This document is an Asbestos Inspection Report for the Coronado National Forest Radar Base Dormitory. The report details the materials containing asbestos found throughout various rooms of the dormitory building, including floor tiles, pipe insulation, and cement board panels. The materials are categorized as either Asbestos-Containing Building Material (ACBM) or Asbestos-Containing Material (ACM), and their physical condition is assessed. The report provides quantitative details on the square footage, diameter, and thickness of the asbestos-containing materials identified. This information appears to be relevant to a federal contract opportunity, Solicitation Number 127EAU24Q0055, for the Coronado (CNF3) NF - Radar Base Dormitory Removal project, issued by the USDA Forest Service.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A S B E S T O S I N S P E C T I O N R E P O R T

CORONADO NATIONAL FOREST

RADAR BASE

IR-60003-0300

Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:53:21 Page 1

BUILDING

Building Name Address City, State Gross Sq. Feet Inspector Name

BASE DORMITORY 1411-B

CATALINA HIGH\.JAY

TUCSON, AZ

16930

JOE LORANGER

EM! Building # Contact Person Title Phone Inspected

: 60003

: RAY \.JIGGINS

: ASBESTOS PROJECT SUPERVISOR

: (602) 670-5455 : 11/08/91

ROOM -------------------------------------------------------------------------------------------------- Functional Space 0300 Room - UNK HALLI.JAY 1ST FLOOR

M A T E R I A L Sample Area Type of Material Asbestos Found :

Physical Assessment Assessment Reason

M A T E R I A L Sample Area Type of Material Asbestos Found :

Physical Assessment Assessment Reason

M A T E R I A L Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason

M A T E R I A L Sample Area Type of Material Asbestos Found :

Physical Assessment Assessment Reason

AA

4A1

YES

9X9 FLOOR TILE GREEN

Floor Tile

ACBM with potential for damage.

Sampled/Assumed/Previous ID SAMPLED

ACM/ACBM : ACBM

Friable: NO

Nonfriable. Significantly Damaged. Damage is distributed. More than percent of surface area is damaged. \.Jater Damage. Gouged/Chipped.

twenty-five

AB

4K

YES

AD

2B

NO

AG

3B

NO

MASTIC SA-AB

Mastic

ACBM with potential for damage.

QUANT I TY ·-··-·-···---·-----·-·-----·-·----

Square Diameter Linear # 1.Jidth Thickness Footage Cinches) Footage Units Cinches) Cinches)

Sampled/Assumed/Previous ID SAMPLED

ACM/ACBM : ACBM

Friable: NO

Nonfriable. Significantly Damaged. Damage is distributed.

percent of surface area is damaged. Delamination.

More than twenty-five

MUDDED PIPE FITTING 5"

Mudded Pipe Fitting Insulation n/a Not found to contain asbestos.

QUANT I TY ----------------------------------

Square Diameter Linear # 1.Jidth Thickness Footage (Inches) Footage Units (Inches) (Inches)

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

YES

QUANTITY ----------------------------------

\.JALLBOARD

\.Jallboard/Dry wall

Square Diameter Linear # 1.Jidth Thickness Footage Cinches) Footage Units (Inches) Cinches)

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

1.00

SAMPLED

n/a

YES

n/a Not found to contain asbestos.

QUANT I TY ·-·------------------····---·····-

Square Diameter Linear # 1.Jidth Thickness Footage (Inches) Footage Units (Inches) (Inches)

Continued on the next page.

RADAR BASE

IR-60003-0300 (cont'd) Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:53:21 Page 2

M A T E R I A L Sample Area : AH

: 4K

NO

Type of Material Asbestos Found Physical Assessment Assessment Reason

M A T E R I A L Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason

M A T E R I A L Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason

M A T E R I A L Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason

AJ

2B

NO

AK

2B

NO

BG

2B

NO

n/a

BASEBOARD MASTIC

Mastic

Not found to contain asbestos.

MUDDED PIPE FITTING 211

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

NO

QUANT I TY ·--·------------------------------

Square Diameter Linear # Width Thickness Footage Cinches) Footage Units Cinches) Cinches)

Mudded Pipe Fitting Insulation Sampled/Assumed/Previous ID

ACM/ACBM

Friable.

SAMPLED

n/a n/a Not found to contain asbestos.

MUDDED PIPE FITTING 311 •

YES

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

18 1.00

Mudded Pipe Fitting Insulation Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a n/a Not found to contain asbestos_

MUDDED PIPE FITTING 411

YES

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units Cinches) Cinches)

20 1.00

Mudded Pipe Fitting Insulation Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

YES

n/a Not found to contain asbestos.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage Cinches) Footage Units Cinches) Cinches)

15 1.00

RADAR BASE

A S B E S T O S I N S P E C T I O N R E P O R T

IR-60003-0300 (cont'd) Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:53:21 Page 3

MATER I AL ------------------------------------------------------·----------------------------------- Sample Area : BK CEMENT BOARD PANEL Sampled/Assumed/Previous ID SAMPLED Type of Material : 4B Cement Board - 'Transite' ACM/ACBM: ACBM Asbestos Found : YES Friable: NO Physical Assessment : Remaining nonfriable ACBM or ACM.

Assessment Reason : Nonfriable. Undamaged.

QUANT I TY ·--------------------~------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

NOTES --------------------------------------------·----------------------------------------------------

(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.

