEND
* NOTE: QUANTITY IS APPROXIMATE, VIF
(E) VENT PIPES TO RECEIVE BOOT FLASHING
SEE DETAIL
(E) EXHAUST FAN OVER (N) CURB ADAPTER,
SEE DETAIL
QTY.SYMBOL DESCRIPTION
DEMOLITION LEGEND
AREA OF (E) BUILT-UP ROOFING SYSTEM TO BE REMOVED,
INCLUDING RIGID INSULATION, COUNTER FLASHING,
FLASHING AROUND PENETRATIONS, ETC. (E)METAL DECK
WITH LIGHT WEIGHT CONCRETE TOPPING TO BE PATCHED
AND REPAIRED AS REQUIRED TO PREPARE STRUCTURE
FOR NEW ROOF SYSTEM.
(E) FUEL GAS PIPING, SMD.
(E) WALKPAD TO BE REMOVED
(E) BUILDING FOOTPRINT BELOW.
32 PER ROOF
32 PER ROOF
(E) CONDENSATE LINE, SMD.
(E) ELECTRICAL CONDUIT, SED.
(E) CAT WALK
DEMOLITION KEYNOTES
(E) PARAPET COPING CAP TO BE REMOVED AND RECYCLED. INSPECTED FOR
WATER DAMAGE.
REMOVE (E) MECHANICAL UNIT AND CURB. STORE AND PROTECT FOR
REINSTALLATION. SMD.
D01
D02
D04
D05
D06
D07
D08
D09
D10
D11
(E) ROOF VENT PIPE TO REMAIN. REMOVE (E) FLASHING. EXTEND TO 12" AFR
WHERE NECESSARY.
DEMOLISH (E) WALK PADS/PAVERS, TYP.
D12
(E) SCUPPER AT LOWER ROOF TO REMAIN.
D13
REMOVE AND PROTECT (E) EXHAUST FAN FOR REINSTALLATION, SMD.
(E) ROOF MOUNTED CONDENSATE PIPE ON SUPPORT BLOCK TO BE REMOVED
AND REPLACED. SMD.
REMOVE (E) CRICKET.
(E) ELECTRICAL CONDUIT TO BE REMOVED AND RE-INSTALLED, SED.
D14 (E) GUARDRAIL TO BE REMOVED.
D15
D16
D03 (E) STAIRCASE TO REMAIN.
REMOVE AND REINSTALL (E) STAIR CAGE
D17
D18
(E) CATWALK TO BE REMOVED. CONDITION AT STAIRS OCCURS AT ALL
BUILDINGS. CONDITION ALONG PARAPET OCCURS AT BUILDINGS 331, 333, 335,
348, AND 3310.
(E) CURB TO REMAIN, EXTEND AS REQUIRED.
(E) ROOF HATCH TO BE REMOVED.
REMOVE (E) WATER HEATER ON CURB. STORE AND PROTECT FOR
REINSTALLATION. SMD.
D19
(E) AHU DUCT SUPPORT AND BRACE TO BE REMOVED AND REPLACED, SMD
REMOVE AND PROTECT (E) TRANSITION LADDER
D20
REMOVE (E) GRAB BAR.D20
TYPICAL 270 HOUSING UNIT ROOF PLAN DEMOLITION
SCALE: 1/8" = 1'-0"
SHEET NUMBER
V1
AA201
BUILDING 332 BUILDING 331 BUILDING 333 BUILDING 335 BUILDING 336 BUILDING 337 BUILDING 338 BUILDING 339 BUILDING 3310 BUILDING 341 BUILDING 342 BUILDING 343 BUILDING 344 BUILDING 345 BUILDING 348 BUILDING 349 BUILDING 3410
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/10/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-0002
11/20/2023 CASp 491 #1317
12'-0" 13'-0" 13'-0" 13'-0" 13'-0"13'-0"13'-0"13'-0"5'-8" 13'-0"11'-2"
DN
1 61.8 2 3 4 5 7 118 9 10
A
B
C
B.4
F
D
E
H
G
J
K
K.8
L
M
1 111.8 2 3 4 5 6 7 8 9 10 5.7 7.3
A
B
B.7
D
E.7
G.3
J
K.7
L
M
134'-2"
1'-4"
2'-2"
S L O
P E
/2
(E
S L O
P E
/4
(E
S L O
P E
/4
(E
S L O
P E
/4
K
H
E
C
F
G
(E
S L O
P E
/4
RIDGE
SLOPE
1/2":1'-0"
S L O
P E
/2
26'-0"
REMODEL KEYNOTES
(N) METAL COPING AT (E) PARAPET, SEE DETAIL
A902
(N) 36" WIDE WALK PAD, 72" WIDE AROUND MECHANICAL EQUIPMENTS06
A900
(E) EXHAUST FAN, REINSTALLED OVER NEW RAISED CURB, SMD.
(N) BOOT FLASHING AT (E) VENT PIPE
(N) CONDENSATE PIPE ON (N) SUPPORT BLOCK, SMD.
(N) CRICKET
(N) OVERFLOW SCUPPER
A900
A902
A902
12 (N) BOOT FLASHING AT (E) ELECTRICAL CONDUIT PIPE, SED
(RE) ELECTRICAL CONDUIT ON NEW SUPPORT BLOCK, SEE DETAIL14
(N) PRIMARY SCUPPER AT LOWER ROOF
A900
A900
GENERAL NOTES
1. ALL CONSTRUCTION DEBRIS GENERATED IN THE COURSE OF THIS PROJECT SHALL
BE REMOVED AND DISPOSED OF IN COMPLIANCE WITH ALL LOCAL, STATE AND
FEDERAL CODES AND REGULATIONS.
2. REPAIR/REPLACE ANY DAMAGED UTILITIES DURING THE COURSE OF WORK.
3. PROTECT BUILDING FROM DAMAGE WHICH MAY OCCUR FROM DEMOLITION, DUST,
WATER, ADVERSE WEATHER, ETC.
4. CONTRACTOR TO PATCH AND REPAIR ALL AREAS DAMAGED BY, OR INCIDENTAL TO
DEMOLITION AND/OR NEW WORK TO MATCH ADJACENT FINISHES UNLESS
OTHERWISE NOTED.
5. REPLACE ALL (E) CONDUIT & PIPE SUPPORTS ON ROOF W/ (N) HARD PIPE SUPPORT
BLOCK. SED & SMD.
6. REMOVE (E) CONDUIT OR PIPE IN CONFLICT WITH THE INSTALLATION OF (N) WORK.
REINSTALL AFTER COMPLETION OF (N) WORK.
7. REMOVE ALL (E) MECHANICAL UNITS, VENTS, AND FANS AS REQUIRED TO PERFORM
ROOFING AND FLASHING WORK. STORE AND PROTECT UNITS FOR REINSTALL TO
WORKING ORDER. SCHEDULE MEETING WITH HEAD OF MAINTENANCE AND
CONTRACTOR TO VERIFY WORKING ORDER OF HVAC SYSTEM PRIOR TO WORK AND
ONCE WORK IS COMPLETE.
8. PROTECT ELECTRICAL BOXES.
9. ALL INFORMATION SHOWN ON THE DRAWING RELATIVE TO (E) CONDITIONS IS GIVEN
AS THE BEST PRESENT KNOWLEDGE . WHERE ACTUAL CONDITIONS CONFLICT WITH
THE DRAWING, THEY SHALL BE REPORTED TO THE ARCHITECT SO THAT THE
CORRECTIONS/CLARIFICATIONS CAN BE PROVIDED.
10. ALL DIMENSIONS ARE TO BE VERIFIED IN FIELD.
11. COORDINATE WITH PLANT OPS BEFORE AND AFTER SHUTTING OFF ANY UTILITIES.
12. ANY GAS LINES THAT HAVE BEEN DISCONNECTED AND RECONNECTED, SHALL BE
INSPECTED AND TESTED FOR LEAKAGE IN ACCORDANCE WITH CPC 1213, CMC 1303
AND NFPA 54.
13.PAINT ALL (N) TRIMS AND FLASHING TO MATCH (E) COLOR.
14.ALL FIRE RETARDANT TREATED WOOD SHALL BE INSPECTED PRIOR TO COVERING.
MATERIAL SHALL BEAR A LABEL THAT INDICATES ITS LISTING.
