1. General
1.1 Scope of Work
CONSTRUCTION SPECIFICATION
CS-UT-263 VARIABLE FREQUENCY DRIVES {VFD)
CS-UT-263
The contractor shall furnish, and install a pump control system designed to operate one pump using Variable Frequency Drives (VFDs) as described herein. The control system shall be designed utilizing proven technology in control design for constant pressure, constant flow rate, or a combination of flow and pressure ranges to provide the desired operating conditions of the pumping system. The control system shall be operator and maintenance friendly to ensure ease of system set up and to limit down time.
The pump control system shall be capable of operating one electric pump motor as manufactured by TBD by sponsor
Model: TBD by sponsor
Horsepower: 25hp *See drawings
Full-load amps (FLA):
Incoming power shall be: Vac Phase, 60Hz
Line/load reactor required by electric supplier? Yes
The desired operating ranges for pump output pressures and flow-rates are:
Minimum Pressure (psi): 32.5 psi
Maximum Pressure (psi): 35.5 psi
Minimum Flow (gpm): 400gpm
Maximum Flow (gpm): 786 gpm
No
The control system shall use a pressure transmitter and/or flow meter connected to the discharge piping of the pump.
The factory assembled system shall include:
USDA-NRCS-UT 36/48 March 2010