This document comprises technical drawings and specifications for the CalVet Headquarters Electrical Upgrades project, a capital improvement project administered by the California Department of General Services (DGS) Real Estate Services Division for the California Department of Veterans Affairs. The project involves comprehensive electrical system replacements and upgrades within a seven-story (six with penthouse) existing building located at 1227 O Street, Sacramento, California. The scope of work includes disconnecting and replacing existing switchgear, switchboards, distribution panelboards, transformers, disconnect switches, and busway systems throughout the facility, with selective feeder replacements and busway replacement from the SMUD vault to the main electrical room. The project encompasses approximately 800 square feet of work area (500 square feet on the first floor and 50 square feet on each upper floor) within a 140,000-square-foot existing building. A temporary power system must be installed prior to service disconnection to maintain continuous power to critical systems including security, server room with HVAC and UPS loads, freight elevator, domestic water pumps, fire alarm and suppression systems, and emergency egress lighting. Sealed bids are due October 7, 2026, at 2:00 PM, with construction expected to be completed in 55 working days or less following award. The project requires all tenants to vacate the building during the main construction sequence.

The contractor must possess an A or B Certificate of Reported Compliance to bid and shall be responsible for circuit tracing documentation, including development of an as-built Revit model and AutoCAD files identifying all powered devices, fixtures, equipment, and systems throughout the building. The work must comply with 2022 California Building Code, California Electrical Code, California Fire Code, and California Energy Code standards, with the Office of the State Fire Marshal having jurisdiction over fire and panic requirements. A site safety plan establishing a fire prevention program must be submitted to and approved by the OSFM Field Deputy prior to building permit issuance. The contractor shall coordinate all work with the California Department of Veterans Affairs, including sequencing that minimizes disruption to adjacent areas and maintains required egress pathways. All materials must be new, UL or ETL listed, and copper conductors shall be utilized throughout. The project includes substantial temporary barriers, fire extinguishers, and dust control measures to protect occupied building areas during construction activities.

View the file

Other files

File Type Posted
12533_-_Project_Manual_Book_II.pdf PDF
12533_-_Project_Manual_Book_I.pdf PDF
12533_-_Bid_Package_Documents.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

th S tr ee t th S tr ee t

Richards Blvd

J Street

L Street

N Street

P StreetQ Street

9t h S tr ee t th S tr ee t th S tr ee t th S tr ee t st S tr ee t

Capitol Ave

Broadway

R iv er si de

B lv d

Stockton Blvd

Folsom Blvd

La nd

P ar k D r

A lh am br a B lv d

Railroad

Railroad

STATE

CAPITOL

PROJECT SITE

Sa cr am en to

R iv er

American River SACRAMENTO, CA

O St

OCCUPANCY:

B (BUSINESS)

MIXED OCCUPANCY:

NO

PROJECT NAME: CALVET HQ ELECTRICAL UPGRADES

PROJECT FLOOR AREA:

FIRST FLOOR: APPROX 500 SF

UPPER FLOORS: APPROX 50 SF EACH

TOTAL PROJECT AREA: APPROX 800 SF

EXISTING BUILDING STORIES:

7 (6 WITH PENTHOUSE)

PROJECT ADDRESS:

CALIFORNIA DEPARTMENT OF VETERANS AFFAIRS

1227 O STREET

SACRAMENTO, CA 95814

PROPOSED USE:

UNCHANGED

DGS PROJECT #:

000000000012533

TYPE OF CONSTRUCTION:

TYPE I-A (1-HOUR) [ASSUMED BASED ON AS-BUILT DOCS]

COMPLETE STEEL FRAME WITH CONCRETE SHEAR WALLS

ALLOWABLE AREA:

UNLIMITED

FIRE ALARM:

OTHER PROTECTION:

NO

SMOKE CONTROL:

NO

HFH SEVERITY ZONE:

NO

SEISMIC JOINTS:

NO

YEAR CONSTRUCTED:

ER RADIO COVERAGE:

NO

AREA INCREASE: N/A

YES, MANUAL & AUTOMATIC

EXISTING BUILDING AREA:

140,000 SF (UNCHANGED)

HEIGHT INCREASE:

N/A

EXISTING BUILDING HEIGHT:

108'-3" TOP OF N.STAIR TOWER (UNCHANGED)

OCCUPANT LOAD:

400 APPROXIMATELY PER FLOOR, 2,400 TOTAL FOR BUILDING (UNCHANGED)

REQUIRED FIRE SEPARATION:

(UNCHANGED)

FIRE SPRINKLERS:

YES, WET, 1ST FLOOR GARAGE ONLY

FIRE PROTECTION:

STANDPIPES IN STAIRWELLS & HOSE CABINETS THROUGHOUT;

CORRIDORS ON ALL FLOORS

OWNER: CA DEPT OF GENERAL SERVICES, RESD-PMDB

CONTACT: TOM SCHANBERGER

ELECTRICAL: THE ENGINEERING ENTERPRISE

CONTACT: SCOTT WHEELER

PHONE: 916.376.1687

tom.schanberger@dgs.ca.gov

CONTACT INFORMATION

PHONE: 530.886.8556

scott@engent.com

STRUCTURAL: BUEHLER ENGINEERING

CONTACT: WILLIAM RADER

PHONE: 916.443.0303.255

brader@buehlerengineering.com

ARCHITECT: HGA

CONTACT: BETH YOUNG

PHONE: 916.787.5145

BYoung@hga.com

2022 CALIFORNIA MECHANICAL CODE (CMC):

PART 4, TITLE 24, CCR; BASED ON THE 2021 UNIFORM MECHANICAL CODE (UMC)

2022 CALIFORNIA ELECTRICAL CODE (CEC):

PART 3, TITLE 24, CCR; BASED ON THE 2020 NATIONAL ELECTRICAL CODE (NEC)

2022 CALIFORNIA BUILDING CODE (CBC):

PART 2, TITLE 24, CCR; BASED ON THE 2021 INTERNATIONAL BUILDING CODE (IBC)

2022 CALIFORNIA ADMINISTRATIVE CODE (CAC)

PART 1, TITLE 24, CALIFORNIA CODE OF REGULATIONS (CCR)

AUTHORITY HAVING JURISDICTION:

OFFICE OF THE STATE FIRE MARSHAL (OSFM) FIRE & PANIC ONLY

DIVISION OF THE STATE ARCHITECT (DSA) ACCESS-ONLY

2022 CALIFORNIA FIRE CODE (CFC):

PART 9, TITLE 24, CCR, BASED ON THE 2021 INTERNATIONAL FIRE CODE (IFC)

ENERGY CODE:

2022 CALIFORNIA ENERGY CODE - PART 6, TITLE 24, CCR

ACCESSIBILITY CODE:

PROJECT EXEMPTED FROM DSA REVIEW [CBC 11B-202.4, EXCEPTION 7]

CODE INFORMATION

COUNTY OF:

SACRAMENTO

SPEC SECTION NUMBER ITEM

DEFERRED SUBMITTALS

N/A NONE.

Site Safety Plan per CFC Chapter 33

The owner's authorized agent shall be responsible for the development, implementation and maintenance of an approved, written site safety plan establishing a fire prevention program at the project site applicable throughout all phases of the construction, repair, alteration or demolition work. the plan shall address the requirements of this chapter and other applicable portions of this code, the duties of staff and staff training requirements.The site safety plan shall include items listed in CFC 3303.1.1 as applicable and shall be submitted to and approved by the OSFM Field Deputy prior to issuance of the building permit and before any construction activities begin. Any changes to plan shall also be submitted for approval.

This project will be publicly bid; the selected Contractor awarded the project shall be responsible for coordination with DGS and Cal Vet to develop a Site Safety Plan as required for construction.

NOTE: An impairment plan is required in addition to the site safety plan. All tenants shall be vacated during construction work.