EQUIPMENT LEGEND
* NOTE: QUANTITY IS APPROXIMATE, VIF
(E) VENT PIPES TO RECEIVE BOOT FLASHING
SEE DETAIL
(E) EXHAUST FAN OVER (N) CURB ADAPTER,
SEE DETAIL
QTY.SYMBOL DESCRIPTION
32 PER ROOF
32 PER ROOF
TYP
TYP
(N) 38"x42" ROOF HATCH WITH RAIL GUARD, SEE DETAILS
(RE) TRANSITION LADDER, SEE DETAIL
(N) GUARDRAIL, SEE DETAIL
A902
A904
A901
TYP
TYP
TYP
REMODEL LEGEND
(N) 80 MIL, FULLY-ADHERED (CLASS A, UL 790) PVC
ROOFING SYSTEM OVER 1/2" PROTECTION BOARD
OVER 6" MIN RIGID INSULATION. PROVIDE NEW
FLASHING FOR ALL (E) ROOF PENETRATIONS.
COORDINATE RE-ROOFING WITH (E) UTILITIES AND
ELECTRICAL CONDUITS.
(N) PVC WALKPAD COMPATIBLE W/ (N) MEMBRANE.
SURFACE MUST BE 36" MIN. WIDE, AND INCREASED TO 72"
MIN. WIDE WHERE INDICATED AT MECHANICAL
EQUIPMENT.
(E) BUILDING FOOTPRINT BELOW.
(N) CMU PARAPET EXTENSION.
(E) FUEL GAS PIPING, SMD.
(E) CONDENSATE LINE, SMD.
(E) ELECTRICAL CONDUIT, SED.
(N) METAL STUD PARAPET EXTENSION.
TYP
TYP
TYP
TYP
TYP
TYP
TYP
TYP
TYP
05 05
TYP
TYP
TYP
TYP
TYP
(N) EDGE TRANSITION CONDITION AT HIGH ROOF
(E)STAIR CAGE TO BE REINSTALLED.
EXTENDED CURB.
A901
05 (E) MECHANICAL UNIT RE-INSTALLED OVER (N) RAISED CURB. SMD.
TYP
21 (N) PLUMBING ACCESS DOOR, SEE DETAIL
A901
22 (E) MECHANICAL DUCT TO BE RE-INSTALLED. SMD.
AA501
AA601
AA601
TYP
TYP
TYP
TYP
TYP
TYP
REINSTALL (E) WATER HEATER ON CURB, SMD.23
24 AHU DUCT SUPPORT AND BRACE, SMD
25 PITCH POCKET, SMD
TYP
TYP
TYP
AA501
AA501
AA501
A903
(N) CROSS OVER BRIDGE, SEE DETAIL
A902
TYP
TYP
REINSTALL (E) METAL GRATING
A900 SIM.
(N) PARAPET EXTENSION. SSD &
A900
A901
(V
IF
26 (E) PRIMARY SCUPPER TO REMAIN.
A905
A903
T Y P
6'-0"
TYP
3' -0
TY
P
TYP
TYP
TYP
TYP
TYP
TYP
A900
27 TRANSITION STRIP AT PARAPET WALL. SEE DETAIL
A905
28 ROOF RAKE. SEE DETAIL
A901
8'-8"
±5'-6"
±5'-1"
±5'-1"
±5 '-4
6'-0"
TYP
T Y P
A902
TYPICAL 270 HOUSING UNIT ROOF PLAN REMODEL
SCALE: 1/8" = 1'-0"
SHEET NUMBER
V1
AA301
BUILDING 332 BUILDING 331 BUILDING 333 BUILDING 335 BUILDING 336 BUILDING 337 BUILDING 338 BUILDING 339 BUILDING 3310 BUILDING 341 BUILDING 342 BUILDING 343 BUILDING 344 BUILDING 345 BUILDING 348 BUILDING 349 BUILDING 3410
V1
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/10/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-0002
RENEWAL
DATE
H I
C
U
AY
N
E K
RENEWAL
S
I L
T
AI
C
DATE
H I
C
U
MAAY
N
E K
H C
U
MAAY
NNNNNNNNNN
E K
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/10/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-0002
0'-0"
T.O. 1ST FLR
18'-6"
T.O. (E) PRECAST
CONCRETE WALL
TYP.
4"
6"
AB C D E F G H J K L M K.7 G.4 E.7 B.3
115.7 6 7 7.3 8 9 10 4 2 1.8 1 3 5
/2
/2
0'-0"
T.O. 1ST FLR
18'-6"
T.O. (E) PRECAST
CONCRETE WALL
21'-6"
T.O. (E) PRECAST PANEL
TYP.
TYP.
03 0807
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
HOUSING UNIT BUILDING SECTION
SCALE: 1/8" = 1'-0"
HOUSING UNIT BUILDING SECTION
SCALE: 1/8" = 1'-0"
AA601
SHEET NUMBER
V1
BUILDING SECTION KEYNOTES
(N) METAL COPING AT PARAPET, SEE DETAIL
(E) EXHAUST FAN, REINSTALLED OVER NEW RAISED CURB, SMD.
(N) CRICKET
A-900
(N) PRIMARY SCUPPER AT LOWER ROOF
(N) ROOF HATCH, SEE DETAIL
(N) GUARDRAIL, SEE DETAIL
(E) MECHANICAL UNIT RE-INSTALLED OVER (N) RAISED CURB. SMD.
(N) 80 MIL, FULLY-ADHERED (CLASS A, UL 790) PVC ROOFING SYSTEM
OVER 1/2" PROTECTION BOARD OVER 6"MIN RIGID INSULATION.
(E) METAL DECK WITH CONCRETE FILL.
10 (E) PRECAST CONCRETE PLANK W/ CONCRETE TOPPING.
A901 TYP.
A-902
A-900
A900
A900
A902
A901
11 (E) STAIR CAGE TO BE REINSTALLED.
A901
A906
A906
SIM.
V1
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/10/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-0002
7.3
7.3
5.7
5.7
1.8
1.8
A A
B B
C C
D D
E E
F F
G G
H H
J J
K K
K.8 K.8
L L
M M
B.4 B.4
11'-2" 5'-8" 13'-0" 13'-0" 13'-0" 8'-0" 5'-0" 13'-0" 5'-0" 8'-0" 13'-0" 13'-0" 13'-4"
134'-2"
'-8
'-2
'-0
'-0
'-0
'-0
'-0
'-0
'-0
'-0
'-0
'-2
(E) 4" PRECAST
CONC SLAB
'-6
T.
O
E) 6"
C O
NC
W
AL
L
TY
P U
NO
21'-6"
T.O
. (E) 8" CO
NC W
ALL
(E) 3 1/4" LW CONC
OVER 3"MTL DECK
'-6
T.
O
E) 8"
C O
NC
W
AL
L
'-6
T.
O
E) 8"
C O
NC
W
AL
L
(E) WF FRMG TYP
(N) GUARDRAIL PER
SEE ARCH PLAN
S501
(N) SCUPPER PER
SEE ARCH PLAN
S501
(N) GUARDRAIL PER
SEE ARCH PLAN
S501
(N) GUARDRAIL PER
SEE ARCH PLAN
S501
(N) SCUPPER PER
SEE ARCH PLAN
S501
(N) ACCESS
PANEL PER ARCH
RE-INSTALL (E) MECH
UNIT OVER (N) RAISED
CURB, PER
TYP SEE
MECH
RE-INSTALL (E) UNIT
BRACING, TYP SEE MECH
(N) ACCESS PANEL
PER ARCH
RE-INSTALL (E)
STAIR CAGE PER
SEE ARCH PLAN
(N) SCUPPER PER
SEE ARCH PLAN
S501
(N) GUARDRAIL PER
SEE ARCH PLAN
S501
A
S301
SA201
'-6
T.
O
E) 8"
C O
NC
W
AL
L
'-6
T.
O
E) 8"
C O
NC
W
AL
L
WALL EXTENSION PER
SEE ARCH PLAN
S501
S501
1 7 11
A
E
H
M
16'-0"
'-0
13'-0"
'-0
'-0
NOTES:
1. CONSTRUCTION SEQUENCE
A. REMOVE EXISTING ROOFING PER ARCHITECTURAL DRAWINGS.
B. INSPECT EXISTING STRUCTURAL ELEMENTS FOR DETERIORATION.
C. IFCONCRETE SUBSTRATE SHOWS EXCESSIVEDETERIORATION REPAIR
PER 1/S501 OR NOTIFY THEARCHITECT AND STRUCTURAL ENGINEER
FOR FURTHER DIRECTION. FURTHER REPAIRS TO ANY DETERIORATION OR
SPALLING WILL BEEVALUATED AND DETAILEDON A CASE-BY CASE BASIS
DEPENDING ON THE TYPE ANDEXTENT, OR THE REPAIRS NEEDED.
