This document is an Asbestos Inspection Report for the Coronado National Forest Radar Base in Tucson, Arizona. The report provides details on the asbestos-containing building materials found in the Base Dormitory building, including the location, type, quantity, and condition of the materials. Key findings include the presence of asbestos-containing floor tiles, mastic, and pipe insulation throughout the building. The report recommends reinspection prior to any renovation or demolition activities.
The related federal contract opportunity is a solicitation from the USDA Forest Service for the Coronado (CNF3) NF - Radar Base Dormitory Removal. This appears to be a contract to remove the dormitory building that was inspected in the report, likely due to the presence of the identified asbestos-containing materials. No additional details are provided on the specific requirements, response due dates, award information, or any set-asides for this procurement.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CORONADO NATIONAL FOREST
RADAR BASE
N S P E C T O R R E P O R T
Printed by EnviroMD SAM system: 12/16/91 12:31:41 Page 1
Building Number - Building Name
Inspector Name ID#
60002 - REC. ROOM BLDG 1412
RICHARD WHITE
60003 - BASE DORMITORY 1411-B
JOE LORANGER
60004 - DORMITORY 1411
JOE LORANGER
60005 - RADAR BASE STORAGE 1410
JOE LORANGER
60006 - COMMANDER'S HOUSE #1405
RICHARD WHITE
60007 - RADAR BASE SAW SHOP
JOE LORANGER
60008 - RADAR BASE GARAGE 1407
RICHARD WHITE
60009 - RADAR BASE 1413 STORAGE
JOE LORANGER
60010 - 1414 STORAGE
JOE LORANGER
60011 - FIRE PUMP HOUSE #1408
RICHARD WHITE
MICHAEL HOLCOMBE
60012 - WATER PUMP HOUSE #1409
MICHAEL HOLCOMBE
60013 - SPRING PUMP HOUSE #1
MICHAEL HOLCOMBE
60014 - SPRING PUMP HOUSE #2
MICHAEL HOLCOMBE
60015 - POWER HOUSE #1406
RICHARD WHITE
60016 - FOREST SERVICE STOR 1411A
JOE LORANGER
This report lists all the inspectors whose ID# appears anywhere in the inspection f~rms~·f,9(~\~E! listed building. Hnilpect1drx}
INSPECTION ST AT IS TI CS (STAT) REPORT
RADAR BASE
EM!
Building Number Building Name
60002 REC. ROOM BLDG 1412
60003 BASE DORMITORY 1411-B
60004 DORMITORY 1411
60005 RADAR BASE STORAGE 1410
60006 COMMANDER'S HOUSE #1405
60007 RADAR BASE SAW SHOP
60008 RADAR BASE GARAGE 1407
60009 RADAR BASE 1413 STORAGE
60010 1414 STORAGE
60011 FIRE PUMP HOUSE #1408
60012 WATER PUMP HOUSE #1409
60013 SPRING PUMP HOUSE #1
60014 SPRING PUMP HOUSE #2
60015 POWER HOUSE #1406
60016 FOREST SERVICE STOR 1411A
*** T O T A L S
(st_rept.ww}
ST
Printed by EnviroMD SAM system (ver. 1.3): 12/16/91 12:32:44 Page 1
Gross # Square Samples Footage Analyzed
5,586 17
16,930 39
3,200 17
5,960 23
1,330 8
1,830 3
900 6
1,860 13
234 9
396 15
242 2
242 2
3,200 6
3,465 15
45,495 176
This is the last page of this report.
A S B E S T O S I N S P E C T I O N R E P O R T
RADAR BASE
IR-60003-0001
Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:32:53 Page 1
B U I L D I N G Building Name Address City, State Gross Sq. Feet Inspector Name
BASE DORMITORY 1411-B
CATALINA HIGHWAY
TUCSON, AZ
16930
JOE LORANGER
EM! Building # Contact Person Title Phone Inspected
: 60003
: RAY WIGGINS
: ASBESTOS PROJECT SUPERVISOR
: (602) 670-5455 : 11/08/91
ROOM -------------------------------------------------------------------------------------------------- Functional Space 0001 Room - UNKNOWN ROOF
M A T E R I A L Sample Area Type of Material Asbestos Found :
Physical Assessment Assessment Reason
M A T E R I A L Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason
CD
3H
YES
ROOFING MATERIAL SEALANT
Roofing Felt
CG
3H
YES
ACBM with potential for Nonfriable. Undamaged.
ROOFING MATERIAL FLAT
Roofing Felt
ACBM with potential for Nonfriable. Undamaged.
damage.
damage.
Sampled/Assumed/Previous ID
ACM/ACBM
Friable
SAMPLED
ACBM
NO
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
Sampled/Assumed/Previous JD
ACM/ACBM
Friable
0.25
SAMPLED
ACBM
NO
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
0.25
NOTES ------------------------------------------------------------------------------------------------
(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.
(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample Summary" report for sample locations and analysis results. {ir_rept.ww}
RADAR BASE
IR-60003-0010
Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:33:00 Page 1
B U I L D I N G Building Name Address City, State Gross Sq. Feet Inspector Name
BASE DORMITORY 1411-B
CATALINA HIGHWAY
TUCSON, AZ
16930
JOE LORANGER
EM! Building # Contact Person Title Phone Inspected
: 60003
: RAY WIGGINS
: ASBESTOS PROJECT SUPERVISOR
: (602) 670-5455 : 11/08/91
ROOM --------------------------------------------------------------·-·--------------------------------- Functional Space: 0010 Room - UNKNOWN BASEMENT
(See Asbestos Inspection Report Notes for additional information about this room.)
MATER I AL ------------------------------------------------------·-·--------------------------------- Sample Area : AA 9X9 FLOOR TILE GREEN Sampled/Assumed/Previous ID SAMPLED Type of Material : 4A1 Floor Tile ACM/ACBM : ACBM Asbestos Found : YES Friable: NO Physical Assessment ACBM with potential for damage.
Assessment Reason ·Nonfriable. Significantly Damaged. Damage is distributed. Ten to twenty-five percent of surface area is damaged. Water Damage. Gouged/Chipped.
