J4_Project_Drawings.pdf

PDF 412 KB Posted

Attached to
PACIFIC SOUTHWEST RESEARCH STATION - Riverside Laboratory Fire Alarm System Upgrade
Solicitation number
129AD618Q0001
Issued by

About this file

Project Drawings

View the file

Other files

File Type Posted
J3_Project_Specifications.pdf PDF
SF-18_Request_for_Quotation.pdf PDF
129AD618Q0001_-_RFQ.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T1.0

AS NOTED

10/10/2017

DR

DR

1 3

FI

R

E A

LA

R

M S

Y S

TE

M

U P

G R

A D

E S

TI

TL

E S

H E

E T

PS

W

R

IV

ER

SI

D

E

FI

R E

LA

B

SHEET OF

DRAWING

PROJECT NUMBER

CHECKED BY

SCALE

DATE

CHECKED BY

DESIGNED BY

DRAWN BY

ST

A

TI

O

N

D R

A W

IN

G

PR

O

JE

C

T N

A M

E:

N A

M E:

FOREST

RESEARCH

SOUTHWEST

PACIFIC

DATENO. REVISIONS

STATION

SERVICE

U S D A

PROJECT DRAWINGS FOR:

RIVERSIDE FIRE ALARM SYSTEM UPGRADES

UNITED STATES DEPARTMENT OF AGRICULTURE

FOREST SERVICE

PACIFIC SOUTHWEST RESEARCH STATION

BLDG.

BLDG.

BLDG.

FA1.1

AS NOTED

10/10/2017

DR

DR

2 3

FI

R

E A

LA

R

M S

Y S

TE

M

U P

G R

A D

E S

B U

IL

D

IN

G

F

IR

E

A

LA

R M

S Y

S

TE

M

PS

W

R

IV

ER

SI

D

E

FI

R E

LA

B

SHEET OF

DRAWING

PROJECT NUMBER

CHECKED BY

SCALE

DATE

CHECKED BY

DESIGNED BY

DRAWN BY

A/E

ST

A

TI

O

N

D R

A W

IN

G

PR

O

JE

C

T N

A M

E:

N A

M E:

FOREST

RESEARCH

SOUTHWEST

PACIFIC

DATENO. REVISIONS

STATION

SERVICE

U S D A

BUILDING 1 & 2 FLOORPLAN

LEGEND

INSTALL TWO (2) DUCT

SMOKE SENSORS ON AHU-1

SYSTEM (SUPPLY AND RETURN).

AHU-1 LOCATED IN MECH ROOM

BUILDING 1

BUILDING 2

REMOVE EX. BELL

PATCH WALL

EXISTING

TO REMAIN

CONTRACTOR SHALL INSTALL

GRC CONDUIT ON TOP OF

BREEZEWAY ROOF FOR FIRE

ALARM SYSTEM WIRING

BUILDING 2 BASEMENT FLOORPLAN

SEE BUILDING 2 BASEMENT

FLOORPLAN THIS PAGE

INSTALL DUCT SMOKE SENSOR

FOR AHU-2 RETURN SYSTEM.

AHU-2 LOCATED ON ROOF

EX SUPPLY DUCT SMOKE SENSOR

(SYSTEM SENSOR MODEL D4120)

CONNECT EX SENSOR FOR AHU-2 TO

NEW FIRE ALARM SYSTEM. TEST SENSOR

FOR PROPER FUNCTIONALITY W/ BOTH

FIRE AND HVAC SYSTEMS. LOCATED IN

PLENUM SPACE

1":20'

REMOVE EX FIRE

ALARM CONTROL PANEL

FIRE ALARM SYSTEM NOTES - BUILDING 1 & 2 :

THESE REQUIREMENTS SHALL BE USED IN CONJUNCTION WITH THE

PROVIDED CSI SPECIFICATIONS. WHERE THERE IS A CONFLICT BETWEEN

THESE REQUIREMENTS AND THE CSI SPECIFICATIONS, THE MOST STRINGENT

SHALL GOVERN.