D. PLACE NEW ROOFING PER ARCHITECTURAL DRAWINGS.
2. SEE KEY PLAN 1/SA201 FOR ROOFING WIND UPLIFT VALUES.
3. INDICATES EXTENSION OF (E) PARAPET, SEE
4. EXCESSIVE DETERIORATION:
A. FOR CONCRETEEXCESSIVE DETERIORATION IS DEFINED AS HAVING
SPALLEDSECTIONS OFCONCRETE LARGER THAN 3" ACROSS, OR HAVING
CRACKING 1/8"WIDE x 3' LONGOR GREATER.
B. FOR METAL DECKING EXCESSIVE DETERIORATION IS DEFINED AS HAVING
FLAKING RUST WHERE THEREMAINING THICKNESS IS LESS THAN 90% OF
ORIGINAL DECK THICKNESS, OVER AN AREA GREATER THAN 1 SQ FOOT.
C. FOR STRUCTURAL STEEL EXCESSIVE DETERIORATION IS DEFINED AS
HAVING FLAKING RUST WHERE THEREMAINING THICKNESS IS LESS THAN
95% OF ORIGINAL MEMBER THICKNESS.
1. WIND UPLIFT VALUES INCLUDE A SAFETY FACTOR OF 2.
LEGEND:
ZONE 1 - FIELD (60 PSF)
ZONE 2 - PERIMETER (75 PSF)
ZONE 3 - CORNERS (105 PSF)
1 21.8
A
B
1'-8" 1'-10"
TY
P
HS
S3 x3 x1
/4
(E ) C
AG
E
PO
ST
T
YP
REMOVE AND
REINSTALL (E)
STAIR CAGE
B
S301
B
S301
A
S301
C
S301
H S S x3 x1 /4
F L A T
H S S x3 x /4
F L A T
HSS12x3x1/4 FLAT
S
S TATE OF CALI FOR N I A
STRUCTURAL
R
EFORP
DERETSI
GE
SI N
ENGINEER
O AL
DE
PA
R T M
EN
T
OF
CO
RRE
CTIONS AND
REHAB
IL
ITA
T
IO
N
S T
A
TE
OF CAL I FORN
I A
A rc h ite ct s, I n c.
H
IB
SE
R Y
A M
A U C H I n d S tr ee t, S u ite
D a vi s, C
A
.7
.1 o ff ic e
.7
.4 fa x
600 Q STREET, SUITE 200
SACRAMENTO, CA 95811
916 443 0303
CALIFORNIA DEPARTMENT OF
CORRECTIONS AND REHABILITATION
ACCESS COMPLIANCE REVIEW
APPROVAL OF THIS PLAN DOES NOT
AUTHORIZE OR APPROVE ANY OMISSION OR
DEVIATION FROM THE APPLICABLE REGULATIONS.
TRACKING NUMBER:___________________
DATE:____________________________
REVIEWER:_________________________
APPROVAL
F
IN
A L
D R
A W
IN
G
S
SHEET NUMBER
ST
AT
E O
F C
AL
IF
O
R N
IA
D
EP
AR
TM
EN
T O
F C
O R
R
EC
TI
O
N S
AN
D R
EH
AB
IL
IT
AT
IO
N
FA
C
IL
IT
Y
PL
AN
N
IN
G , C
O N
ST
R
U C
TI
O N
A N
D M
AN
AG
EM
EN
T D
IV
IS
IO
N
DE
SI
GN
S
ER
VI
CE
S
AN
D
ST
AN
DA
RD
S
BR
AN
CH
DE
SI
GN
S
ER
VI
CE
S
SE
CT
IO
N
R E V
D A T E
D
S C R
IP
T
IO
N
L A C
V1
C A
LI
F O
R N
IA
S T A T E P
R
IS
O N , L
O S A
N G
E
LE
S C
O U N
T Y
TH
S
TR
E E T, W E S T
LA
N C A S
TE
R , C
A
R E P
LA
C E R
O O
F
P H A S
C
C R
P H A S E
J O B
N U M B E R
A T E A
U G
U S T
1, P ro je c t N o
.1
P ro je c t
P h a s e
H E E T
T
IT
L
M. TODD
THORP
No. 2990
/9
/2
:3 :2
P
M c re v it \2
-0
.0
C D
C R
L A P
H R C
E N
T R A L d d ir e .r v t
R O
O F F
R A M
IN
G
P L A N
T
Y P
H
O U
S
IN
G U
N
IT
SSSSAAAA222200001 111
ROOF FRAMING PLAN - TYP 270 HOUSING UNIT
0' 4'-0" 8'-0" 16'-0" 32'-0" (1/8" = 1')
331/341 332/342 333/343 335/336/345 344 339/349 337 338/348 3310/3410
DETAIL
SA201
1/16" = 1'-0"3
WIND PRESSURE PLAN
WIND PRESSURE PLAN SA201
0' 8' 16' 32' 64'
SA201
1/2" = 1'-0"2STAIR CAGE PARTIAL ROOF PLAN
0' 1'-0" 2'-0" 4'-0" 8'-0"
S
R
EFOROOP
DDDDDDDDDDDDDDDDDEEEEEEEEEEEEEEEEEERRRRRRRRRRRRRRREEEEEETTTTTTTTTTTTTTTTTTTTTTTTSSSSSSSSSSSSSSSI
GGGEGG
SI NN
EEEEEEEEEEEEENNNNNNNNNNNNNNNNGGGGGGGGGGGGGGGGGGGGGGGGIIIIIIIIIIIIIINNNNNNNNNNNNNNNNEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEERR
O AAAAAAAAALLLLLLLLLLLLLLLLLLLLLLL
MMMMMMMMMMMMMM. TODDTODDTTOTTOOOOOD
THORP
No 2990
08/24/2023
V1
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/10/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-0002
KING NUMBENUNU ENU ER:_____R:__________________ ______ ___________
WER:_____R:_____R:R::__________R:_____:R:R:R:R:::RRRRR:___RRRR ___ _________________________ ____ _11/20/2023
3 1 1.8 2 6 4 5 7 8 9 1110
B.4
A
B
D
C
J
E
F
G
H
K
K.8
L
M
1 111.8 2 3 4 5 6 7 8 9 105.7 7.3
A
B
B.7
D
E.7
G.3
J
K.7
L
M
D04
TYP
D11
D07
D13
D05
D07
D05
D05
D05
D19
D10
D10
D11
D14
D13
D13
D04
D08
D08
D21
D20
D20
D20
D11 D11 D11
D11 D11 D11
D11
D11
D11
D11
D10 D10 D10
D10 D10 D10
D10
D10
D10
D10
D04 D04 D04 D04 D04 D04 D04 D04 D04D04 D04 D04 D04
D04D04 D04D04 D04 D04 D04
D04
D04 D04 D04 D04 D04 D04
D08 D08 D08 D08 D08 D08 D08 D08
D08
D08
D08
D08
D08
D08
D08
D08
D08
D08
D08
D07 D07 D07 D07 D07 D07 D07 D07
D07D08D08D08D08D08D08D08D08 D07D07D07D07D07D07D07D07
D07
D07
D07
D07
D07
D07
D07
D07
D07
D07
D07
D07
D07
(E)AC-1
(E)AHU-1
(E)AHU-2
(E)AHU-3
(E)EF-1(E)EF-2 (E)EF-3 (E)EF-4
(E)EF-5
(E)EF-6 (E)EF-7 (E)EF-8 (E)EF-9
(E)EF-32
(E)EF-10
(E)EF-11
(E)EF-12
(E)EF-13
(E)EF-30
(E)EF-14
(E)EF-15
(E)EF-16
(E)EF-17
(E)EF-29
(E)EF-28
(E)EF-18 (E)EF-19 (E)EF-20 (E)EF-21 (E)EF-22 (E)EF-23 (E)EF-24 (E)EF-25 (E)EF-26
D07
(E)EF-27
(E)EF-31
(E)EF-33
(E)WH-1
D22
D22
D22
(E)1 14"CD
(E)1 14"CD
(E)11
4"CD
D14
D14
D14
D14
D13
D15
(E)34"ICW
D16
D16
(E)34"ICW
(E)34"ICW
D17
(E)11
2"MPG
D17
(E)34"MPG
D17
(E)34"MPG
D17
(E)34"MPG
(E)34"CD
D17
(E)34"MPG
D16A
D18
D18
D18
D18
Project Engineer:
U R L E YT M E C H A N IC A L
E N G I N E E R I N G
G R O U P, I N C.& ASSOCIATES
(916) 325-1065
FAX: (916) 325-1075
Email: office@turleymech.com
2431 Capitol Avenue
Sacramento, CA 95816
Project Manager:
GYang
Job Number:
Project Drafter: Login:
Plot Date: Aug 25, 2023 - 4:07pm
22107-PH1JT
JT
SHEET NUMBER
S
TA
TE
O
F C
A
LI
FO
R N
IA
D
E P A R
TM
E N T
O F
C O
R R
E C
TI
O
N S A
N D R
E H
A B
IL
IT
A
TI
O N
FA
C
IL
IT
Y P
LA
N
N
IN
G , C
O N
S
TR
U C
TI
O
N A
N D
M A N A G
E M
E N
T D
IV
IS
IO
N
DE
SI
G N
SE
RV
IC
ES
A
ND
S
TA
ND
AR
DS
B
RA
NC
H
DE
SI
G
N
SE
RV
IC
ES
S
EC
TI
O N
APPROVAL
V1
C A L
IF
O R
N
IA
S T A T E P
R
IS
O N
L O
S A
N G
E L E S C
O U N T Y
T H
S T R
E E T , W
E S T
LA
N
C A S T E R
, C A
R E P L A C
E R
O O
F S
P H
A S E
A U
G U
S T
W O
R K
IN
G D
R A W
IN
.1
A rc h it e ct s, I n c.
