12533_-_Drawings_with_Issue_Date.pdf
PDF 29 MB Posted
- Solicitation number
- 0000040083
- Issued by
- Sacramento County, California
About this file
This document comprises technical drawings and specifications for the CalVet Headquarters Electrical Upgrades project, a capital improvement project administered by the California Department of General Services (DGS) Real Estate Services Division for the California Department of Veterans Affairs. The project involves comprehensive electrical system replacements and upgrades within a seven-story (six with penthouse) existing building located at 1227 O Street, Sacramento, California. The scope of work includes disconnecting and replacing existing switchgear, switchboards, distribution panelboards, transformers, disconnect switches, and busway systems throughout the facility, with selective feeder replacements and busway replacement from the SMUD vault to the main electrical room. The project encompasses approximately 800 square feet of work area (500 square feet on the first floor and 50 square feet on each upper floor) within a 140,000-square-foot existing building. A temporary power system must be installed prior to service disconnection to maintain continuous power to critical systems including security, server room with HVAC and UPS loads, freight elevator, domestic water pumps, fire alarm and suppression systems, and emergency egress lighting. Sealed bids are due October 7, 2026, at 2:00 PM, with construction expected to be completed in 55 working days or less following award. The project requires all tenants to vacate the building during the main construction sequence.
The contractor must possess an A or B Certificate of Reported Compliance to bid and shall be responsible for circuit tracing documentation, including development of an as-built Revit model and AutoCAD files identifying all powered devices, fixtures, equipment, and systems throughout the building. The work must comply with 2022 California Building Code, California Electrical Code, California Fire Code, and California Energy Code standards, with the Office of the State Fire Marshal having jurisdiction over fire and panic requirements. A site safety plan establishing a fire prevention program must be submitted to and approved by the OSFM Field Deputy prior to building permit issuance. The contractor shall coordinate all work with the California Department of Veterans Affairs, including sequencing that minimizes disruption to adjacent areas and maintains required egress pathways. All materials must be new, UL or ETL listed, and copper conductors shall be utilized throughout. The project includes substantial temporary barriers, fire extinguishers, and dust control measures to protect occupied building areas during construction activities.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 12533_-_Project_Manual_Book_II.pdf | ||
| 12533_-_Project_Manual_Book_I.pdf | ||
| 12533_-_Bid_Package_Documents.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
th S tr ee t th S tr ee t
Richards Blvd
J Street
L Street
N Street
P StreetQ Street
9t h S tr ee t th S tr ee t th S tr ee t th S tr ee t st S tr ee t
Capitol Ave
Broadway
R iv er si de
B lv d
Stockton Blvd
Folsom Blvd
La nd
P ar k D r
A lh am br a B lv d
Railroad
Railroad
STATE
CAPITOL
PROJECT SITE
Sa cr am en to
R iv er
American River SACRAMENTO, CA
O St
OCCUPANCY:
B (BUSINESS)
MIXED OCCUPANCY:
NO
PROJECT NAME: CALVET HQ ELECTRICAL UPGRADES
PROJECT FLOOR AREA:
FIRST FLOOR: APPROX 500 SF
UPPER FLOORS: APPROX 50 SF EACH
TOTAL PROJECT AREA: APPROX 800 SF
EXISTING BUILDING STORIES:
7 (6 WITH PENTHOUSE)
PROJECT ADDRESS:
CALIFORNIA DEPARTMENT OF VETERANS AFFAIRS
1227 O STREET
SACRAMENTO, CA 95814
PROPOSED USE:
UNCHANGED
DGS PROJECT #:
000000000012533
TYPE OF CONSTRUCTION:
TYPE I-A (1-HOUR) [ASSUMED BASED ON AS-BUILT DOCS]
COMPLETE STEEL FRAME WITH CONCRETE SHEAR WALLS
ALLOWABLE AREA:
UNLIMITED
FIRE ALARM:
OTHER PROTECTION:
NO
SMOKE CONTROL:
NO
HFH SEVERITY ZONE:
NO
SEISMIC JOINTS:
NO
YEAR CONSTRUCTED:
ER RADIO COVERAGE:
NO
AREA INCREASE: N/A
YES, MANUAL & AUTOMATIC
EXISTING BUILDING AREA:
140,000 SF (UNCHANGED)
HEIGHT INCREASE:
N/A
EXISTING BUILDING HEIGHT:
108'-3" TOP OF N.STAIR TOWER (UNCHANGED)
OCCUPANT LOAD:
400 APPROXIMATELY PER FLOOR, 2,400 TOTAL FOR BUILDING (UNCHANGED)
REQUIRED FIRE SEPARATION:
(UNCHANGED)
FIRE SPRINKLERS:
YES, WET, 1ST FLOOR GARAGE ONLY
FIRE PROTECTION:
STANDPIPES IN STAIRWELLS & HOSE CABINETS THROUGHOUT;
CORRIDORS ON ALL FLOORS
OWNER: CA DEPT OF GENERAL SERVICES, RESD-PMDB
CONTACT: TOM SCHANBERGER
ELECTRICAL: THE ENGINEERING ENTERPRISE
CONTACT: SCOTT WHEELER
PHONE: 916.376.1687
tom.schanberger@dgs.ca.gov
CONTACT INFORMATION
PHONE: 530.886.8556
scott@engent.com
STRUCTURAL: BUEHLER ENGINEERING
CONTACT: WILLIAM RADER
PHONE: 916.443.0303.255
brader@buehlerengineering.com
ARCHITECT: HGA
CONTACT: BETH YOUNG
PHONE: 916.787.5145
BYoung@hga.com
2022 CALIFORNIA MECHANICAL CODE (CMC):
PART 4, TITLE 24, CCR; BASED ON THE 2021 UNIFORM MECHANICAL CODE (UMC)
2022 CALIFORNIA ELECTRICAL CODE (CEC):
PART 3, TITLE 24, CCR; BASED ON THE 2020 NATIONAL ELECTRICAL CODE (NEC)
2022 CALIFORNIA BUILDING CODE (CBC):
PART 2, TITLE 24, CCR; BASED ON THE 2021 INTERNATIONAL BUILDING CODE (IBC)
2022 CALIFORNIA ADMINISTRATIVE CODE (CAC)
PART 1, TITLE 24, CALIFORNIA CODE OF REGULATIONS (CCR)
AUTHORITY HAVING JURISDICTION:
OFFICE OF THE STATE FIRE MARSHAL (OSFM) FIRE & PANIC ONLY
DIVISION OF THE STATE ARCHITECT (DSA) ACCESS-ONLY
2022 CALIFORNIA FIRE CODE (CFC):
PART 9, TITLE 24, CCR, BASED ON THE 2021 INTERNATIONAL FIRE CODE (IFC)
ENERGY CODE:
2022 CALIFORNIA ENERGY CODE - PART 6, TITLE 24, CCR
ACCESSIBILITY CODE:
PROJECT EXEMPTED FROM DSA REVIEW [CBC 11B-202.4, EXCEPTION 7]
CODE INFORMATION
COUNTY OF:
SACRAMENTO
SPEC SECTION NUMBER ITEM
DEFERRED SUBMITTALS
N/A NONE.
Site Safety Plan per CFC Chapter 33
The owner's authorized agent shall be responsible for the development, implementation and maintenance of an approved, written site safety plan establishing a fire prevention program at the project site applicable throughout all phases of the construction, repair, alteration or demolition work. the plan shall address the requirements of this chapter and other applicable portions of this code, the duties of staff and staff training requirements.The site safety plan shall include items listed in CFC 3303.1.1 as applicable and shall be submitted to and approved by the OSFM Field Deputy prior to issuance of the building permit and before any construction activities begin. Any changes to plan shall also be submitted for approval.
This project will be publicly bid; the selected Contractor awarded the project shall be responsible for coordination with DGS and Cal Vet to develop a Site Safety Plan as required for construction.
NOTE: An impairment plan is required in addition to the site safety plan. All tenants shall be vacated during construction work.
R
ELECTRICAL
E E
NI
GNE
LANOISSEFORP
DERET
SI
G
E R
C A L I F ORN
I A
S T A T E
O F
707 Third Street, Suite 4-105
Architecture & Engineering Sections
Project Management & Development Branch Real Estate Services Division
State of California
West Sacramento, California 95605
Department of General Services
CONSULTING ENGINEERS
ALAMEDA | AUBURN | LOS ANGELES
https://www.engent.com
NEOSHO | SAN DIEGO | SANTA BARBARA
JJ
AS NOTED
V1
C o p y ri g h t
C a lif o rn ia D e p a rt m e n t o f G e n e ra l S e rv ic e s
R e a l E s ta te S e rv ic e s D iv is io n
PROFESSIONAL
STAMP
0 1 2 3
Issue
DateNo. Description
Project
DSA App No.
Supervisor
Sheet Title
Designed
Sheet Number
Sheet Scale
Reference North
Project Number
Drawn
OSFM Permit No. 25-N-3911-C
12533
SWSW
1227 O STREET
SACRAMENTO, CA 95814
#E015491 Exp. 06/30/27
SCOTT WHEELER
PROJECT NUMBER: 12533
1227 O STREET
CALVET
SACRAMENTO, CA 95814
PROJECT TEAM
PROJECT MANAGER: TOM SCHANBERGER
STRUCTURAL:
ELECTRICAL:
WILLIAM RADER
SCOTT WHEELER
PROJECT SCOPE
SHEET INDEXAPPLICABLE CODES
LOCATION MAP
PROJECT INFORMATION
CALIFORNIA VETERANS HEADQUARTERS ELECTRICAL UPGRADE
ARCHITECT: BETH YOUNG
OVERALL SITE PLAN
PERMIT APPLICATION NUMBER: 25-N-3911-C
PERMIT APPLICATION NO.