(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample Summary" report for sample locations and analysis results. {ir_rept.ww}

RADAR BASE

IR-60003-0310

Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:53:44 Page 1

B U I L D I N G Building Name Address City, State Gross Sq. Feet Inspector Name

BASE DORMITORY 1411-B

CATALINA HIGHWAY

TUCSON, AZ

16930

JOE LORANGER

EM! Building# Contact Person Title Phone Inspected

: 60003

: RAY WIGGINS

: ASBESTOS PROJECT SUPERVISOR

: (602) 670-5455 : 11/08/91

ROOM --------------------------------------------------------------·-·--------------------------------- Functional Space: 0310 Room - UNK DORM ROOM

MATER I AL ------------------------------------------------------·-·-·------------------------------- Sample Area : AA 9X9 FLOOR TILE GREEN Sampled/Assumed/Previous ID SAMPLED Type of Material : 4A1 Floor Tile ACM/ACBM : ACBM Asbestos Found : YES Friable: NO Physical Assessment ACBM with potential for damage.

Assessment Reason Nonfriable. Significantly Damaged. Damage is distributed. Ten to twenty-five percent of surface area is damaged. Water Damage. Gouged/Chipped.

QUANT I TY ·-·-------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

165 0.13

MATERIAL ------------------------------------------------------·-·-·------------------------------- Sample Area : AB MASTIC SA-AB Sampled/Assumed/Previous ID SAMPLED Type of Material : 4K Mastic ACM/ACBM ACBM Asbestos Found : YES Friable NO Physical Assessment: Remaining nonfriable ACBM or ACM.

Assessment Reason : Nonfriable. Undamaged.

QUANT I TY ·-·-------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches).

165 0.10

MATER I AL ------------------------------------------------------··--·------------------------------- Sample Area : AG WALLBOARD Sampled/Assumed/Previous ID SAMPLED Type of Material : 3B Wallboard/Dry wall ACM/ACBM n/a Asbestos Found : NO Friable YES Physical Assessment n/a Assessment Reason : Not found to contain asbestos.

QUANT I TY --·--·-·--·-----------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

400 0.40

MATERIAL -----···----------------------------------------------··--·--·-·--·----------------------- Sample Area : AH BASEBOARD MASTIC Sampled/Assumed/Previous ID SAMPLED Type of Material : 4K Mastic ACM/ACBM n/a Asbestos Found : NO Friable NO Physical Assessment n/a Assessment Reason : Not found to contain asbestos.

QUANT I TY --·--···--------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

52 0.10

A S B E S T O S I N S P E C T I O N R E P O R T

IR-60003-0310 (cont'd) Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:53:44 Page 2

MATER I AL ------------------------------------------------------------------------------------------ Sample Area : AK Type of Material Asbestos Found :

2B

NO

: n/a

MUDDED PIPE FITTING 311

Mudded Pipe Fitting Insulation Sampled/Assumed/Previous ID SAMPLED

ACM/ACBM : n/a Friable: YES

Physical Assessment Assessment Reason : Not found to contain asbestos.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

1.00

NOTES ------------------------------------------------------------------------------------------------

(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.

(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample Summary"

RADAR BASE

IR-60003-0311

Printed by EnviroMD SAM system ever. 1.3): 12/07/91 10:53:58 Page 1

B U I L D I N G Building Name Address City, State Gross Sq. Feet Inspector Name

BASE DORMITORY 1411-B

CATALINA HIGHWAY

TUCSON, AZ

16930

JOE LORANGER

EM! Building # Contact Person Title Phone Inspected

: 60003

: RAY WIGGINS

: ASBESTOS PROJECT SUPERVISOR

: (602) 670-5455 : 11/08/91

ROOM -------------------------------------------------------------------------------------------------- Functional Space 0311 Room - UNK PIPE CHASE

M A T E R I A L Sample Area : AG

3B

NO

Type of Material Asbestos Found :

Physical Assessment Assessment Reason

M A T E R I A L Sample Area n/a Not

WALLBOARD

Wallboard/Dry wall found to contain asbestos.

MUDDED PIPE FITTING 311

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

YES

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

16 0.40

: AK

2B

NO

Type of Material Asbestos Found Physical Assessment Assessment Reason

Mudded Pipe Fitting Insulation Sampled/Assumed/Previous ID

ACM/ACBM·

Friable

SAMPLED

n/a

YES

M A T E R I A L Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason

M A T E R I A L Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason

BC

4G

NO

BD

3K

NO

n/a Not found to contain asbestos.

n/a Not

WALLBOARD SEAM TAPE

Seam Tape found to contain asbestos.

WALL JOINT

n/a Not

Other Miscellaneous Friable found to contain asbestos.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

1.00

SAMPLED

n/a

NO

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

No measurements were taken for this material.

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

NO

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

No measurements were taken for this material.

A S B E S T O S I N S P E C T I O N R E P O R T

IR-6DD03-0311 (cont'd) Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:53:58 Page 2

NOTES ------------------------------------------------------------··----------------------------------

(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.