H
IB
S E R Y
A M
A U C
H I n d S tr e e t, S u it e
D a vi s, C
A
.7
.1 o ff ic e
.7
.4 f a x
DEMOLITION NOTES
GENERAL NOTES
D07 (E) EXHAUST FAN TO BE REMOVED FROM THE EXISTING CURB AND PROTECTED
TO ALLOW FOR THE REROOF. INSPECT EXISTING BACKDRAFT DAMPER AND
LUBRICATE AND CLEAN DAMPER. LABEL FAN (STENCIL PAINT 2" HIGH LETTERS)
BEFORE REMOVAL. LABEL WITH CORRESPONDING NUMBERS LISTED ON PLANS.
PHOTO SEE
D11 (E) SCUPPER CONDUCTOR HEAD, TR, PHOTO SEE
H
MP801
1. WHERE PIPE SIZES ARE DIFFERENT THAN SHOWN, MATCH (E)SIZES TO
MAINTAIN THE SAME PIPE SIZE AS EXISTING CONDITIONS.
2. FIELD VERIFY EXACT HEIGHT OF EACH (E) CURB. IF TOP (E)CURB IS EQUAL
TO OR MORE THAN 8" ABOVE NEW FINISHED ROOF TOP, (E)UNIT ON THE
CURD CAN BE REMAIN IN PLACE AND PROTECTED DURING
CONSTRUCTION. INSTALL (N)FLASHING ON (E)CURB AFTER REROOFING.
D08 (E) ROOF VENT PIPE PENETRATION TO REMAIN. REMOVE/REPLACE
(E)FLASHING, EXTEND VENT THRU ROOF DUE TO NEW INSULATION HEIGHT.
TOTAL 29 VENT ON ROOF WITHIN CONSTRUCTION AREA. PHOTO SEE
D10 (E) 12X6 SCUPPER OPENING FOR LOW ROOF, TR, PHOTO SEE
H
MP801
G
MP801
D04 (E) SCUPPER OPENING FROM HIGH ROOM TO LOW ROOF, TBR, PHOTO SEE
B
MP801
F
MP801
D05 (E) AHU OR AC UNIT ON CURB TO BE TEMPORARILY REMOVED AND PROTECTED
TO ALLOW FOR THE REROOF. DISCONNECT ALL CONTROLS, PIPING, DRAINS,
AND DUCTING FOR REMOVAL. COORDINATE WITH CDCR REPRESENTATIVE FOR
CRANE IS REQUIRED TO MOVE UNIT. UNIT IS TO BE SET ON GROUND TO ALLOW
FOR NEW CURB ADAPTOR TO BE ADDED. LABEL UNIT (STENCIL PAINT 2" HIGH
LETTERS) BEFORE REMOVAL. LABEL WITH CORRESPONDING NUMBER ON PLAN.
SEE OR
C
MP801
D
MP801
D19
N
MP801
(E) WATER HEATER TO BE REMOVED FROM THE EXISTING CURB AND
PROTECTED TO ALLOW FOR THE REROOF. DISCONNECT ALL CONTROLS AND
PIPING PIPING, AND DRAIN TO EMPTY THE TANK FOR REMOVAL. LABEL UNIT
(STENCIL PAINT 2" HIGH LETTERS) BEFORE REMOVAL. LABEL WITH
CORRESPONDING NUMBER ON PLAN. SEE
D22 (E) DUCT THRU ROOF, TO BE TEMPORARY DISCONNECTED. FIELD MEASURE
DUCT SIZE. PHOTO SEE
O
MP801
(E)36X24 DUCT ON ROOF, TO REMAIN. DISCONNECT AND TEMPORARILY
REMOVE DURING RE-ROOFING, PROTECT IN PLACE. DUCT WILL BE
REQUIRED TO BE ON NEW SUPPORT. REPLACE WITH (N) DUCT AT SAME SIZE
IF NECESSARY. SIZE TO BE FIELD VERIFIED AND RECORD, PHOTO SEE
D20
O
MP801
(E) G, CW, HW, HWR UTR, TEMPORARY DISCONNECT DURING
CONSTRUCTION. PHOTO SEE
D21
N
MP801
D13 (E) CONDENSATE DRAIN PIPING ON ROOF, TEMPORARY REMOVED DURING
CONSTRUCTION. REMOVE ALL PIPING SUPPORT. PHOTO SEE
I
MP801
D14 (E) CONDENSATE DRAIN PIPING (D)THRU ROOF, TR. PHOTO SEE
I
MP801
D15 (E) INDUSTRIAL COLD WATER PIPING ON ROOF, TEMPORARY REMOVED DURING
CONSTRUCTION. REMOVE ALL PIPING SUPPORT. PHOTO SEE
J
MP801
D16 (E) INDUSTRIAL COLD WATER PIPING (D)THRU ROOF, TR. PHOTO SEE
L
MP801
D17 (E) MEDIUM PRESSURE NATURAL GAS PIPING ON ROOF, TEMPORARY REMOVED
DURING CONSTRUCTION. REMOVE ALL PIPING SUPPORT. PHOTO SEE
M
MP801
D16A (E) INDUSTRIAL COLD WATER PIPING PENETRATE INTO CURB, TEMPORARY
DISCONNECTED AND TO BE RE-ROUTED. PHOTO SEE
K
MP801
D18 (E) NATURAL GAS PIPING CONNECT TO AC OR AHU W/ PRESSURE REGULATOR.
TEMPORARY DISCONNECT DURING CONSTRUCTION. PHOTO SEE
M
MP801
MPA201
M E C
H A N
IC
A L P
L U M
B
IN
G
T Y P
IC
A L
H
O U S
IN
G U
N
IT
R O
O F P
L A
N D
E M
O L
IT
IO
N
BUILDING 332 BUILDING 331
N
N
N
BUILDING 333 BUILDING 335
N
BUILDING 336 BUILDING 337 BUILDING 338 BUILDING 339 BUILDING 3310 BUILDING 341 BUILDING 342 BUILDING 343 BUILDING 344
N
N N N
N
N
BUILDING 345
N N
N
N
BUILDING 348 BUILDING 349 BUILDING 3410
N N
N
(E)AHU-1 THRU 3 EXISTING HANDLING UNIT, "ENERGY LAB" UNIT W/
"REZNOR" NATURAL GAS FURNACE AND EVAP COOLER,
MODEL# AND DETAILED INFORMATION UNKNOWN.
(E)AC-1 EXISTING AIR CONDITIONING UNIT ON HIGH ROOF,
ROOF TOP UNIT W/ NATURAL GAS FURNACE,
MANUFACTURE, MODEL# AND DETAILED INFORMATION
UNKNOWN.
(E)EF-1 THRU 33 EXISTING EXHAUST FAN, UNIT MODEL# AND DETAILED
INFORMATION UNKNOWN.
(E)WH-1 EXISTING WATER HEATER ON HIGH ROOF.