25-N-3911-C
GENERAL
G001
CalVet Electrical Upgrades
SHEET NO. SHEET NAME
G001 GENERAL
E001 SYMBOLS AND ABBREVIATIONS
E002 FEEDER SCHEDULE, NOTES, & TABLES
E003 TITLE 24
E004 NOT USED
E005 SCHEDULES - PANELBOARDS - 1ST FLOOR
E006 SCHEDULES - PANELBOARDS - 2ND FLOOR
E007 SCHEDULES - PANELBOARDS - 3RD FLOOR
E008 SCHEDULES - PANELBOARDS - 4TH FLOOR
E009 SCHEDULES - PANELBOARDS - 5TH FLOOR
E010 SCHEDULES - PANELBOARDS - 6TH FLOOR
E011 SCHEDULES - PANELBOARDS - ROOF/PENTHOUSE
E100 SITE & FIRE ACCESS
E101 ELECTRICAL POWER PLAN - 1ST FLOOR
E102 ELECTRICAL POWER PLAN - 2ND FLOOR
E103 ELECTRICAL POWER PLAN - 3RD FLOOR
E104 ELECTRICAL POWER PLAN - 4TH FLOOR
E105 ELECTRICAL POWER PLAN - 5TH FLOOR
E106 ELECTRICAL POWER PLAN - 6TH FLOOR
E107 ELECTRICAL POWER PLAN - ROOF/PENTHOUSE
E200 ENLARGED PLANS - SMUD VAULT
E201 ENLARGED PLANS - MAIN ELECTRICAL ROOM
E202 ENLARGED PLANS -1ST FLOOR EAST ELECTRICAL CLOSET
E203 ENLARGED PLANS - 1st FLOOR WEST ELECTRICAL CLOSET
E204 ENLARGED PLANS - 2ND FLOOR EAST ELECTRICAL CLOSET
E205 ENLARGED PLANS - 2ND FLOOR WEST ELECTRICAL CLOSET
E206 ENLARGED PLANS - 3RD FLOOR EAST ELECTRICAL CLOSET/ROOM
E207 ENLARGED PLANS - 3RD FLOOR WEST ELECTRICAL CLOSET
E208 ENLARGED PLANS - 4th FLOOR EAST ELECTRICAL CLOSET/ROOM
E209 ENLARGED PLANS - 4th FLOOR WEST ELECTRICAL CLOSET/ROOM
E210 ENLARGED PLANS - 5th FLOOR EAST ELECTRICAL CLOSET & SPACES
E211 ENLARGED PLANS - 5th FLOOR WEST ELECTRICAL CLOSET & SPACES
E212 ENLARGED PLANS - 6th FLOOR EAST ELECTRICAL CLOSET/ROOM
E213 ENLARGED PLANS - 6th FLOOR WEST ELECTRICAL CLOSET/ROOM
E214 ENLARGED PLANS - ROOF/PENTHOUSE PANELS
E300 ELECTRICAL SINGLE-LINE DIAGRAM - EXISTING
E301 ELECTRICAL SINGLE-LINE DIAGRAM - NEW
E400 DETAILS - GROUNDING AND BONDING
E401 DETAILS - CABLE TRAY AND BUS DUCT ANCHORAGE
E402 DETAILS - ELECTRICAL EQUIPMENT ANCHORAGE
E403 DETAILS - WALL PENETRATIONS
A. RISK CATEGORY – II
B. SEISMIC DESIGN CATEGORY – D
C. SEISMIC SITE CLASS – D
D. SEISMIC IMPORTANCE FACTOR – 1.00
E. SEISMIC COEFFICIENTS – SDS = 0.510, SD1 = 0.530
SEISMIC PARAMETERS
A. CONCRETE (UP TO 15% FLYASH SUBSTITUTION FOR
PORTLAND CEMENT)
1. FOUNDATIONS AND WALLS – 3,000 PSI, 145PCF
NORMAL WEIGHT, W/C RATIO = .58
2. SLAB ON GRADE AND CURBS – 3,500 PSI, 145PCF
NORMAL WEIGHT, W/C RATIO = .45
3. CONCRETE FLATWORK AND PAVING – 2,500 PSI,
145PCF NORMAL WEIGHT
B. CONCRETE REINFORCING:
1. ASTM A615 GRADE 60
2. ASTM A706 GRADE 60 AT WELDED BARS
C. ANGLES, CHANNELS, PLATES, ETC.:
1. ASTM A36 (36 KSI)
2. ASTM A572 GRADE 50 (50 KSI)
D. LIGHT GAGE METAL INCLUDING STUDS, ANGLES, ETC.
1. ASTM A653 (33 KSI OR 50 KSI)
E. POST INSTALLED ANCHORS
1. HILTI KB-TZ2
STRUCTURAL MATERIALS
PROJECT SCOPE INCLUDES, BUT IS NOT LIMITED TO, INTERIOR WORK WITHIN PORTIONS OF AN EXISTING BUILDING:
- ELECTRICAL UPGRADES INCLUDE DISCONNECTING AND REPLACEMENT OF EXISTING SWITCHGEAR, SWITCHBOARDS, DISTRIBUTION PANELBOARDS, TRANSFORMERS, PANELBOARDS, DISCONNECT SWITCHES, BUSWAY, AND SELECTIVE FEEDERS THROUGHOUT, AND REPLACEMENT OF BUSWAY FROM SMUD VAULT TO MAIN ELECTRICAL ROOM. MUCH OF THE CONDUIT SHALL BE REUSED. WHERE IT IS KNOWN THAT CONDUITS NEED TO BE REROUTED OR ADJUSTED WE HAVE DENOTED. ASSUME ALL ELECTRICAL EQUIPMENT IS TO BE REPLACED
UNLESSDENOTED AS EXISTING TO REMAIN.
- INSTALLATION OF ALL NEW EQUIPMENT, INCLUDING ANCHORAGE AS REQUIRED.
- CIRCUIT TRACING AND DEVELOPMENT OF RECORD DOCUMENTS AS DESCRIBED ON E002.
- UPS IS TO BE REPLACED AS SHOWN ON E212. THE UPS IS REPLACING AN EXISTING UNIT AND IS
SERVING JUST IT LOADS. THIS IS NOT AN EMERGENCY SOURCE. THE VALVE-REGULATED LEAD- ACID (VRLA) BATTERY ENERGY CAPACITY IS BELOW THE 70 KWH CALIFORNIA FIRE CODE (CFC)
SECTION 1207.1.1 THRESHOLD FOR SPECIAL OCCUPANCY.
TEMP POWER IS REQUIRED PRIOR TO DISCONNECTING SERVICE TO THE FACILITY FOR THE FOLLOWING SYSTEM. THE TEMPORARY POWER SHALL PROVIDE POWER WITH NO INTERRUPTION OF SERVICE TO ASSURE THE
EMERGENCY LOADS ARE ALWAYS ACTIVE.
- SECURITY
- SERVER ROOM / INCLUDING HVAC AND UPS LOADS
- FREIGHT ELEVATOR
- PUMPS (DOMESTIC WATER)
- FIRE ALARM & FIRE SUPRESSION
- EXIT SIGNS AND EGRESS LIGHTING
FOLLOW THE APPROVED SEQUENCING PLAN AS DESCRIBED IN CONTRACT DOCUMENTS.
*EXEMPT FROM ACCESSIBLE PATH OF TRAVEL REQUIREMENTS PER CBC 11B-202.4, EXCEPTION 7.
CONTRACTOR TO CONFIRM NO EGRESS ROUTES ARE OBSTRUCTED OR OCCUPANCY SAFETY IS
COMPROMISED BY ELECTRICAL WORK OR PROTECTION BARRIERS.
Per CBC Table 601: for Type I-A construction, primary structural frame has 3-hour protection and floor construction requires 2-hour protection.
Any penetrations in floor/deck assemblies must be fire-stopped to maintain or restore the required 2-hour rating.
Information on existing wall ratings is limited; field investigation is required to identify any rated wall assembly locations that may be impacted by the scope of work. All penetrations through rated walls must be fire-stopped to maintain or restore the existing assembly continuity.
PER ORIGINAL AS-BUILT DRAWINGS:
(E) STEEL COLUMNS NOT ENCASED IN CONCRETE HAVE 3-HOUR FIREPROOFING WITH PUTTY
COAT FINISH ON 1 3/8" LIGHTWEIGHT AGGREGATE PLASTER AND SELF-FURRING METAL LATH.
(E) 2-HOUR WALLS ARE 1" PLASTER & LATH BOTH SIDES OF 4" METAL STUDS AT 16" OC.
(E) GYP BOARD WALLS ARE NON-RATED WITH 3 5/8" METAL NAILING STUDS (M.N.S.) AT 24" OC.
NOTE: NOT TO SCALE
CONTRACTOR STAGING / LAY DOWN AREA
PROJECT LOCATION
1 2025/03/02 SFM RESUBMITTAL
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
4/21/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3911
2026-06-30
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
7/2/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3911
ISSUE DATE: JULY 14, 2026
A
AFI
AF
AFF
AIC
AL
AT
ATS
C
CEC
CL
CT
CU
D
(E)
EC
EF
EPO
EMT
F
(F)
FACP
FLA
FMC
G
GB
GFCI
GND
GRC
IG
IMC
K
KAIC
KCMIL
KO
LCP
MBGB
MCB
MLO
MTC
MTS
(N)
NC
NF
NIEC
NL
NO
NTS
OC
OFCI
PNL
PT
PVC
(R)
(RR)
TC
TP
SPD
TX
TYP
UON
UPS
V
VA
VFD
WP
Y
1Ø
3Ø
1P
2P
3P
3W
4W
ABBREVIATIONS
AMPERES
ARC FAULT CIRCUIT INTERRUPTER
AMPERE OVERCURRENT FRAME SIZE
(WHEN APPLIED TO CIRCUIT
BREAKERS) OR AMPERE FUSE SIZE
(WHEN APPLIED TO FUSES)
ABOVE FINISHED FLOOR
ASYMMETRIC INTERRUPTING CURRENT
ALUMINUM
AMPERE OVERCURRENT TRIP (WHEN
APPLIED TO CIRCUIT BREAKERS)
AUTOMATIC TRANSFER SWITCH
CONDUIT
CALIFORNIA ELECTRICAL CODE
CURRENT LIMITING CIRCUIT BREAKER
OR FUSE
CURRENT TRANSFORMER
COPPER
DELTA
EXISTING TO REMAIN
ELECTRICAL CONTRACTOR
EXHAUST FAN
EMERGENCY POWER OFF
ELECTRICAL METALLIC TUBING
FUSED
FUTURE
FIRE ALARM CONTROL PANEL
FULL LOAD AMPERES
FLEXIBLE METAL CONDUIT
GROUND
GROUND BUS
GROUND FAULT CIRCUIT INTERRUPTER
GROUND
GALVANIZED RIGID CONDUIT
ISOLATED GROUND
INTERMEDIATE METAL CONDUIT
KILO
KILO AIC
KILO CIRCULAR MIL
CONDUIT KNOCKOUT
LIGHTING CONTROL PANEL
MAIN BUILDING GROUND BUS
MAIN CIRCUIT BREAKER
MAIN LUGS ONLY
EMPTY CONDUIT
MANUAL TRANSFER SWITCH
NEW
NORMALLY CLOSED
NON-FUSED
NOT IN ELECTRICAL CONTRACT
NIGHT LIGHT, UNSWITCHED
NORMALLY OPEN
NOT TO SCALE
ON CENTER
OWNER FURNISHED CONTRACTOR
INSTALLED
PANEL
POTENTIAL TRANSFORMER
POLYVINYL CHLORIDE
EXISTING TO BE REMOVED
REMOVE AND RELOCATE
TIME CLOCK
TWISTED-PAIR
SURGE PROTECTION DEVICE
TRANSFORMER
TYPICAL
UNLESS OTHERWISE NOTED
UNINTERRUPTIBLE POWER SUPPLY
VOLTS
VOLTS-AMPS
VARIABLE FREQUENCY DRIVE
WEATHERPROOF
WYE
1-PHASE
3-PHASE
1-POLE
2-POLE
3-POLE
3-WIRE
4-WIRE
R
ELECTRICAL
E E
NI
GN
E
LANOISSEFORP
DERET
SI
G
E R
C A L I F ORN
I A
S T A T E
O F
707 Third Street, Suite 4-105
Architecture & Engineering Sections
Project Management & Development Branch Real Estate Services Division
State of California
West Sacramento, California 95605
Department of General Services
CONSULTING ENGINEERS
ALAMEDA | AUBURN | LOS ANGELES
https://www.engent.com
NEOSHO | SAN DIEGO | SANTA BARBARA
JJ
AS NOTED
V1
C o p y ri g h t
C a lif o rn ia D e p a rt m e n t o f G e n e ra l S e rv ic e s
R e a l E s ta te S e rv ic e s D iv is io n
PROFESSIONAL
STAMP
0 1 2 3
Issue
DateNo. Description
Project
DSA App No.