(3) Reinspect ion is advised prior to renovation or demolition. (4) See "Inspection Report Sample Summary"

RADAR BASE

IR-60003-0320

Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:54:10 Page 1

B U I L D I N G Building Name Address City, State Gross Sq. Feet Inspector Name

BASE DORMITORY 1411-B

CATALINA HIGHWAY

TUCSON, AZ

16930

JOE LORANGER

EM! Building # Contact Person Title Phone Inspected

: 60003 : RAY rWIGGINS

ASBESTOS PROJECT SUPERVISOR

(602) 670-5455 11/08/91

ROOM -------------------------------------------------------------------------------------------------- Functional Space 0320 Room - UNK DORM ROOM

M A T E R I A L Sample Area : AA

4A1

YES

Type of Material Asbestos Found :

9X9 FLOOR TILE GREEN

Floor Ti le

ACBM with potential for damage.

Sampled/Assumed/Previous ID SAMPLED

ACM/ACBM : ACBM

Friable : NO Physical Assessment Assessment Reason Nonfriable. Significantly Damaged. Damage is distributed.

of surface area is damaged. Water Damage. Gouged/Chipped.

Ten to twenty-five percent

QUANT I TY ·---------------------------------

Square Diameter Linear # Width Thickness Footage Cinches) Footage Units (Inches) Cinches)

165 0.13

MATERIAL ------------------------------------------------------------------------------------------ Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason

M A T E R I A L Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason

M A T E R I A L Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason

AB

4K

YES

MASTIC SA-AB

Mastic

Remaining nonfriable ACBM or ACM.

Nonfriable. Undamaged.

AG

NO

AH

4K

NO

n/a Not n/a

WALLBOARD

Wallboard/Dry wall found to contain asbestos.

BASEBOARD MASTIC

Mastic

Not found to contain asbestos.

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

ACBM

NO

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage Cinches) Footage Units (Inches) Cinches)

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

0.10

SAMPLED

n/a

YES

QUANTITY ------------------- 0 --------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) Cinches)

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

0.40

SAMPLED

n/a

NO

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

M A T E R I A L Sample Area : AK Type of Material Asbestos Found Physical Assessment Assessment Reason

2B

NO

n/a Not

A S B E S T O S I N S P E C T I O N R E P O R T

IR-60003-0320 (cont'd) Printed by EnviroMD SAM system ever. 1.3): 12/07/91 10:54:10 Page 2

MUDDED PIPE FITTING 311

Mudded Pipe Fitting Insulation found to contain asbestos.

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

YES

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

1.00

NOTES ------------------------------------------------------------------------------------------------

(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.

(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample Summary"

RADAR BASE

IR-60003-0330

Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:54:26 Page 1

B U I L D I N G Building Name Address City, State Gross Sq. Feet Inspector Name

BASE DORMITORY 1411-B

CATALINA HIGHWAY

TUCSON, AZ

16930

JOE LORANGER

EMI Building # Contact Person Title Phone Inspected

: 60003

: RAY WIGGINS

: ASBESTOS PROJECT SUPERVISOR

: (602) 670-5455 : 11/08/91

RO ·o M ----------- ✓--------------------------------------------------·-·--------------------------------- Functional Space: 0330 Room - UNK DORM ROOM

MATER I AL ------------------------------------------------------------------------------------------ Sample Area : AA 9X9 FLOOR TILE GREEN Sampled/Assumed/Previous ID SAMPLED Type of Material : 4A1 Floor Tile ACM/ACBM : ACBM Asbestos Found : YES Friable: NO Physical Assessment ACBM with potential for damage.

Assessment Reason Nonfriable. Significantly Damaged. Damage is distributed_ Ten to twenty-five percent of surface area is damaged. Water Damage. Gouged/Chipped.

QUANT I TY ·---------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

240 0.13

MATER I AL ------------------------------------------------------------------------------------------ Sample Area : AB MASTIC SA-AB Sampled/Assumed/Previous ID SAMPLED Type of Material : 4K Mastic ACM/ACBM ACBM Asbestos Found : YES Friable NO Physical Assessment: ·Remaining nonfriable ACBM or ACM.

Assessment Reason : Nonfriable. Undamaged.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

240 0.10

MATERIAL ------------------------------------------------------------------------------------------ Sample Area : AG WALLBOARD Sampled/Assumed/Previous ID SAMPLED Type of Material : 3B Wallboard/Dry wall ACM/ACBM n/a Asbestos Found : NO Friable YES Physical Assessment : n/a Assessment Reason : Not found to contain asbestos.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

854 0.40

MATERIAL -------------------------------------------------------·---------------------------------- Sample Area : AH

4K

NO

Type of Material Asbestos Found :

Physical Assessment Assessment Reason n/a : Not

BASEBOARD MASTIC

Mastic found to contain asbestos.

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

NO

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

70 0.10

M A T E R I A L Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason

BC

4G

NO

n/a Not

A S B E S T O S I N S P E C T I O N R E P O R T

IR-60003-0330 (cont'd) Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:54:26 Page 2

WALLBOARD SEAM TAPE

Seam Tape found to contain asbestos.

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

NO

QUANT I TY ·---------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) Cinches)

0.10

MATER I AL ------------------------------------------------------------------------------------------ Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason

BD

3K

NO

n/a Not

WALL JOINT

Other Miscellaneous Friable found to contain asbestos.

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

NO

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units Cinches) Cinches)

0.10

NOTES -----------------------· ------------------------------------------------------------------------

(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.