QUANT I TY ·---------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units Cinches) Cinches)
10 0.13
MATERIAL ------------------------------------------------------------------------------------------ Sample Area : AB MASTIC SA-AB Sampled/Assumed/Previous ID SAMPLED Type of Material : 4K Mastic ACM/ACBM: ACBM Asbestos Found : YES Friable : NO Physical Assessment : Remaining nonfriable ACBM or ACM.
Assessment Reason : Nonfriable. Undamaged.
QUANT I TY ·---------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
10 0.10
MATERIAL ------------------------------------------------------·---·------------------------------- Sample Area : AD MUDDED PIPE FITTING 511 Sampled/Assumed/Previous ID SAMPLED Type of Material : 2B Mudded Pipe Fitting Insulation ACM/ACBM n/a Asbestos Found : NO Friable YES Physical Assessment: n/a Assessment Reason : Not found to contain asbestos.
QUANT I TY --·-------------------------------
Square Diameter Linear # Width Thickness Footage Cinches) Footage Units (Inches) (Inches)
14 1.00
MATERIAL ------------------------------------------------------------------------------------------ Sample Area : AG
3B
NO
Type of Material Asbestos Found :
Physical Assessment Assessment Reason n/a : Not
WALLBOARD
Wallboard/Dry wall found to contain asbestos.
Sampled/Assumed/Previous ID
ACM/ACBM
Friable
SAMPLED
n/a
YES
QUANT I TY ·------·--------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
180 0.50
Continued on the next page.
A S B E S T O S I N S P E C T I O N R E P O R T
IR-60003-0010 (cont'd) Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:33:00 Page 2
NOTES -----·-·--·-------·-----------------·-----------------------·-·-·-------------------------------
(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.
(3) Reinspect ion is advised prior to renovation or demolition. (4) See "Inspection Report Sample Summary"
RADAR BASE
IR-60003-0020
Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:43:37 Page 1
B U I L D I N G Building Name Address City, State Gross Sq. Feet Inspector Name
BASE DORMITORY 1411-B
CATALINA HIGHWAY
TUCSON, AZ
16930
JOE LORANGER
EM! Building # Contact Person Title Phone Inspected
: 60003
: RAY WIGGINS
: ASBESTOS PROJECT SUPERVISOR
: (602) 670-5455 : 11/08/91
ROOM -------------------------------------------------------------------------------------------------- Functional Space: 0020 Room - UNKNOWN WEST ENTRY & STAIR 1ST FL
MATER I AL --------------------------------------------------------------------------- ·-------------- Sample Area : AA 9X9 FLOOR TILE GREEN Sampled/Assumed/Previous ID SAMPLED Type of Material : 4A1 Floor Tile ACM/ACBM : ACBM Asbestos Found : YES Friable: NO Physical Assessment ACBM with potential for damage.
Assessment Reason Nonfriable. 'Significantly Damaged. Damage is distributed. More than twenty-five percent of surface area is damaged. Gouged/Chipped. Torn/Broken.
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage Cinches) Footage Units Cinches) Cinches)
105 0.13
MATERIAL ------------------------------------------------------------------------------------------ Sample Area : AB
4K
YES
Type of Material Asbestos Found :
MAST! C SA-AB
Mastic
ACBM with potential for damage.
Sampled/Assumed/Previous ID SAMPLED
ACM/ACBM : ACBM
Friable: NO
Physical Assessment Assessment Reason Nonfriable .. Significantly Damaged. Damage is distributed. More than twenty-five percent of surface area is damaged. Gouged/Chipped. Torn/Broken. Delamination.
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage Cinches) Footage Units Cinches) Cinches)
105 0.10
MATERIAL ------------------------------------------------------···--------------------------------- Sample Area : AD MUDDED PIPE FITTING 511 Sampled/Assumed/Previous ID. SAMPLED Type of Material : 2B Mudded Pipe Fitting Insulation ACM/ACBM : n/a Asbestos Found : NO Friable : YES Physical Assessment n/a Assessment Reason : Not found to contain asbestos.
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage Cinches) Footage Units Cinches) Cinches)
4 1.00
MATERIAL ------------------------------------------------------------------------------------------ Sample Area : AG WALLBOARD Sampled/Assumed/Previous ID SAMPLED Type of Material : 3B Wallboard/Dry wall ACM/ACBM n/a Asbestos Found : NO Friable YES Physical Assessment n/a Assessment Reason : Not found to contain asbestos.
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage Cinches) Footage Units Cinches) Cinches)
675 0.40
RADAR BASE
IR-6DD03-0020 (cont'd) Printed by EnviroMD SAM system ever. 1.3): 12/07/91 10:43:37 Page 2
MATER I AL ------------------------------------------------------------------------------------------ Sample Area : AH
4K
NO
Type of Material Asbestos Found Physical Assessment Assessment Reason
M A T E R I A L Sample Area : AJ
2B
NO
Type of Material Asbestos Found :
Physical Assessment Assessment Reason
M A T E R I A L Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason
AK
2B
NO
n/a
BASEBOARD MASTIC
Mastic
Not found to contain asbestos.
MUDDED PIPE FITTING 211
Sampled/Assumed/Previous ID
ACM/ACBM
Friable
SAMPLED
n/a
NO
QUANT I TY ·---------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
10 0.10
Mudded Pipe Fitting Insulation Sampled/Assumed/Previous ID
ACM/ACBM
Friable
SAMPLED
n/a n/a Not found to contain asbestos.
MUDDED PIPE FITTING 311
Mudded Pipe Fitting Insulation n/a Not found to contain asbestos.
YES
QUANT I TY ·-·--·-·--------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units Cinches) Cinches)
Sampled/Assumed/Previous ID
ACM/ACBM
Friable
1.00
SAMPLED
n/a
YES
QUANT I TY ·-·--·-·--------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
10 1.00
MATERIAL ------------------------------------------------------···-·------------------------------- Sample Area : AL LINOLEUM RED Sampled/Assumed/Previous ID SAMPLED Type of Material Asbestos Found Physical Assessment Assessment Reason
4A3 Linoleum
YES
·ACBM with potential for damage.
ACM/ACBM : ACBM
Friable : NO
Nonfriable. Damaged. Damage is distributed. Less than ten percent of surface area is damaged. Gouged/Chipped.