Supervisor
Sheet Title
Designed
Sheet Number
Sheet Scale
Reference North
Project Number
Drawn
OSFM Permit No. 25-N-3911-C
12533
SWSW
1227 O STREET
SACRAMENTO, CA 95814
#E015491 Exp. 06/30/27
SCOTT WHEELER
PERMIT APPLICATION NO.
25-N-3911-C
SYMBOLS AND
ABBREVIATIONS
E001
CalVet Electrical Upgrades
SOME OF THESE SYMBOLS SHOWN MAY NOT BE USED ON THIS PROJECTSYMBOLS LIST
EXISTING TO REMAIN
EXISTING TO BE REMOVED (R) OR RELOCATED (RR)
NEW CONSTRUCTION
AREA NOT IN SCOPE
IN ELEVATIONS, EXISTING LOCATION OF EQUIPMENT THAT IS TO BE RELOCATED OR
REMOVED
LINESTYLES
POWER DISTRIBUTION
SWITCHGEAR, SWITCHBOARD, DISTRIBUTION BOARD, SUBSTATION OR MOTOR CONTROL
CENTER, FLOOR MOUNTED ON CONCRETE HOUSEKEEPING PAD WHERE INDICATED ON
DRAWINGS. DOUBLE LINE INDICATES FRONT FACE OF GEAR.
DISTRIBUTION BOARD, SURFACE MOUNTED ON WALL.
PANELBOARD, 277/480V, SURFACE MOUNTED ON WALL.
PANELBOARD, 277/480V, FLUSH MOUNTED IN WALL.
PANELBOARD, 120/208V, SURFACE MOUNTED ON WALL.
PANELBOARD, 120/208V, FLUSH MOUNTED IN WALL.
DRY-TYPE STEP-DOWN TRANSFORMER, FLOOR MOUNTED 480-120/208V 3Ø, UON. DOUBLE
LINE INDICATES FRONT FACE OF TRANSFORMER.
PULLBOX OR HANDHOLE, SIZE AND TYPE AS NOTED ON PLANS.
SAFETY DISCONNECT SWITCH, 3 POLE, UON. ADJACENT NUMBER INDICATES FUSE SIZE
WHEN APPLICABLE. LABELING CONVENTION AS FOLLOWS:
A: 30A, NON-FUSED AF: 30A, FUSED
B: 60A, NON-FUSED BF: 60A, FUSED
C: 100A, NON-FUSED CF: 100A, FUSED
D: 200A, NON-FUSED DF: 200A, FUSED
E: 400A, NON-FUSED EF: 400A, FUSED
F: 600A, NON-FUSED FF: 600A, FUSED
G: 800A, NON-FUSED GF: 800A, FUSED
MAGNETIC MOTOR STARTER WITH INTEGRAL OVERCURRENT PROTECTION. ADJACENT
NUMBER INDICATES NEMA SIZE OF STARTER. "HANDLE" DENOTES INTEGRAL DISCONNECT.
VARIABLE FREQUENCY DRIVE FURNISHED UNDER ANOTHER DIVISION. INSTALL VFD AND
PROVIDE POWER SERVICE CONNECTION UNDER THIS DIVISION. "HANDLE" DENOTES
INTEGRAL DISCONNECT.
ELECTRONICALLY COMMUTATED MOTOR CONTROLLER FURNISHED UNDER ANOTHER
DIVISION. INSTALL ECM AND PROVIDE POWER SERVICE CONNECTION UNDER THIS
DIVISION. "HANDLE" DENOTES INTEGRAL DISCONNECT.
PACKAGE MOTOR CONTROLLER OR STARTER FURNISHED AND INSTALLED UNDER
ANOTHER DIVISION WITH EQUIPMENT CONTROLLED. PROVIDE SINGLE-POINT POWER
SERVICE CONNECTION UNDER THIS DIVISION AS NOTED ON PLANS.
DRIVEN GROUND ROD.
DRIVEN GROUND ROD IN GROUND WELL WITH COVER.
CABLE TO BUS TERMINATION LUGS.
BOLTED PRESSURE OR HIGH PRESSURE CONTACT OR FUSED SWITCHES.
GROUP MOUNTED MOLDED CASE CIRCUIT BREAKER.
INDIVIDUALLY FIXED MOUNTED INSULATED-CASE OR POWER CIRCUIT BREAKER.
INDIVIDUALLY DRAW-OUT MOUNTED INSULATED-CASE OR POWER CIRCUIT BREAKER.
MEDIUM-VOLTAGE, INDIVIDUALLY DRAW-OUT MOUNTED VACUUM CIRCUIT BREAKER.
MEDIUM-VOLTAGE LOAD INTERRUPTER SWITCH, FUSED TYPE.
MEDIUM-VOLTAGE LOAD INTERRUPTER SWITCH, NON-FUSED TYPE.
GROUND FAULT RELAY INTEGRAL WITH CIRCUIT BREAKER.
ELECTRICALLY OPERATED CIRCUIT BREAKER, INTEGRAL.
SHUNT-TRIP INTEGRAL WITH OVERCURRENT PROTECTION DEVICES.
KIRK-KEY INTERLOCK INTEGRAL WITH OVERCURRENT PROTECTION DEVICES. ADJACENT
NUMBER CORRESPONDS WITH DEVICE INTERLOCK.
PRIVATE METER, MOUNTED INTEGRAL WITH OVERCURRENT PROTECTION OR SEPARATE
WITHIN SWITCHGEAR.
UTILITY METER, MOUNTED IN UTILITY METER SECTION OF SWITCHGEAR OR
SWITCHBOARDS.
PRIVATE METER, MOUNTED IN SEPARATE ENCLOSURE FROM SWITCHGEAR OR
SWITCHBOARDS.
GROUND FAULT RELAY WITH SHUNT TRIP.
GROUND FAULT ALARM, NO SHUNT TRIP.
TRANSFORMER.
CONNECTION TO GROUND.
AUTOMATIC OR MANUAL TRANSFER SWITCH.
AUTOMATIC TRANSFER & BY-PASS ISOLATION SWITCH.
EMERGENCY GENERATOR.
BATTERIES.
NEUTRAL SERVICE DISCONNECT LINK.
SURGE PROTECTION DEVICE, 'SPD'.
CONTROL CONTACTOR.
NORMALLY OPEN CONTACT.
NORMALLY CLOSED CONTACT.
DIGITAL METERING UNIT.
GROUND BUS AS SHOWN ON SINGLE LINE DIAGRAMS.
GROUND BUS AS SHOWN ON PLAN VIEWS.
NEUTRAL BUS.NEU
DMU
GND
C
SPD
G
GFA
GFR
K
ST
EO
M
G
M
WIRING DEVICES
JUNCTION BOX, WALL MOUNTED, +18" UON.
JUNCTION BOX, MOUNTED IN FLUSH FLOOR BOX.
JUNCTION BOX, MOUNTED FLUSH IN CEILING.
JUNCTION BOX, SURFACE OR PENDANT MOUNTED TO BOTTOM OF STRUCTURE IN
ACCESSIBLE CEILING SPACE OR EXPOSED IN OPEN CEILING AREAS.
JUNCTION BOX, MOUNTED ON CONDUIT STANCHION FLOOR PENETRATION, +12" UON.
SINGLE-PLEX CONVENIENCE RECEPTACLE DEVICE, WALL MOUNTED, +18" UON.
DUPLEX CONVENIENCE RECEPTACLE DEVICE, WALL MOUNTED, +18" UON. LETTERING
ADJACENT TO THE DEVICE ON THE PLANS INDICATE THE FOLLOWING FOR THOSE
RECEPTACLES.
A: ARC FAULT CURRENT INTERRUPTER (AFCI)
G: GROUND FAULT CURRENT INTERRUPTER (GFCI)
IG: ISOLATED GROUND
TR: TAMPER RESISTANT
U: INTEGRAL USB PORTS
WP: WEATHER-RESISTANT, GROUND FAULT CURRENT INTERRUPTER (GFCI) WITH
WEATHERPROOF "IN USE" COVER
DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, WALL MOUNTED, +18" UON.
DUPLEX CONVENIENCE RECEPTACLE DEVICE, WALL MOUNTED OVER COUNTER, 6"
ABOVE BACK SPLASH UON, BUT NO HIGHER THAN ADA REQUIREMENTS.
DUPLEX CONVENIENCE RECEPTACLE DEVICE, SPLIT-WIRED, WALL MOUNTED, +18" UON.
DUPLEX CONVENIENCE RECEPTACLE DEVICE, ON BACK-UP POWER SYSTEM, WALL
MOUNTED, +18" UON.