1. OCCUPANCY: EXISTING BUSINESS OCCUPANCY. FIRE ALARM SYSTEM IS

"NOT REQUIRED" BY CODE AND IS VOLUNTARILY INSTALLED TO ACHIEVE

SPECIFIC FIRE SAFETY OBJECTIVES. NFPA 72 - 17.5.3.3.1: DETECTION

INSTALLED FOR REASONS OF ACHIEVING SPECIFIC FIRE SAFETY

OBJECTIVES, BUT NOT REQUIRED BY ANY LAWS, CODES, OR STANDARDS,

SHALL MEET ALL OF THE REQUIREMENTS OF THIS CODE WITH THE

EXCEPTION OF THE PRESCRIPTIVE SPACING CRITERIA OF CHAPTER 17.

2. UNLESS OTHERWISE NOTED, DRAWINGS SHOW LOCATIONS OF NEW AND

REPLACEMENT EQUIPMENT TO BE INSTALLED. CONTRACTOR MAY REUSE

EXISTING WIRING AND CONDUIT AS LONG AS IT MEETS THE

MANUFACTURER'S INSTALLATION INSTRUCTIONS AND THE

SPECIFICATIONS. EQUIPMENT SHOWN AS EXISTING IS TO REMAIN IN

SERVICE UNLESS OTHERWISE NOTED.

3. FLOORPLAN DRAWINGS ARE INTENDED TO SHOW GENERAL LOCATIONS

OF EQUIPMENT TO BE INSTALLED. FIELD LOCATIONS MAY VARY

DEPENDING ON PROXIMITY TO OTHER FACILITY AND SITE FEATURES.

4. DETECTORS AND NOTIFICATION APPLIANCES SHOWN ON THE DRAWINGS

INDICATE SPECIFIC ROOMS AND CORRIDORS TO BE MONITORED AND

NOTIFIED BY THE FIRE ALARM SYSTEM. DRAWINGS DO NOT INDICATE

SPECIFIC QUANTITIES OR LOCATIONS OF THESE DEVICES. THE

CONTRACTOR SHALL DETERMINE THE APPROPRIATE DEVICE LOCATIONS

AND QUANTITIES FOR THESE SPECIFIC ROOMS AND CORRIDORS PER

MANUFACTURER'S INSTRUCTION, NFPA, ADA, & THE AUTHORITY HAVING

JURISDICTION. CONTRACTOR IS RESPONSIBLE FOR PROVIDING AND

INSTALLING ALL DEVICES TO MEET THESE REQUIREMENTS. NO DEVICES

ARE REQUIRED IN ROOMS WHERE DEVICES ARE NOT SHOWN ON THE

DRAWINGS. IN CORRIDORS, DETECTORS SHALL BE INSTALLED WITHIN 4

FT OF EXIT DOORS AND 40 FT MAX SPACING WHERE POSSIBLE.

5. CONTRACTOR SHALL REMOVE AND REPLACE NON-ADDRESSABLE PULL

STATIONS WITH NEW ADDRESSABLE PULL STATIONS WHERE EXISTING

PULL STATIONS EXIST. TWO NEW PULL STATION LOCATIONS SHALL BE

INSTALLED: THE KITCHEN OF BLDG 1 AND THE BASEMENT OF BLDG 2.

6. DUCT SMOKE SENSORS SHALL BE INSTALLED FOR THE HVAC SYSTEMS

INDICATED ON THE DRAWINGS AND SHALL BE MONITORED AND ALARMED

BY THE FIRE ALARM SYSTEM. DUCT SMOKE SENSORS SHALL BE

INTEGRATED WITH EXISTING HVAC CONTROL SYSTEMS TO SHUTDOWN

ALL OPERATIONAL CAPACITIES OF THE AIR DISTRIBUTION SYSTEM UPON

ACTIVATION. EXISTING DUCT SMOKE SENSORS ARE INDICATED ON THE

DRAWING AND SHALL BE TESTED FOR PROPER FUNCTIONALITY AND

INTEGRATED WITH THE FIRE ALARM SYSTEM. CONTRACTOR SHALL BE

RESPONSIBLE FOR VERIFYING EXISTING HVAC CONTROL SYSTEMS AND

PROPERLY INSTALLING SENSORS IN CODE COMPLIANT LOCATIONS.

