13_-_Plan_Sheets_1.pdf

PDF 6 MB Posted

Attached to
FPCM-LAC-I001104-M047-CS/ Complete Roof System
Solicitation number
0000039915
Issued by
Los Angeles County, California

About this file

Summary of Plan Sheets for California State Prison Los Angeles County Roof Replacement Project

This is a comprehensive set of architectural and engineering plan sheets for Phase 1 of a roof replacement project at California State Prison, Los Angeles County (CDCR), located at 44750 60th Street, West Lancaster, California 93536. The project involves replacing roofs on 18 typical 270-housing unit buildings (Buildings 331–345, 348–349, and 3410) with an 80 mil, fully-adhered Class A, UL 790 PVC roofing system over 1/2-inch protection board and 6-inch minimum rigid insulation. The scope of work includes demolition of existing built-up roofing systems, repair and patching of metal deck substrates, removal and reinstallation of mechanical units, exhaust fans, water heaters, and associated roof penetrations, as well as installation of new metal coping, flashing, scuppers, guard rails, roof hatches, walk pads, parapet extensions, and condensate and plumbing systems. The project document is dated August 31, 2023, with Office of the State Fire Marshal approval granted on October 10, 2023, for fire and panic code compliance only, with final approval subject to field inspection. Project number 5843.10 is managed by Hibserayamauchi Architects, Inc., with structural engineering by a registered California state engineer and mechanical/plumbing design by Turley Mechanical Engineering Group, Inc., with electrical design by M. Neilsen Engineering.

The plan sheets include detailed demolition and remodel keynotes, general construction notes requiring all debris removal in compliance with local, state, and federal codes, protection of building and utilities during work, repair of damaged areas to match existing finishes, and coordination with plant operations and the head of maintenance. Gas line reconnections must be inspected and tested per CPC 1213, CMC 1303, and NFPA 54. All existing mechanical units, including AHUs, exhaust fans, and a 250-gallon water heater, are to be temporarily removed, labeled, stored, and protected for reinstallation in working order, with verification meetings scheduled before and after work completion. Roof drainage calculations are provided based on a 2-inch per hour rainfall rate per CPC standards, with equivalent areas ranging from 200 to 2,200 square feet, requiring 3-inch roof drains or 10-inch by 4-inch scupper openings. Electrical work includes disconnection and reconnection of HVAC circuits, conduit replacement, and installation of new weatherproof GFCI receptacles. Wind uplift design zones are identified with field values of 60 PSF (field), 75 PSF (perimeter), and 105 PSF (corners), with a safety factor of 2 included.

View the file

Other files

File Type Posted
13_-_Plan_Specs.pdf PDF
12_-_FPCM-LAC-I001104-M047-CS.pdf PDF
13_-_Plan_Sheets_2.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

12'-0" 13'-0" 13'-0" 13'-0" 13'-0"13'-0" 13'-0"13'-0"5'-8" 13'-0"11'-2"

DN

3 1 1.8 2 6 4 5 7 8 9 1110

B.4

A

B

D

C

J

E

F

G

H

K

K.8

L

M

1 111.8 2 3 4 5 6 7 8 9 10 5.7 7.3

A

B

B.7

D

E.7

G.3

J

K.7

L

M

134'-2"

1'-4"

2'-2"

(E

S L O

P E

/4

(E) SLOPE

1/4" : 1'-0"

(E

S L O

P E

/4

(E

S L O

P E

/4

(E

S L O

P E

/4

(E

S L O

P E

/4

( E

S L O

P E

/4

RIDGE

D04

TYP

D01

TYP

D01

TYP

D01

TYP

D01

TYP

D02

TYP

D01

D15

D14

D17

D01

TYP

D02

TYP

D03

D09

D14

D10

TYP

D07

TYP

D13

TYP

D18

D05

D07

TYP

D05

TYP

D05

D05

D19

D10

TYP

D06

TYP

D06

TYP

D16

D14

D13

TYP

D13

TYP

D04

TYP

D08

TYP

D08

TYP

D04

TYP

D21

D11

TYP

D11

TYP

D11

TYP

D12

D12

D14

D02

TYP

D07

TYP

D14

D18

(E) SCUPPER AT HIGHER ROOF TO BE REMOVED.

GENERAL NOTES

1. ALL CONSTRUCTION DEBRIS GENERATED IN THE COURSE OF THIS PROJECT SHALL

BE REMOVED AND DISPOSED OF IN COMPLIANCE WITH ALL LOCAL, STATE AND

FEDERAL CODES AND REGULATIONS.

2. REPAIR/REPLACE ANY DAMAGED UTILITIES DURING THE COURSE OF WORK.

3. PROTECT BUILDING FROM DAMAGE WHICH MAY OCCUR FROM DEMOLITION, DUST,

WATER, ADVERSE WEATHER, ETC.

4. CONTRACTOR TO PATCH AND REPAIR ALL AREAS DAMAGED BY, OR INCIDENTAL TO

DEMOLITION AND/OR NEW WORK TO MATCH ADJACENT FINISHES UNLESS

OTHERWISE NOTED.

5. REPLACE ALL (E) CONDUIT & PIPE SUPPORTS ON ROOF W/ (N) HARD PIPE SUPPORT

BLOCK. SED & SMD.

6. REMOVE (E) CONDUIT OR PIPE IN CONFLICT WITH THE INSTALLATION OF (N) WORK.

REINSTALL AFTER COMPLETION OF (N)WORK.

7. REMOVE ALL (E) MECHANICAL UNITS, VENTS, AND FANS AS REQUIRED TO PERFORM

ROOFING AND FLASHING WORK. STORE AND PROTECT UNITS FOR REINSTALL TO

WORKING ORDER. SCHEDULE MEETING WITH HEAD OF MAINTENANCE AND

CONTRACTOR TO VERIFY WORKING ORDER OF HVAC SYSTEM PRIOR TO WORK AND

ONCE WORK IS COMPLETE.

8. PROTECT ELECTRICAL BOXES.

9. ALL INFORMATION SHOWN ON THE DRAWING RELATIVE TO (E) CONDITIONS IS GIVEN

AS THE BEST PRESENT KNOWLEDGE . WHERE ACTUAL CONDITIONS CONFLICT WITH

THE DRAWING, THEY SHALL BE REPORTED TO THE ARCHITECT SO THAT THE

CORRECTIONS/CLARIFICATIONS CAN BE PROVIDED.

10. ALL DIMENSIONS ARE TO BE VERIFIED IN FIELD.

11. COORDINATE WITH PLANT OPS BEFORE AND AFTER SHUTTING OFF ANY UTILITIES.

12. ANY GAS LINES THAT HAVE BEEN DISCONNECTED AND RECONNECTED, SHALL BE

INSPECTED AND TESTED FOR LEAKAGE IN ACCORDANCE WITH CPC 1213, CMC 1303

AND NFPA 54.

13.PAINT ALL (N) TRIMS AND FLASHING TO MATCH (E) COLOR.

14.ALL FIRE RETARDANT TREATED WOOD SHALL BE INSPECTED PRIOR TO COVERING.

MATERIAL SHALL BEAR A LABEL THAT INDICATES ITS LISTING.

EQUIPMENT LEGEND

* NOTE: QUANTITY IS APPROXIMATE, VIF

(E) VENT PIPES TO RECEIVE BOOT FLASHING

SEE DETAIL

(E) EXHAUST FAN OVER (N) CURB ADAPTER,

SEE DETAIL

QTY.SYMBOL DESCRIPTION

DEMOLITION LEGEND

AREA OF (E) BUILT-UP ROOFING SYSTEM TO BE REMOVED,

INCLUDING RIGID INSULATION, COUNTER FLASHING,

FLASHING AROUND PENETRATIONS, ETC. (E)METAL DECK

WITH LIGHT WEIGHT CONCRETE TOPPING TO BE PATCHED

AND REPAIRED AS REQUIRED TO PREPARE STRUCTURE

FOR NEW ROOF SYSTEM.

(E) FUEL GAS PIPING, SMD.

(E) WALKPAD TO BE REMOVED

(E) BUILDING FOOTPRINT BELOW.

32 PER ROOF

32 PER ROOF

(E) CONDENSATE LINE, SMD.

(E) ELECTRICAL CONDUIT, SED.

(E) CAT WALK

DEMOLITION KEYNOTES

(E) PARAPET COPING CAP TO BE REMOVED AND RECYCLED. INSPECTED FOR

WATER DAMAGE.

REMOVE (E) MECHANICAL UNIT AND CURB. STORE AND PROTECT FOR

REINSTALLATION. SMD.

D01

D02

D04

D05

D06

D07

D08

D09

D10

D11

(E) ROOF VENT PIPE TO REMAIN. REMOVE (E) FLASHING. EXTEND TO 12" AFR

WHERE NECESSARY.

DEMOLISH (E) WALK PADS/PAVERS, TYP.

D12

(E) SCUPPER AT LOWER ROOF TO REMAIN.

D13

REMOVE AND PROTECT (E) EXHAUST FAN FOR REINSTALLATION, SMD.

(E) ROOF MOUNTED CONDENSATE PIPE ON SUPPORT BLOCK TO BE REMOVED

AND REPLACED. SMD.

REMOVE (E) CRICKET.

(E) ELECTRICAL CONDUIT TO BE REMOVED AND RE-INSTALLED, SED.

D14 (E) GUARDRAIL TO BE REMOVED.