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage Cinches) Footage Units (Inches) (Inches)
42 0.13
RADAR BASE
IR-60003-0020 (cont'd) Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:43:37 Page 3
M A T E R I A L Sample Area : AM
: 4K
NO
Type of Material Asbestos Found Physical Assessment Assessment Reason n/a Not
MASTIC SA-AL
Mastic found to contain asbestos.
M A T E R I A L Sample Area : AN DOOR CAULK Type of Material Asbestos Found :
41 · Adhesives/Caulk/Putty
YES
Sampled/Assumed/Previous ID
ACM/ACBM
Friable
SAMPLED
n/a
NO
QUANT I TY ·-·-------------------------------
Square Diameter Linear # Width Thickness Footage Cinches) Footage Units (Inches) Cinches)
42 0.10
Sampled/Assumed/Previous ID SAMPLED
ACM/ ACBM : ACBM
Fri able : NO Physical Assessment Assessment Reason
Remaining nonfriable ACBM or ACM.
Nonfriable. ·oamaged. Damage is distributed.
damaged.
Less than ten percent of surface area is
M A T E R I A L Sample Area Type of Material Asbestos Found :
Physical Assessment Assessment Reason
BK
4B
YES
CEMENT BOARD PANEL
Cement Board - 'Transite'
Remaining nonfriable ACBM Nonfriable. Undamaged.
or ACM.
QUANT I TY ·-·----·--------------------------
Square Diameter Linear # Width Thickness Footage Cinches) Footage Units (Inches) Cinches)
Sampled/Assumed/Previous 10·
ACM/ACBM
Friable
0.25
SAMPLED
ACBM
NO
QUANT I TY ·-·----·--------------------------
Square Diameter Linear # Width Thickness Footage Cinches) Footage Units (Inches) Cinches)
440 0.25
NOTES -------------------------------------------------------------·--·-·-----------------------------
(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.
(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample Summary"
RADAR BASE
IR-60003-0030
Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:44:03 Page 1
B U I L D I N G Building Name Address City, State Gross Sq. Feet Inspector Name
BASE DORMITORY 1411-B
CATALINA HIGHIJAY
TUCSON, AZ
16930
JOE LORANGER
EMI Building # Contact Person Title Phone Inspected
: 60003
: RAY \JI GGI NS
: ASBESTOS PROJECT SUPERVISOR
: (602) 670-5455 : 11/08/91
ROOM -------------------------------------------------------------------------------------------------- Functional Space: 0030 Room - UNKNOIJN DORM ROOM
MATER I AL ------------------------------------------------------------------------------------------ Sample Area : AA 9X9 FLOOR TILE GREEN Sampled/Assumed/Previous ID SAMPLED Type of Material : 4A1 Floor Tile ACM/ACBM : ACBM Asbestos Found : YES Friable: NO Physical Assessment ACBM with potential for damage.
Assessment Reason Nonfriable. Significantly Damaged. Damage is distributed. More than twenty-five percent of surface area is damaged. Gouged/Chipped. Torn/Broken.
QUANT I TY ----------------------------------
Square Diameter Linear # IJidth Thickness Footage (Inches) Footage Units (Inches) Cinches)
165 0.13
MATERIAL ------------------------------------------------------------------------------------------ Sample Area : AB MASTIC SA-AB Sampled/Assumed/Previous ID SAMPLED Type of Material : 4K Mastic ACM/ACBM: ACBM Asbestos Found : YES Friable: NO Physical Assessment ACBM with potential for damage.
Assessment Reason Nonfriable. Significantly Damaged. Damage is distributed.·More than twenty-five percent of surface area is damaged. Gouged/Chipped. Torn/Broken.
QUANT I TY ----------------------------------
Square Diameter Linear # IJidth Thickness Footage (Inches) Footage Units (Inches) (Inches)
165 0.10
MATER I AL ---------------------------------------------------------------------------·-------------- Sample Area : AG IJALLBOARD Sampled/Assumed/Previous ID SAMPLED Type of Material : 3B Wallboard/Dry wall ACM/ACBM: n/a Asbestos Found : NO Friable: NO Physical Assessment n/a Assessment Reason : Not found to contain asbestos.
QUANT I TY ----------------------------------
Square Diameter Linear # IJidth Thickness Footage (Inches) Footage Units (Inches) (Inches)
MATERIAL ------------------------------------------------------------------------------------------ Sample Area : AH BASEBOARD MASTIC Sampled/Assumed/Previous ID SAMPLED Type of Material : 4K Mastic ACM/ACBM n/a Asbestos Found : NO Friable NO Physical Assessment n/a Assessment Reason : Not found to contain asbestos.
QUANT I TY ----------------------------------
Square Diameter Linear # IJidth Thickness Footage (Inches) Footage Units (Inches) (Inches)
52 0.10
A S B E S T O S I N S P E C T I O N R E P O R T
IR-60003-0030 (cont'd) Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:44:03 Page 2
MATER I AL ------------------------------------------------------·-·--------------------------------- Sample Area : AK MUDDED PIPE FITTING 311 Sampled/Assumed/Previous ID SAMPLED Type of Material : 2B Mudded Pipe Fitting Insulation ACM/ACBM : n/a Asbestos Found : NO Friable: YES Physical Assessment: n/a Assessment Reason : Not found to contain asbestos.
QUANT I TY ·---------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
1.00
NOTES -------------·----------------------------------------------------------------------------------(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.
(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample Summary"
RADAR BASE
IR-6DDD3-DD31
Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:44:17 Page 1
B U I L D I N G Building Name Address City, State Gross Sq. Feet Inspector Name
BASE DORMITORY 1411-B
CATALINA HIGHWAY
TUCSON, AZ
16930
JOE LORANGER
EMI Building # Contact Person Title Phone Inspected
: 60003
: RAY WIGGINS
: ASBESTOS PROJECT SUPERVISOR
: (602) 670-5455 : 11/08/91
ROOM -------------------------------------------------------------------------------------------------- Functional Space 0031 Room - UNKNOWN CABINET PIPE CHASE
MATERIAL
Sample Area : AG
3B
NO
Type of Material Asbestos Found :
Physical Assessment Assessment Reason n/a Not
WALLBOARD
Wallboard/Dry wall found to contain asbestos.
