Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

(a) By completing items 8 and 15, and returning or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

E. IMPORTANT: Contractor is not is required to sign this document and return copies to the issuing office.

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE

2. AMENDMENT/MODIFICATION NUMBER 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)

7. ADMINISTERED BY (If other than Item 6) CODE

STANDARD FORM 30 (REV. 11/2016)

Prescribed by GSA FAR (48 CFR) 53.243

FACILITY CODE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED (SEE ITEM 11)

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED (SEE ITEM 13)

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended. is not extended.

12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER

NUMBER IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15C. DATE SIGNED

15A. NAME AND TITLE OF SIGNER (Type or print)

16C. DATE SIGNED

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

PAGE OF PAGES

6. ISSUED BY CODE

8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X)

CODE

15B. CONTRACTOR/OFFEROR

(Signature of person authorized to sign)

16B. UNITED STATES OF AMERICA

(Signature of Contracting Officer)

Previous edition unusable

RFQ 12905B22Q0034 - Update/Replace Boilers at Riverside, CA.

Amendment #3

Riverside Boiler Repair/Replacement

Questions/Responses

1) Please confirm DHW if the heat exchanger sizing is 1,150,000 BTUH to match the existing boiler output and not 11500 BTUH as listed in the scope of work.

Response: Max BTU/HOUR INPUT 1,375,000; BTU/HOUR OUTPUT 1,127,000

MIN BTU/HOUR INPUT 687,500; MIN BTU/HOUR OUTPUT 563,750

Temperature In: 160 degrees Fahrenheit Temperature Out: 200 degrees Fahrenheit Max Operating Pressure: 45 PSIG There is a separate hot water boiler coil that should have 11,500 BTUH output that will need to be added to the new boiler loop. This will require some additional plumbing and appropriate valves, pump and other appurtenances to provide domestic hot water. The domestic hot water has an existing pump downstream of the boiler that does not need to be replaced.

2) Please confirm how far to demo steam and condensate piping to the air handler coils.

Response: Terminate at boiler room wall or nearest joint. Nearest joint no more than 10 feet.

Amend 0003 - 12905B22Q0034 - SF-30
Questions-Responses Riverside 22Q0034 4-7-2022
topmostSubform[0]:
Page1[0]:
AmendmentNo[0]: 0003
Code[0]: 12905B
Code[1]:
AccountingData[0]:
A13[0]:
C13[0]:
D13[0]:
NameandTitleSigner[0]:
NameandTitleOfficer[0]: Michael Hassett
Description[0]: RFQ 12905B22Q0034 - Update/Replace Boilers at Riverside, CA.

The purpose of this amendment is to give answers to questions offers had; see the following pages for details. The due date for this RFP remains unchanged.

FacilityCode[0]:
Code[2]:
IssuedBy[0]: USDA ARS PWA AAO ACQ/PER PROP

800 BUCHANAN STREET

ALBANY CA 94710

Theodore Blume Email: theodore.blume@usda.gov

NameandAddress[0]:
AdministeredBy[0]:
ContractIDCode[0]:
ReqNumber[0]: 1053794
AmendmentNo[1]: 12905B22Q0034
ModificationNo[0]:
ProjectNo[0]: LSY 20037.01
Page[0]:
Pages[0]:
EffectiveDate[0]: 04/07/2022
Dated9B[0]: 03/17/2022
Dated10B[0]:
CheckBox9[0]: 1
CheckBox10[0]: Off
CheckBox11[0]: 1
CheckBox13A[0]: Off
CheckBox13B[0]: Off
CheckBox13C[0]: Off
CheckBox13D[0]: Off
IsNot[0]: Off
Is[0]: Off
Extended[0]: Off
NotExtended[0]: 1
DateSigned[0]:
DateSigned[1]:
Copies[0]: 1
CopiesReturned[0]:

File details come from the government source that posted it. Updated .