D15

D16

D03 (E) STAIRCASE TO REMAIN.

REMOVE AND REINSTALL (E) STAIR CAGE

D17

D18

(E) CATWALK TO BE REMOVED. CONDITION AT STAIRS OCCURS AT ALL

BUILDINGS. CONDITION ALONG PARAPET OCCURS AT BUILDINGS 331, 333, 335,

348, AND 3310.

(E) CURB TO REMAIN, EXTEND AS REQUIRED.

(E) ROOF HATCH TO BE REMOVED.

REMOVE (E) WATER HEATER ON CURB. STORE AND PROTECT FOR

REINSTALLATION. SMD.

D19

(E) AHU DUCT SUPPORT AND BRACE TO BE REMOVED AND REPLACED, SMD

REMOVE AND PROTECT (E) TRANSITION LADDER

D20

REMOVE (E) GRAB BAR.D20

TYPICAL 270 HOUSING UNIT ROOF PLAN DEMOLITION

SCALE: 1/8" = 1'-0"

SHEET NUMBER

V1

AA201

BUILDING 332 BUILDING 331 BUILDING 333 BUILDING 335 BUILDING 336 BUILDING 337 BUILDING 338 BUILDING 339 BUILDING 3310 BUILDING 341 BUILDING 342 BUILDING 343 BUILDING 344 BUILDING 345 BUILDING 348 BUILDING 349 BUILDING 3410

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/10/23

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

23-0002

11/20/2023 CASp 491 #1317

12'-0" 13'-0" 13'-0" 13'-0" 13'-0"13'-0"13'-0"13'-0"5'-8" 13'-0"11'-2"

DN

1 61.8 2 3 4 5 7 118 9 10

A

B

C

B.4

F

D

E

H

G

J

K

K.8

L

M

1 111.8 2 3 4 5 6 7 8 9 10 5.7 7.3

A

B

B.7

D

E.7

G.3

J

K.7

L

M

134'-2"

1'-4"

2'-2"

S L O

P E

/2

(E

S L O

P E

/4

(E

S L O

P E

/4

(E

S L O

P E

/4

K

H

E

C

F

G

(E

S L O

P E

/4

RIDGE

SLOPE

1/2":1'-0"

S L O

P E

/2

26'-0"

REMODEL KEYNOTES

(N) METAL COPING AT (E) PARAPET, SEE DETAIL

A902

(N) 36" WIDE WALK PAD, 72" WIDE AROUND MECHANICAL EQUIPMENTS06

A900

(E) EXHAUST FAN, REINSTALLED OVER NEW RAISED CURB, SMD.

(N) BOOT FLASHING AT (E) VENT PIPE

(N) CONDENSATE PIPE ON (N) SUPPORT BLOCK, SMD.

(N) CRICKET

(N) OVERFLOW SCUPPER

A900

A902

A902

12 (N) BOOT FLASHING AT (E) ELECTRICAL CONDUIT PIPE, SED

(RE) ELECTRICAL CONDUIT ON NEW SUPPORT BLOCK, SEE DETAIL14

(N) PRIMARY SCUPPER AT LOWER ROOF

A900

A900

GENERAL NOTES

1. ALL CONSTRUCTION DEBRIS GENERATED IN THE COURSE OF THIS PROJECT SHALL

BE REMOVED AND DISPOSED OF IN COMPLIANCE WITH ALL LOCAL, STATE AND

FEDERAL CODES AND REGULATIONS.

2. REPAIR/REPLACE ANY DAMAGED UTILITIES DURING THE COURSE OF WORK.

3. PROTECT BUILDING FROM DAMAGE WHICH MAY OCCUR FROM DEMOLITION, DUST,

WATER, ADVERSE WEATHER, ETC.

4. CONTRACTOR TO PATCH AND REPAIR ALL AREAS DAMAGED BY, OR INCIDENTAL TO

DEMOLITION AND/OR NEW WORK TO MATCH ADJACENT FINISHES UNLESS

OTHERWISE NOTED.

5. REPLACE ALL (E) CONDUIT & PIPE SUPPORTS ON ROOF W/ (N) HARD PIPE SUPPORT

BLOCK. SED & SMD.

6. REMOVE (E) CONDUIT OR PIPE IN CONFLICT WITH THE INSTALLATION OF (N) WORK.

REINSTALL AFTER COMPLETION OF (N) WORK.

7. REMOVE ALL (E) MECHANICAL UNITS, VENTS, AND FANS AS REQUIRED TO PERFORM

ROOFING AND FLASHING WORK. STORE AND PROTECT UNITS FOR REINSTALL TO

WORKING ORDER. SCHEDULE MEETING WITH HEAD OF MAINTENANCE AND

CONTRACTOR TO VERIFY WORKING ORDER OF HVAC SYSTEM PRIOR TO WORK AND

ONCE WORK IS COMPLETE.

8. PROTECT ELECTRICAL BOXES.

9. ALL INFORMATION SHOWN ON THE DRAWING RELATIVE TO (E) CONDITIONS IS GIVEN

AS THE BEST PRESENT KNOWLEDGE . WHERE ACTUAL CONDITIONS CONFLICT WITH

THE DRAWING, THEY SHALL BE REPORTED TO THE ARCHITECT SO THAT THE

CORRECTIONS/CLARIFICATIONS CAN BE PROVIDED.

10. ALL DIMENSIONS ARE TO BE VERIFIED IN FIELD.

11. COORDINATE WITH PLANT OPS BEFORE AND AFTER SHUTTING OFF ANY UTILITIES.

12. ANY GAS LINES THAT HAVE BEEN DISCONNECTED AND RECONNECTED, SHALL BE

INSPECTED AND TESTED FOR LEAKAGE IN ACCORDANCE WITH CPC 1213, CMC 1303

AND NFPA 54.

13.PAINT ALL (N) TRIMS AND FLASHING TO MATCH (E) COLOR.

14.ALL FIRE RETARDANT TREATED WOOD SHALL BE INSPECTED PRIOR TO COVERING.

MATERIAL SHALL BEAR A LABEL THAT INDICATES ITS LISTING.

EQUIPMENT LEGEND

* NOTE: QUANTITY IS APPROXIMATE, VIF

(E) VENT PIPES TO RECEIVE BOOT FLASHING

SEE DETAIL

(E) EXHAUST FAN OVER (N) CURB ADAPTER,

SEE DETAIL

QTY.SYMBOL DESCRIPTION

32 PER ROOF

32 PER ROOF

TYP

TYP

(N) 38"x42" ROOF HATCH WITH RAIL GUARD, SEE DETAILS

(RE) TRANSITION LADDER, SEE DETAIL

(N) GUARDRAIL, SEE DETAIL

A902

A904

A901

TYP

TYP

TYP

REMODEL LEGEND

(N) 80 MIL, FULLY-ADHERED (CLASS A, UL 790) PVC

ROOFING SYSTEM OVER 1/2" PROTECTION BOARD

OVER 6" MIN RIGID INSULATION. PROVIDE NEW

FLASHING FOR ALL (E) ROOF PENETRATIONS.

COORDINATE RE-ROOFING WITH (E) UTILITIES AND

ELECTRICAL CONDUITS.

(N) PVC WALKPAD COMPATIBLE W/ (N) MEMBRANE.

SURFACE MUST BE 36" MIN. WIDE, AND INCREASED TO 72"

MIN. WIDE WHERE INDICATED AT MECHANICAL

EQUIPMENT.

(E) BUILDING FOOTPRINT BELOW.

(N) CMU PARAPET EXTENSION.

(E) FUEL GAS PIPING, SMD.

(E) CONDENSATE LINE, SMD.

(E) ELECTRICAL CONDUIT, SED.

(N) METAL STUD PARAPET EXTENSION.

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

05 05

TYP

TYP

TYP

TYP

TYP

(N) EDGE TRANSITION CONDITION AT HIGH ROOF

(E)STAIR CAGE TO BE REINSTALLED.

EXTENDED CURB.

A901

05 (E) MECHANICAL UNIT RE-INSTALLED OVER (N) RAISED CURB. SMD.

TYP

21 (N) PLUMBING ACCESS DOOR, SEE DETAIL

A901

22 (E) MECHANICAL DUCT TO BE RE-INSTALLED. SMD.

AA501

AA601

AA601

TYP

TYP

TYP

TYP

TYP

TYP

REINSTALL (E) WATER HEATER ON CURB, SMD.23

24 AHU DUCT SUPPORT AND BRACE, SMD

25 PITCH POCKET, SMD

TYP

TYP

TYP

AA501

AA501

AA501

A903

(N) CROSS OVER BRIDGE, SEE DETAIL

A902

TYP

TYP

REINSTALL (E) METAL GRATING

A900 SIM.

(N) PARAPET EXTENSION. SSD &

A900

A901

(V

IF

26 (E) PRIMARY SCUPPER TO REMAIN.