DUPLEX, OR DOUBLE DUPLEX, CONVENIENCE RECEPTACLE DEVICE, CONTROLLED PER
T24, WALL MOUNTED, +18" UON.
DUPLEX CONVENIENCE RECEPTACLE DEVICE, HORIZONTALLY WALL MOUNTED, +18"
UON.
SPECIALTY OUTLET DEVICE, NEMA CONFIGURATION TYPE AS NOTED ON PLANS, WALL
MOUNTED, +18" UON.
DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FLUSH FLOOR BOX.
DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FLUSH FLOOR BOX.
COMBINATION POWER/TELECOMMUNICATION DEVICE, MOUNTED IN FLUSH FLOOR BOX.
TYPE AS NOTED ON PLANS OR IN SPECIFICATIONS.
DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FIRE-RATED POKE-THRU
FLOOR FITTING.
DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FIRE-RATED POKE-
THRU FLOOR FITTING.
COMBINATION POWER/TELECOMMUNICATION DEVICE, MOUNTED IN FIRE-RATED POKE-
THRU FLOOR FITTING. TYPE AS NOTED ON PLANS OR IN SPECIFICATIONS.
DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED FLUSH IN CEILING.
DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED FLUSH IN CEILING.
DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED ON CONDUIT STANCHION
FLOOR PENETRATION, +12" UON.
DUPLEX CONVENIENCE RECEPTACLE DEVICE, CORD OR REEL HUNG FROM STRUCTURE
ABOVE. TYPE AS NOTED ON PLANS.
ELECTRIFIED FURNITURE PARTITION POWER FEED, WALL MOUNTED, +18" UON.
CONSISTS OF 4 11/16" SQ. X 2 1/8" DEEP JUNCTION BOX, SINGLE GANG RING, AND
STAINLESS STEEL COVER PLATE WITH KO TO ACCEPT FURNITURE WHIP.
ELECTRIFIED FURNITURE PARTITION COMBINATION POWER/TELECOMMUNICATION
FEEDS, MOUNTED IN FIRE-RATED POKE-THRU FLOOR FITTING WITH KO'S OR THREADED
HUB IN COVER TO ACCEPT FURNITURE WHIPS
ELECTRIFIED FURNITURE PARTITION POWER FEED, MOUNTED IN FIRE-RATED POKE-
THRU FLOOR FITTING WITH KO OR THREADED HUB IN COVER TO ACCEPT FURNITURE
WHIP.
POWER/TELECOMMUNICATION POLE, MOUNTED TO EXTEND FROM FLOOR TO CEILING.
TYPE AS NOTED ON PLANS.
SINGLE-POLE, MANUAL DISCONNECT SWITCH WITH THERMAL OVERLOAD ELEMENT,
MOUNTED ADJACENT TO MOTOR.
SINGLE-POLE, FRACTIONAL HORESPOWER MOTOR STARTER/DISCONNECT SWITCH,
MOUNTED ADJACENT TO MOTOR.
SWITCH FURNISHED UNDER ANOTHER DIVISION, BUT INSTALLED AND WIRED UNDER
THIS DIVISION, WALL MOUNTED, +42" UON.
LINE-VOLTAGE THERMOSTAT, NIEC, WALL MOUNTED +48" UON. INSTALLED AND WIRED
BY ELECTRICAL.
CONTROL STATION, WALL MOUNTED, +42" UON.
NUMBERED NOTE, APPLIES TO ALL DRAWINGS.
NUMBERED SHEET NOTE, APPLIES TO DRAWING CONTAINING NOTES ONLY.
OVERCURRENT PROTECTIVE DEVICE NUMBER IDENTIFICATION TAG. REFERS TO
LOCATION OF PROTECTIVE OR CONTROL DEVICE WITHIN SWITCHBOARDS,
DISTRIBUTION BOARDS, MOTOR CONTROL CENTERS, ETC.
EQUIPMENT IDENTIFICATION TAG: ITEM FURNISHED AND INSTALLED UNDER
ANOTHER DIVISION AND WIRED UNDER THIS DIVISION.
FEEDER TAG. REFER TO FEEDER SCHEDULE.
DETAIL REFERENCE:
DETAIL DESIGNATION
SHEET NUMBER
LUMINAIRE IDENTIFICATION TAG:
LUMINAIRE TYPE
QUANTITY
UNDERGROUND CONDUIT DESIGNATION:
CONDUIT SIZE IN INCHES
CONDUIT SYSTEM DESIGNATION
P: PRIMARY POWER
S: SECONDARY POWER
T: TELECOMMUNCATIONS
QUANTITY OF CONDUITS
EQ
E-801
2 - F3
CONVENTIONS
RACEWAYS
CONDUIT RUN EXPOSED ON WALL OR CEILING.
CONDUIT RUN CONCEALED IN SLAB, UNDER SLAB OR UNDERGROUND.
CONDUIT RUN CONCEALED IN WALL OR ABOVE CEILING.
CONDUIT HOMERUN, CONTINUOUS RUN TO PANEL OR EQUIPMENT CABINET.
HOMERUN CAN OCCUR ON ANY OF THE ABOVE ROUTING CONDITIONS.
CONDUIT TURNED UP, CAN OCCUR ON ANY OF THE ABOVE ROUTING
CONDITIONS.
CONDUIT TURNED DOWN, CAN OCCUR ON ANY OF THE ABOVE ROUTING
CONDITIONS.
CONDUIT CAPPED OR STUBBED WITH INSULATED BUSHINGS, CAN OCCUR ON
ANY OF THE ABOVE ROUTING CONDITIONS.
CONDUIT SLEEVE, WITH INSULATING BUSHINGS.
FLEXIBLE METALLIC CONDUIT, EQUIPMENT CONNECTION.
CROSSMARKS ON BRANCH CIRCUIT CONDUIT RUNS INDICATE THE QUANTITY OF
CONDUCTORS AS FOLLOWS (GROUND CONDUCTORS ARE NOT NOTED, BUT
SHOULD BE INCLUDED IN EVERY CONDUIT WITH POWER CONDUCTORS):
1. NO CROSSMARKS INDICATES TWO #12 AWG CONDUCTORS, UON.
2. THREE TO SIX CROSSMARKS INDICATES THE QUANTITY OF #12 AWG
CONDUCTORS, UON.
3. SEVEN OR MORE CROSSMARKS INDICATES THE QUANTITY OF #10
AWG CONDUCTORS, UON.
SURFACE RACEWAY; TYPE, DEVICE SPACING AND MOUNTING AS NOTED ON
PLANS.
CABLE TRAYS/RUNWAYS, REFER TO PLANS AND/OR SPECS FOR SIZE AND
MOUNTING.
A AF
1 1
VFD
VFD
ECM
ECM
LINE VOLTAGE LIGHTING CONTROL
SINGLE-POLE, SINGLE-THROW SWITCH, WALL MOUNTED, +42" UON.
THREE-WAY SWITCH, WALL MOUNTED, +42" UON.
FOUR-WAY SWITCH, WALL MOUNTED, +42" UON.
SINGLE-POLE, SINGLE-THROW SWITCH, KEY-OPERATED, WALL MOUNTED, +42" UON.
SINGLE-POLE, SINGLE-THROW SWITCH, WITH PILOT LIGHT, WALL MOUNTED, +42" UON.
WALLBOX DIMMER SWITCH, +42" UON. SIZED PER CONNECTED LOAD ON PLANS AND
FURNISHED FOR LAMP SOURCE SERVED. PROVIDED FOR DERATING WHEN INSTALLED
GANGED LOCATIONS.
SINGLE-POLE, TIMER CONTROLLED SWITCH, WALL MOUNTED, +42" UON.
SINGLE-POLE, SINGLE-THROW SWITCH, EXPLOSION PROOF, WALL MOUNTED, +42" UON.
LINE VOLTAGE SINGLE RELAY VACANCY SENSOR, WALL MOUNTED, +42" UON.
SINGLE-POLE, SINGLE-THROW SWITCH WITH WEATHERPROOF COVER, WALL MOUNTED,
+42" UON.
SINGLE-POLE SWITCH WITH AUTOMATIC HUMIDITY CONTROL, WALL MOUNTED, +42" UON.
DUAL LEVEL OCCUPANCY SENSOR SWITCH, WALL MOUNTED, +42" UON.
SINGLE LEVEL OCCUPANCY SENSOR SWITCH, WALL MOUNTED, +42" UON.
COMBINATION OCCUPANCY SENSOR AND DIMMER SWITCH, WALL MOUNTED, +42" UON.
OCCUPANCY SENSOR FOR AREA COVERAGE, CEILING MOUNTED.
PHOTOELECTRIC CELL SENSOR, CEILING MOUNTED.
EGRESS LIGHTING TRANSFER DEVICE.
BYPASS DEVICE FOR CONTROLLED EMERGENCY LIGHTING.
S
WP
S V
S
EP
S
TC
S D
S P
S K
S
S
S
OS
PC
S
DM
S M1
S M
S H
J
J
J
J
J
ETD
T
P
P
7S4
S F
S
MS
S T
M
P
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
4/21/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3911
2026-06-30
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
7/2/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
1. ELECTRICAL SCOPE SHALL COMPLY WITH THE LATEST ADOPTED EDITIONS OF THE CALIFORNIA
ELECTRIC CODE (CEC), CALIFORNIA BUILDING CODE (CBC), CALIFORNIA FIRE CODE (CFC),
CALIFORNIA MECHANICAL CODE (CMC), NATIONAL FIRE PROTECTION ASSOCIATION (NFPA 72) AND
THE CALIFORNIA ENERGY CODE.
2. THE CONTRACTOR SHALL VISIT THE JOBSITE AND VERIFY ALL EXISTING CONDITIONS PRIOR TO
BIDDING THE PROJECT AND SHALL INCLUDE IN THEIR BID THE NECESSARY COSTS TO
CONSTRUCT THIS PROJECT IN ACCORDANCE WITH THE DRAWINGS, SPECIFICATIONS, AND ALL
APPLICABLE CODES.
3. DRAWINGS INDICATE GENERAL ARRANGEMENT OF ELECTRICAL SYSTEMS AND WORK. FOLLOW
THE DRAWINGS IN LAYING OUT WORK AND VERIFY EXACT LOCATIONS WITH ARCHITECTURAL
FLOOR PLAN AND RCP DRAWINGS. ALSO, CHECK DRAWINGS OF OTHER TRADES TO VERIFY
LOCATIONS OF EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS AND COORDINATE SPACE
CONDITIONS WITH THEIR INSTALLATION. FINAL LOCATIONS SHALL BE ADJUSTED TO MEET FIELD
CONDITIONS.