Sampled/Assumed/Previous ID
ACM/ACBM
Friable
SAMPLED
n/a
YES
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
16 0.40
MATERIAL ------------------------------------------------------------------------------------------ Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason
M A T E R I A L Sample Area Type of Material Asbestos Found :
Physical Assessment Assessment Reason
M A T E R I A L Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason
AK
2B
NO
BC
4G
NO
BD
3K
NO
MUDDED PIPE FITTING 311
Mudded Pipe Fitting Insulation Sampled/Assumed/Previous ID
ACM/ACBM
Friable
SAMPLED
n/a n/a Not found to contain asbestos.
n/a Not
WALLBOARD SEAM TAPE
Seam Tape found to contain asbestos.
WALL JOINT
n/a Not
Other Miscellaneous Friable found to contain asbestos.
YES
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
Sampled/Assumed/Previous ID
ACM/ACBM
Friable
7.00
SAMPLED
n/a
NO
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
No measurements were taken for this material.
Sampled/Assumed/Previous ID
ACM/ACBM
Friable
SAMPLED
n/a
NO
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units Cinches) (Inches)
No measurements were taken for this material.
A S B E S T O S I N S P E C T I O N R E P O R T
IR-60003-0031 (cont'd) Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:44:17 Page 2
NOTES ------------------------------------------------------------------------------------------------
(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.
(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample Summary"
RADAR BASE
IR-6OOO3-OO4O
Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10;44:29 Page 1
B U I L D I N G Building Name Address City, State Gross Sq. Feet Inspector Name
BASE DORMITORY 1411-B
CATALINA HIGHWAY
TUCSON, AZ
16930
JOE LORANGER
EM! Building # Contact Person Title Phone Inspected
: 60003
: RAY WIGGINS
: ASBESTOS PROJECT SUPERVISOR
: (602) 670-5455 : 11/08/91
ROOM -------------------------------------------------------------------------------------------------- Functional Space 0040 Room - UNKNOWN DORM ROOM
M A T E R I A L Sample Area Type of Material Asbestos Found :
AA 9X9 FLOOR TILE GREEN
4A1 Floor Tile
YES
ACBM with potential for damage.
Sampled/Assumed/Previous ID SAMPLED
ACM/ACBM : ACBM
Friable: NO
Physical Assessment Assessment Reason Nonfriable. Significantly Damaged. Damage is distributed. More than twenty-five percent of surface area is damaged. Gouged/Chipped. Torn/Broken.
M A T E R I A L Sample Area : AB
4K
YES
Type of Material Asbestos Found :
MAST! C SA-AB
Mastic
ACBM with potential for damage.
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage Cinches) Footage Units Cinches) Cinches)
165 0.13
Sampled/Assumed/Previous ID SAMPLED
ACM/ACBM : ACBM
Friable: NO
Physical Assessment Assessment Reason Nonfriable. Significantly Damaged. Damage is distributed. More than twenty-five percent of surface area is damaged. Gouged/Chipped. Torn/Broken.
M A T E R I A L Sample Area : AG
3B
NO
Type of Material Asbestos Found Physical Assessment Assessment Reason n/a Not
WALLBOARD
Wallboard/Dry wall found to contain asbestos.
QUANT I TY --------------------------·----·--
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units Cinches) Cinches)
Sampled/Assumed/Previous ID
ACM/ACBM
Friable
0.10
SAMPLED
n/a
YES
QUANT I TY --·----·--------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units Cinches) Cinches)
400 0.40
MATERIAL ------------------------------------------------------------------------------------------ Sample Area : AH
4K
NO
Type of Material Asbestos Found :
Physical Assessment Assessment Reason n/a Not
BASEBOARD MASTIC
Mastic found to contain asbestos.
Sampled/Assumed/Previous ID
ACM/ACBM
Friable
SAMPLED
n/a
NO
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage Cinches) Footage Units Cinches) (Inches)
M A T E R I A L Sample Area : AK
2B
NO
Type of Material Asbestos Found Physical Assessment Assessment Reason n/a Not
A S B E S T O S I N S P E C T I O N R E P O R T
IR-60003-0040 (cont'd) Printed by EnviroMD SAM system ever. 1.3): 12/07/91 10:44:29 Page 2
MUDDED PIPE FITTING 311
Mudded Pipe Fitting Insulation Sampled/Assumed/Previous ID
ACM/ACBM
Friable
SAMPLED
n/a found to contain asbestos.
YES
QUANT I TY ·---------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) Cinches)
1.00
NOTES ------------------------------- ------------·---------------------------------------------------
(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.
(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample Summary"
RADAR BASE
IR-60003-0050
Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:44:44 Page 1
B U I L D I N G Building Name Address City, State Gross sq. Feet Inspector Name
BASE DORMITORY 1411-B
CATALINA HIGHWAY
TUCSON, AZ
16930
JOE LORANGER
EM! Building# Contact Person Title Phone Inspected
: 60003
: RAY WIGGINS
: ASBESTOS PROJECT SUPERVISOR
: (602) 670-5455 : 11/08/91
ROOM -----------------------------. -------------------------------------------------------------------- Functional Space: 0050 Room - 20 DORM ROOM
MATERIAL ------------------------------------------------------------------------------------------ Sample Area : AA 9X9 FLOOR TILE GREEN Sampled/Assumed/Previous ID SAMPLED Type of Material : 4A1 Floor Tile ACM/ACBM : ACBM Asbestos Found : YES Friable : NO Physical Assessment ACBM with potential for damage.
Assessment Reason Nonfriable. Significantly Damaged. Damage is distributed- More than twenty-five percent of surface area is damaged. Gouged/Chipped. Torn/Broken.
QUANT I TY ·---------------------------------
Square Diameter Linear # Width Thickness Footage Cinches) Footage Units (Inches) Cinches)
165 0.13
MATERIAL --------------------------------------------------------·--------------------------------- Sample Area : AB MASTIC SA-AB Sampled/Assumed/Previous ID SAMPLED Type of Material : 4K Mastic ACM/ACBM: ACBM Asbestos Found : YES Friable : NO Physical Assessment ACBM with potential for damage.
