Attachment_8_Drawing_Clarifications.pdf
PDF 531 KB Posted
- Attached to
- Sawyers Bar Emergency Generator Building Repair
- Solicitation number
- 129AC719Q0037
About this file
Attachment 8
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
knolan Line emove & Replace knolan Callout Remove & replace 1/2" drywall (2 layers) & sound dampening backer board along southeast wall from double door frame to S/E building corner, approx. 70 SF (verify).
knolan Callout Remove & replace 1/2" drywall (2 layers) & sound dampening backer board entire sealing, approx 480 SF (verify). All ceiling penetrations to be sealed and fire taped.
knolan Line knolan Rectangle knolan Polygon knolan Line knolan Line knolan Line knolan Line knolan Callout Relocate generator engine exhausts, including insulated thimble collar & spark arrestor system per NFPA. Plug, re-side & seal old penetration with matching panel material, caulking & fasteners.
knolan Line knolan Text Box Prime and paint of interior walls is to include existing and new drywall only, approximately 800 SF
File details come from the government source that posted it.