A905

A903

T Y P

6'-0"

TYP

3' -0

TY

P

TYP

TYP

TYP

TYP

TYP

TYP

A900

27 TRANSITION STRIP AT PARAPET WALL. SEE DETAIL

A905

28 ROOF RAKE. SEE DETAIL

A901

8'-8"

±5'-6"

±5'-1"

±5'-1"

±5 '-4

6'-0"

TYP

T Y P

A902

TYPICAL 270 HOUSING UNIT ROOF PLAN REMODEL

SCALE: 1/8" = 1'-0"

SHEET NUMBER

V1

AA301

BUILDING 332 BUILDING 331 BUILDING 333 BUILDING 335 BUILDING 336 BUILDING 337 BUILDING 338 BUILDING 339 BUILDING 3310 BUILDING 341 BUILDING 342 BUILDING 343 BUILDING 344 BUILDING 345 BUILDING 348 BUILDING 349 BUILDING 3410

V1

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/10/23

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

23-0002

RENEWAL

DATE

H I

C

U

AY

N

E K

RENEWAL

S

I L

T

AI

C

DATE

H I

C

U

MAAY

N

E K

H C

U

MAAY

NNNNNNNNNN

E K

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/10/23

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

23-0002

0'-0"

T.O. 1ST FLR

18'-6"

T.O. (E) PRECAST

CONCRETE WALL

TYP.

4"

6"

AB C D E F G H J K L M K.7 G.4 E.7 B.3

115.7 6 7 7.3 8 9 10 4 2 1.8 1 3 5

/2

/2

0'-0"

T.O. 1ST FLR

18'-6"

T.O. (E) PRECAST

CONCRETE WALL

21'-6"

T.O. (E) PRECAST PANEL

TYP.

TYP.

03 0807

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

HOUSING UNIT BUILDING SECTION

SCALE: 1/8" = 1'-0"

HOUSING UNIT BUILDING SECTION

SCALE: 1/8" = 1'-0"

AA601

SHEET NUMBER

V1

BUILDING SECTION KEYNOTES

(N) METAL COPING AT PARAPET, SEE DETAIL

(E) EXHAUST FAN, REINSTALLED OVER NEW RAISED CURB, SMD.

(N) CRICKET

A-900

(N) PRIMARY SCUPPER AT LOWER ROOF

(N) ROOF HATCH, SEE DETAIL

(N) GUARDRAIL, SEE DETAIL

(E) MECHANICAL UNIT RE-INSTALLED OVER (N) RAISED CURB. SMD.

(N) 80 MIL, FULLY-ADHERED (CLASS A, UL 790) PVC ROOFING SYSTEM

OVER 1/2" PROTECTION BOARD OVER 6"MIN RIGID INSULATION.

(E) METAL DECK WITH CONCRETE FILL.

10 (E) PRECAST CONCRETE PLANK W/ CONCRETE TOPPING.

A901 TYP.

A-902

A-900

A900

A900

A902

A901

11 (E) STAIR CAGE TO BE REINSTALLED.

A901

A906

A906

SIM.

V1

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/10/23

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

23-0002

7.3

7.3

5.7

5.7

1.8

1.8

A A

B B

C C

D D

E E

F F

G G

H H

J J

K K

K.8 K.8

L L

M M

B.4 B.4

11'-2" 5'-8" 13'-0" 13'-0" 13'-0" 8'-0" 5'-0" 13'-0" 5'-0" 8'-0" 13'-0" 13'-0" 13'-4"

134'-2"

'-8

'-2

'-0

'-0

'-0

'-0

'-0

'-0

'-0

'-0

'-0

'-2

(E) 4" PRECAST

CONC SLAB

'-6

T.

O

E) 6"

C O

NC

W

AL

L

TY

P U

NO

21'-6"

T.O

. (E) 8" CO

NC W

ALL

(E) 3 1/4" LW CONC

OVER 3"MTL DECK

'-6

T.

O

E) 8"

C O

NC

W

AL

L

'-6

T.

O

E) 8"

C O

NC

W

AL

L

(E) WF FRMG TYP

(N) GUARDRAIL PER

SEE ARCH PLAN

S501

(N) SCUPPER PER

SEE ARCH PLAN

S501

(N) GUARDRAIL PER

SEE ARCH PLAN

S501

(N) GUARDRAIL PER

SEE ARCH PLAN

S501

(N) SCUPPER PER

SEE ARCH PLAN

S501

(N) ACCESS

PANEL PER ARCH

RE-INSTALL (E) MECH

UNIT OVER (N) RAISED

CURB, PER

TYP SEE

MECH

RE-INSTALL (E) UNIT

BRACING, TYP SEE MECH

(N) ACCESS PANEL

PER ARCH

RE-INSTALL (E)

STAIR CAGE PER

SEE ARCH PLAN

(N) SCUPPER PER

SEE ARCH PLAN

S501

(N) GUARDRAIL PER

SEE ARCH PLAN

S501

A

S301

SA201

'-6

T.

O

E) 8"

C O

NC

W

AL

L

'-6

T.

O

E) 8"

C O

NC

W

AL

L

WALL EXTENSION PER

SEE ARCH PLAN

S501

S501

1 7 11

A

E

H

M

16'-0"

'-0

13'-0"

'-0

'-0

NOTES:

1. CONSTRUCTION SEQUENCE

A. REMOVE EXISTING ROOFING PER ARCHITECTURAL DRAWINGS.

B. INSPECT EXISTING STRUCTURAL ELEMENTS FOR DETERIORATION.

C. IFCONCRETE SUBSTRATE SHOWS EXCESSIVEDETERIORATION REPAIR

PER 1/S501 OR NOTIFY THEARCHITECT AND STRUCTURAL ENGINEER

FOR FURTHER DIRECTION. FURTHER REPAIRS TO ANY DETERIORATION OR

SPALLING WILL BEEVALUATED AND DETAILEDON A CASE-BY CASE BASIS

DEPENDING ON THE TYPE ANDEXTENT, OR THE REPAIRS NEEDED.

D. PLACE NEW ROOFING PER ARCHITECTURAL DRAWINGS.

2. SEE KEY PLAN 1/SA201 FOR ROOFING WIND UPLIFT VALUES.

3. INDICATES EXTENSION OF (E) PARAPET, SEE

4. EXCESSIVE DETERIORATION:

A. FOR CONCRETEEXCESSIVE DETERIORATION IS DEFINED AS HAVING

SPALLEDSECTIONS OFCONCRETE LARGER THAN 3" ACROSS, OR HAVING

CRACKING 1/8"WIDE x 3' LONGOR GREATER.

B. FOR METAL DECKING EXCESSIVE DETERIORATION IS DEFINED AS HAVING

FLAKING RUST WHERE THEREMAINING THICKNESS IS LESS THAN 90% OF

ORIGINAL DECK THICKNESS, OVER AN AREA GREATER THAN 1 SQ FOOT.

C. FOR STRUCTURAL STEEL EXCESSIVE DETERIORATION IS DEFINED AS

HAVING FLAKING RUST WHERE THEREMAINING THICKNESS IS LESS THAN

95% OF ORIGINAL MEMBER THICKNESS.

1. WIND UPLIFT VALUES INCLUDE A SAFETY FACTOR OF 2.

LEGEND:

ZONE 1 - FIELD (60 PSF)

ZONE 2 - PERIMETER (75 PSF)

ZONE 3 - CORNERS (105 PSF)

1 21.8

A

B

1'-8" 1'-10"

TY

P

HS

S3 x3 x1

/4

(E ) C

AG

E

PO

ST

T

YP

REMOVE AND

REINSTALL (E)

STAIR CAGE

B

S301

B

S301

A

S301

C

S301

H S S x3 x1 /4

F L A T

H S S x3 x /4

F L A T

HSS12x3x1/4 FLAT

S

S TATE OF CALI FOR N I A

STRUCTURAL

R

EFORP

DERETSI

GE

SI N

ENGINEER

O AL

DE

PA

R T M

EN

T

OF

CO

RRE

CTIONS AND

REHAB

IL

ITA

T

IO

N

S T

A

TE

OF CAL I FORN

I A

A rc h ite ct s, I n c.

H

IB

SE

R Y

A M

A U C H I n d S tr ee t, S u ite

D a vi s, C

A

.7

.1 o ff ic e

.7

.4 fa x

600 Q STREET, SUITE 200

SACRAMENTO, CA 95811

916 443 0303

CALIFORNIA DEPARTMENT OF

CORRECTIONS AND REHABILITATION

ACCESS COMPLIANCE REVIEW

APPROVAL OF THIS PLAN DOES NOT

AUTHORIZE OR APPROVE ANY OMISSION OR

DEVIATION FROM THE APPLICABLE REGULATIONS.