SITE PLAN

REMOVE EX FACP

INSTALL NEW FACP

*SCALES ARE ACCURATE WHEN PRINTED AT 11"x17"

EXISTING

REMOVE

CONTRACTOR SHALL INSTALL

GRC CONDUIT UNDER

BREEZEWAY ROOF FOR FIRE

ALARM SYSTEM WIRING

EXISTING HORN

REPLACE W/ HORN STROBE

BLDG.

BLDG.

BLDG.

FA1.2

AS NOTED

10/10/2017

DR

DR

3 3

FI

R

E A

LA

R

M S

Y S

TE

M

U P

G R

A D

E S

B U

IL

D

IN

G

F

IR

E

A

LA

R M

S Y

S

TE

M U

P G

R A

D E

S

PS

W

R

IV

ER

SI

D

E

FI

R E

LA

B

SHEET OF

DRAWING

PROJECT NUMBER

CHECKED BY

SCALE

DATE

CHECKED BY

DESIGNED BY

DRAWN BY

A/E

ST

A

TI

O

N

D R

A W

IN

G

PR

O

JE

C

T N

A M

E:

N A

M E:

FOREST

RESEARCH

SOUTHWEST

PACIFIC

DATENO. REVISIONS

STATION

SERVICE

U S D A

BUILDING 3 - 2ND FLOOR

SITE PLAN

LEGEND

BUILDING 3 - 1ST FLOOR

1":25'

1":25'

INSTALL TWO (2) DUCT

SMOKE SENSORS FOR AC-5

SYSTEM (SUPPLY AND RETURN)

EX SUPPLY DUCT SMOKE SENSOR

(SILENT KNIGHT MODEL SD505-ADHR)

TEST SENSOR FOR PROPER

FUNCTIONALITY W/ BOTH

FIRE AND HVAC SYSTEMS

INSTALL TWO (2) DUCT

SMOKE SENSORS FOR AC-6

SYSTEM (SUPPLY AND RETURN)

INSTALL COMPATIBLE ADDRESSABLE

HEAT SENSOR ABOVE EX FACP

EX FACP

(SILENT KNIGHT

5820XL)

EXISTING

TO REMAIN

EXISTING

TO REMAIN

EXISTING

ALL EQUIPMENT IN HATCHED

AREA IS EXISTING AND

SHALL REMAIN IN SERVICE.

EXISTING

TO REMAIN

EXISTING

TO REMAIN

FIRE ALARM SYSTEM NOTES - BUILDING 3 :

THESE REQUIREMENTS SHALL BE USED IN CONJUNCTION WITH THE

PROVIDED CSI SPECIFICATIONS. WHERE THERE IS A CONFLICT BETWEEN

THESE REQUIREMENTS AND THE CSI SPECIFICATIONS, THE MOST STRINGENT

SHALL GOVERN.

1. OCCUPANCY: EXISTING BUSINESS OCCUPANCY. FIRE ALARM SYSTEM IS

"NOT REQUIRED" BY CODE AND IS VOLUNTARILY INSTALLED TO ACHIEVE

SPECIFIC FIRE SAFETY OBJECTIVES. NFPA 72 - 17.5.3.3.1: DETECTION

INSTALLED FOR REASONS OF ACHIEVING SPECIFIC FIRE SAFETY

OBJECTIVES, BUT NOT REQUIRED BY ANY LAWS, CODES, OR STANDARDS,

SHALL MEET ALL OF THE REQUIREMENTS OF THIS CODE WITH THE

EXCEPTION OF THE PRESCRIPTIVE SPACING CRITERIA OF CHAPTER 17.

2. UNLESS OTHERWISE NOTED, DRAWINGS SHOW LOCATIONS OF NEW AND

REPLACEMENT EQUIPMENT TO BE INSTALLED. CONTRACTOR MAY REUSE

EXISTING WIRING AND CONDUIT AS LONG AS IT MEETS THE

MANUFACTURER'S INSTALLATION INSTRUCTIONS AND THE PROJECT

SPECIFICATIONS. EQUIPMENT SHOWN AS EXISTING IS TO REMAIN IN

SERVICE UNLESS OTHERWISE NOTED.