"TURBOPOWER" LOW NOX CATEGORY I FAN-ASSISTED
STORAGE WATER HEATER, 500 LHE 250A-TPL, 250
GALLON, 399,000 BTU/HR NATURAL GAS INPUT,
4.5"-10.5" W.C. GAS INLET PRESSURE, 120V/1PH/60 HZ,
5AMPS.
NOTES:
1. NO AS-BUILT DRAWING FOR THE BUILDINGS. NAMEPLATE FOR
MOST UNITS CANNOT BE FOUND OR NOT READABLE. CONTRACTOR
SHALL FIELD VERIFY ACTUAL UNIT INFORMATION FOR EACH BUILDING.
2. MANY AHU'S WERE FOUND TO BE LEAKING. THEY MUST BE
REPAIRED PRIOR TO REROOFING.
EXISTING EQUIPMENT SCHEDULE
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/10/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-0002
1 61.8 2 3 4 5 7 118 9 10
B
C
B.4
F
D
E
H
G
J
K
K.8
L
M
1 111.8 2 3 4 5 6 7 8 9 105.7 7.3
A
B
B.7
D
E.7
G.3
J
K.7
L
M
K
H
E
C
F
G
D14
08 08 08 08 08 08 08 08
07 07 07 07 07 07 07 07
070808 080808 08 08 08 07070707 07 07 07 07
(E)AC-1
(E)AHU-1
(E)AHU-2
(E)AHU-3
(E)EF-1(E)EF-2 (E)EF-3 (E)EF-4
(E)EF-5
(E)EF-6 (E)EF-7 (E)EF-8 (E)EF-9
(E)EF-32
(E)EF-10
(E)EF-11
(E)EF-12
(E)EF-13
(E)EF-30
(E)EF-14
(E)EF-15
(E)EF-16
(E)EF-17
(E)EF-29
(E)EF-28
(E)EF-18 (E)EF-19 (E)EF-20 (E)EF-21 (E)EF-22 (E)EF-23 (E)EF-24 (E)EF-25 (E)EF-26
(E)EF-27
(E)EF-31
(E)EF-33
(E)WH-1
(E)1 14"CD
(E)1 14"CD
(E)114"CD
D14
(E)3 4"ICW
(E)3 4"ICW
(E)34"ICW
(E)112"MPG
(E)34"MPG
(E)34"MPG
(E)34"MPG
(E)3 4"CD
(E)3 4"MPG
16A
Project Engineer:
U R L E YT M E C H A N IC A L
E N G I N E E R I N G
G R O U P, I N C.& ASSOCIATES
(916) 325-1065
FAX: (916) 325-1075
Email: office@turleymech.com
2431 Capitol Avenue Sacramento, CA 95816
Project Manager:
GYang
Job Number:
Project Drafter: Login:
Plot Date: Aug 25, 2023 - 4:07pm
22107-PH1JT
JT
SHEET NUMBER
S
TA
TE
O F C A
LI
FO
R N
IA
D E P A R
TM
E N T
O F
C O
R R E C
TI
O
N S A
N D
R E H A B
IL
IT
A
TI
O N
FA
C
IL
IT
Y P
LA
N N
IN
G
, C O
N S
TR
U C
TI
O
N A
N D
M A N A G E M E N
T D
IV
IS
IO
N
DE
SI
G
N
SE
RV
IC
ES
A
ND
S
TA
ND
AR
DS
B
RA
NC
H
DE
SI
G
N
SE
RV
IC
ES
S
EC
TI
O
N
APPROVAL
V1
C A L
IF
O R
N
IA
S T A T E P
R
IS
O N L O
S A
N G E L E S C
O U N T Y
T H
S T R E E T , W
E S T
LA
N C A S T E R
, C A
R E P L A C E R
O O F S
P H A S E
A U G U
S T
W O
R K
IN
G
D R A W
IN
.1
A rc h it e ct s, I n c.
H
IB
S E R Y
A M
A U C
H I n d S tr e e t, S u it e
D a vi s, C
A
.7
.1 o ff ic e
.7
.4 f a x
MPA301
M E C
H A N
IC
A
L P
L U M
B
IN
G
T Y P
IC
A L
H
O U S
IN
G U
N
IT
R O
O F P
L A N
R E M
O D
E L
GENERAL NOTES
16A (E) INDUSTRIAL COLD WATER PIPING PENETRATE INTO CURB, TEMPORARY
DISCONNECTED, RE-ROUTED AND RECONNECTED. DETAIL SEE
18 RECONNECT (E) NATURAL GAS PIPING CONNECT TO AC OR AHU W/ (E)PRESSURE
REGULATOR. DETAIL SEE
1. PROVIDE START UP OF ALL EQUIPMENT TO ENSURE IT IS OPERATING
PROPERLY. SEE GENERAL MECHANICAL/PLUMBING NOTES ON MP001.
2. WHERE SIZES ARE LARGER THAN SHOWN, MATCH (E)SIZES TO
MAINTAIN THE SAME SIZE AS EXISTING CONDITIONS.
3. FIELD VERIFY EXISTING GAS PIPE MATERIAL AT EACH BUILDING.
MATERIAL OF NEW GAS PIPING AND FITTINGS SHALL MATCH EXISTING
PIPING MATERIAL.
4. FIELD VERIFY EXACT HEIGHT OF EACH (E) CURB. IF TOP (E)CURB IS
EQUAL TO ORMORE THAN 8" ABOVE NEW FINISHED ROOF TOP, (E)UNIT
ON THE CURD CAN BE REMAIN IN PLACE AND PROTECTED DURING
CONSTRUCTION. INSTALL (N)FLASHING ON (E)CURB AFTER
REROOFING.
RE-INSTALL (E) AHU ON (N) RAISED CURB. RECONNECT ALL CONTROLS, PIPING,
DRAINS AND DUCTING. PROVIDE EXACT MEASUREMENTS OF CURB FOR THE
ADDITION OF A CURB EXTENDER. VERIFY DUCT SIZE. MOUNTING DETAIL SEE
, PIPING (GAS,WATER AND DRAIN) CONNECTION SEE
05 RE-INSTALL (E) AC UNIT ON (N) RAISED CURB. RECONNECT ALL CONTROLS,
PIPING, DRAINGS AND DUCTING. VERIFY DUCT SIZE. PROVIDE EXACT
MEASUREMENTS OF CURB FOR THE ADDITION OF A CURB ADAPTOR. MOUNTING
DETAIL SEE , GAS PIPE CONNECTION DETAIL SEE ,
CONDENSATE DRAIN CONNECTION SEE
RE-INSTALL (E) EXHAUST FAN ON (N) RAISED CURB, PROVIDE EXACT
MEASUREMENTS OF CURB FOR THE ADDITION OF A CURB ADAPTOR. SEE
DETAIL
(N) PLUMBING VENT PIPE @ (E) PENETRATION, TOTAL 29 VENT ON ROOFWITHIN
CONSTRUCTION AREA. RAISE VENT TO MAINTAIN REQUIRED DISTANCE FROM
TOP OF VENT TO TOP OF ROOF. DETAIL SEE
(E) CONDENSATE DRAIN (D) THRU ROOF, RECONNECTED, PROVIDE NEW FLASHING
AND NEW OFFSET. DETAIL SEE
(E) CONDENSATE DRAIN PIPING, TO BE REINSTALLED. PROVIDE NECESSARY
OFFSET FOR NEW HEIGHT OF CURB. NEW PIPE SIZE IS TO MATCH EXISTING.
REPLACE (E)PIPING WITH SAME SIZE (N)PIPING IS ACCEPTABLE. PIPE SUPPORT
DETAIL SEE
(E) INDUSTRIAL COLD WATER PIPING, TO BE REINSTALLED. PROVIDE NECESSARY
OFFSET FOR NEW HEIGHT OF CURB. NEW PIPE SIZE IS TO MATCH EXISTING.