4. NOT EVERY ELECTRICAL RACEWAY, BOX, CONDUCTOR, ETC., FOR A COMPLETE ELECTRICAL
INSTALLATION IS SHOWN ON THESE DRAWINGS. THIS IS DONE FOR CLARITY PURPOSES AND
EASE OF INTERPRETING DRAWINGS. PROVIDE ALL ADDITIONAL ITEMS REQUIRED TO MAKE THE
ELECTRICAL SYSTEMS COMPLETE AND OPERATIONAL.
5. WORK PERFORMED UNDER THIS CONTRACT SHALL CONFORM TO THESE DRAWINGS AND SHALL
ALSO COMPLY WITH THE ELECTRICAL SPECIFICATIONS. IN THE EVENT THAT THERE IS A
DISCREPANCY BETWEEN THE DRAWINGS AND SPECIFICATIONS, THE MORE STRINGENT OF THE
REQUIREMENTS SHALL TAKE PRECEDENT.
6. ALL NEW ELECTRICAL MATERIALS AND EQUIPMENT SHALL BE UNDERWRITER’S LABORATORIES (UL) LISTED OR ELECTRICAL TESTING LABORATORIES (ETL) LISTED AND BEAR THEIR LABELS.
7. ALL ELECTRICAL MATERIALS SHALL BE NEW AND UNUSED, AND THE SAME MANUFACTURER OF
LIKE EQUIPMENT AND/OR SYSTEMS.
8. CONTRACTOR SHALL REMOVE ALL LEFTOVER CONDUIT, WIRE, SCRAPS, ETC. AND LEAVE
PREMISES CLEAN AND FREE OF TRASH AND DEBRIS RESULTING FROM THEIR WORK.
9. COORDINATE ALL INCOMING ELECTRICAL SERVICE WORK WITH THE SERVING POWER UTILITY
COMPANY PRIOR TO ANY INSTALLATION.
10. ALL ON-SITE INFRASTRUCTURE FOR SERVICE ENTRANCE INSTALLATION WORK OF POWER UTILITY
COMPANY SHALL BE PROVIDED UNDER THIS CONTRACT. COORDINATE INSTALLATION WITH
POWER UTILITY COMPANY’S STANDARDS AND SPECIFICATIONS.
11. ALL EQUIPMENT, DEVICES, AND RACEWAYS SHOWN AS SOLID LINEWORK ON THESE DRAWINGS
ARE NEW CONSTRUCTION.
12. THE EXISTING INSTALLATION SHOWN ON THESE DRAWINGS WAS DEVELOPED FROM VARIOUS
SOURCES, WHICH WERE NOT ALL FIELD VERIFIED AND NOT ALL CONDITIONS ARE SHOWN.
CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS PRIOR TO CONSTRUCTION.
13. CONTRACTOR SHALL DISCONNECT AND REMOVE ALL EQUIPMENT, DEVICES, AND RACEWAYS
DENOTED TO BE DEMOLISHED ON THESE DRAWINGS. LEGALLY DISPOSE OF ALL MATERIALS THAT
THE OWNER DOES NOT WANT.
14. RECONNECT EXISTING TO REMAIN DEVICES WHERE CIRCUITS HAVE BEEN INTERRUPTED BY
DEMOLITION WORK TO MAINTAIN CONTINUITY. PROVIDE NEW CONNECTIONS TO ANOTHER
EXISTING DEVICE OR NEW CIRCUIT BREAKER FROM PANELBOARD. VERIFY CIRCUIT LOADING ON
EXISTING CIRCUITS BEFORE MAKING THESE CONNECTION.
15. WHERE EXISTING DEVICES TO BE REMOVED ARE SHOWN ON THESE DRAWINGS, THE
CONTRACTOR SHALL ALSO REMOVE ALL WIRING, CONDUIT, AND BOXES SERVING THE DEVICES,
UNLESS CONDUIT AND BOXES CAN BE REUSED IN NEW CONSTRUCTION.
16. WHEN A DEVICE IS REMOVED FROM AN EXISTING WALL TO REMAIN, PATCH WALL TO MATCH
EXISTING OR NEW WALL FINISHES.
17. MOUNTING HEIGHTS FOR ALL NEW DEVICES SHALL BE LOCATED TO MATCH EXISTING TO REMAIN
DEVICES, UNLESS OTHERWISE NOTED.
18. WHERE ADDITIONAL CIRCUITS ARE REQUIRED AND EXISTING PANELBOARDS HAVE AVAILABLE
SPACE, PROVIDE NEW CIRCUIT BREAKERS IN EXISTING PANELBOARDS TO MATCH THE AIC
RATINGS AND THE MANUFACTURER OF THE EXISTING BREAKERS.
19. ALL GROUNDING ELECTRODES WITHIN BUILDING OR STRUCTURE SHALL BE BONDED TOGETHER
TO FORM A SINGLE GROUNDING ELECTRODE SYSTEM.
20. ALL SEPARATELY DERIVED SYSTEMS SHALL COMPLY WITH CODE, CEC 250.104, FOR BONDING TO
METAL WATER PIPING AND STRUCTURAL METAL.
21. FURNISH, INSTALL, AND CONNECT A CODE SIZED INSULATED OR BARE COPPER GROUND
CONDUCTOR IN ALL BRANCH CIRCUITS AND FEEDER CONDUITS.
22. WHERE UNGROUNDED CONDUCTORS ARE INCREASED IN SIZE TO ACCOMMODATE VOLTAGE
DROP, THE EQUIPMENT GROUND CONDUCTOR SHALL ALSO BE INCREASED IN SIZE
PROPORTIONATELY, ACCORDING TO THE CIRCULAR MIL AREA OF UNGROUNDED CONDUCTORS.
23. ALL EQUIPMENT CONNECTED BY PERMANENT WIRING METHODS SHALL BE GROUNDED.
24. BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED TO PREVENT VOLTAGE DROP EXCEEDING 3% AT
THE FARTHEST OUTLET OR DEVICE. THE MAXIMUM VOLTAGE DROP ALLOWED ON COMBINED
FEEDERS AND BRANCH CIRCUITS SHALL NOT EXCEED 5% TO THE FARTHEST OUTLET OR DEVICE.
25. ALL CONDUCTORS ON THIS PROJECT SHALL BE COPPER.
26. CONDUCTORS 600VOLT OR LESS RATED SHALL UTILIZE THE AMPACITY OF THE 60-DEGREE C
COLUMN OF CEC TABLE 310.16 FOR CONDUCTOR SIZES #14 AWG THROUGH #1 AWG. FOR
CONDUCTOR SIZES OVER #1 AWG, UTILIZE AMPACITY FROM THE 75-DEGREE C COLUMN OF CEC
TABLE 310.16.
27. MULTIWIRE BRANCH CIRCUITS SHALL ORIGINATE FROM THE SAME PANELBOARD.
28. MULTIWIRE BRANCH CIRCUITS SHALL BE PROVIDED WITH A MEANS TO SIMULTANEOUSLY
DISCONNECT ALL UNGROUNDED CONDUCTORS AT THE POINT WHERE THE BRANCH CIRCUIT
ORIGINATES, I.E. HANDLE TIES OR MULTIPOLE CIRCUIT BREAKERS.
29. ALL MULTIWIRE BRANCH CIRCUITS SHOWN WITH THREE (3) CONSECUTIVE PHASE CONDUCTORS (E.G., 1,3,5 OR 4,6,8), NONE SHARING THE SAME PHASE, SHALL INCLUDE A DEDICATED NEUTRAL CONDUCTOR, THREE (3) HOTS AND ONE (1) NEUTRAL. CIRCUITING OUT OF PHASE ORDER (E.G., 1,5,7 OR 4,6,10) WILL REQUIRE AN ADDITIONAL NEUTRAL CONDUCTOR, TWO (2) HOTS AND ONE (1)
NEUTRAL PLUS ONE (1) HOT AND ONE (1) NEUTRAL.
30. BRANCH CIRCUIT CONDUCTOR HOMERUNS SHALL BE INSTALLED IN CONDUIT. MC TYPE CABLE
SHALL NOT BE USED FOR ANY HOMERUNS ON THIS PROJECT.
FEEDER CONDUCTORS SHALL BE INSTALLED IN CONDUIT, UNLESS OTHERWISE NOTED.
31. PROVIDE FEEDER CONDUCTOR SUPPORT IN VERTICAL RACEWAYS AS REQUIRED BY CODE, CEC 300.19.
32. WHERE MORE THAN THREE UNGROUNDED CONDUCTORS ARE ROUTED WITHIN A RACEWAY, THE
CONTRACTOR SHALL APPLY THE DERATING FACTOR REQUIRED BY CODE.
33. MINIMUM CONDUIT TRADE SIZE FOR INTERIOR APPLICATIONS SHALL BE 0.5”, UNLESS OTHERWISE
NOTED.
34. CONDUIT ROUTING ON DRAWINGS IS ESSENTIALLY DIAGRAMMATIC. CONTRACTOR SHALL LAYOUT
RUNS TO SUIT FIELD CONDITIONS, LIMITING BENDS AND BOXES, AND SHALL COORDINATE
INSTALLATION WITH WORK OF OTHER TRADES.
35. PENETRATIONS OF PIPES, CONDUITS, ETC. IN RATED ASSEMBLIES SHALL BE FIRE-STOPPED. FIRE-
STOPPING SHALL BE AN APPROVED MATERIAL AS PRESCRIBED BY THE STATE FIRE MARSHAL
STANDARDS PROTECTION DETAILS OF THRU-PENETRATIONS THROUGH FIRE RATED PARTITIONS
SHALL BE UL/WH LISTED AND COMPLY WITH CBC, SECTION 714. PROTECTION DETAILS OF
MEMBRANE PENETRATIONS THROUGH FIRE PARTITIONS SHALL COMPLY WITH CBC SECTION
714.4.2. ALL FIRE STOPPING MATERIAL SHALL BE RED IN COLOR.
36. PROVIDE INSULATING BUSHINGS OR INSULATED THROAT CONNECTORS AT BOTH ENDS OF ALL
CONDUIT SLEEVES.
37. ALL JUNCTION AND PULL BOXES SHALL BE SIZED PER CODE TO ACCOMMODATE NUMBER OF
CONDUITS AND/OR CONDUCTORS ROUTED TO AND FROM BOXES.