(3) Reinspect ion is advised prior to renovation or demolition. (4) See "Inspection Report Sample Summary"

RADAR BASE

IR-6OOO3-O34O

Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:54:43 Page 1

B U I L D I N G Building Name Address City, State Gross Sq. Feet Inspector Name

BASE DORMITORY 1411-B

CATALINA HIGHWAY

TUCSON, AZ

16930

JOE LORANGER

EM! Building# Contact Person Title Phone Inspected

: 60003

: RAY WIGGINS

: ASBESTOS PROJECT SUPERVISOR

: (602) 670-5455 : 11/08/91

ROOM -------------------------------------------------------------------------------------------------- Functional Space: 0340 Room - UNK DORM ROOM

MATER I AL ------------------------------------------------------------------------------------------ Sample Area : AA 9X9 FLOOR TILE GREEN Sampled/Assumed/Previous ID SAMPLED Type of Material : 4A1 Floor Tile ACM/ACBM : ACBM Asbestos Found : YES Friable: NO Physical Assessment ACBM with potential for damage.

Assessment Reason Nonfriable. Significantly Damaged. Damage is distributed. Ten to twenty-five percent of surface area is damaged. Water Damage. Gouged/Chipped.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage Cinches) Footage Units Cinches) (Inches)

165 0.13

MATER I AL ------------------------------------------------------------------------------------------ Sample Area : AB MASTIC SA-AB Sampled/Assumed/Previous ID SAMPLED Type of Material : 4K Mastic ACM/ACBM ACBM Asbestos Found : YES Friable NO Physical Assessment: Remaining nonfriable ACBM or ACM.

Assessment Reason : Nonfriable. Undamaged.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

165 0.10

MATER I A. L -------·---------------------------------------------------------------------------------- Sample Area : AG WALLBOARD Sampled/Assumed/Previous ID SAMPLED Type of Material : 3B Wallboard/Dry wall ACM/ACBM n/a Asbestos Found : NO Friable YES Physical Assessment n/a Assessment Reason : Not found to contain asbestos.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units Cinches) (Inches)

400 0.40

MATERIAL ------------------------------------------------------···--------------------------------- Sample Area : AH BASEBOARD MASTIC Sampled/Assumed/Previous ID· SAMPLED Type of Material : 4K Mastic ACM/ACBM n/a Asbestos Found : NO Friable NO Physical Assessment n/a Assessment Reason : Not found to contain asbestos.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

A S B E S T O S I N S P E C T I O N R E P O R T

IR-60003-0340 (cont'd) Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:54:43 Page 2

MATER I AL ------------------------------------------------------·----------------------------------- Sample Area : AK

2B

NO

Type of Material Asbestos Found :

Physical Assessment Assessment Reason

MUDDED PIPE FITTING 311

Mudded Pipe Fitting Insulation Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

YES

n/a Not found to contain asbestos.

QUANT I TY ·---------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

1.00

NOTES ------------------------------------------------------------------------------------------------

(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.

(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample Surrmary"

RADAR BASE

IR-60003-0341

Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:54:57 Page 1

B U I L D I N G Building Name Address City, State Gross Sq. Feet Inspector Name

BASE DORMITORY 1411-B

CATALINA HIGHWAY

TUCSON, AZ

16930

JOE LORANGER

EM! Building#: 60003 Contact Person: RAY WIGGINS Title : ASBESTOS PROJECT SUPERVISOR Phone : (602) 670-5455 Inspected : 11/08/91

ROOM --- ------------------------------------------------------.--------------------------------------- Functional Space 0341 Room - UNK PIPE CHASE

M A T E R I A L Sample Area : AG

3B

NO

Type of Material Asbestos Found :

Physical Assessment Assessment Reason n/a Not

WALLBOARD

Wallboard/Dry wall found to contain asbestos.

Sampled/Assumed/Previous ID·

ACM/ACBM

Friable

SAMPLED

n/a

YES

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

16 0.40

MATER I AL ------------------------------------------------------------------------------------------ Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason

M A T E R I A L Sample Area Type of Material Asbestos Found :

Physical Assessment Assessment Reason

M A T E R I A L sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason

MUDDED PIPE FITTING 311 SAMPLED AK

2B

NO

Mudded Pipe Fitting Insulation Sampled/Assumed/Previous ID

ACM/ACBM

Friable n/a

YES

BC

4G

NO

BD

3K

NO

n/a Not found to contain asbestos.

n/a Not

WALLBOARD SEAM TAPE

Seam Tape found to contain asbestos.

WALL JOINT

Other Miscellaneous Friable n/a : Not found to contain asbestos.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units Cinches) (Inches)

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

1.00

SAMPLED

n/a

NO

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

No measurements were taken for this material.

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

NO

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

A S B E S T O S I N S P E C T I O N R E P O R T

IR-60003-0341 (cont'd) Printed by EnviroMD SAM system ever. 1.3): 12/07/91 10:54:57 Page 2

NOTES ------------------------------------------------------------------------------------------------

(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.

(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample summary"

RADAR BASE

IR-60003-0350

Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:55:08 Page 1

B U I L D I N G Building Name Address City, State Gross Sq. Feet Inspector Name

BASE DORMITORY 1411-B

CATALINA HIGHWAY

TUCSON, AZ

16930

JOE LORANGER

EMI Building# Contact Person Title Phone Inspected

: 60003

: RAY WIGGINS

: ASBESTOS PROJECT SUPERVISOR

: (602) 670-5455 : 11/08/91

ROOM -------------------------------------------------------------------------------------------------- Functional Space: 0350 Room - UNK DORM ROOM

MAT.ER I AL ------------------------------------------------------------------------------------------ Sample Area : AA 9X9 FLOOR TILE GREEN Sampled/Assumed/Previous ID SAMPLED Type of Material : 4A1 Floor Tile ACM/ACBM : ACBM Asbestos Found : YES Friable: NO Physical Assessment ACBM with potential for damage.