TRACKING NUMBER:___________________

DATE:____________________________

REVIEWER:_________________________

APPROVAL

F

IN

A L

D R

A W

IN

G

S

SHEET NUMBER

ST

AT

E O

F C

AL

IF

O

R N

IA

D

EP

AR

TM

EN

T O

F C

O R

R

EC

TI

O

N S

AN

D R

EH

AB

IL

IT

AT

IO

N

FA

C

IL

IT

Y

PL

AN

N

IN

G , C

O N

ST

R

U C

TI

O N

A N

D M

AN

AG

EM

EN

T D

IV

IS

IO

N

DE

SI

GN

S

ER

VI

CE

S

AN

D

ST

AN

DA

RD

S

BR

AN

CH

DE

SI

GN

S

ER

VI

CE

S

SE

CT

IO

N

R E V

D A T E

D

S C R

IP

T

IO

N

L A C

V1

C A

LI

F O

R N

IA

S T A T E P

R

IS

O N , L

O S A

N G

E

LE

S C

O U N

T Y

TH

S

TR

E E T, W E S T

LA

N C A S

TE

R , C

A

R E P

LA

C E R

O O

F

P H A S

C

C R

P H A S E

J O B

N U M B E R

A T E A

U G

U S T

1, P ro je c t N o

.1

P ro je c t

P h a s e

H E E T

T

IT

L

M. TODD

THORP

No. 2990

/9

/2

:3 :2

P

M c re v it \2

-0

.0

C D

C R

L A P

H R C

E N

T R A L d d ir e .r v t

R O

O F F

R A M

IN

G

P L A N

T

Y P

H

O U

S

IN

G U

N

IT

SSSSAAAA222200001 111

ROOF FRAMING PLAN - TYP 270 HOUSING UNIT

0' 4'-0" 8'-0" 16'-0" 32'-0" (1/8" = 1')

331/341 332/342 333/343 335/336/345 344 339/349 337 338/348 3310/3410

DETAIL

SA201

1/16" = 1'-0"3

WIND PRESSURE PLAN

WIND PRESSURE PLAN SA201

0' 8' 16' 32' 64'

SA201

1/2" = 1'-0"2STAIR CAGE PARTIAL ROOF PLAN

0' 1'-0" 2'-0" 4'-0" 8'-0"

S

R

EFOROOP

DDDDDDDDDDDDDDDDDEEEEEEEEEEEEEEEEEERRRRRRRRRRRRRRREEEEEETTTTTTTTTTTTTTTTTTTTTTTTSSSSSSSSSSSSSSSI

GGGEGG

SI NN

EEEEEEEEEEEEENNNNNNNNNNNNNNNNGGGGGGGGGGGGGGGGGGGGGGGGIIIIIIIIIIIIIINNNNNNNNNNNNNNNNEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEERR

O AAAAAAAAALLLLLLLLLLLLLLLLLLLLLLL

MMMMMMMMMMMMMM. TODDTODDTTOTTOOOOOD

THORP

No 2990

08/24/2023

V1

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/10/23

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

23-0002

KING NUMBENUNU ENU ER:_____R:__________________ ______ ___________

WER:_____R:_____R:R::__________R:_____:R:R:R:R:::RRRRR:___RRRR ___ _________________________ ____ _11/20/2023

3 1 1.8 2 6 4 5 7 8 9 1110

B.4

A

B

D

C

J

E

F

G

H

K

K.8

L

M

1 111.8 2 3 4 5 6 7 8 9 105.7 7.3

A

B

B.7

D

E.7

G.3

J

K.7

L

M

D04

TYP

D11

D07

D13

D05

D07

D05

D05

D05

D19

D10

D10

D11

D14

D13

D13

D04

D08

D08

D21

D20

D20

D20

D11 D11 D11

D11 D11 D11

D11

D11

D11

D11

D10 D10 D10

D10 D10 D10

D10

D10

D10

D10

D04 D04 D04 D04 D04 D04 D04 D04 D04D04 D04 D04 D04

D04D04 D04D04 D04 D04 D04

D04

D04 D04 D04 D04 D04 D04

D08 D08 D08 D08 D08 D08 D08 D08

D08

D08

D08

D08

D08

D08

D08

D08

D08

D08

D08

D07 D07 D07 D07 D07 D07 D07 D07

D07D08D08D08D08D08D08D08D08 D07D07D07D07D07D07D07D07

D07

D07

D07

D07

D07

D07

D07

D07

D07

D07

D07

D07

D07

(E)AC-1

(E)AHU-1

(E)AHU-2

(E)AHU-3

(E)EF-1(E)EF-2 (E)EF-3 (E)EF-4

(E)EF-5

(E)EF-6 (E)EF-7 (E)EF-8 (E)EF-9

(E)EF-32

(E)EF-10

(E)EF-11

(E)EF-12

(E)EF-13

(E)EF-30

(E)EF-14

(E)EF-15

(E)EF-16

(E)EF-17

(E)EF-29

(E)EF-28

(E)EF-18 (E)EF-19 (E)EF-20 (E)EF-21 (E)EF-22 (E)EF-23 (E)EF-24 (E)EF-25 (E)EF-26

D07

(E)EF-27

(E)EF-31

(E)EF-33

(E)WH-1

D22

D22

D22

(E)1 14"CD

(E)1 14"CD

(E)11

4"CD

D14

D14

D14

D14

D13

D15

(E)34"ICW

D16

D16

(E)34"ICW

(E)34"ICW

D17

(E)11

2"MPG

D17

(E)34"MPG

D17

(E)34"MPG

D17

(E)34"MPG

(E)34"CD

D17

(E)34"MPG

D16A

D18

D18

D18

D18

Project Engineer:

U R L E YT M E C H A N IC A L

E N G I N E E R I N G

G R O U P, I N C.& ASSOCIATES

(916) 325-1065

FAX: (916) 325-1075

Email: office@turleymech.com

2431 Capitol Avenue

Sacramento, CA 95816

Project Manager:

GYang

Job Number:

Project Drafter: Login:

Plot Date: Aug 25, 2023 - 4:07pm

22107-PH1JT

JT

SHEET NUMBER

S

TA

TE

O

F C

A

LI

FO

R N

IA

D

E P A R

TM

E N T

O F

C O

R R

E C

TI

O

N S A

N D R

E H

A B

IL

IT

A

TI

O N

FA

C

IL

IT

Y P

LA

N

N

IN

G , C

O N

S

TR

U C

TI

O

N A

N D

M A N A G

E M

E N

T D

IV

IS

IO

N

DE

SI

G N

SE

RV

IC

ES

A

ND

S

TA

ND

AR

DS

B

RA

NC

H

DE

SI

G

N

SE

RV

IC

ES

S

EC

TI

O N

APPROVAL

V1

C A L

IF

O R

N

IA

S T A T E P

R

IS

O N

L O

S A

N G

E L E S C

O U N T Y

T H

S T R

E E T , W

E S T

LA

N

C A S T E R

, C A

R E P L A C

E R

O O

F S

P H

A S E

A U

G U

S T

W O

R K

IN

G D

R A W

IN

.1

A rc h it e ct s, I n c.

H

IB

S E R Y

A M

A U C

H I n d S tr e e t, S u it e

D a vi s, C

A

.7

.1 o ff ic e

.7

.4 f a x

DEMOLITION NOTES

GENERAL NOTES

D07 (E) EXHAUST FAN TO BE REMOVED FROM THE EXISTING CURB AND PROTECTED

TO ALLOW FOR THE REROOF. INSPECT EXISTING BACKDRAFT DAMPER AND

LUBRICATE AND CLEAN DAMPER. LABEL FAN (STENCIL PAINT 2" HIGH LETTERS)

BEFORE REMOVAL. LABEL WITH CORRESPONDING NUMBERS LISTED ON PLANS.

PHOTO SEE

D11 (E) SCUPPER CONDUCTOR HEAD, TR, PHOTO SEE

H

MP801

1. WHERE PIPE SIZES ARE DIFFERENT THAN SHOWN, MATCH (E)SIZES TO

MAINTAIN THE SAME PIPE SIZE AS EXISTING CONDITIONS.

2. FIELD VERIFY EXACT HEIGHT OF EACH (E) CURB. IF TOP (E)CURB IS EQUAL

TO OR MORE THAN 8" ABOVE NEW FINISHED ROOF TOP, (E)UNIT ON THE

CURD CAN BE REMAIN IN PLACE AND PROTECTED DURING

CONSTRUCTION. INSTALL (N)FLASHING ON (E)CURB AFTER REROOFING.

D08 (E) ROOF VENT PIPE PENETRATION TO REMAIN. REMOVE/REPLACE

(E)FLASHING, EXTEND VENT THRU ROOF DUE TO NEW INSULATION HEIGHT.

TOTAL 29 VENT ON ROOF WITHIN CONSTRUCTION AREA. PHOTO SEE

D10 (E) 12X6 SCUPPER OPENING FOR LOW ROOF, TR, PHOTO SEE

H

MP801

G

MP801

D04 (E) SCUPPER OPENING FROM HIGH ROOM TO LOW ROOF, TBR, PHOTO SEE

B

MP801

F

MP801

D05 (E) AHU OR AC UNIT ON CURB TO BE TEMPORARILY REMOVED AND PROTECTED

TO ALLOW FOR THE REROOF. DISCONNECT ALL CONTROLS, PIPING, DRAINS,

AND DUCTING FOR REMOVAL. COORDINATE WITH CDCR REPRESENTATIVE FOR

CRANE IS REQUIRED TO MOVE UNIT. UNIT IS TO BE SET ON GROUND TO ALLOW

FOR NEW CURB ADAPTOR TO BE ADDED. LABEL UNIT (STENCIL PAINT 2" HIGH

LETTERS) BEFORE REMOVAL. LABEL WITH CORRESPONDING NUMBER ON PLAN.

