Qs and As_photos.docx
DOCX document 672 KB Posted
- Solicitation number
- 12639424R0024
About this file
This document appears to be a set of Questions and Answers (Q&A) related to Solicitation 12639524R0024 for a Steam Boiler Replacement project at the Moore Air Base in Edinburg, Texas.
The key details are:
- The operating pressure of the boiler is 0 to 150psi, with a maximum allowable pressure of 150psi.
- The existing boiler to be replaced has electrical requirements of 208/3ph to a 20amp circuit breaker.
- The solicitation is being issued by the Department of Agriculture Animal and Plant Health Inspection Service Marketing and Regulatory Programs Business Services.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Boiler Site Visit Attendance List 6-6-24.pdf | ||
| Atch 2_Federal Construction Wage Rates_Hidalgo County.pdf | ||
| 12639524R0024.pdf | ||
| Atch 1_SOW Steam Boiler Replacement.doc | DOC document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Solicitation 12639524R0024, Q’s and A’s
1. In the statement of work I did not see any information about the operating and maximum allowable pressure of the boiler. Can you please advise what this would be?
The operating pressure is 0 to 150psi. Maximum allowable pressure is 150psi.
2. Could you also verify the electrical requirements (460/3?) and gas pressure available at the boiler?
The existing Sellers boiler, to be replaced, the voltages are 208/3ph to a 20amp circuit breaker. Please see photos below.