Assessment Reason Nonfriable. Significantly Damaged. Damage is distributed. Ten to twenty-five percent of surface area is damaged. Water Damage. Gouged/Chipped.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

165 0.13

MATERIAL ------------------------------------------------------------------------------------------ Sample Area : AB MASTIC SA-AB Sampled/Assumed/Previous ID SAMPLED Type of Material : 4K Mastic ACM/ACBM ACBM Asbestos Found : YES Friable NO Physical Assessment : Remaining nonfriable ACBM or ACM.

Assessment Reason : Nonfriable. Undamaged.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) Cinches)

165 0.10

MATER I AL ------------------------------------------------------------------------------------------ Sample Area : AG WALLBOARD Sampled/Assumed/Previous ID SAMPLED Type of Material : 3B Wallboard/Dry wall ACM/ACBM n/a Asbestos Found : NO Friable YES Physical Assessment: n/a Assessment Reason : Not found to contain asbestos.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

400 0.40

MATER I AL ------------------------------------------------------·-·-·------------------------------- Sample Area : AH BASEBOARD MASTIC Sampled/Assumed/Previous ID SAMPLED Type of Material : 4K Mastic ACM/ACBM n/a Asbestos Found : NO Friable NO Physical Assessment : n/a Assessment Reason : Not found to contain asbestos.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

M A T E R I A L Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason

AK

2B

NO

n/a Not

A S B E S T O S I N S P E C T I O N R E P O R T

IR-60003-0350 (cont'd) Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:55:08 Page 2

MUDDED PIPE FITTING 311

Mudded Pipe Fitting Insulation found to contain asbestos.

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

YES

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage Cinches) Footage Units (Inches) (Inches)

1.00

NOTES ------------------------------------------------------------------------------------------------

(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.

(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample Sunvnary"

RADAR BASE

IR-60003-0360

Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:55:25 Page 1

BUILDING

Building Name Address City, State Gross Sq. Feet Inspector Name

BASE DORMITORY 1411-B

CATALINA HIGHWAY

TUCSON, AZ

16930

JOE LORANGER

EMI Building # Contact Person Title Phone Inspected

: 60003

: RAY WIGGINS

: ASBESTOS PROJECT SUPERVISOR

: (602) 670-5455 : 11/08/91

ROOM --------------- .---------------------------------------------------------------------------------- Functional Space : 0360 Room - UNK DORM ROOM

MATER I AL --------------------------------------------------------·--------------------------------- Sample Area : AA 9X9 FLOOR TILE GREEN Sampled/Assumed/Previous ID SAMPLED Type of Material : 4A1 Floor Tile ACM/ACBM: ACBM Asbestos Found : YES Friable: NO Physical Assessment 'ACBM with potential for damage.

Assessment Reason Nonfriable. Significantly Damaged. Damage is distributed. Ten to twenty-five percent of surface area is damaged. Water Damage. Gouged/Chipped.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

165 0.13

MATER I AL ------------------------------------------------------------------------------------------ Sample Area : AB MASTIC SA-AB Sampled/Assumed/Previous ID SAMPLED Type of Material : 4K Mastic ACM/ACBM ACBM Asbestos Found : YES Friable NO Physical Assessment: Remaining nonfriable ACBM or ACM.

Assessment Reason : Nonfriable. Undamaged.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage Cinches) Footage Units (Inches) (Inches)

165 0.10

MATERIAL ------------------------------------------------------------------------------------------ Sample Area : AC

1E

NO

Type of Material Asbestos Found :

Physical Assessment Assessment Reason n/a : Not

PLASTER

Troweled Plaster Wall found to contain asbestos.

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

YES

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

400 0.40

MATERIAL ------------------------------------------------------------------------------------------ Sample Area : AH BASEBOARD MASTIC Sampled/Assumed/Previous ID SAMPLED Type of Material : 4K Mastic ACM/ACBM n/a Asbestos Found : NO Friable NO Physical Assessment : n/a Assessment Reason : Not found to contain asbestos.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

M A T E R I A L Sample Area : AK

2B

NO

n/a

A S B E S T O S I N S P E C T I O N R E P O R T

IR-60003-0360 (cont'd) Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:55:25 Page 2

MUDDED PIPE FITTING 311

Mudded Pipe Fitting Insulation Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

YES

Type of Material Asbestos Found Physical Assessment Assessment Reason Not found to contain asbestos.

QUANT I TY ·----·----------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units Cinches) (Inches)

1.00

NOTES -------------------------------------------------------------·--· ---·--------------------------

(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.

(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample Sunvnary"

A $ B E S T O S I N S P E C T I O N R E P O R T

RADAR BASE

IR-60003-0370

Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:55:40 Page 1

B U I L D I N G Building Name Address City, State Gross Sq. Feet Inspector Name

BASE DORMITORY 1411-B

CATALINA HIGHWAY

TUCSON, AZ

16930

JOE LORANGER

EM! Building# Contact Person Title Phone Inspected

: 60003

: RAY WIGGINS

: ASBESTOS PROJECT SUPERVISOR

: (602) 670-5455 : 11/08/91

ROOM ----------------------------------------------------------------·--------------------------------- Functional Space: 0370 Room - 33 DORM ROOM

MATER I AL --------------------------------------------------------·--------------------------------- Sample Area : AA 9X9 FLOOR TILE GREEN Sampled/Assumed/Previous ID SAMPLED Type of Material : 4A1 Floor Tile ACM/ACBM : ACBM Asbestos Found : YES Friable: NO Physical Assessment ACBM with potential for damage.