SEE OR

C

MP801

D

MP801

D19

N

MP801

(E) WATER HEATER TO BE REMOVED FROM THE EXISTING CURB AND

PROTECTED TO ALLOW FOR THE REROOF. DISCONNECT ALL CONTROLS AND

PIPING PIPING, AND DRAIN TO EMPTY THE TANK FOR REMOVAL. LABEL UNIT

(STENCIL PAINT 2" HIGH LETTERS) BEFORE REMOVAL. LABEL WITH

CORRESPONDING NUMBER ON PLAN. SEE

D22 (E) DUCT THRU ROOF, TO BE TEMPORARY DISCONNECTED. FIELD MEASURE

DUCT SIZE. PHOTO SEE

O

MP801

(E)36X24 DUCT ON ROOF, TO REMAIN. DISCONNECT AND TEMPORARILY

REMOVE DURING RE-ROOFING, PROTECT IN PLACE. DUCT WILL BE

REQUIRED TO BE ON NEW SUPPORT. REPLACE WITH (N) DUCT AT SAME SIZE

IF NECESSARY. SIZE TO BE FIELD VERIFIED AND RECORD, PHOTO SEE

D20

O

MP801

(E) G, CW, HW, HWR UTR, TEMPORARY DISCONNECT DURING

CONSTRUCTION. PHOTO SEE

D21

N

MP801

D13 (E) CONDENSATE DRAIN PIPING ON ROOF, TEMPORARY REMOVED DURING

CONSTRUCTION. REMOVE ALL PIPING SUPPORT. PHOTO SEE

I

MP801

D14 (E) CONDENSATE DRAIN PIPING (D)THRU ROOF, TR. PHOTO SEE

I

MP801

D15 (E) INDUSTRIAL COLD WATER PIPING ON ROOF, TEMPORARY REMOVED DURING

CONSTRUCTION. REMOVE ALL PIPING SUPPORT. PHOTO SEE

J

MP801

D16 (E) INDUSTRIAL COLD WATER PIPING (D)THRU ROOF, TR. PHOTO SEE

L

MP801

D17 (E) MEDIUM PRESSURE NATURAL GAS PIPING ON ROOF, TEMPORARY REMOVED

DURING CONSTRUCTION. REMOVE ALL PIPING SUPPORT. PHOTO SEE

M

MP801

D16A (E) INDUSTRIAL COLD WATER PIPING PENETRATE INTO CURB, TEMPORARY

DISCONNECTED AND TO BE RE-ROUTED. PHOTO SEE

K

MP801

D18 (E) NATURAL GAS PIPING CONNECT TO AC OR AHU W/ PRESSURE REGULATOR.

TEMPORARY DISCONNECT DURING CONSTRUCTION. PHOTO SEE

M

MP801

MPA201

M E C

H A N

IC

A L P

L U M

B

IN

G

T Y P

IC

A L

H

O U S

IN

G U

N

IT

R O

O F P

L A

N D

E M

O L

IT

IO

N

BUILDING 332 BUILDING 331

N

N

N

BUILDING 333 BUILDING 335

N

BUILDING 336 BUILDING 337 BUILDING 338 BUILDING 339 BUILDING 3310 BUILDING 341 BUILDING 342 BUILDING 343 BUILDING 344

N

N N N

N

N

BUILDING 345

N N

N

N

BUILDING 348 BUILDING 349 BUILDING 3410

N N

N

(E)AHU-1 THRU 3 EXISTING HANDLING UNIT, "ENERGY LAB" UNIT W/

"REZNOR" NATURAL GAS FURNACE AND EVAP COOLER,

MODEL# AND DETAILED INFORMATION UNKNOWN.

(E)AC-1 EXISTING AIR CONDITIONING UNIT ON HIGH ROOF,

ROOF TOP UNIT W/ NATURAL GAS FURNACE,

MANUFACTURE, MODEL# AND DETAILED INFORMATION

UNKNOWN.

(E)EF-1 THRU 33 EXISTING EXHAUST FAN, UNIT MODEL# AND DETAILED

INFORMATION UNKNOWN.

(E)WH-1 EXISTING WATER HEATER ON HIGH ROOF.

"TURBOPOWER" LOW NOX CATEGORY I FAN-ASSISTED

STORAGE WATER HEATER, 500 LHE 250A-TPL, 250

GALLON, 399,000 BTU/HR NATURAL GAS INPUT,

4.5"-10.5" W.C. GAS INLET PRESSURE, 120V/1PH/60 HZ,

5AMPS.

NOTES:

1. NO AS-BUILT DRAWING FOR THE BUILDINGS. NAMEPLATE FOR

MOST UNITS CANNOT BE FOUND OR NOT READABLE. CONTRACTOR

SHALL FIELD VERIFY ACTUAL UNIT INFORMATION FOR EACH BUILDING.

2. MANY AHU'S WERE FOUND TO BE LEAKING. THEY MUST BE

REPAIRED PRIOR TO REROOFING.

EXISTING EQUIPMENT SCHEDULE

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/10/23

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

23-0002

1 61.8 2 3 4 5 7 118 9 10

B

C

B.4

F

D

E

H

G

J

K

K.8

L

M

1 111.8 2 3 4 5 6 7 8 9 105.7 7.3

A

B

B.7

D

E.7

G.3

J

K.7

L

M

K

H

E

C

F

G

D14

08 08 08 08 08 08 08 08

07 07 07 07 07 07 07 07

070808 080808 08 08 08 07070707 07 07 07 07

(E)AC-1

(E)AHU-1

(E)AHU-2

(E)AHU-3

(E)EF-1(E)EF-2 (E)EF-3 (E)EF-4

(E)EF-5

(E)EF-6 (E)EF-7 (E)EF-8 (E)EF-9

(E)EF-32

(E)EF-10

(E)EF-11

(E)EF-12

(E)EF-13

(E)EF-30

(E)EF-14

(E)EF-15

(E)EF-16

(E)EF-17

(E)EF-29

(E)EF-28

(E)EF-18 (E)EF-19 (E)EF-20 (E)EF-21 (E)EF-22 (E)EF-23 (E)EF-24 (E)EF-25 (E)EF-26

(E)EF-27

(E)EF-31

(E)EF-33

(E)WH-1

(E)1 14"CD

(E)1 14"CD

(E)114"CD

D14

(E)3 4"ICW

(E)3 4"ICW

(E)34"ICW

(E)112"MPG

(E)34"MPG

(E)34"MPG

(E)34"MPG

(E)3 4"CD

(E)3 4"MPG

16A

Project Engineer:

U R L E YT M E C H A N IC A L

E N G I N E E R I N G

G R O U P, I N C.& ASSOCIATES

(916) 325-1065

FAX: (916) 325-1075

Email: office@turleymech.com

2431 Capitol Avenue Sacramento, CA 95816

Project Manager:

GYang

Job Number:

Project Drafter: Login:

Plot Date: Aug 25, 2023 - 4:07pm

22107-PH1JT

JT

SHEET NUMBER

S

TA

TE

O F C A

LI

FO

R N

IA

D E P A R

TM

E N T

O F

C O

R R E C

TI

O

N S A

N D

R E H A B

IL

IT

A

TI

O N

FA

C

IL

IT

Y P

LA

N N

IN

G

, C O

N S

TR

U C

TI

O

N A

N D

M A N A G E M E N

T D

IV

IS

IO

N

DE

SI

G

N

SE

RV

IC

ES

A

ND

S

TA

ND

AR

DS

B

RA

NC

H

DE

SI

G

N

SE

RV

IC

ES

S

EC

TI

O

N

APPROVAL

V1

C A L

IF

O R

N

IA

S T A T E P

R

IS

O N L O

S A

N G E L E S C

O U N T Y

T H

S T R E E T , W

E S T

LA

N C A S T E R

, C A

R E P L A C E R

O O F S

P H A S E

A U G U

S T

W O

R K

IN

G

D R A W

IN

.1

A rc h it e ct s, I n c.

H

IB

S E R Y

A M

A U C

H I n d S tr e e t, S u it e

D a vi s, C

A

.7

.1 o ff ic e

.7

.4 f a x

MPA301

M E C

H A N

IC

A

L P

L U M

B

IN

G

T Y P

IC

A L

H

O U S

IN

G U

N

IT

R O

O F P

L A N

R E M

O D

E L

GENERAL NOTES

16A (E) INDUSTRIAL COLD WATER PIPING PENETRATE INTO CURB, TEMPORARY

DISCONNECTED, RE-ROUTED AND RECONNECTED. DETAIL SEE

18 RECONNECT (E) NATURAL GAS PIPING CONNECT TO AC OR AHU W/ (E)PRESSURE

REGULATOR. DETAIL SEE

1. PROVIDE START UP OF ALL EQUIPMENT TO ENSURE IT IS OPERATING

PROPERLY. SEE GENERAL MECHANICAL/PLUMBING NOTES ON MP001.

2. WHERE SIZES ARE LARGER THAN SHOWN, MATCH (E)SIZES TO

MAINTAIN THE SAME SIZE AS EXISTING CONDITIONS.

3. FIELD VERIFY EXISTING GAS PIPE MATERIAL AT EACH BUILDING.

MATERIAL OF NEW GAS PIPING AND FITTINGS SHALL MATCH EXISTING

PIPING MATERIAL.

4. FIELD VERIFY EXACT HEIGHT OF EACH (E) CURB. IF TOP (E)CURB IS

EQUAL TO ORMORE THAN 8" ABOVE NEW FINISHED ROOF TOP, (E)UNIT

ON THE CURD CAN BE REMAIN IN PLACE AND PROTECTED DURING

CONSTRUCTION. INSTALL (N)FLASHING ON (E)CURB AFTER

REROOFING.