REPLACE (E)PIPING WITH SAME SIZE (N)PIPING IS ACCEPTABLE. PIPE SUPPORT
DETAIL SEE
(E) INDUSTRIAL COLD WATER PIPE (R) THRU ROOF, RECONNECTED, PROVIDE NEW
FLASHING AND NEW OFFSET. DETAIL SEE
(E) MEDIUM PRESSURE NATURAL GAS PIPING, TO BE REINSTALLED. PROVIDE
NECESSARY OFFSET FOR NEW HEIGHT OF CURB. NEW PIPE SIZE IS TO MATCH
EXISTING. REPLACE (E)PIPING WITH SAME SIZE (N)PIPING IS ACCEPTABLE. PIPE
SUPPORT DETAIL SEE
G
MP501
H,I
MP501
A
MP502
E
MP501
H
MP501
I
MP501
A
MP501
B
MP501
C
MP501
F
MP501
D
MP501
F
MP501
C
MP502
D
MP501
H
MP501
BUILDING 332 BUILDING 331
N
N
N
BUILDING 333 BUILDING 335
N
BUILDING 336 BUILDING 337 BUILDING 338 BUILDING 339 BUILDING 3310 BUILDING 341 BUILDING 342 BUILDING 343 BUILDING 344
N
N N N
N
N
BUILDING 345
N N
N
N
BUILDING 348 BUILDING 349 BUILDING 3410
N N
N
(E)AHU-1 THRU 3 EXISTING HANDLING UNIT, "ENERGY LAB" UNIT W/
"REZNOR" NATURAL GAS FURNACE AND EVAP COOLER,
MODEL# AND DETAILED INFORMATION UNKNOWN.
(E)AC-1 EXISTING AIR CONDITIONING UNIT ON HIGH ROOF,
ROOF TOP UNIT W/ NATURAL GAS FURNACE,
MANUFACTURE, MODEL# AND DETAILED INFORMATION
UNKNOWN.
(E)EF-1 THRU 33 EXISTING EXHAUST FAN, UNIT MODEL# AND DETAILED
INFORMATION UNKNOWN.
(E)WH-1 EXISTING WATER HEATER ON HIGH ROOF.
"TURBOPOWER" LOW NOX CATEGORY I FAN-ASSISTED
STORAGE WATER HEATER, 500 LHE 250A-TPL, 250
GALLON, 399,000 BTU/HR NATURAL GAS INPUT,
4.5"-10.5" W.C. GAS INLET PRESSURE, 120V/1PH/60 HZ,
5AMPS.
NOTES:
1. NO AS-BUILT DRAWING FOR THE BUILDINGS. NAMEPLATE FOR
MOST UNITS CANNOT BE FOUND OR NOT READABLE. CONTRACTOR
SHALL FIELD VERIFY ACTUAL UNIT INFORMATION FOR EACH BUILDING.
2. MANY AHU'S WERE FOUND TO BE LEAKING. THEY MUST BE
REPAIRED PRIOR TO REROOFING.
EXISTING EQUIPMENT SCHEDULE
REMODEL NOTES
(E) G, CW, HW, HWR UTR, RECONNECTED, PROVIDE (N)CURB ADAPTOR FOR
MULTIPLE PIPES OR (N)FLASHING FOR SINGLE PIPE. PROVIDE NECESSARY
OFFSET. SINGLE PIPE PENERTRATION DETAIL SEE
MULTIPLE PIPE PENETRATION DETAIL SEE
(E) 36X24 DUCT ON ROOF, REINSTALLED AND PROVIDE NEW DUCT SUPPORT.
DETAIL SEE
(E) DUCT THRU ROOF. PROVIDE NEW CURB EXTENSION AND EXTEND/MODIFY
DUCT. RE-INSULATE DUCT. DETAIL SEE
D
MP502
B
MP502
G
MP502
F
MP501
19 RE-INSTALL (E) WATER HEATER ON (N) CURBS. RECONNECT ALL CONTROLS
AND PIPING, MOUNTING DETAIL SEE AND ,WATER PIPE
CONNECTION DETAIL SEE ,
NATURAL GAS PIPE CONNECTION SEE
A906F
MP502
H
MP501
S501
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/10/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-0002
B
C
B.4
F
D
E
H
G
J
K
K.8
L
M
1 111.8 2 3 4 5 6 7 8 9 105.7 7.3
A
B
B.7
D
E.7
G.3
J
K.7
L
M
K
H
E
C
F
G
11 11 11
11 11 11
10 10 10
(AREA A1)(AREA A2)(AREA A3) (AREA A4)(AREA A5)
(AREA A15)
1150 SQ.FT. EQA
(AREA A14)(AREA A13) (AREA A12)(AREA A11)
650 SQ.FT.
EQA
(AREA A6)
250 SQ.FT.
EQA
(AREA A7)
250 SQ.FT.
EQA
(AREA A8)
200 SQ.FT.
EQA
(AREA A9)
450 SQ.FT.
EQA
(AREA A10)
10101010
1800 SQ.FT. EQA2200 SQ.FT. EQA 1600 SQ.FT. EQA1500 SQ.FT. EQA
1150 SQ.FT. EQA 1800 SQ.FT. EQA 2200 SQ.FT. EQA 1600 SQ.FT. EQA
1500 SQ.FT. EQA
OPEN END OF HIGH
ROOF TO LOW ROOF
Project Engineer:
U R L E YT M E C H A N IC A L
E N G I N E E R I N G
G R O U P, I N C.& ASSOCIATES
(916) 325-1065
FAX: (916) 325-1075
Email: office@turleymech.com
2431 Capitol Avenue
Sacramento, CA 95816
Project Manager:
GYang
Job Number:
Project Drafter: Login:
Plot Date: Aug 25, 2023 - 4:07pm
22107-PH1JT
JT
SHEET NUMBER
S
TA
TE
O
F C
A
LI
FO
R N
IA
D
E P A R
TM
E N
T O
F C
O R R
E C
TI
O
N S A
N D
R E H
A B
IL
IT
A
TI
O N
FA
C
IL
IT
Y P
LA
N
N
IN
G , C
O N
S
TR
U C
TI
O
N A
N D
M A N
A G
E M
E N
T D
IV
IS
IO
N
DE
SI
G N
SE
RV
IC
ES
A
ND
S
TA
ND
AR
DS
B
RA
NC
H
DE
SI
G
N
SE
RV
IC
ES
S
EC
TI
O N
APPROVAL
V1
C A L
IF
O R
N
IA
S T A T E P
R
IS
O N
L O
S A
N G
E L E S C
O U N
T Y
T H
S T R
E E T , W
E S T
LA
N
C A S T E R
, C A
R E P L A C
E R
O O
F S
P H
A S E
A U
G U S T
W O
R K
IN
G D
R A W
IN
.1
A rc h it e ct s, I n c.
H
IB
S E R Y
A M
A U C
H I n d S tr e e t, S u it e
D a vi s, C
A
.7
.1 o ff ic e
.7
.4 f a x
MPA302
P L U M
B
IN
G
T Y P
IC
A L
H
O U S
IN
G U
N
IT
R O
O F P
L A
N R
A
IN
W A
T E R
REMODEL KEY NOTES
#### EQA
NOTE
EQUIVALENT AREA OF ROOF AREA PLUS AREA OF VERTICAL
WALLS, PER CPC 1103.4, 2019.
PER US WEATHER BUREAU TECHNICAL PAPER NO.40 CHART 14:
100-YEAR 1-HOUR RAINFALL (INCH), LOCAL RAIN WATER FALL RATE
IS BETWEEN 0.5"/HR AND 1.0"/HR. WHILE CONSIDERING A SAFETY
FACTOR, 2"/HR RAINFALL IS USED IN THIS PROJECT.
PER 2022 CPC TABLE 1103.1 AND TABLE 1103.2, MAX PROTECTED
ROOF AREA OF PIPES ARE SHOWING BELOW:
PIPING MAX PROTECTED ROOF AREA (SQ.FT.)
SIZE HORIZONTAL SLOPE VERTICAL PIPING
(INCH) 1
8"/LF 1
4"/LF 1
2"/LF ROOF DRAIN, LEADER
2" - - - 1440 3" 1,644 2,320 3,288 4,400 4" 3,760 5,300 7,520 9,200 5" 6,680 9,440 13,360 17,300 6" 10,700 15,100 21,400 27,000
PER 2022 CPC 1101.12.2.1, WHEN SCUPPER OR SIDE OPENING IS
USED FOR OVERFLOW, HEIGHT OF OPENING SHALL BE NO LESS
THAN 4", AND WIDTH SHALL BE NO LESS THAN CIRCUMFERENCE OF
THE ROOF DRAIN REQUIRED FOR THE AREA SERVED.
AN ALTERNATIVE MEANS IS USING SCUPPER INSTEAD OF THE ROOF
DRAIN FOR THE PRIMARY RAINWATER DRAINAGE. ALTERNATIVE
MEANS IS UNDER THE AGREEMENT WITH OF CDCR PROJECT
MANAGER. IN THIS CASE, HEIGHT OF OPENING SHALL BE NO LESS
THAN 4", AND WIDTH SHALL BE NO LESS THAN CIRCUMFERENCE OF
THE ROOF DRAIN REQUIRED FOR THE AREA SERVED. WHERE ROOF
DRAIN AND SCUPPER ARE COMBINED, THE HEIGHT OF OPENING
MUST BE A MINIMUM OF TWICE THE REQUIRED HEIGHT (MIN OF 8").