Assessment Reason Nonfriable. Significantly Damaged. Damage is distributed- More than twenty-five percent of surface area is damaged. Delamination.
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage Cinches) Footage Units Cinches) Cinches)
165 0.10
MATER I AL ------------------------------------------------------------------------------------------ Sample Area : AG WALLBOARD Sampled/Assumed/Previous ID SAMPLED Type of Material : 3B Wallboard/Dry wall ACM/ACBM n/a Asbestos Found : NO Friable YES Physical Assessment n/a Assessment Reason : Not found to contain asbestos.
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) Cinches)
400 0.40
MATERIAL ------------------------------------------------------·----------------------------------- Sample Area : AH BASEBOARD MASTIC Sampled/Assumed/Previous ID SAMPLED Type of Material : 4K Mastic ACM/ACBM n/a Asbestos Found : NO Friable NO Physical Assessment n/a Assessment Reason : Not found to contain asbestos.
QUANT I TY -----------·----------------------
Square Diameter Linear # Width Thickness Footage Cinches) Footage Units (Inches) Cinches)
Continued on·the next page.
A S B E S T O S I N S P E C T I O N R E P O R T
IR-60003-0050 (cont'd) Printed by EnviroMD SAM system ever. 1.3): 12/07/91 10:44:44 Page 2
MATER I AL ------------------------------------------------------------------------------------------ Sample Area : AK
2B
NO
Type of Material Asbestos Found :
Physical Assessment Assessment Reason n/a : Not
MUDDED PIPE FITTING 311
Mudded Pipe Fitting Insulation found to contain asbestos.
Sampled/Assumed/Previous ID SAMPLED ACM/ACBM: n/a Friable: YES
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
1.00
NOTES ------------------------------------------------------------------------------------------------
(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.
(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample Sunmary"
RADAR BASE
IR-6OOO3-OO6O
Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:44:59 Page 1
B U I L D I N G Building Name Address City, State Gross Sq. Feet Inspector Name
BASE DORMITORY 1411-B
CATALINA HIGHWAY
TUCSON, AZ
16930
JOE LORANGER
EM! Building# Contact Person Title Phone Inspected
: 60003
: RAY WIGGINS
: ASBESTOS PROJECT SUPERVISOR
: (602) 670-5455 : 11/08/91
ROOM --------------------------------------------------------------·-·--------------------------------- Functional Space: 0060 Room - UNKNOWN DORM ROOM
MATER I AL --·--------------------·-·--·-------------------------·-·--·-----------------------------· Sample Area : AA 9X9 FLOOR TILE GREEN Sampled/Assumed/Previous ID SAMPLED Type of Material : 4A1 Floor Tile ACM/ACBM : ACBM Asbestos Found : YES Friable: NO Physical Assessment ACBM with potential for damage.
Assessment Reason Nonfriable. Significantly Damaged. Damage is distributed. More than twenty-five percent of surface area is damaged. Water Damage. Gouged/Chipped. Torn/Broken.
QUANT I TY ·-··-·-··-····-··-------------·-·-
Square Diameter Linear # Width Thickness Footage Cinches) Footage Units (Inches) (Inches)
165 0.13
MATER I AL -·---------------·------------------------------------·-·-·--·-·-----------·-------------- Sample Area : AB MASTIC SA·AB Sampled/Assumed/Previous ID SAMPLED Type of Material : 4K Mastic ACM/ACBM: ACBM Asbestos Found : YES Friable: NO Physical Assessment ACBM with potential for damage.
Assessment Reason Nonfriable. Significantly Damaged. Damage is distributed. More than twenty-five percent of surface area is damaged. Water Damage.
QUANT I TY ·--------------·--·-------·--·----
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units Cinches) Cinches)
165 0.10
MATERIAL ··-------------·----------·---···-----··-·------------···-·----·---·---------------------- Sample Area : AG WALLBOARD Sampled/Assumed/Previous ID SAMPLED Type of Material : 3B Wallboard/Dry wall ACM/ACBM n/a Asbestos Found : NO Friable YES Physical Assessment n/a Assessment Reason : Not found to contain asbestos.
QUANT I TY ·-·--------------·-·------------·-
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units Cinches) (Inches)
400 0.40
MATERIAL ---··--·--------···--···---··---····---------·----·---·---·-·--·--·--------·-------------- Sample Area : AH BASEBOARD MASTIC Sampled/Assumed/Previous ID SAMPLED Type of Material : 4K Mastic ACM/ACBM. n/a Asbestos Found : NO Friable NO Physical Assessment: n/a Assessment Reason : Not found to contain asbestos.
QUANT I TY --·----·-·--·---------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
A S B E S T O S I N S P E C T I O N R E P O R T
IR-60003-0060 (cont'd) Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:44:59 Page 2
MATER I AL ------------------------------------------------------·-·--------------------------------- Sample Area : AK MUDDED PIPE FITTING 311 Sampled/Assumed/Previous ID SAMPLED Type of Material : 2B Mudded Pipe Fitting Insulation ACM/ACBM : n/a Asbestos Found : NO Friable: YES Physical Assessment: n/a Assessment Reason : Not found to contain asbestos.
QUANT I TY ·---------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
1.00
NOTES ------------------------------------------------------·------·----·-·---------------------------
(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in tbis section.
(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample Surrvnary"
RADAR BASE
IR-60003-0061
Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:45:14 Page 1
B U I L D I N G Building Name Address City, State Gross Sq. Feet Inspector Name
BASE DORMITORY 1411-B
CATALINA HIGHWAY
TUCSON, AZ
16930
JOE LORANGER
EM! Building # Contact Person Title Phone Inspected
: 60003
: RAY WIGGINS
: ASBESTOS PROJECT SUPERVISOR
: (602) 670-5455 : 11/08/91
ROOM -------------------------------------------------------------------------------------------------- Functional Space 0061 Room - UNKNOWN CABINET PIPE CHASE
MATER I AL ------------------------------------------------------------------------------------------ Sample Area : AG
3B
NO
Type of Material Asbestos Found :
Physical Assessment Assessment Reason
M A T E R I A L Sample Area : AK Type of Material Asbestos Found Physical Assessment Assessment Reason
M A T E R I A L Sample Area Type of Material Asbestos Found :
Physical Assessment Assessment Reason
M A T E R I A L Sample Area Type of Material Asbestos Found :
Physical Assessment Assessment Reason
2B
NO
BC
4G
NO
BD
3K
NO
n/a Not
WALLBOARD
Wallboard/Dry wall found to contain asbestos.