38. RACEWAYS ROUTED IN EXPOSED CEILING AREAS SHALL BE RUN PARALLEL AND AT RIGHT
ANGLES TO WALLS WITHIN SPACES. MC CABLE IS NOT ALLOWED IN EXPOSED CEILING SPACES.
39. PROVIDE A PULL WIRE/TAPE IN ALL EMPTY CONDUIT RUNS OVER 15’ IN LENGTH.
40. NO PIPING, DUCTWORK, OR EQUIPMENT FOREIGN TO ELECTRICAL EQUIPMENT SHALL BE
ALLOWED WITHIN THE DEDICATED SPACE ABOVE ELECTRICAL EQUIPMENT.
41. REQUIRED ELECTRICAL EQUIPMENT WORKING SPACE DEPTH SHALL NOT BE LESS THAN THAT INDICATED IN CEC TABLE 110.26(A)(1). THE WIDTH OF THE WORKING SPACE IN FRONT OF THE
ELECTRICAL EQUIPMENT SHALL BE THE WIDTH OF THE EQUIPMENT OR 30", WHICHEVER IS
GREATER. THIS REQUIREMENT ALSO APPLIES TO DISCONNECT SWITCHES.
42. FOR EQUIPMENT RATED 1200AMPS OR MORE AND OVER 6.5’ WIDE, CONTAINING OVERCURRENT, SWITCHING, AND CONTROL DEVICES, THERE SHALL BE ONE ENTRANCE TO AND EGRESS FROM
THE REQUIRED WORKING SPACE LOCATED AT EACH END OF THE WORKING SPACE, NOT LESS
THAN 24” WIDE AND 6.5’ HIGH. A SINGLE ENTRANCE TO AND EGRESS FROM THE REQUIRED
WORKING SPACE SHALL BE PERMITTED WHERE EITHER UNOBSTRUCTED EGRESS OR EXTRA
WORKING SPACE IS PROVIDED IN CONFORMANCE WITH THE CEC.
43. FOR EQUIPMENT RATED 800AMPS OR MORE, CONTAINING OVERCURRENT, SWITCHING, AND
CONTROL DEVICES, WHERE THERE IS A PERSONNEL DOOR(S) INTENDED FOR ENTRANCE TO AND
EGRESS FROM THE WORKING SPACE WHICH IS LESS THAN 25’ FROM THE NEAREST EDGE OF THE
WORKING SPACE, THE DOOR(S) SHALL OPEN IN THE DIRECTION OF EGRESS AND BE EQUIPPED
WITH LISTED PANIC HARDWARE.
PROJECT GENERAL NOTES PROJECT GENERAL NOTES (cont.)
44. NO ELECTRICAL EQUIPMENT SHALL BE RELEASED FOR SHIPMENT OR INSTALLED ON-SITE PRIOR
TO ENGINEER’S REVIEW OF THE POWER SYSTEM STUDY AND APPROVED ADJUSTMENTS TO
ELECTRICAL EQUIPMENT SUBMITTALS.
45. CONTRACTOR SHALL PROVIDE ARC FLASH LABELS FOR ALL ELECTRICAL EQUIPMENT WITHIN THE
SCOPE OF THIS PROJECT. THESE LABELS SHALL BE GENERATED BY THE CONTRACTOR FROM
THE POWER SYSTEM STUDY AND SUBMITTED WITH THE POWER SYSTEM STUDY SUBMITTAL FOR
ENGINEER’S REVIEW. THIS INCLUDES ALL FIELD MARKING OF AIC VALUES ON ALL BOARDS PER
THE CEC.
46. PROVIDE ENGRAVED NAMEPLATES FOR ALL ELECTRICAL PANELBOARDS, SWITCHBOARDS,
SWITCHGEAR, TRANSFORMERS, AND DISCONNECT SWITCHES, AS DESCRIBED IN THE
SPECIFICATIONS.
47. CONTRACTOR SHALL ENSURE THAT THE ELECTRICAL EQUIPMENT PROVIDED UNDER THEIR
CONTRACTOR WILL FIT WITHIN THE ELECTRICAL ROOMS AND SPACES PROVIDED IN THE BID
DOCUMENTS, WHETHER PROVIDED BY THE SPECIFIED EQUIPMENT MANUFACTURER OR NOT. NO
ADDITIONAL COMPENSATION WILL BE CONSIDERED IF CONTRACTOR NEEDS TO ADJUST
EQUIPMENT PACKAGE TO OBTAIN REDUCED DIMENSIONS.
48. CONTRACTOR IS RESPONSIBLE FOR SUBMITTING REVISED LAYOUTS OF DISTRIBUTION
EQUIPMENT IN ELECTRICAL ROOMS AND/OR SPACES, FOR APPROVAL BY ENGINEER, IF
PROPOSED INSTALLATION DIFFERS FROM CONSTRUCTION DOCUMENTS. SUBMISSION MUST BE
REVIEWED PRIOR TO RELEASE OF EQUIPMENT ORDER AND PRIOR TO INSTALLATION.
49. WHERE NEW EQUIPMENT IS REPLACING THE EXISTING EQUIPMENT IN THE SAME LOCATION ONLY THE NEW EQUIPMENT IS SHOWN. UTILIZE EXISTING CONDUIT AND BRANCH CIRCUIT CONDUIT &
WIRING. REMOVE EXISTING FEEDER WIRE AND THE EQUIPMENT. INSTALL THE NEW EQUIPMENT
AND RECONNECT EXISTING BRANCH CONDUIT AND WIRE. CONNECT EXISTING FEEDER CONDUIT
AND PULL NEW FEEDER WIRE. IF NEW EQUIPMENT IS TO BE IN A NEW LOCATION, WE HAVE
SHOWN THAT ON THE PLANS AND ELEVATIONS, INCLUDING THE REVISED WORK REQUIRED FOR
THE RELOCATION. CONTRACTOR SHALL SURVEY EACH EQUIPMENT LOCATION AND DETERMINE
NEW EQUIPMENT INSTALLATION REQUIREMENTS PRIOR TO RELEASE OF EQUIPMENT.
50. ALL WORK ASSOCIATED WITH THE NEW AND EXISTING UPS SYSTEMS AND ASSOCIATED
DISTRIBUTION SHALL BE COORDINATED WITH CALVET. ASSUME ALL WORK REQUIRING A POWER
OUTAGE WILL BE PERFORMED OUTSIDE OF NORMAL BUSINESS HOURS ON WEEKENDS OR
HOLIDAYS. NOTE, THE OWNER MAY PERFORM WORK WITHIN THE DATA CENTER DURING THE
OUTAGE REQUIRED TO CONNECT THE NEW UPS EQUIPMENT, WHICH IS WHY IT IS IMPERATIVE TO
CLOSELY COORDINATE ANY OUTAGE.
51. WIRING SPACE IN PANELBOARD'S, DISTRIBUTION BOARDS, SWITCHBOARDS, AND SWITCHGEAR
SHALL BE DEDICATED TO CONDUCTORS TERMINATED IN THAT ENCLOSURE AND SHALL NOT BE
USED AS PULL AND/OR SPLICE BOXES FOR CONDUCTORS THAT TERMINATE IN OTHER
ENCLOSURES.
52. ALL CIRCUIT BREAKERS SERVING THE FIRE ALARM CONTROL PANEL AND FIRE ALARM SYSTEM
COMPONENTS SHALL HAVE LOCKABLE HANDLES AND SHALL BE RED IN COLOR, FOR EASE IN
IDENTIFICATION.
53. PROVIDE PROTECTION FROM PHYSICAL DAMAGE FOR ALL ELECTRICAL EQUIPMENT, LUMINARIES, WIRING DEVICES, ETC., DURING THE CONSTRUCTION OF THE PROJECT.
54. MOUNTING HEIGHTS OF ALL WIRING DEVICES ARE DIMENSIONED TO THE CENTER OF THE DEVICE, UNLESS OTHERWISE NOTED.
55. DURING CONSTRUCTION, PROVIDE TEMPORARY POWER TO EXISTING SYSTEMS AS DESCRIBED IN SPECIFICATION 260090, SECTION 3.05. SYSTEMS INCLUDED, BUT NOT LIMITED TO THE FOLLOWING:
A. SECURITY
B. SERVER ROOM / UPS LOADS / COOLING WITHIN THE SERVER ROOM
C. FREIGHT ELEVATOR
D. PUMPS ( DOMESTIC WATER)
E. FIRE ALARM & FIRE SUPPRESSION
F. EXIT SIGNS & EGRESS LIGHTING
56. EXISTING CONDUIT OR GUTTER RACEWAYS SHALL BE ADJUSTED TO ENTER THE NEW
SWITCHBOARD, PANELS, GUTTERS, ETC. AS REQUIRED TO ACCOMODATE NEW EQUIPMENT.
57. PANEL AND EQUIPMENT SCHEDULES ARE SHOWN FOR NEW EQUIPMENT (EQUIPMENT REPLACING EXISTING). EXISTING TO REMAIN EQUIPMENT IS NOT SCHEDULED AS IT REMAINS AND IS NOT
ALTERED.
58. COORDINATE ALL PROJECT SEQUENCING WITH OWNER OR AS SPECIFIED AND/OR SHOWN ON
THE DRAWINGS.
59. GENERAL CONTRACTOR SHALL FOLLOW REQUIREMENTS FOR FIRE SAFETY DURING
CONSTRUCTION. REFER TO CALIFORNIA FIRE CODE CHAPTER 33.
60. PROVIDE FIRE DEPARTMENT ACCESS AND A SAFE MEANS OF EGRESS THROUGH AND/OR
AROUND THE BUILDING AND SITE PER APPLICABLE CODES AT ALL TIMES DURING THE
CONSTRUCTION PROCESS. MINIMIZE DISRUPTION TO ADJACENT AREAS/FLOORS AS MUCH
AS POSSIBLE.
61. MAINTAIN EGRESS FROM EXISTING OCCUPIED SPACES AND SURROUNDING BUILDING AREAS AS
INDICATEDAND AS REQUIRED BY AUTHORITIES HAVING JURISDICTION.
62. PER CFC 3312.2, REQUIRED MEANS OF EGRESS SHALL BE MAINTAINED DURING CONSTRUCTION
AND DEMOLITION, REMODELING, OR ALTERATIONS TO ANY BUILDING. EXCEPTION: APPROVED
TEMPORARY MEANS OF EGRESS.