RE-INSTALL (E) AHU ON (N) RAISED CURB. RECONNECT ALL CONTROLS, PIPING,

DRAINS AND DUCTING. PROVIDE EXACT MEASUREMENTS OF CURB FOR THE

ADDITION OF A CURB EXTENDER. VERIFY DUCT SIZE. MOUNTING DETAIL SEE

, PIPING (GAS,WATER AND DRAIN) CONNECTION SEE

05 RE-INSTALL (E) AC UNIT ON (N) RAISED CURB. RECONNECT ALL CONTROLS,

PIPING, DRAINGS AND DUCTING. VERIFY DUCT SIZE. PROVIDE EXACT

MEASUREMENTS OF CURB FOR THE ADDITION OF A CURB ADAPTOR. MOUNTING

DETAIL SEE , GAS PIPE CONNECTION DETAIL SEE ,

CONDENSATE DRAIN CONNECTION SEE

RE-INSTALL (E) EXHAUST FAN ON (N) RAISED CURB, PROVIDE EXACT

MEASUREMENTS OF CURB FOR THE ADDITION OF A CURB ADAPTOR. SEE

DETAIL

(N) PLUMBING VENT PIPE @ (E) PENETRATION, TOTAL 29 VENT ON ROOFWITHIN

CONSTRUCTION AREA. RAISE VENT TO MAINTAIN REQUIRED DISTANCE FROM

TOP OF VENT TO TOP OF ROOF. DETAIL SEE

(E) CONDENSATE DRAIN (D) THRU ROOF, RECONNECTED, PROVIDE NEW FLASHING

AND NEW OFFSET. DETAIL SEE

(E) CONDENSATE DRAIN PIPING, TO BE REINSTALLED. PROVIDE NECESSARY

OFFSET FOR NEW HEIGHT OF CURB. NEW PIPE SIZE IS TO MATCH EXISTING.

REPLACE (E)PIPING WITH SAME SIZE (N)PIPING IS ACCEPTABLE. PIPE SUPPORT

DETAIL SEE

(E) INDUSTRIAL COLD WATER PIPING, TO BE REINSTALLED. PROVIDE NECESSARY

OFFSET FOR NEW HEIGHT OF CURB. NEW PIPE SIZE IS TO MATCH EXISTING.

REPLACE (E)PIPING WITH SAME SIZE (N)PIPING IS ACCEPTABLE. PIPE SUPPORT

DETAIL SEE

(E) INDUSTRIAL COLD WATER PIPE (R) THRU ROOF, RECONNECTED, PROVIDE NEW

FLASHING AND NEW OFFSET. DETAIL SEE

(E) MEDIUM PRESSURE NATURAL GAS PIPING, TO BE REINSTALLED. PROVIDE

NECESSARY OFFSET FOR NEW HEIGHT OF CURB. NEW PIPE SIZE IS TO MATCH

EXISTING. REPLACE (E)PIPING WITH SAME SIZE (N)PIPING IS ACCEPTABLE. PIPE

SUPPORT DETAIL SEE

G

MP501

H,I

MP501

A

MP502

E

MP501

H

MP501

I

MP501

A

MP501

B

MP501

C

MP501

F

MP501

D

MP501

F

MP501

C

MP502

D

MP501

H

MP501

BUILDING 332 BUILDING 331

N

N

N

BUILDING 333 BUILDING 335

N

BUILDING 336 BUILDING 337 BUILDING 338 BUILDING 339 BUILDING 3310 BUILDING 341 BUILDING 342 BUILDING 343 BUILDING 344

N

N N N

N

N

BUILDING 345

N N

N

N

BUILDING 348 BUILDING 349 BUILDING 3410

N N

N

(E)AHU-1 THRU 3 EXISTING HANDLING UNIT, "ENERGY LAB" UNIT W/

"REZNOR" NATURAL GAS FURNACE AND EVAP COOLER,

MODEL# AND DETAILED INFORMATION UNKNOWN.

(E)AC-1 EXISTING AIR CONDITIONING UNIT ON HIGH ROOF,

ROOF TOP UNIT W/ NATURAL GAS FURNACE,

MANUFACTURE, MODEL# AND DETAILED INFORMATION

UNKNOWN.

(E)EF-1 THRU 33 EXISTING EXHAUST FAN, UNIT MODEL# AND DETAILED

INFORMATION UNKNOWN.

(E)WH-1 EXISTING WATER HEATER ON HIGH ROOF.

"TURBOPOWER" LOW NOX CATEGORY I FAN-ASSISTED

STORAGE WATER HEATER, 500 LHE 250A-TPL, 250

GALLON, 399,000 BTU/HR NATURAL GAS INPUT,

4.5"-10.5" W.C. GAS INLET PRESSURE, 120V/1PH/60 HZ,

5AMPS.

NOTES:

1. NO AS-BUILT DRAWING FOR THE BUILDINGS. NAMEPLATE FOR

MOST UNITS CANNOT BE FOUND OR NOT READABLE. CONTRACTOR

SHALL FIELD VERIFY ACTUAL UNIT INFORMATION FOR EACH BUILDING.

2. MANY AHU'S WERE FOUND TO BE LEAKING. THEY MUST BE

REPAIRED PRIOR TO REROOFING.

EXISTING EQUIPMENT SCHEDULE

REMODEL NOTES

(E) G, CW, HW, HWR UTR, RECONNECTED, PROVIDE (N)CURB ADAPTOR FOR

MULTIPLE PIPES OR (N)FLASHING FOR SINGLE PIPE. PROVIDE NECESSARY

OFFSET. SINGLE PIPE PENERTRATION DETAIL SEE

MULTIPLE PIPE PENETRATION DETAIL SEE

(E) 36X24 DUCT ON ROOF, REINSTALLED AND PROVIDE NEW DUCT SUPPORT.

DETAIL SEE

(E) DUCT THRU ROOF. PROVIDE NEW CURB EXTENSION AND EXTEND/MODIFY

DUCT. RE-INSULATE DUCT. DETAIL SEE

D

MP502

B

MP502

G

MP502

F

MP501

19 RE-INSTALL (E) WATER HEATER ON (N) CURBS. RECONNECT ALL CONTROLS

AND PIPING, MOUNTING DETAIL SEE AND ,WATER PIPE

CONNECTION DETAIL SEE ,

NATURAL GAS PIPE CONNECTION SEE

A906F

MP502

H

MP501

S501

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/10/23

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

23-0002

B

C

B.4

F

D

E

H

G

J

K

K.8

L

M

1 111.8 2 3 4 5 6 7 8 9 105.7 7.3

A

B

B.7

D

E.7

G.3

J

K.7

L

M

K

H

E

C

F

G

11 11 11

11 11 11

10 10 10

(AREA A1)(AREA A2)(AREA A3) (AREA A4)(AREA A5)

(AREA A15)

1150 SQ.FT. EQA

(AREA A14)(AREA A13) (AREA A12)(AREA A11)

650 SQ.FT.

EQA

(AREA A6)

250 SQ.FT.

EQA

(AREA A7)

250 SQ.FT.

EQA

(AREA A8)

200 SQ.FT.

EQA

(AREA A9)

450 SQ.FT.

EQA

(AREA A10)

10101010

1800 SQ.FT. EQA2200 SQ.FT. EQA 1600 SQ.FT. EQA1500 SQ.FT. EQA

1150 SQ.FT. EQA 1800 SQ.FT. EQA 2200 SQ.FT. EQA 1600 SQ.FT. EQA

1500 SQ.FT. EQA

OPEN END OF HIGH

ROOF TO LOW ROOF

Project Engineer:

U R L E YT M E C H A N IC A L

E N G I N E E R I N G

G R O U P, I N C.& ASSOCIATES

(916) 325-1065

FAX: (916) 325-1075

Email: office@turleymech.com

2431 Capitol Avenue

Sacramento, CA 95816

Project Manager:

GYang

Job Number:

Project Drafter: Login:

Plot Date: Aug 25, 2023 - 4:07pm

22107-PH1JT

JT

SHEET NUMBER

S

TA

TE

O

F C

A

LI

FO

R N

IA

D

E P A R

TM

E N

T O

F C

O R R

E C

TI

O

N S A

N D

R E H

A B

IL

IT

A

TI

O N

FA

C

IL

IT

Y P

LA

N

N

IN

G , C

O N

S

TR

U C

TI

O

N A

N D

M A N

A G

E M

E N

T D

IV

IS

IO

N

DE

SI

G N

SE

RV

IC

ES

A

ND

S

TA

ND

AR

DS

B

RA

NC

H

DE

SI

G

N

SE

RV

IC

ES

S

EC

TI

O N

APPROVAL

V1

C A L

IF

O R

N

IA

S T A T E P

R

IS

O N

L O

S A

N G

E L E S C

O U N

T Y

T H

S T R

E E T , W

E S T

LA

N

C A S T E R

, C A

R E P L A C

E R

O O

F S

P H

A S E

A U

G U S T

W O

R K

IN

G D

R A W

IN

.1

A rc h it e ct s, I n c.

H

IB

S E R Y

A M

A U C

H I n d S tr e e t, S u it e

D a vi s, C

A

.7

.1 o ff ic e

.7

.4 f a x

MPA302

P L U M

B

IN

G

T Y P

IC

A L

H

O U S

IN

G U

N

IT

R O

O F P

L A

N R

A

IN

W A

T E R

REMODEL KEY NOTES

#### EQA

NOTE

EQUIVALENT AREA OF ROOF AREA PLUS AREA OF VERTICAL

WALLS, PER CPC 1103.4, 2019.

PER US WEATHER BUREAU TECHNICAL PAPER NO.40 CHART 14:

100-YEAR 1-HOUR RAINFALL (INCH), LOCAL RAIN WATER FALL RATE

IS BETWEEN 0.5"/HR AND 1.0"/HR. WHILE CONSIDERING A SAFETY

FACTOR, 2"/HR RAINFALL IS USED IN THIS PROJECT.