THE ABOVE DATA ARE ONLY MINIMUM REQUIREMENT OF DRAINS
AND PIPES. THEY CAN BE OVERSIZED IN THE PROJECT.
RAIN WATER CALCULATION
FOR AREA A1 THRU A15, MAX TOTAL EQUIVALENT ROOF AREA IS
2,200 SQ.FT. A MIN 3" ROOF DRAIN OR MIN 10"Wx4"H SCUPPER
OPENING IS SUFFICIENT TO SUPPORT EACH AREA. MIN OVERFLOW
SIDE WALL OPENING IS 10"Wx4"H. THE NEW PRIMARY AND
SECONDARY SIDE WALL OPENINGS ARE MEET THE CODE
REQUIREMENT.
BUILDING 332 BUILDING 331
N
N
N
BUILDING 333 BUILDING 335
N
BUILDING 336 BUILDING 337 BUILDING 338 BUILDING 339 BUILDING 3310 BUILDING 341 BUILDING 342 BUILDING 343 BUILDING 344
N
N N N
N
N
BUILDING 345
N N
N
N
BUILDING 348 BUILDING 349 BUILDING 3410
N N
N
11 (E) SCUPPER CONDUCTOR HEAD
12 (N) SCUPPER CONDUCTOR HEAD, SIZE MATCH OTHER (E) CONDUCTOR HEAD
ON THE SAME WALL. INSTALLATION DETAILS SEE 4/S501.
10 (E) OR (N) PRIMARY SCUPPER AND (N)OVERFLOW SCUPPER FOR LOW ROOF.
EACH SCUPPER OPENING SHALL BE MIN 10"WIDE x 4"HIGH. THE LOCATION
OF (N) PRIMARY SCUPPER SHALL MATCH (E) OR (N)SCUPPER CONDUCTORS.
SEE ARCHITECTURAL DETAIL 28/A905.
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/10/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-0002
3 6 7 9 1110
C
E
F
G
H
K
K.8
L
1 112 5 9 105.7 7.3
B
D
E.7
J
M
1 1.8 2 4 5 8
B.4
A
B
D
J
M
1.8 3 4 6 7 8
A
B.7
G.3
K.7
L
(E) 3/4" CONDUIT UP
THROUGH ROOF
(E)
(R)
(E) (3) 3/4" CONDUITS
IN PITCH POCKET
(E) 1-1/2" CONDUIT UP
THROUGH ROOF
(E) (3) 3/4" CONDUITS
IN PITCH POCKET
(E) (2) 3/4" CONDUITS
IN PITCH POCKET
J
(E) (3) 3/4" CONDUITS
UP THROUGH ROOF
TO DUCT DETECTORS
AND CONTROLS
(E) 3/4" CONDUIT UP
THROUGH ROOF TO
J-BOX
(R)
(E) CONTROL
PANELS
(E) 1-1/2" CONDUIT UP
THROUGH ROOF
(E) (4) 3/4" CONDUITS
UP THROUGH ROOF
(E) MAIN CIRCUIT
BREAKER
DISCONNECT
J
(R)
(E) CONTROL
PANELS
(E) MAIN CIRCUIT
BREAKER
DISCONNECT
(E) 1-1/2" CONDUIT UP
THROUGH ROOF
(E) (4) 3/4" CONDUITS
UP THROUGH ROOF
(E) (3) 3/4" CONDUITS
UP THROUGH ROOF
TO DUCT DETECTORS
AND CONTROLS
(E) 3/4" CONDUIT UP
THROUGH ROOF TO
J-BOX
(E) (3) 3/4" CONDUITS
UP THROUGH ROOF
TO DUCT DETECTORS
AND CONTROLS
J
(E) 3/4" CONDUIT UP
THROUGH ROOF TO
J-BOX
(R)
(E) 1-1/2" CONDUIT UP
THROUGH ROOF
(E) (4) 3/4" CONDUITS
UP THROUGH ROOF
(E) CONTROL
PANELS
(E) MAIN CIRCUIT
BREAKER
DISCONNECT
EXISTING MECHANICAL UNIT TO BE DISCONNECTED FOR ROOF REPAIR. COORDINATE WITH
MECHANICAL. REINSTALL USING NEW ELECTRICAL CONDUIT, CONDUCTORS AND DEVICES.
CONDUIT SIZE, WIRING SIZE, QUANTITY AND TYPE SHALL MATCH EXISTING. SEE REMODEL PLAN
"1/EA301".
EXISTING NON-GFCI RECEPTACLE TO BE REPLACED. SEE REMODEL PLAN "1/EA301".
NUMBERED NOTES
GENERAL NOTES
1. PLACE ALL EXISTING ELECTRICAL CIRCUITS FEEDING EXISTING HVAC AND ELECTRICAL EQUIPMENT ON
ROOFTOP IN A "SAFE-OFF" CONDITION, PRIOR TO CONSTRUCTION. NO NEW LOADS ADDED TO
CIRCUITS.
2. REMOVE PORTIONS OF EXISTING CONDUITS AND WIRING NECESSARY TO RE-ROOF EXISTING
BUILDING.
3. DO NOT DAMAGE DURING CONSTRUCTION AND REUSE ALL EXISTING CIRCUITS, PROVIDE NEW HVAC DISCONNECTS, PROVIDE NEW WEATHERPROOF GFCI SERVICE RECEPTACLES TO REPLACE EXISTING
RECEPTACLES FOR REMODEL.
4. REMOVE EXISTING JUNCTION BOXES AND FLEX CONDUITS BACK TO ROOF PENETRATION POINT, AND DO NOT REUSE. REPLACE ALL ABOVE ROOF CONDUITS WITH NEW - WIRING SIZE, QUANTITY AND TYPE SHALL MATCH EXISTING. SPLICE IN POWER WIRING IS NOT ACCEPTABLE. NEW CONTROL WIRING TO HVAC EQUIPMENT MAY ONLY BE INSTALLED FOR THE RUN FROM THE EQUIPMENT CONTROL PANEL TO
THE NEAREST EXISTING TERMINATION POINT OR SPLICE LOCATION. INSTALL NEW EMT WITH
COMPRESSION FITTINGS AND LIQUID-TIGHT METAL CONDUIT TERMINATION AT THE MECHANICAL
EQUIPMENT .
5. DO NOT DAMAGE HVAC DUCTS WITH DUCT DETECTORS. MAINTAIN FIRE ALARM DEVICE AND CIRCUIT
DURING CONSTRUCTION.
6. DO NOT DAMAGE WP SERVICE RECEPTACLE BACK BOXES. REMOVE ANCHORING, AS NEEDED, TO
ALLOW MOVEMENT DURING ROOFING REPAIR. MAINTAIN CIRCUIT CONTINUITY AND RECEPTACLE
FUNCTIONALITY AFTER CONSTRUCTION.