63. PROVIDE AND MAINTAIN FIRE EXTINGUISHERS IN AREA OF WORK, IN ACCORDANCE WITH
REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION.
64. PROVIDE TEMPORARY BARRIERS AND ENCLOSURES AS REQUIRED TO PROTECT MATERIALS
AND PEOPLE (REF CFC 3305). PREVENT DUST, FUMES, AND ODORS FROM ENTERING OCCUPIED
AREAS. MAINTAIN AND RELOCATE TEMPORARY BARRIERS AND ENCLOSURES AS REQUIRED BY
THE PROGRESS OF THE WORK. REMOVE TEMPORARY BARRIERS AND ENCLOSURES AT
COMPLETION OF WORK.
65. PRIOR TO STARTING DEMOLITION, VERIFY EXISTING CONDITIONS AND DIMENSIONS. COORDINATE
EXTENT OF DEMOLITION WORK AND EXITING CONSTRUCTION TO REMAIN WITH NEW WORK.
NOTIFY [ENGINEER/DESIGN TEAM] IF CONFLICTS OR DISCREPANCIES.
SEQUENCE OF WORK
THE PROCUREMENT OF THE EQUIPMENT SHALL BEGIN AFTER PROJECT AWARD, WITH SUBMITTALS, APPROVALS, PROCUMENT, ETC. COORDINATE THE SEQUENCING WITH THE
OWNER. SUBMIT PROJECT SCHEDULE FOR APPROVAL UPON AWARD.
THE CIRCUIT TRACING AND DOCUMENTATION (DESCRIBED BELOW) SHALL BE PERFORMED DURING THE PROCUREMENT SEQUENCE.
UPS AND ASSOCIATED EQUIPMENT SHALL BE PROCURED AT THE BEGINNING OF THE PROJECT WITH THE GOAL OF INSTALLATION OCCURRING AS SOON AS POSSIBLE.
THE MAIN CONSTRUCTION SEQUENCE SHALL BEGIN ONCE ALL EQUIPMENT AND MATERIALS ARE DELIVERED. THIS SHALL BE COORDINATED WITH THE OWNER AS THE INTENT IS FOR THE OCCUPANTS TO VACATE THE BUILDING DURING THIS SEQUENCE. AS DENOTED IN THE GENERAL CONDITIONS, THE CONSTRUCTION PORTION OF THIS PROJECT NEEDS TO BE
COMPLETED IN 55 WORKING DAYS OR LESS.
CIRCUIT TRACING SCOPE OF WORK
THE CONTRACTOR IS RESPONSIBLE FOR CIRCUIT TRACING WITH THE INTENT THAT AN AS-BUILT REVIT MODEL AND AUTOCAD FILES WILL BE PROVIDED AT THE CONCLUSION OF THE
PROJECT. THIS SHALL ENTAIL, BUT NOT BE LIMITED TO:
A. DOCUMENTING LOCATIONS OF ALL DEVICES THAT ARE POWERED IN A REVIT MODEL. A COPY OF THE MODEL WITH THE FLOOR PLANS WILL BE FURNISHED BY THE ENGINEER.
THE MODEL FROM THE ENGINEER WILL NOT BE POPULATEED WITH DEVICES, MECHANICAL/PLUMBING EQUIPMENT, LIGHTING FIXTURES, SWITCHES, ETC. VERIFY ALL POWERED ITEMS IN THE MODEL AS WELL AS ALL POWERED ITEMS NOT SHOWN IN THE MODEL, INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING:
•RECEPTACLES – FLOOR RECEPTACLES AND WHIPS ONLY IF VISIBLE, NOT COVERED BY CARPET
•LIGHTING FIXTURES/TIMERS, INCLUDING EXTERIOR FIXTURES
•SWITCHES – (LIGHT SWITCHES, SWITCHES CONTROLLING DEVICES SUCH AS GARBAGE DISPOSALS/PROJECTION SCREENS, ETC)
•FIRE SMOKE DAMPERS
•DRINKING FOUNTAINS
•EMERGENCY POWER SYSTEM
•EXIT/EGRESS LIGHTS
•SECURITY/ACCESS SYSTEM EQUIPMENT
•BACK-UP GENERATOR LOADS
•MECH & PLUMBING EQUIP, “INCLUDING BUT NOT LIMITED TO”:
•FIRE ALARM SYSTEM EQUIPMENT
•MIXING BOXES
•HVAC SYSTEM AND COMPONENTS
•EXHAUST FANS
•BOOSTER PUMPS
•ELEVATORS
•GARAGE DOOR
•POWERED DOORS (EXAMPLE, ADA FRONT DOORS)
•HEAT EXCHANGER
B. TRACE AND IDENTIFY ALL CIRCUITS FOR DEVICES AND EQUIPMENT. DOCUMENT CIRCUITS AT THE DEVICES AND EQUIPMENT WITHIN THE REVIT MODEL.
C. PROVIDE PDF FOR REVIEW AND UPDATE THE MODEL PER COMMENTS FROM THE ENGINEER AND OWNER. REVIEW DOCUMENTS SHALL ALSO INCLUDE PANEL SCHEDULES.
D. PROVIDE LABELS AND NAMEPLATES FOR ALL EXISTING AND NEW DEVICES AND EQUIPMENT AND ADHERE TO DEVICE COVERS, DISCONNECTS, ETC PER SPECIFICATIONS.
E. PROVIDE JUNCTION BOX IDENTIFICATION WITH CIRCUITS.
F. PROVIDE UPDATED PANELS DIRECTORIES COMPLIANT WITH CEC ARTICLE 408.4 AND PLACE IN EACH PANELBOARD.
G. PROVIDE PDF, AUTOCAD FILES AND REVIT MODEL TO ENGINEER AND OWNER AS RECORD DOCUMENT.
NOTES:
1. THE CIRCUIT TRACING WORK WITHIN THE BUILDING SHALL BE CONDUCTED DURING NON WORK HOURS. IT SHALL BEGIN UPON AWARD AND BE
COMPLETED AS NOTED IN DIVISION 00 & 01.
2. REFER TO SPECIFICATION SECTION 26 05 53 FOR ADDITIONAL LABELING AND IDENTIFICATION INFORMATION.
3. CONTRACTOR TO COORDINATE BUILDING ACCESS TO PERFORM CIRCUIT TRACING SCOPE OF WORK WITH CALVET.
R
ELECTRICAL
E E
NI
GN
E
LANOISSEFORP
DERET
SI
G
E R
C A L I F ORN
I A
S T A T E
O F
707 Third Street, Suite 4-105
Architecture & Engineering Sections
Project Management & Development Branch Real Estate Services Division
State of California
West Sacramento, California 95605
Department of General Services
CONSULTING ENGINEERS
ALAMEDA | AUBURN | LOS ANGELES
https://www.engent.com
NEOSHO | SAN DIEGO | SANTA BARBARA
JJ
AS NOTED
V1
C o p y ri g h t
C a lif o rn ia D e p a rt m e n t o f G e n e ra l S e rv ic e s
R e a l E s ta te S e rv ic e s D iv is io n
PROFESSIONAL
STAMP
0 1 2 3
Issue
DateNo. Description
Project
DSA App No.
Supervisor
Sheet Title
Designed
Sheet Number
Sheet Scale
Reference North
Project Number
Drawn
OSFM Permit No. 25-N-3911-C
12533
SWSW
1227 O STREET
SACRAMENTO, CA 95814
#E015491 Exp. 06/30/27
SCOTT WHEELER
PERMIT APPLICATION NO.
25-N-3911-C
FEEDER
SCHEDULE,
NOTES, & TABLES
E002
CalVet Electrical Upgrades
FEEDER SCHEDULE
FEEDER SCHEDULE GENERAL NOTES
1. COPPER FEEDER SIZES SHOWN IN THIS SCHEDULE ARE BASED ON CONDUCTORS WITH THHN/THWN-2 INSULATION IN EMT CONDUIT.
2. FEEDER SIZES SHOWN IN THIS SCHEDULE ARE BASED ON AN AMBIENT TEMPERATURE OF 30 DEGREES C (86 DEGREES F).
3. FEEDERS CONSISTING OF MULTIPLE SETS OF CONDUCTORS AND CONDUITS ARE TO BE PROVIDED WITH THE INDICATED SIZE GROUND CONDUCTOR
IN EACH CONDUIT.
4. PER CEC ARTICLE 110.14, ALL FEEDERS SIZED AT #2 AWG OR LESS ARE CALCULATED PER 60 DEGREE TABLE. FEEDERS GREATER THAN #2 AWG
ARE RATED 75 DEGREE. 90 DEGREE COLUMN IS USED WHEN APPLYING DERATING FACTORS.
FEEDER SCHEDULE REMARKS
A. OVERSIZED 150% NEUTRAL, SUITABLE FOR SERVICE FROM K-13 RATED TRANSFORMERS.
B. FEEDER APPROVED FOR USE WITH SEPARATELY DERIVED SYSTEM; GROUNDING AS REQUIRED BY CEC ARTICLES 240 AND 250.
C. FEEDER GROUND AND BONDING JUMPER SHALL HAVE AN AREA NOT LESS THAN 12.5% OF THE AREA OF THE LARGEST PHASE CONDUCTOR.
D. INCREASE CONDUIT TO THE NEXT LARGER TRADE SIZE WHEN USING SCHEDULE 40 OR 80 PVC CONDUIT.
E. PER CEC SECTION 240.4(B), FOR OVERCURRENT DEVICES RATED 800A OR LESS, THE NEXT HIGHER STANDARD OVERCURRENT DEVICE RATING (ABOVE THE
AMPACITY OF THE CONDUCTORS) CAN BE USED. RULE CAN NOT BE APPLIED IF 100% RATED BREAKERS ARE USED.
F. PER CEC 240.21(C), THE PROVISIONS OF 240.4(B) SHALL NOT BE PERMITTED FOR TRANSFORMER SECONDARY CONDUCTORS.
G. USE EXTRA-FLEXIBLE CONDUCTORS (CLASS I OR K STRANDING) WITH TERMINATIONS RATED FOR THE EXTRA-FLEXIBLE
CONDUCTORS.