Assessment Reason Nonfriable. Significantly Damaged. Damage is distributed. Ten to twenty-five percent of surface area is damaged. Water Damage. Gouged/Chipped.

QUANT I TY ·---------------------------------

Square Diameter Linear # Width Thickness Footage Cinches) Footage Units Cinches) Cinches)

165 0.13

MATERIAL ------------------------------------------------------·----------------------------------- Sample Area : AB MASTIC SA-AB Sampled/Assumed/Previous ID SAMPLED Type of Material : 4K Mastic ACM/ACBM ACBM Asbestos Found : YES Friable NO Physical Assessment : Remaining nonfriable ACBM or ACM.

Assessment Reason : Nonfriable. Undamaged.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage Cinches) Footage Units Cinches) Cinches)

165 0.10

MATERIAL ------------------------------------------------------------------------------------------ Sample Area : AG

3B

NO

Type of Material Asbestos Found :

Physical Assessment Assessment Reason n/a : Not

WALLBOARD

Wallboard/Dry wall found to contain asbestos.

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

YES

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage Cinches) Footage Units Cinches) (Inches)

400 0.40

MATERIAL ------------------------------------------------------------------------------------------ Sample Area : AH BASEBOARD MASTIC Sampled/Assumed/Previous ID SAMPLED Type of Material : 4K Mastic ACM/ACBM n/a Asbestos Found : NO Friable NO Physical Assessment : n/a Assessment Reason : Not found to contain asbestos.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units Cinches) Cinches)

MATERIAL

Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason

AK

2B

NO

n/a Not

ASBESTOS INSPECTION REPORT

IR-60003-0370 (cont'd) Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:55:40 Page 2

MUDDED PIPE FITTING 311

Mudded Pipe Fitting Insulation found to contain asbestos.

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

YES

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage Cinches) Footage Units Cinches) Cinches)

1.00

NOTES ------------------------------------------------------------------------------------------------

(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.

(3) Reinspect ion is advised prior to renovation or demolition. (4) See "Inspection Report Sample Sunvnary"

RADAR BASE

IR-60003-0371

Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:55:55 Page 1

BUILDING

Building Name Address City, State Gross Sq. Feet Inspector Name

BASE DORMITORY 1411-B

CATALINA HIGHWAY

TUCSON, AZ

16930

JOE LORANGER

EM! Building # Contact Person Title Phone Inspected

: 60003

: RAY WIGGINS

: ASBESTOS PROJECT SUPERVISOR

(602) 670-5455 : 11/08/91

ROOM -------------------------------------------------------------------------------------------------- Functional Space 0371 Room - UNKNOWN DORM ROOM

M A T E R I A L Sample Area Type of Material Asbestos Found :

Physical Assessment Assessment Reason

M A T E R I A L Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason

AA 9X9 FLOOR TILE GREEN

4A 1 Floor Ti le

YES

ACBM with potential for damage.

Sampled/Assumed/Previous ID SAMPLED

ACM/ACBM : ACBM

Friable : NO

Nonfriable. Significantly Damaged. Damage is distributed.

of surface area is damaged. Water Damage. Gouged/Chipped.

Ten to twenty-five percent

AB

4K

YES

MASTIC SA-AB

Mastic

Remaining nonfriable ACBM Nonfriable. Undamaged.

or ACM.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

0.13

SAMPLED

ACBM

NO

QUANT I TY ·---------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

165 0.10

MATERIAL ------------------------------------------------------------------------------------------ Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason

M A T E R I A L Sample Area Type of Material Asbestos Found :

Physical Assessment Assessment Reason

AG WALLBOARD

3B Wallboard/Dry wall

NO

AH

4K

NO

n/a Not found to contain asbestos.

n/a

BASEBOARD MAST! C

Mastic

Not found to contain asbestos.

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

YES

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

0.40

SAMPLED

n/a

NO

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

M A T E R I A L Sample Area : AK

2B

NO

Type of Material Asbestos Found Physical Assessment Assessment Reason n/a Not

A S B E S T O S I N S P E C T I O N R E P O R T

IR-60003-0371 (cont'd) Printed by EnviroMD SAM system ever. 1.3): 12/07/91 10:55:55 Page 2

MUDDED PIPE FITTING 3"

Mudded Pipe Fitting Insulation found to contain asbestos.

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

YES

QUANT I TY ·--···----------·---·----------·-·

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

1.00

NOTES -·-··-··-·------------·-----------------·--------------------·----------------------------------

(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.

(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample Summary"

RADAR BASE

IR-60003-0380

Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:56:09 Page 1

B U I L D I N G Building Name Address City, State Gross Sq. Feet Inspector Name

BASE DORMITORY 1411-B

CATALINA HIGHWAY

TUCSON, AZ

16930

JOE LORANGER

EMI Building# Contact Person Title Phone Inspected

: 60003

: RAY WIGGINS

: ASBESTOS PROJECT SUPERVISOR

: (602) 670-5455 : 11/08/91

ROOM -------------------------------------------------------------------------------------------------- Functional Space: 0380 Room - UNKNOWN DORM ROOM

MATER I AL ------------------------------------------------------------------------------------------ Sample Area : AA 9X9 FLOOR TILE GREEN Sampled/Assumed/Previous ID SAMPLED Type of Material : 4A1 Floor Tile ACM/ACBM : ACBM Asbestos Found : YES Friable: NO Physical Assessment ACBM with potential for damage.