MUDDED PIPE FITTING 311
Sampled/Assumed/Previous ID
ACM/ACBM
Friable
SAMPLED
n/a
YES
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
16 0.40
Mudded Pipe Fitting Insulation Sampled/Assumed/Previous ID
ACM/ACBM
Friable
SAMPLED
n/a
YES
n/a Not found to contain asbestos.
WALLBOARD SEAM TAPE
Seam Tape n/a Not found to contain asbestos.
WALL JOINT
n/a Not
Other Miscellaneous Friable found to contain asbestos.
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
Sampled/Assumed/Previous ID
ACM/ACBM
Friable
SAMPLED
n/a
NO
QUANT I TY ---------------·---•--------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
No measurements were taken for this material.
Sampled/Assumed/Previous ID
ACM/ACBM
Friable
SAMPLED
n/a
NO
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) Cinches)
A S B E S T O S I N S P E C T I O N R E P O R T
IR-60003-0061 (cont'd> Printed by EnviroMD SAM system ever. 1.3): 12/07/91 10:45:14 Page 2
NOTES ------------------------------------------------------------------------------------------------
(1) n/a = not applicable. '(2) Signatures of Building Inspectors are provided elsewhere in this section.
(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample Summary"
RADAR BASE
IR-60003-0070
Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:45:26 Page 1
BUILDING
Building Name Address City, State Gross Sq. Feet Inspector Name
BASE DORMITORY 1411-B
CATALINA HIGHWAY
TUCSON, AZ
16930
JOE LORANGER
EM! Building # Contact Person Title Phone Inspected
: 60003
: RAY WIGGINS
: ASBESTOS PROJECT SUPERVISOR
: (602) 670-5455 : 11/08/91
ROOM -------------------------------------------------------------------------------------------------- Functional Space 0070 Room - 9 DORM ROOM
M A T E R I A L Sample Area : AA 9X9 FLOOR TILE GREEN Sampled/Assumed/Previous ID SAMPLED Type of Material Asbestos Found :
Physical Assessment Assessment Reason
M A T E R I A L sample Area Type of Material Asbestos Found :
Physical Assessment Assessment Reason
M A T E R I A L Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason
M A T E R I A L Sample Area Type of Material Asbestos Found :
Physical Assessment Assessment Reason
4A1 Floor Ti le
YES
ACBM with potential for damage.
ACM/ACBM : ACBM
Friable: NO
Nonfriable. Damaged. Damage is distributed. Less than ten percent of surface area is damaged. Water Damage.
AB MASTIC SA-AB
4K Mastic
YES •
QUANTITY ·---------------------------------
Square Diameter Linear # Width Thickness Footage Cinches) Footage Units (Inches) Cinches)
165 0.13
Sampled/Assumed/Previous ID SAMPLED
ACM/ACBM: ACBM
Friable: NO
ACBM with potential for damage.
Nonfriable. Damaged. Damage is distributed. Less than ten percent of surface area is damaged. Water Damage.
AG
3B
NO
AH
4K
NO
n/a Not
WALLBOARD
Wallboard/Dry wall found to contain asbestos.
BASEBOARD MASTIC
Mastic n/a Not found to contain asbestos.
QUANT I TY -----·-------------,--------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units Cinches) Cinches)
Sampled/Assumed/Previous ID
ACM/ACBM
Friable
0.10
SAMPLED
n/a
NO
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
Sampled/Assumed/Previous ID
ACM/ACBM
Friable
0.40
SAMPLED
n/a
NO
QUANT I TY ----·--·--·-----------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
A S B E S T O S I N S P E C T I O N R E P O R T
IR-60003-0070 (cont'd) Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:45:26 Page 2
MATER I AL --------------------------------------------------------·-·------------------------------- Sample Area : AK Type of Material Asbestos Found :
Physical Assessment Assessment Reason
2B
NO
n/a : Not
MUDDED PiPE FITTING 3" Sampled/Assumed/Previous ID SAMPLED Mudded Pipe Fitting Insulation ACM/ACBM : n/a
Friable: YES found to contain asbestos.
QUANT I TY --------·----------···--·--·----·-
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
1.00
NOTES -·--··--····--------··--------·--------------------------------------·--------------------------
(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.
(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample Summary"
RADAR BASE
IR-6OOO3-OO71
Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:45:43 Page 1
B U I L D I N G Building Name Address City, State Gross Sq. Feet Inspector Name
BASE DORMITORY 1411-B
CATALINA HIGHWAY
TUCSON, AZ
16930
JOE LORANGER
EMI Building # Contact Person Title Phone Inspected
: 60003
: RAY WIGGINS
: ASBESTOS PROJECT SUPERVISOR
: (602) 670-5455 : 11/08/91
ROOM -------------------------------------------------------------------------------------------------- Functional Space 0071 Room - UNKNOWN PIPE CHASE
MATER I AL --------------------------------------------------------·--------------------------------- Sample Area : AG WALLBOARD Sampled/Assumed/Previous ID SAMPLED Type of Material : 3B Wallboard/Dry wall ACM/ACBM n/a Asbestos Found : NO Friable YES Physical Assessment n/a Assessment Reason Not found to contain asbestos.
M A T E R I A L Sample Area : AK MUDDED PIPE FITTING 311
QUANT I TY ·---------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
16 0.40
Type of Material Asbestos Found Physical Assessment Assessment Reason
2B
NO
Mudded Pipe Fitting Insulation Sampled/Assumed/Previous ID
ACM/ACBM
Friable
SAMPLED
n/a
M A T E R I A L Sample Area Type of Material Asbestos Found :
Physical Assessment Assessment Reason
BC
4G
NO
M A T E R I A L Sample Area : BD
: 3K
NO
Type of Material Asbestos Found Physical Assessment Assessment Reason n/a Not found to contain asbestos.
n/a Not
WALLBOARD SEAM TAPE
Seam Tape found to contain asbestos.