FEEDER
TAG
FEEDER
DESCRIPTION
CONDUIT
FEEDER CONDUCTORS
SEPARATELY DERIVED
SYSTEM
REMARKS
PHASE/NEUTRAL GROUND
GROUNDING
ELECTRODE
SYSTEM
BONDING
JUMPER
604 55 AMP, 4 WIRE SEE E301
SHEET
4 #6 CU 1 #10 CU
- - E
704 70 AMP, 4 WIRE SEE E301
SHEET
4 #4 CU 1 #8 CU
1003 95 AMP, 3 WIRE SEE E301
SHEET
3 #2 CU 1 #8 CU
- - E
1004 95 AMP, 4 WIRE SEE E301
SHEET
4 #2 CU 1 #8 CU
- - D,E
1254 130 AMP, 4 WIRE SEE E301
SHEET
4 #1 CU 1 #6 CU
T1504 150 AMP, 4 WIRE SEE E301
SHEET
4 #1/0 CU 1 #6 CU
#6 CU IN 0.75" C. #6 CU B,F
1753 175 AMP, 3 WIRE SEE E301
SHEET
3 #2/0 CU 1 #6 CU
1754 175 AMP, 4 WIRE SEE E301
SHEET
4 #2/0 CU 1 #6 CU
2003 200 AMP, 3 WIRE SEE E301
SHEET
3 #3/0 CU 1 #6 CU
2004 200 AMP, 4 WIRE 1-2.00" 4 #3/0 CU 1 #6 CU - - -
2253 230 AMP, 3 WIRE SEE E301
SHEET
3 #4/0 CU 1 #4 CU
2254 230 AMP, 4 WIRE SEE E301
SHEET
4 #4/0 CU 1 #4 CU
2504 255 AMP, 4 WIRE SEE E301
SHEET
4 #250 KCMIL CU 1 #4 CU
T2504 255 AMP, 4 WIRE SEE E301
SHEET
4 #250 KCMIL CU 1 #2 CU
#2 CU IN 0.75" C. #2 CU B,F
4003 380 AMP, 3 WIRE SEE E301
SHEET
3 #500 KCMIL CU 1 #2 CU
- - D,E
4004 380 AMP, 4 WIRE SEE E301
SHEET
4 #500 KCMIL CU 1 #2 CU
- - D,E
T4004 400 AMP, 4 WIRE SEE E301
SHEET
2 SETS OF 4 #3/0 CU 1 #1/0 CU/SET
#1/0 CU IN 0.75" C, #1/0 CU B,F
6003 600 AMP, 3 WIRE SEE E301
SHEET
2 SETS OF 3 #400 KCMIL CU 1 #1 CU
- - D
16004 1680 AMP, 4 WIRE 4-3.50" 4 SETS OF 4 #600 KCMIL CU 1 #4/0 CU/SET - - D,G
1 2025/03/02 SFM RESUBMITTAL
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
4/21/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3911
2026-06-30
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
7/2/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
R
ELECTRICAL
E E
NI
GN
E
LANOISSEFORP
DERET
SI
G
E R
C A L I F ORN
I A
S T A T E
O F
707 Third Street, Suite 4-105
Architecture & Engineering Sections
Project Management & Development Branch Real Estate Services Division
State of California
West Sacramento, California 95605
Department of General Services
CONSULTING ENGINEERS
ALAMEDA | AUBURN | LOS ANGELES
https://www.engent.com
NEOSHO | SAN DIEGO | SANTA BARBARA
JJ
AS NOTED
V1
C o p y ri g h t
C a lif o rn ia D e p a rt m e n t o f G e n e ra l S e rv ic e s
R e a l E s ta te S e rv ic e s D iv is io n
PROFESSIONAL
STAMP
0 1 2 3
Issue
DateNo. Description
Project
DSA App No.
Supervisor
Sheet Title
Designed
Sheet Number
Sheet Scale
Reference North
Project Number
Drawn
OSFM Permit No. 25-N-3911-C
12533
SWSW
1227 O STREET
SACRAMENTO, CA 95814
#E015491 Exp. 06/30/27
SCOTT WHEELER
PERMIT APPLICATION NO.
25-N-3911-C
TITLE 24
E003
CalVet Electrical Upgrades
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
4/21/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-3911
2026-06-30
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
7/2/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
1A 1B
1P
1LA 1LB
R
ELECTRICAL
E E
NI
GN
E
LANOISSEFORP
DERET
SI
G
E R
C A L I F ORN
I A
S T A T E
O F
707 Third Street, Suite 4-105
Architecture & Engineering Sections
Project Management & Development Branch Real Estate Services Division
State of California
West Sacramento, California 95605
Department of General Services
CONSULTING ENGINEERS
ALAMEDA | AUBURN | LOS ANGELES
https://www.engent.com
NEOSHO | SAN DIEGO | SANTA BARBARA
JJ
AS NOTED
V1
C o p y ri g h t
C a lif o rn ia D e p a rt m e n t o f G e n e ra l S e rv ic e s
R e a l E s ta te S e rv ic e s D iv is io n
PROFESSIONAL
STAMP
0 1 2 3
Issue
DateNo. Description
Project
DSA App No.
Supervisor
Sheet Title
Designed
Sheet Number
Sheet Scale
Reference North
Project Number
Drawn
OSFM Permit No. 25-N-3911-C
12533
SWSW
1227 O STREET
SACRAMENTO, CA 95814
#E015491 Exp. 06/30/27
SCOTT WHEELER
PERMIT APPLICATION NO.
25-N-3911-C
SCHEDULES -
PANELBOARDS -
1ST FLOOR
E005
CalVet Electrical Upgrades
{1} CONNECT EXISTING NITE LITES TO EXISTING CIRCUIT.
Notes:
Code Demand Amps: 0 A
Code Demand Load: 0 kVA
Connected Amps: 0 A
Connected Load: 0.00 kVA
Load Classification Conn. Load Demand Factor Code Demand Panel Totals
0 A 0 A 0 A
0 kVA 0 kVA 0 kVA
0 kVA 0 kVA 0 kVA
-- (N) SPARE 20 A 1 11 0.00 0.00 12 1 20 A (N) SPARE --
-- (N) SPARE 20 A 1 9 0.00 0.00 10 1 20 A (N) SPARE --
-- {1} (E) LTG FRONT STAIRS 20 A 1 7 0.00 0.00 8 1 20 A (E) LOAD --
-- (E) LOAD 20 A 1 5 0.00 0.00 6 1 20 A (E) LTG REAR STAIRS --
-- (E) LTG S.E. 20 A 1 3 0.00 0.00 4 1 20 A (E) LTG HALL --
-- (E) LTG N.E. 20 A 1 1 0.00 0.00 2 1 20 A (E) LTG REST RMS --
LC Load Served Amp P # A (kVA) B (kVA) C (kVA) # P Amp Load Served LC
Mounting: SURFACE Volts: 277/480 Wires 4 Main Type: MCB Main Rating: 50 A
Location: LEVEL 1 EAST ELEC. CLOSET Served From MDB Phases 3 A.I.C. Rating: 65KAIC Bus Rating 50 A
Branch Panel: PANEL 1A
{1} CONNECT EXISTING EXIT LTS TO EXISTING CIRCUIT
Notes:
Code Demand Amps: 0 A
Code Demand Load: 0 kVA
Connected Amps: 0 A
Connected Load: 0.00 kVA
Load Classification Conn. Load Demand Factor Code Demand Panel Totals
0 A 0 A 0 A
0 kVA 0 kVA 0 kVA
0 kVA 0 kVA 0 kVA
-- (N) SPARE 20 A 1 11 0.00 0.00 12 1 20 A (N) SPARE --
-- (N) SPARE 20 A 1 9 0.00 0.00 10 1 20 A (N) SPARE --
-- {1} (E) LOAD 20 A 1 7 0.00 0.00 8 1 20 A (E) LOAD --
-- (E) LTG GARAGE 20 A 1 5 0.00 0.00 6 1 20 A (E) LTG AVDT. --
-- (E) LTG WEST 20 A 1 3 0.00 0.00 4 1 20 A (E) LTG HALL --
-- (E) LTG SOUTH 20 A 1 1 0.00 0.00 2 1 20 A (E) LTG EXCERCISE RM. --
LC Load Served Amp P # A (kVA) B (kVA) C (kVA) # P Amp Load Served LC
Mounting: SURFACE Volts: 277/480 Wires 4 Main Type: MCB Main Rating: 50 A
Location: L1 WEST ELEC. CLOSET 115 Served From MDB Phases 3 A.I.C. Rating: 65KAIC Bus Rating 50 A
Branch Panel: PANEL 1B
{1} SEE PROJECT GENERAL SHEET NOTE 52 ON SHEET E002.
Notes:
Code Demand Amps: 0 A
Code Demand Load: 0 kVA
Connected Amps: 0 A
Connected Load: 0.00 kVA
Load Classification Conn. Load Demand Factor Code Demand Panel Totals
0 A 0 A 0 A
0 kVA 0 kVA 0 kVA
0 kVA 0 kVA 0 kVA
-- (N) SPARE 20 A 1 53 0.00 0.00 54 1 20 A (N) SPARE --
-- (N) SPARE 20 A 1 51 0.00 0.00 52 1 20 A (N) SPARE --
-- (N) SPARE 20 A 1 49 0.00 0.00 50 1 20 A (N) SPARE --
47 0.00 -- 48 1 -- space --
45 0.00 0.00 46 1 20 A (E) SPARE ---- (E) MAIN 100 A 3
43 0.00 0.00 44 1 20 A (E) SPARE --
-- (E) LOBBY TRACK LITES 20 A 1 41 0.00 0.00 42
-- (E) LOBBY TRACK LITES 20 A 1 39 0.00 0.00 40
-- (E) LOBBY TRACK LITES 20 A 1 37 0.00 0.00 38
3 20 A (E) GARAGE DOOR OPENER --
-- (E) LOBBY TRACK LITES 20 A 1 35 0.00 0.00 36 1 20 A (E) RECEPT. EXISTING --
-- (E) LOBBY TRACK LITES 20 A 1 33 0.00 0.00 34 1 20 A (E) RECEPT. EXISTING --
-- (E) DRINK. FOUNTAIN &... 30 A 1 31 0.00 0.00 32 1 20 A (E) RECEPT. EXISTING --
-- (E) FURNITURE PARTITIONS 20 A 1 29 0.00 0.00 30 1 20 A (E) RECEPT. EXISTING --
-- (E) FURNITURE PARTITIONS 20 A 1 27 0.00 0.00 28 1 20 A (E) HVAC TRANS. RECEPT. EAST --
-- (E) FURNITURE PARTITIONS 20 A 1 25 0.00 0.00 26 1 20 A (E) LOAD --
-- (E) FURNITURE…