PER 2022 CPC TABLE 1103.1 AND TABLE 1103.2, MAX PROTECTED

ROOF AREA OF PIPES ARE SHOWING BELOW:

PIPING MAX PROTECTED ROOF AREA (SQ.FT.)

SIZE HORIZONTAL SLOPE VERTICAL PIPING

(INCH) 1

8"/LF 1

4"/LF 1

2"/LF ROOF DRAIN, LEADER

2" - - - 1440 3" 1,644 2,320 3,288 4,400 4" 3,760 5,300 7,520 9,200 5" 6,680 9,440 13,360 17,300 6" 10,700 15,100 21,400 27,000

PER 2022 CPC 1101.12.2.1, WHEN SCUPPER OR SIDE OPENING IS

USED FOR OVERFLOW, HEIGHT OF OPENING SHALL BE NO LESS

THAN 4", AND WIDTH SHALL BE NO LESS THAN CIRCUMFERENCE OF

THE ROOF DRAIN REQUIRED FOR THE AREA SERVED.

AN ALTERNATIVE MEANS IS USING SCUPPER INSTEAD OF THE ROOF

DRAIN FOR THE PRIMARY RAINWATER DRAINAGE. ALTERNATIVE

MEANS IS UNDER THE AGREEMENT WITH OF CDCR PROJECT

MANAGER. IN THIS CASE, HEIGHT OF OPENING SHALL BE NO LESS

THAN 4", AND WIDTH SHALL BE NO LESS THAN CIRCUMFERENCE OF

THE ROOF DRAIN REQUIRED FOR THE AREA SERVED. WHERE ROOF

DRAIN AND SCUPPER ARE COMBINED, THE HEIGHT OF OPENING

MUST BE A MINIMUM OF TWICE THE REQUIRED HEIGHT (MIN OF 8").

THE ABOVE DATA ARE ONLY MINIMUM REQUIREMENT OF DRAINS

AND PIPES. THEY CAN BE OVERSIZED IN THE PROJECT.

RAIN WATER CALCULATION

FOR AREA A1 THRU A15, MAX TOTAL EQUIVALENT ROOF AREA IS

2,200 SQ.FT. A MIN 3" ROOF DRAIN OR MIN 10"Wx4"H SCUPPER

OPENING IS SUFFICIENT TO SUPPORT EACH AREA. MIN OVERFLOW

SIDE WALL OPENING IS 10"Wx4"H. THE NEW PRIMARY AND

SECONDARY SIDE WALL OPENINGS ARE MEET THE CODE

REQUIREMENT.

BUILDING 332 BUILDING 331

N

N

N

BUILDING 333 BUILDING 335

N

BUILDING 336 BUILDING 337 BUILDING 338 BUILDING 339 BUILDING 3310 BUILDING 341 BUILDING 342 BUILDING 343 BUILDING 344

N

N N N

N

N

BUILDING 345

N N

N

N

BUILDING 348 BUILDING 349 BUILDING 3410

N N

N

11 (E) SCUPPER CONDUCTOR HEAD

12 (N) SCUPPER CONDUCTOR HEAD, SIZE MATCH OTHER (E) CONDUCTOR HEAD

ON THE SAME WALL. INSTALLATION DETAILS SEE 4/S501.

10 (E) OR (N) PRIMARY SCUPPER AND (N)OVERFLOW SCUPPER FOR LOW ROOF.

EACH SCUPPER OPENING SHALL BE MIN 10"WIDE x 4"HIGH. THE LOCATION

OF (N) PRIMARY SCUPPER SHALL MATCH (E) OR (N)SCUPPER CONDUCTORS.

SEE ARCHITECTURAL DETAIL 28/A905.

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/10/23

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

23-0002

3 6 7 9 1110

C

E

F

G

H

K

K.8

L

1 112 5 9 105.7 7.3

B

D

E.7

J

M

1 1.8 2 4 5 8

B.4

A

B

D

J

M

1.8 3 4 6 7 8

A

B.7

G.3

K.7

L

(E) 3/4" CONDUIT UP

THROUGH ROOF

(E)

(R)

(E) (3) 3/4" CONDUITS

IN PITCH POCKET

(E) 1-1/2" CONDUIT UP

THROUGH ROOF

(E) (3) 3/4" CONDUITS

IN PITCH POCKET

(E) (2) 3/4" CONDUITS

IN PITCH POCKET

J

(E) (3) 3/4" CONDUITS

UP THROUGH ROOF

TO DUCT DETECTORS

AND CONTROLS

(E) 3/4" CONDUIT UP

THROUGH ROOF TO

J-BOX

(R)

(E) CONTROL

PANELS

(E) 1-1/2" CONDUIT UP

THROUGH ROOF

(E) (4) 3/4" CONDUITS

UP THROUGH ROOF

(E) MAIN CIRCUIT

BREAKER

DISCONNECT

J

(R)

(E) CONTROL

PANELS

(E) MAIN CIRCUIT

BREAKER

DISCONNECT

(E) 1-1/2" CONDUIT UP

THROUGH ROOF

(E) (4) 3/4" CONDUITS

UP THROUGH ROOF

(E) (3) 3/4" CONDUITS

UP THROUGH ROOF

TO DUCT DETECTORS

AND CONTROLS

(E) 3/4" CONDUIT UP

THROUGH ROOF TO

J-BOX

(E) (3) 3/4" CONDUITS

UP THROUGH ROOF

TO DUCT DETECTORS

AND CONTROLS

J

(E) 3/4" CONDUIT UP

THROUGH ROOF TO

J-BOX

(R)

(E) 1-1/2" CONDUIT UP

THROUGH ROOF

(E) (4) 3/4" CONDUITS

UP THROUGH ROOF

(E) CONTROL

PANELS

(E) MAIN CIRCUIT

BREAKER

DISCONNECT

EXISTING MECHANICAL UNIT TO BE DISCONNECTED FOR ROOF REPAIR. COORDINATE WITH

MECHANICAL. REINSTALL USING NEW ELECTRICAL CONDUIT, CONDUCTORS AND DEVICES.

CONDUIT SIZE, WIRING SIZE, QUANTITY AND TYPE SHALL MATCH EXISTING. SEE REMODEL PLAN

"1/EA301".

EXISTING NON-GFCI RECEPTACLE TO BE REPLACED. SEE REMODEL PLAN "1/EA301".

NUMBERED NOTES

GENERAL NOTES

1. PLACE ALL EXISTING ELECTRICAL CIRCUITS FEEDING EXISTING HVAC AND ELECTRICAL EQUIPMENT ON

ROOFTOP IN A "SAFE-OFF" CONDITION, PRIOR TO CONSTRUCTION. NO NEW LOADS ADDED TO

CIRCUITS.

2. REMOVE PORTIONS OF EXISTING CONDUITS AND WIRING NECESSARY TO RE-ROOF EXISTING

BUILDING.

3. DO NOT DAMAGE DURING CONSTRUCTION AND REUSE ALL EXISTING CIRCUITS, PROVIDE NEW HVAC DISCONNECTS, PROVIDE NEW WEATHERPROOF GFCI SERVICE RECEPTACLES TO REPLACE EXISTING

RECEPTACLES FOR REMODEL.

4. REMOVE EXISTING JUNCTION BOXES AND FLEX CONDUITS BACK TO ROOF PENETRATION POINT, AND DO NOT REUSE. REPLACE ALL ABOVE ROOF CONDUITS WITH NEW - WIRING SIZE, QUANTITY AND TYPE SHALL MATCH EXISTING. SPLICE IN POWER WIRING IS NOT ACCEPTABLE. NEW CONTROL WIRING TO HVAC EQUIPMENT MAY ONLY BE INSTALLED FOR THE RUN FROM THE EQUIPMENT CONTROL PANEL TO

THE NEAREST EXISTING TERMINATION POINT OR SPLICE LOCATION. INSTALL NEW EMT WITH

COMPRESSION FITTINGS AND LIQUID-TIGHT METAL CONDUIT TERMINATION AT THE MECHANICAL

EQUIPMENT .

5. DO NOT DAMAGE HVAC DUCTS WITH DUCT DETECTORS. MAINTAIN FIRE ALARM DEVICE AND CIRCUIT

DURING CONSTRUCTION.

6. DO NOT DAMAGE WP SERVICE RECEPTACLE BACK BOXES. REMOVE ANCHORING, AS NEEDED, TO

ALLOW MOVEMENT DURING ROOFING REPAIR. MAINTAIN CIRCUIT CONTINUITY AND RECEPTACLE

FUNCTIONALITY AFTER CONSTRUCTION.