Assessment Reason Nonfriable. Significantly Damaged. Damage is distributed. Ten to twenty-five percent of surface area is damaged. Water Damage. Gouged/Chipped.

QUANT I TY ·---------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

165 0.13

MATERIAL ------------------------------------------------------------------------------------------ Sample Area : AB MASTIC SA-AB Sampled/Assumed/Previous ID SAMPLED Type of Material : 4K Mastic ACM/ACBM ACBM Asbestos Found : YES Friable NO Physical Assessment : Remaining nonfriable ACBM or ACM.

Assessment Reason : Nonfriable. Undamaged.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

165 0.10

MATERIAL -------------------------------------------------------------·-··------------------------- Sample Area : AG WALLBOARD Sampled/Assumed/Previous ID SAMPLED Type of Material : 3B Wallboard/Dry wall ACM/ACBM n/a Asbestos Found : NO Friable NO Physical Assessment n/a Assessment Reason : Not found to contain asbestos.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

400 0.40

MATERIAL ------------------------------------------------------------------------------------------ Sample Area : AH BASEBOARD MASTIC Sampled/Assumed/Previous ID SAMPLED Type of Material : 4K Mastic ACM/ACBM n/a Asbestos Found : NO Friable NO Physical Assessment n/a Assessment Reason : Not found to contain asbestos.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

A S B E S T O S I N S P E C T I O N R E P O R T

IR-60003-0380 (cont'd) Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:56:09 Page 2

MATER I AL ------------------------------------------------------·----------------------------------- Sample Area : AK

2B

NO

Type of Material Asbestos Found Physical Assessment Assessment Reason

MUDDED PIPE FITTING 311

Mudded Pipe Fitting Insulation n/a Not found to contain asbestos.

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

YES

QUANT I TY ---·----·-------------------------

Square Diameter Linear # Width Thickness Footage Cinches) Footage Units Cinches) (Inches)

1.00

NOTES -------------------------------------------------------------·--·-------------------------------

(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.

(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample Summary"

RADAR BASE

IR-60003-0381

Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:56:24 Page 1

B U I L D I N G Building Name Address City, State Gross Sq. Feet Inspector Name

BASE DORMITORY 1411-B

CATALINA HIGHWAY

TUCSON, AZ

16930

JOE LORANGER

EM! Building#: 60003 Contact Person: RAY WIGGINS Title : ASBESTOS PROJECT SUPERVISOR Phone : (602) 670-5455 Inspected : 11/08/91

ROOM -------------------------------------------------------------------------------------------------- Functional Space 0381 Room - UNKNOWN PIPE CHASE

M A T E R I A L Sample Area : AG

: 3B

NO

Type of Material Asbestos Found Physical Assessment Assessment Reason

M A T E R I A L Sample Area n/a

WALLBOARD

Wallboard/Dry wall

Not found to contain asbestos.

MUDDED PIPE FITTING 311

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

YES

QUANTITY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

16 0.13

Type of Material Asbestos Found Physical Assessment Assessment Reason

AK

2B

NO

Mudded Pipe Fitting Insulation Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

M A T E R I A L Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason

M A T E R I A L Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason

BC

4G

NO

BD

3K

NO

n/a Not found to contain asbestos.

n/a

WALLBOARD SEAM TAPE

Seam Tape

Not found to contain asbestos.

WALL JOINT

Other Miscellaneous Friable n/a Not found to contain asbestos.

YES

QUANTITY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

1.00

SAMPLED

n/a

NO

QUANTITY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

No measurements were taken for this material.

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

NO

QUANTITY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

A S B E S T O S I N S P E C T I O N R E P O R T

IR-60003-0381 (cont'd) Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:56:24 Page 2

NOTES -------------------------------------------------------------·-·----·---------------------------

(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.

(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample Summary"

RADAR BASE

IR-60003-0390

Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:56:37 Page 1

B U I L D I N G Building Name Address City, State Gross Sq. Feet Inspector Name

BASE DORMITORY 1411-B

CATALINA HIGHWAY

TUCSON, AZ

16930

JOE LORANGER

EM! !3ui lding # Contact Person Title Phone Inspected

: 60003

: RAY WIGGINS

: ASBESTOS PROJECT

(602) 670-5455 : 11/08/91

SUPERVISOR

ROOM --··---·-·---·-··-··----·--·---------------·--------------------·-··-·-··------------------------- Functional Space 0390 Room - UNKNOWN DORM ROOM

MATERIAL -----·------------------------------------------------·-·-·--·-··------------------------- Sample Area : AA 9X9 FLOOR TILE GREEN

Floor Tile Sampled/Assumed/Previous ID SAMPLED

Type of Material Asbestos Found :

Physical Assessment Assessment Reason

M A T E R I A L Sample Area Type of Material Asbestos Found :

Physical Assessment Assessment Reason

M A T E R I A L Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason

4A1

YES

ACBM with potential for damage.

ACM/ACBM : ACBM

Friable : NO

Nonfriable. Significantly Damaged. Damage is distributed.

of surface area is damaged. Water Damage. Gouged/Chipped.