3. FLOORPLAN DRAWINGS ARE INTENDED TO SHOW GENERAL LOCATIONS

OF EQUIPMENT TO BE INSTALLED. FIELD LOCATIONS MAY VARY

DEPENDING ON PROXIMITY TO OTHER FACILITY AND SITE FEATURES.

4. DETECTORS AND NOTIFICATION APPLIANCES SHOWN ON THE DRAWINGS

INDICATE SPECIFIC ROOMS AND CORRIDORS TO BE MONITORED AND

NOTIFIED BY THE FIRE ALARM SYSTEM. DRAWINGS DO NOT INDICATE

SPECIFIC QUANTITIES OR LOCATIONS OF THESE DEVICES. THE

CONTRACTOR SHALL DETERMINE THE APPROPRIATE DEVICE LOCATIONS

AND QUANTITIES FOR THESE SPECIFIC ROOMS AND CORRIDORS PER

MANUFACTURER'S INSTRUCTION, NFPA, ADA, & THE AUTHORITY HAVING

JURISDICTION. CONTRACTOR IS RESPONSIBLE FOR PROVIDING AND

INSTALLING ALL DEVICES TO MEET THESE REQUIREMENTS. NO DEVICES

ARE REQUIRED IN ROOMS WHERE DEVICES ARE NOT SHOWN ON THE

DRAWINGS. IN CORRIDORS, DETECTORS SHALL BE INSTALLED WITHIN 4

FT OF EXIT DOORS AND 40 FT MAX SPACING WHERE POSSIBLE.

5. DUCT SMOKE DETECTORS SHALL BE INSTALLED FOR THE HVAC SYSTEMS

INDICATED ON THE DRAWINGS AND SHALL BE MONITORED AND ALARMED

BY THE FIRE ALARM SYSTEM. DUCT SMOKE DETECTORS SHALL BE

INTEGRATED WITH EXISTING HVAC CONTROL SYSTEMS TO SHUTDOWN

ALL OPERATIONAL CAPACITIES OF THE AIR DISTRIBUTION SYSTEM UPON

ACTIVATION. EXISTING DUCT SMOKE DETECTORS ARE INDICATED ON

THE DRAWING AND SHALL BE TESTED FOR PROPER FUNCTIONALITY AND

INTEGRATED WITH THE FIRE ALARM SYSTEM. CONTRACTOR SHALL BE

RESPONSIBLE FOR VERIFYING EXISTING HVAC CONTROL SYSTEMS AND

PROPERLY INSTALLING DETECTORS IN CODE COMPLIANT LOCATIONS.

6. ALL NEW AND EXISTING PULL STATIONS SHALL MEET ADA

REQUIREMENTS. WHERE EXISTING PULL STATIONS DO NOT MEET THESE

REQUIREMENTS, THE CONTRACTOR SHALL MODIFY TO BE COMPLIANT.

*SCALES ARE ACCURATE WHEN PRINTED AT 11"x17"

ALL EQUIPMENT IN HATCHED

AREA IS EXISTING AND

SHALL REMAIN IN SERVICE.

EXISTING

TO REMAIN

EXISTING

REMOVE

INSTALL EXISTING EXPOSED

ALARM WIRING IN CONDUIT

(APPROX 3 FT)

SEAL CEILING PENETRATION

INSTALL EXISTING EXPOSED

ALARM WIRING IN CONDUIT

(APPROX 20 FT)

SEAL CEILING PENETRATION

INSTALL EXISTING EXPOSED

ALARM WIRING IN CONDUIT

ALONG WALL (APPROX 40 FT)

SEAL WALL PENETRATION

INSTALL WATERFLOW DETECTOR

ON EXISTING 4" FIRE SPRINKLER

SYSTEM RISER

Bldg1&2&3_ShopDrawing_v4-TITLE
Bldg1&2&3_ShopDrawing_v4-Bldg 1&2_11x17
Bldg1&2&3_ShopDrawing_v4-Bldg 3_11x17

File details come from the government source that posted it.