7. REPLACE JUNCTION BOXES. REPLACEMENT BOX TO MATCH EXISTING TYPE AND SIZE.

SHEET NUMBER

S

TA

TE

O

F C

A

LI

FO

R N

IA

D E P A R

TM

E N T

O F

C O

R R E C

TI

O

N S A

N D

R E H

A B

IL

IT

A

TI

O N

FA

C

IL

IT

Y P

LA

N N

IN

G , C

O N S

TR

U C

TI

O

N A

N D

M A N A G

E M

E N

T D

IV

IS

IO

N

DE

SI

G N

SE

RV

IC

ES

A

ND

S

TA

ND

AR

DS

B

RA

NC

H

DE

SI

G

N

SE

RV

IC

ES

S

EC

TI

O N

APPROVAL

V1

C A L

IF

O R

N

IA

S T A T E P

R

IS

O N L O

S A

N G

E L E S C

O U N T Y

T H

S T R

E E T , W

E S T

LA

N C

A S T E R

, C A

.1

Electrical Engineers Lighting Designers

100 Howe Ave., Suite 235N

Sacramento, CA 95825-8217

PROJECT #:

www.mneilsengineering.com

Tel: (916) 923-4400

PROJECT MGR: Stuart LinGsa\

21318.21

08/29/2023

R E P L A C E R

O O

F S

P H

A S E

A U G

U S T

W O

R K

IN

G D

R A W

IN

1/8"=1'-0"

TYPICAL 270 HOUSING UNIT ROOF PLAN - DEMOLITION - ELECTRICAL1

EA201

EA201

T Y P

IC

A L

H

O U

S

IN

G U

N

IT

R O

O F P

L A

N D

E M

O L

IT

IO

N

E L E C

T R

IC

A L

5'

1/8" = 1'-0"

0 25'10' 15' 20'

GRAPHIC SCALE

BUILDING 332 BUILDING 331

N

N N

BUILDING 333 BUILDING 335

N

BUILDING 336 BUILDING 337 BUILDING 338 BUILDING 339 BUILDING 3310 BUILDING 341 BUILDING 342 BUILDING 343 BUILDING 344

N

N N N

N

N

BUILDING 345

N N

N

N

BUILDING 348 BUILDING 349 BUILDING 3410

N N

N

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/10/23

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

23-0002

B

C

B.4

F

D

E

H

G

J

K

K.8

L

M

1 111.8 2 3 4 5 6 7 8 9 105.7 7.3

A

B

B.7

D

E.7

G.3

J

K.7

L

M

K

H

E

C

F

G

(E) 3/4" CONDUIT UP

THROUGH ROOF

(E)

(E) (3) 3/4" CONDUITS

IN PITCH POCKET

(E) 1-1/2" CONDUIT UP

THROUGH ROOF

(E) (3) 3/4" CONDUITS

IN PITCH POCKET

(E) (2) 3/4" CONDUITS

IN PITCH POCKET

J

(E) 3/4" CONDUIT UP

THROUGH ROOF TO

J-BOX

(E) CONTROL

PANELS

(E) 1-1/2" CONDUIT UP

THROUGH ROOF

(E) (4) 3/4" CONDUITS

UP THROUGH ROOF

(E) MAIN CIRCUIT

BREAKER

DISCONNECT

J

WP

(E) CONTROL

PANELS

(E) MAIN CIRCUIT

BREAKER

DISCONNECT

(E) 1-1/2" CONDUIT UP

THROUGH ROOF

(E) (4) 3/4" CONDUITS

UP THROUGH ROOF

(E) 3/4" CONDUIT UP

THROUGH ROOF TO

J-BOX

J

(E) 3/4" CONDUIT UP

THROUGH ROOF TO

J-BOX

(E) 1-1/2" CONDUIT UP

THROUGH ROOF

(E) (4) 3/4" CONDUITS

UP THROUGH ROOF

(E) CONTROL

PANELS

(E) MAIN CIRCUIT

BREAKER

DISCONNECT

(E) (3) 3/4" CONDUITS

UP THROUGH ROOF

TO DUCT DETECTORS

AND CONTROLS

3 (E) (3) 3/4" CONDUITS

UP THROUGH ROOF

TO DUCT DETECTORS

AND CONTROLS

(E) (3) 3/4" CONDUITS

UP THROUGH ROOF

TO DUCT DETECTORS

AND CONTROLS

NUMBERED NOTES

GENERAL NOTES

1. EXTEND EXISTING CIRCUITS, WIRING AND CONDUITS AND RECONNECT TO EXISTING RELOCATED

MECHANICAL, LIGHTING AND ELECTRICAL EQUIPMENT. REUSE SAME CIRCUIT TO FEED SAME

MECHANICAL AND ELECTRICAL EQUIPMENT, AS PRIOR TO CONSTRUCTION. MAINTAIN EXISTING

CIRCUIT CONTINUITY AND EQUIPMENT FUNCTIONALITY. ALL ABOVE ROOF CONDUIT AND WIRING MUST BE REPLACED WITH NEW . WIRE SIZE, QUANTITY AND TYPE SHALL MATCH EXISTING. SPLICE IN POWER WIRING IS NOT ACCEPTABLE. NEW CONTROL WIRING TO HVAC EQUIPMENT MAY ONLY BE INSTALLED

FOR THE RUN FROM THE EQUIPMENT CONTROL PANEL TO THE NEAREST EXISTING TERMINATION

POINT OR SPLICE LOCATION INSTALL NEW EMT WITH COMPRESSION FITTINGS AND LIQUID-TIGHT

FLEXIBLE METAL CONDUIT TERMINATION AT THE MECHANICAL EQUIPMENT.

2. REPLACE EXISTING DISCONNECT/MANUAL STARTERS WITH NEW TO FEED SAME HVAC, AS PRIOR TO

CONSTRUCTION. NEW DISCONNECT/STARTER TO MATCH EXISTING TYPE, VOLTAGE, PHASE, AND

CURRENT RATING. REPLACE ALL EXISTING WEATHERPROOF GFCI SERVICE RECEPTACLES WITH NEW

WP/WR/GFCI RECEPTACLES THAT ARE TO CURRENT CODE.

3. PROVIDE NEW WEATHERPROOF, NEMA 3R JUNCTION BOXES AND WATERTIGHT FLEX CONDUITS FOR EACH MECHANICAL AND ELECTRICAL EQUIPMENT. KEEP EXISTING CONDUIT PENETRATIONS AT THE

SAME LOCATIONS AS PRIOR TO CONSTRUCTION.

4. PROVIDE BLOCKING AND CHANNELS TO CONDUIT RACEWAY AS NEEDED ON ROOFTOP. COORDINATE

WITH MECHANICAL AND PLUMBING CONTRACTORS FOR JOINT USE BLOCKING. SEE "2/E9.001"

REINSTALLED MECHANICAL UNIT. RECONNECT EXISTING POWER AFTER ROOFING REPLACEMENT.

SEE DETAIL "1/E9.001" ON SHEET E9.001.

REPLACE EXISTING RECEPTACLE WITH NEW GFCI, WEATHER PROOF, WEATHER RESISTANT

RECEPTACLE.

LOCATE AND INTERCEPT EXISTING CIRCUIT AND CONTROLS BELOW ROOF DECK. SPLICE AND

EXTEND TO RAISED EQUIPMENT AND RE-CONNECT. TYPICAL FOR ALL MECHANICAL UNITS

MOUNTED ON RAISED ROOF.

PROVIDE NEW GFCI, WEATHER PROOF, WEATHER RESISTANT RECEPTACLE WITH METAL

WHILE-IN-USE COVER. CONNECT TO THE EXISTING ROOF RECEPTACLE CIRCUIT.

ALL CONDUIT RUN EXPOSED ON THE ROOF SHALL BE SUPPORTED PER DETAIL "2/E9.001".

SUPPORT SPACING SHALL BE PER DETAIL "2/E9.001", NOTES 1 AND 2.

SHEET NUMBER

S

TA

TE

O

F C

A

LI

FO

R N

IA

D E P A R

TM

E N T

O F

C O

R R E C

TI

O

N S A

N D

R E H

A B

IL

IT

A

TI

O N

FA

C

IL

IT

Y P

LA

N N

IN

G , C

O N S

TR

U C

TI

O

N A

N D

M A N A G

E M

E N

T D

IV

IS

IO

N

DE

SI

G N

SE

RV

IC

ES

A

ND

S

TA

ND

AR

DS

B

RA

NC

H

DE

SI

G

N

SE

RV

IC

ES

S

EC

TI

O N

APPROVAL

V1

C A L

IF

O R

N

IA

S T A T E P

R

IS

O N L O

S A

N G

E L E S C

O U N T Y

T H

S T R

E E T , W

E S T

LA

N C

A S T E R

, C A

.1

Electrical Engineers Lighting Designers

100 Howe Ave., Suite 235N

Sacramento, CA 95825-8217

PROJECT #:

www.mneilsengineering.com

Tel: (916) 923-4400

PROJECT MGR: Stuart LinGsa\

21318.21

08/29/2023

R E P L A C E R

O O

F S

P H

A S E

A U G

U S T

W O

R K

IN

G D

R A W

IN

1/8"=1'-0"

TYPICAL 270 HOUSING UNIT ROOF PLAN - REMODEL - ELECTRICAL1

EA301

EA301

T Y P

IC

A L

H

O U

S

IN

G U

N

IT

R O

O F P

L A

N R

E M

O D

E L

E L E C

T R

IC

A L

5'

1/8" = 1'-0"

0 25'10' 15' 20'

GRAPHIC SCALE

BUILDING 332 BUILDING 331

N

N N

BUILDING 333 BUILDING 335

N

BUILDING 336 BUILDING 337 BUILDING 338 BUILDING 339 BUILDING 3310 BUILDING 341 BUILDING 342 BUILDING 343 BUILDING 344

N

N N N

N

N

BUILDING 345

N N

N

N

BUILDING 348 BUILDING 349 BUILDING 3410

N N

N

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/10/23

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

23-0002