WALL JOINT
Other Miscellaneous Friable n/a Not found to contain asbestos.
YES
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
Sampled/Assumed/Previous ID
ACM/ACBM
Friable
1.00
SAMPLED
n/a
NO
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
No measurements were taken for this material.
Sampled/Assumed/Previous ID
ACM/ACBM
Friable
SAMPLED
n/a
NO
QUANT I TY -------·--------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
A S B E S T O S I N S P E C T I O N R E P O R T
IR-60003-0071 (cont'd) Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:45:43 Page 2
NOTES -------------------------------------------------------------·----------------------------------
(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.
(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample Summary"
RADAR BASE
IR-60003-0080
Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:45:56 Page 1
B U I L D I N G Building Name Address City, State Gross Sq. Feet Inspector Name
BASE DORMITORY 1411-B
CATALINA HIGHWAY
TUCSON, AZ
16930
JOE LORANGER
EM! Building# Contact Person Title Phone Inspected
: 60003
: RAY WIGGINS
: ASBESTOS PROJECT SUPERVISOR
: (602) 670-5455 : 11/08/91
ROOM --------------------------------------------------------------·----------------------------------- Functional Space : 0080 Room - UNKNOWN DORM ROOM
MATERIAL ------------------------------------------------------------------------------------------ Sample Area : AA 9X9 FLOOR TILE GREEN Sampled/Assumed/Previous ID SAMPLED Type of Material : 4A1 Floor Tile ACM/ACBM : ACBM Asbestos Found : YES Friable: NO Physical Assessment ACBM with potential for damage.
Assessment Reason Nonfriable. Damaged. Damage is distributed. Less than ten percent of surface area is damaged.
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) Cinches)
165 0.13
MATERIAL ------------------------------------------------------·----------------------------------- Sample Area : AB MASTIC SA-AB Sampled/Assumed/Previous ID SAMPLED Type of Material : 4K Mastic ACM/ACBM ACBM Asbestos Found : YES Friable NO Physical Assessment: Remaining nonfriable ACBM or ACM.
Assessment Reason : Nonfriable. Undamaged.
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
165 0.10
MATER I AL ------------------------------------------------------------------------------------------ Sample Area : AG WALLBOARD Sampled/Assumed/Previous ID SAMPLED Type of Material : 3B Wallboard/Dry wall ACM/ACBM n/a Asbestos Found : NO Friable· NO Physical Assessment n/a Assessment Reason : Not found to contain asbestos.
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage Cinches) Footage Units Cinches) (Inches)
400 0.13
MATERIAL ------------------------------------------------------------------------------------------ Sample Area : AH BASEBOARD MASTIC Sampled/Assumed/Previous ID SAMPLED Type of Material : 4K Mastic ACM/ACBM n/a Asbestos Found : NO Friable NO Physical Assessment n/a Assessment Reason Not found to contain asbestos.
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
A S B E S T O S I N S P E C T I O N R E P O R T
IR-60003-0080 (cont'd) Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:45:56 Page 2
MATER I AL -----------------------------------------------------------------------------·------------ Sample Area : AK
2B
NO
Type of Material Asbestos Found Physical Assessment Assessment Reason n/a Not
MUDDED PIPE FITTING 311
Mudded Pipe Fitting Insulation Sampled/Assumed/Previous ID
ACM/ACBM
Friable
SAMPLED
n/a
YES
found to contain asbestos.
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
1.00
NOTES ------------------------------------;-----------------------------------------------------------
(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.
(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample Summary"
ASBESTOS INSPECTION REPORT
RADAR BASE
IR-60003-0090
Printed by EnviroMD SAM system ever. 1.3): 12/07/91 10:46:12 Page 1
BUILDING
Building Name Address City, State Gross Sq. Feet Inspector Name
BASE DORMITORY 1411-B
CATALINA HIGHWAY
TUCSON, AZ
16930
JOE LORANGER
EM! Building # Contact Person Title Phone Inspected
: 60003
: RAY WIGGINS
: ASBESTOS PROJECT SUPERVISOR
: (602) 670-5455 : 11/08/91
ROOM -------------------------------------------------------------------------------------------------- Functional Space: 0090 Room - UNKNOWN LATRINE
MATER I AL ------------------------------------------------------------------------------------------ Sample Area : AC
1E
NO
Type of Material Asbestos Found :
Physical Assessment Assessment Reason n/a Not
PLASTER
Troweled Plaster Wall found to contain asbestos.
Sampled/Assumed/Previous ID
ACM/ACBM
Friable
SAMPLED
n/a
YES
QUANT I TY ·---------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
360 0.50
MATERIAL ---------------------------------------------------------------·-------------------------- Sample Area : AK Type of Material 28 Asbestos Found : NO Physical Assessment: n/a
MUDDED PIPE FITTING 311
Mudded Pipe Fitting Insulation
Assessment Reason : Not found to contain asbestos.
Sampled/Assumed/Previous ID
ACM/ACBM
Friable
SAMPLED
n/a
YES
QUANT I TY ·---------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) Cinches)
4 1.00
NOTES ------------------------------------------------------------------------------------------------
(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.
(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample Summary"
RADAR BASE
IR-60003-0100
Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:46:21 Page 1
BUILDING
Building Name Address City, State Gross Sq. Feet Inspector Name
BASE DORMITORY 1411-B
CATALINA HIGHWAY
TUCSON, AZ
16930
JOE LORANGER
EM! Building # Contact Person Title Phone Inspected
: 60003
: RAY WIGGINS
: ASBESTOS PROJECT SUPERVISOR
: (602) 670-5455 : 11/08/91
ROOM --·-------------------------------------------------------------·-·--·---------------------------- Functional Space: 0100 Room - UNKNOWN BOILER ROOM
MATER I AL ------------------------------------------------------------------------------------------ Sample Area MUDDED PIPE FITTING 511 Sampled/Assumed/Previous ID SAMPLED : AD
2B
NO
Type of Material Asbestos Found :
Mudded Pipe Fitting Insulation ACM/ACBM: n/a Friable: YES
Physical Assessment Assessment Reason n/a : Not found to contain asbestos.