Ten to twenty-five percent

AB

4K

YES

AG

3B

NO

MASTIC SA-AB

Mastic

Remaining nonfriable ACBM Nonfriable. Undamaged.

n/a

WALLBOARD

Wallboard/Dry wall or ACM.

Not found to contain asbestos.

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

0.13

SAMPLED

ACBM

NO

QUANT I TY ·---·--·--------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

0.10

SAMPLED

n/a

YES

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

400 0.40

MATERIAL -------------------------------------------------------·---------------------------------- Sample Area Type of Material Asbestos Found :

Physical Assessment Assessment Reason

AH BASEBOARD MASTIC

4K Mastic

NO

n/a Not found to contain asbestos.

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

NO

QUANT I TY -------------------~-------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

M A T E R I A L Sample Area : AK

NO

n/a

A S B E S T O S I N S P E C T I O N R E P O R T

IR-60003-0390 (cont'd) Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:56:37 Page 2

MUDDED PIPE FITTING 311

Mudded Pipe Fitting Insulation Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

YES

Type of Material Asbestos Found Physical Assessment Assessment Reason Not found to contain asbestos.

QUANTITY -------------------0--------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

1.00

NOTES ------------------------------------------------------------------------------------------------

(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.

(3) Reinspection is advised prior to renovation or demolition, (4) See "Inspection Report Sample Summary"

RADAR BASE

IR-60003-0391

Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 11:14:59 Page 1

BUILDING

Building Name Address City, State Gross Sq. Feet Inspector Name

BASE DORMITORY 1411-B

CATALINA HIGHWAY

TUCSON, AZ

16930

JOE LORANGER

EM! Building # Contact Person Title Phone Inspected

: 60003

: RAY WIGGINS

: ASBESTOS PROJECT SUPERVISOR

: (602) 670-5455 : 11/08/91

ROOM --------------------------------------------------------------·------·---------------------------- Functional Space 0391 Room - UNKNOWN PIPE CHASE

M A T E R I A L Sample Area : AG

3B

NO

Type of Material Asbestos Found Physical Assessment Assessment Reason

M A T E R I A L Sample Area n/a

WALLBOARD

Wallboard/Dry wall

Not found to contain asbestos.

MUDDED PIPE FITTING 3"

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

YES

QUANT I TY ---------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

16 0.40

Type of Material Asbestos Found Physical Assessment Assessment Reason

AK

2B

NO

Mudded Pipe Fitting Insulation Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

YES

M A T E R I A L Sample Area Type of Material Asbestos Found :

Physical Assessment Assessment Reason

M A T E R I A L Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason

BC

4G

NO

BO

3K

NO

n/a Not found to contain asbestos.

n/a Not n/a Not

WALLBOARD SEAM TAPE

Seam Tape found to contain asbestos.

WALL JOINT

Other Miscellaneous Friable found to contain asbestos.

QUANTITY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

1.00

SAMPLED

n/a

NO

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

No measurements were taken for this material.

Sampled/Assumed/Previous ID

ACM/ACBM

Friable

SAMPLED

n/a

NO

QUANT I TY ----------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

A S B E S T O S I N S P E C T I O N R E P O R T

IR-60003-0391 (cont'd) Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 11:14:59 Page 2

NOTES ------------------------------------------------------------------------------------------------

(1) n/a = not applicable. (2) Signatures of Building Inspectors are prov;ded elsewhere in this section.

(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample Summary" report for sample locat;ons and analysis results. {ir_rept.ww}

RADAR BASE

IR-60003-0400

Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 11:15:11 Page 1

B U I L D I N G Building Name Address City, State Gross Sq. Feet Inspector Name

BASE DORMITORY 1411-B

CATALINA HIGHWAY

TUCSON, AZ

16930

JOE LORANGER

EM! Building # Contact Person Title Phone Inspected

: 60003

: RAY WIGGINS

: ASBESTOS PROJECT SUPERVISOR

: (602) 670-5455 : 11/08/91

ROOM --------------------------------------------------------------------------------------------------.

Functional Space 0400 Room - 26 DORM ROOM

M A T E R I A L Sample Area : AA 9X9 FLOOR TILE GREEN Type of Material Asbestos Found :

4A1 Floor Ti le

YES

ACBM with potential for damage.

Sampled/Assumed/Previous ID SAMPLED

ACM/ACBM : ACBM

Friable: NO

Physical Assessment Assessment Reason Nonfriable. Significantly Damaged. Damage is distributed. More than percent of surface area is damaged. Water Damage. Gouged/Chipped.

twenty-five

M A T E R I A L Sample Area : AB

4K

YES

MASTIC SA-AB

Mastic

ACBM with potential for damage.

QUANT I TY ·---------------------------------

Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)

165 0.13

Sampled/Assumed/Previous ID SAMPLED

ACM/ACBM : ACBM

Friable: NO Type of Material Asbestos Found Physical Assessment Assessment Reason Nonfriable. Significantly Damaged. Damage is distributed.

percent of surface area is damaged.

More than twenty-five

M A T E R I A L Sample Area : AG

NO

Type of Material Asbestos Found Physical Assessment Assessment Reason

M A T E R I A L Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason

AH

4K

NO

WALLBOARD

Wallboard/Dry wall n/a Not found to contain asbestos.

n/a

BASEBOARD MASTIC

Mastic

Not found to contain asbestos.

QUANT I TY…