7. REPLACE JUNCTION BOXES. REPLACEMENT BOX TO MATCH EXISTING TYPE AND SIZE.
SHEET NUMBER
S
TA
TE
O
F C
A
LI
FO
R N
IA
D E P A R
TM
E N T
O F
C O
R R E C
TI
O
N S A
N D
R E H
A B
IL
IT
A
TI
O N
FA
C
IL
IT
Y P
LA
N N
IN
G , C
O N S
TR
U C
TI
O
N A
N D
M A N A G
E M
E N
T D
IV
IS
IO
N
DE
SI
G N
SE
RV
IC
ES
A
ND
S
TA
ND
AR
DS
B
RA
NC
H
DE
SI
G
N
SE
RV
IC
ES
S
EC
TI
O N
APPROVAL
V1
C A L
IF
O R
N
IA
S T A T E P
R
IS
O N L O
S A
N G
E L E S C
O U N T Y
T H
S T R
E E T , W
E S T
LA
N C
A S T E R
, C A
.1
Electrical Engineers Lighting Designers
100 Howe Ave., Suite 235N
Sacramento, CA 95825-8217
PROJECT #:
www.mneilsengineering.com
Tel: (916) 923-4400
PROJECT MGR: Stuart LinGsa\
21318.21
08/29/2023
R E P L A C E R
O O
F S
P H
A S E
A U G
U S T
W O
R K
IN
G D
R A W
IN
1/8"=1'-0"
TYPICAL 270 HOUSING UNIT ROOF PLAN - DEMOLITION - ELECTRICAL1
EA201
EA201
T Y P
IC
A L
H
O U
S
IN
G U
N
IT
R O
O F P
L A
N D
E M
O L
IT
IO
N
E L E C
T R
IC
A L
5'
1/8" = 1'-0"
0 25'10' 15' 20'
GRAPHIC SCALE
BUILDING 332 BUILDING 331
N
N N
BUILDING 333 BUILDING 335
N
BUILDING 336 BUILDING 337 BUILDING 338 BUILDING 339 BUILDING 3310 BUILDING 341 BUILDING 342 BUILDING 343 BUILDING 344
N
N N N
N
N
BUILDING 345
N N
N
N
BUILDING 348 BUILDING 349 BUILDING 3410
N N
N
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/10/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-0002
B
C
B.4
F
D
E
H
G
J
K
K.8
L
M
1 111.8 2 3 4 5 6 7 8 9 105.7 7.3
A
B
B.7
D
E.7
G.3
J
K.7
L
M
K
H
E
C
F
G
(E) 3/4" CONDUIT UP
THROUGH ROOF
(E)
(E) (3) 3/4" CONDUITS
IN PITCH POCKET
(E) 1-1/2" CONDUIT UP
THROUGH ROOF
(E) (3) 3/4" CONDUITS
IN PITCH POCKET
(E) (2) 3/4" CONDUITS
IN PITCH POCKET
J
(E) 3/4" CONDUIT UP
THROUGH ROOF TO
J-BOX
(E) CONTROL
PANELS
(E) 1-1/2" CONDUIT UP
THROUGH ROOF
(E) (4) 3/4" CONDUITS
UP THROUGH ROOF
(E) MAIN CIRCUIT
BREAKER
DISCONNECT
J
WP
(E) CONTROL
PANELS
(E) MAIN CIRCUIT
BREAKER
DISCONNECT
(E) 1-1/2" CONDUIT UP
THROUGH ROOF
(E) (4) 3/4" CONDUITS
UP THROUGH ROOF
(E) 3/4" CONDUIT UP
THROUGH ROOF TO
J-BOX
J
(E) 3/4" CONDUIT UP
THROUGH ROOF TO
J-BOX
(E) 1-1/2" CONDUIT UP
THROUGH ROOF
(E) (4) 3/4" CONDUITS
UP THROUGH ROOF
(E) CONTROL
PANELS
(E) MAIN CIRCUIT
BREAKER
DISCONNECT
(E) (3) 3/4" CONDUITS
UP THROUGH ROOF
TO DUCT DETECTORS
AND CONTROLS
3 (E) (3) 3/4" CONDUITS
UP THROUGH ROOF
TO DUCT DETECTORS
AND CONTROLS
(E) (3) 3/4" CONDUITS
UP THROUGH ROOF
TO DUCT DETECTORS
AND CONTROLS
NUMBERED NOTES
GENERAL NOTES
1. EXTEND EXISTING CIRCUITS, WIRING AND CONDUITS AND RECONNECT TO EXISTING RELOCATED
MECHANICAL, LIGHTING AND ELECTRICAL EQUIPMENT. REUSE SAME CIRCUIT TO FEED SAME
MECHANICAL AND ELECTRICAL EQUIPMENT, AS PRIOR TO CONSTRUCTION. MAINTAIN EXISTING
CIRCUIT CONTINUITY AND EQUIPMENT FUNCTIONALITY. ALL ABOVE ROOF CONDUIT AND WIRING MUST BE REPLACED WITH NEW . WIRE SIZE, QUANTITY AND TYPE SHALL MATCH EXISTING. SPLICE IN POWER WIRING IS NOT ACCEPTABLE. NEW CONTROL WIRING TO HVAC EQUIPMENT MAY ONLY BE INSTALLED
FOR THE RUN FROM THE EQUIPMENT CONTROL PANEL TO THE NEAREST EXISTING TERMINATION
POINT OR SPLICE LOCATION INSTALL NEW EMT WITH COMPRESSION FITTINGS AND LIQUID-TIGHT
FLEXIBLE METAL CONDUIT TERMINATION AT THE MECHANICAL EQUIPMENT.
2. REPLACE EXISTING DISCONNECT/MANUAL STARTERS WITH NEW TO FEED SAME HVAC, AS PRIOR TO
CONSTRUCTION. NEW DISCONNECT/STARTER TO MATCH EXISTING TYPE, VOLTAGE, PHASE, AND
CURRENT RATING. REPLACE ALL EXISTING WEATHERPROOF GFCI SERVICE RECEPTACLES WITH NEW
WP/WR/GFCI RECEPTACLES THAT ARE TO CURRENT CODE.
3. PROVIDE NEW WEATHERPROOF, NEMA 3R JUNCTION BOXES AND WATERTIGHT FLEX CONDUITS FOR EACH MECHANICAL AND ELECTRICAL EQUIPMENT. KEEP EXISTING CONDUIT PENETRATIONS AT THE
SAME LOCATIONS AS PRIOR TO CONSTRUCTION.
4. PROVIDE BLOCKING AND CHANNELS TO CONDUIT RACEWAY AS NEEDED ON ROOFTOP. COORDINATE
WITH MECHANICAL AND PLUMBING CONTRACTORS FOR JOINT USE BLOCKING. SEE "2/E9.001"
REINSTALLED MECHANICAL UNIT. RECONNECT EXISTING POWER AFTER ROOFING REPLACEMENT.
SEE DETAIL "1/E9.001" ON SHEET E9.001.
REPLACE EXISTING RECEPTACLE WITH NEW GFCI, WEATHER PROOF, WEATHER RESISTANT
RECEPTACLE.
LOCATE AND INTERCEPT EXISTING CIRCUIT AND CONTROLS BELOW ROOF DECK. SPLICE AND
EXTEND TO RAISED EQUIPMENT AND RE-CONNECT. TYPICAL FOR ALL MECHANICAL UNITS
MOUNTED ON RAISED ROOF.
PROVIDE NEW GFCI, WEATHER PROOF, WEATHER RESISTANT RECEPTACLE WITH METAL
WHILE-IN-USE COVER. CONNECT TO THE EXISTING ROOF RECEPTACLE CIRCUIT.
ALL CONDUIT RUN EXPOSED ON THE ROOF SHALL BE SUPPORTED PER DETAIL "2/E9.001".
SUPPORT SPACING SHALL BE PER DETAIL "2/E9.001", NOTES 1 AND 2.
SHEET NUMBER
S
TA
TE
O
F C
A
LI
FO
R N
IA
D E P A R
TM
E N T
O F
C O
R R E C
TI
O
N S A
N D
R E H
A B
IL
IT
A
TI
O N
FA
C
IL
IT
Y P
LA
N N
IN
G , C
O N S
TR
U C
TI
O
N A
N D
M A N A G
E M
E N
T D
IV
IS
IO
N
DE
SI
G N
SE
RV
IC
ES
A
ND
S
TA
ND
AR
DS
B
RA
NC
H
DE
SI
G
N
SE
RV
IC
ES
S
EC
TI
O N
APPROVAL
V1
C A L
IF
O R
N
IA
S T A T E P
R
IS
O N L O
S A
N G
E L E S C
O U N T Y
T H
S T R
E E T , W
E S T
LA
N C
A S T E R
, C A
.1
Electrical Engineers Lighting Designers
100 Howe Ave., Suite 235N
Sacramento, CA 95825-8217
PROJECT #:
www.mneilsengineering.com
Tel: (916) 923-4400
PROJECT MGR: Stuart LinGsa\
21318.21
08/29/2023
R E P L A C E R
O O
F S
P H
A S E
A U G
U S T
W O
R K
IN
G D
R A W
IN
1/8"=1'-0"
TYPICAL 270 HOUSING UNIT ROOF PLAN - REMODEL - ELECTRICAL1
EA301
EA301
T Y P
IC
A L
H
O U
S
IN
G U
N
IT
R O
O F P
L A
N R
E M
O D
E L
E L E C
T R
IC
A L
5'
1/8" = 1'-0"
0 25'10' 15' 20'
GRAPHIC SCALE
BUILDING 332 BUILDING 331
N
N N
BUILDING 333 BUILDING 335
N
BUILDING 336 BUILDING 337 BUILDING 338 BUILDING 339 BUILDING 3310 BUILDING 341 BUILDING 342 BUILDING 343 BUILDING 344
N
N N N
N
N
BUILDING 345
N N
N
N
BUILDING 348 BUILDING 349 BUILDING 3410
N N
N
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
10/10/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-0002