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
6 1.00
MATERIAL ------------------------------------------------------------------------------------------ Sample Area : AG WALLBOARD Sampled/Assumed/Previous ID SAMPLED Type of Material : 3B Wallboard/Dry wall ACM/ACBM : n/a Asbestos Found : NO Friable: YES Physical Assessment: n/a Assessment Reason : Not found to contain asbestos.
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
MATERIAL ------------------------------------------------------------------------------------------ Sample Area MUDDED PIPE FITTING 211 : AJ
2B
NO
Type of Material Asbestos Found :
Mudded Pipe Fitting Insulation Sampled/Assumed/Previous ID
ACM/ACBM
Friable
SAMPLED
n/a
YES
Physical Assessment Assessment Reason
: n/a : Not found to contain asbestos.
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage Cinches) Footage Units (Inches) (Inches)
2 1 .00
MATERIAL ------------------------------------------------------------------------------------------ Sample Area : AK
2B
NO
Type of Material Asbestos Found :
Physical Assessment Assessment Reason n/a : Not
MUDDED PIPE FITTING 311
Mudded Pipe Fitting Insulation found to contain asbestos.
Sampled/Assumed/Previous ID
ACM/ACBM
Friable
SAMPLED
n/a
YES
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
18 1.00
RADAR BASE
IR-60003-0100 (cont'd) Printed by EnviroMD SAM system (ver. 1.3): 12/07/91 10:46:21 Page 2
M A T E R I A L Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason
BG
2B
NO
n/a Not
MUDDED PIPE FITTING 411
Mudded Pipe Fitting Insulation found to contain asbestos.
Sampled/Assumed/Previous ID
ACM/ACBM
Friable
SAMPLED
n/a
YES
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
7 1.00
MATER I AL ------------------------------------------------------------------------------------------ Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason
M A T E R I A L Sample Area Type of Material Asbestos Found Physical Assessment Assessment Reason
M A T E R I A L Sample Area Type of Material Asbestos Found :
Physical Assessment Assessment Reason
MUDDED PIPE FITTING 611 BH
2B
NO
Mudded Pipe Fitting Insulation Sampled/Assumed/Previous ID
ACM/ACBM
Friable
SAMPLED
n/a
YES
n/a Not found to contain asbestos.
TANK INSULATION
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
2 1.00
BJ
2C
NO
Tank Insulation (including tank brick) Sampled/Assumed/Previous ID
'ACM/ACBM
Friable
SAMPLED
n/a n/a Not found to contain asbestos.
BK CEMENT BOARD PANEL
4B. Cement Board - 'Transite'
YES
ACBM with potential for damage.
Nonfriable. Undamaged.
YES
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
Sampled/Assumed/Previous ID
ACM/ACBM
Friable
1.00
SAMPLED
ACBM
NO
QUANT I TY ----------------------------------
Square Diameter Li'near # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
56 0.13
NOTES ------------------------------------------------------------------------------------------------
(1) n/a = not applicable. (2) Signatures of Building Inspectors are provided elsewhere in this section.
(3) Reinspection is advised prior to renovation or demolition. (4) See "Inspection Report Sample Summary"
RADAR BASE
IR-60003-0110
Printed by EnviroMD SAM system ever. 1.3): 12/07/91 10:46:40 Page 1
B U I L D I N G Building Name Address City, State Gross Sq. Feet Inspector Name
BASE DORMITORY 1411-B
CATALINA HIGHWAY
TUCSON, AZ
16930
JOE LORANGER
EM! Building # Contact Person Title Phone Inspected
: 60003
: RAY WIGGINS
: ASBESTOS PROJECT SUPERVISOR
: (602) 670-5455 : 11/08/91
ROOM -------------------------------------------------------------------------------------.------------ Functional Space: 0110 Room - 7 DORM ROOM
MATERIAL ------------------------------------------------------------------------------------------ Sample Area : AA 9X9 FLOOR TILE GREEN Sampled/Assumed/Previous ID SAMPLED Type of Material : 4A1 Floor Tile ACM/ACBM : ACBM Asbestos Found : YES Friable: NO Physical Assessment ACBM with potential for damage.
Assessment Reason Nonfriable. Significantly Damaged. Damage is distributed. More than twenty-five percent of surface area is damaged.
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
165 0.13
MATERIAL --------------------------------------------------------·--------------------------------- Sample Area : AB MASTIC SA-AB Sampled/Assumed/Previous ID SAMPLED Type of Material : 4K Mastic ACM/ACBM.: ACBM Asbestos Found : YES Friable: NO Physical Assessment ACBM with potential for damage.
Assessment Reason Nonfriable. Significantly Damaged. Damage is distributed. More than twenty-five percent of surface area is damaged.
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
165 0.10
MATER I AL ------------------------------------------------------------------------------------------ Sample Area : AG WALLBOARD Sampled/Assumed/Previous ID SAMPLED Type of Material : 3B Wallboard/Dry wall ACM/ACBM n/a Asbestos Found : NO Friable YES Physical Assessment : n/a Assessment Reason : Not found to contain asbestos.
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
400 0.40
MATERIAL ------------------------------------------------------------------------------------------ Sample Area : AH BASEBOARD MASTIC Sampled/Assumed/Previous ID SAMPLED Type of Material : 4K Mastic ACM/ACBM n/a Asbestos Found : NO Friable NO Physical Assessment: n/a Assessment Reason : Not found to contain asbestos.
QUANT I TY ----------------------------------
Square Diameter Linear # Width Thickness Footage (Inches) Footage Units (Inches) (Inches)
A S B E S T O S I N S P E C T I O N R E P O R T
IR-60003-0110 (cont'd) Printed by EnviroMD SAM system ever. 1.3): 12/07/91 10:46:40 Page 2
MATER I AL --------------------------------------------------------·--·------------------------------ Sample Area : AK MUDDED PIPE FITTING 311 Sampled/Assumed/Previous ID SAMPLED Type of Material Asbestos Found
2B
NO
Mudded Pipe Fitting Insulation…