R

ELECTRICAL

E E

NI

GNE

LANOISSEFORP

DERET

SI

G

E R

C A L I F ORN

I A

S T A T E

O F

707 Third Street, Suite 4-105

Architecture & Engineering Sections

Project Management & Development Branch Real Estate Services Division

State of California

West Sacramento, California 95605

Department of General Services

CONSULTING ENGINEERS

ALAMEDA | AUBURN | LOS ANGELES

https://www.engent.com

NEOSHO | SAN DIEGO | SANTA BARBARA

JJ

AS NOTED

V1

C o p y ri g h t

C a lif o rn ia D e p a rt m e n t o f G e n e ra l S e rv ic e s

R e a l E s ta te S e rv ic e s D iv is io n

PROFESSIONAL

STAMP

0 1 2 3

Issue

DateNo. Description

Project

DSA App No.

Supervisor

Sheet Title

Designed

Sheet Number

Sheet Scale

Reference North

Project Number

Drawn

OSFM Permit No. 25-N-3911-C

12533

SWSW

1227 O STREET

SACRAMENTO, CA 95814

#E015491 Exp. 06/30/27

SCOTT WHEELER

PROJECT NUMBER: 12533

1227 O STREET

CALVET

SACRAMENTO, CA 95814

PROJECT TEAM

PROJECT MANAGER: TOM SCHANBERGER

STRUCTURAL:

ELECTRICAL:

WILLIAM RADER

SCOTT WHEELER

PROJECT SCOPE

SHEET INDEXAPPLICABLE CODES

LOCATION MAP

PROJECT INFORMATION

CALIFORNIA VETERANS HEADQUARTERS ELECTRICAL UPGRADE

ARCHITECT: BETH YOUNG

OVERALL SITE PLAN

PERMIT APPLICATION NUMBER: 25-N-3911-C

PERMIT APPLICATION NO.

25-N-3911-C

GENERAL

G001

CalVet Electrical Upgrades

SHEET NO. SHEET NAME

G001 GENERAL

E001 SYMBOLS AND ABBREVIATIONS

E002 FEEDER SCHEDULE, NOTES, & TABLES

E003 TITLE 24

E004 NOT USED

E005 SCHEDULES - PANELBOARDS - 1ST FLOOR

E006 SCHEDULES - PANELBOARDS - 2ND FLOOR

E007 SCHEDULES - PANELBOARDS - 3RD FLOOR

E008 SCHEDULES - PANELBOARDS - 4TH FLOOR

E009 SCHEDULES - PANELBOARDS - 5TH FLOOR

E010 SCHEDULES - PANELBOARDS - 6TH FLOOR

E011 SCHEDULES - PANELBOARDS - ROOF/PENTHOUSE

E100 SITE & FIRE ACCESS

E101 ELECTRICAL POWER PLAN - 1ST FLOOR

E102 ELECTRICAL POWER PLAN - 2ND FLOOR

E103 ELECTRICAL POWER PLAN - 3RD FLOOR

E104 ELECTRICAL POWER PLAN - 4TH FLOOR

E105 ELECTRICAL POWER PLAN - 5TH FLOOR

E106 ELECTRICAL POWER PLAN - 6TH FLOOR

E107 ELECTRICAL POWER PLAN - ROOF/PENTHOUSE

E200 ENLARGED PLANS - SMUD VAULT

E201 ENLARGED PLANS - MAIN ELECTRICAL ROOM

E202 ENLARGED PLANS -1ST FLOOR EAST ELECTRICAL CLOSET

E203 ENLARGED PLANS - 1st FLOOR WEST ELECTRICAL CLOSET

E204 ENLARGED PLANS - 2ND FLOOR EAST ELECTRICAL CLOSET

E205 ENLARGED PLANS - 2ND FLOOR WEST ELECTRICAL CLOSET

E206 ENLARGED PLANS - 3RD FLOOR EAST ELECTRICAL CLOSET/ROOM

E207 ENLARGED PLANS - 3RD FLOOR WEST ELECTRICAL CLOSET

E208 ENLARGED PLANS - 4th FLOOR EAST ELECTRICAL CLOSET/ROOM

E209 ENLARGED PLANS - 4th FLOOR WEST ELECTRICAL CLOSET/ROOM

E210 ENLARGED PLANS - 5th FLOOR EAST ELECTRICAL CLOSET & SPACES

E211 ENLARGED PLANS - 5th FLOOR WEST ELECTRICAL CLOSET & SPACES

E212 ENLARGED PLANS - 6th FLOOR EAST ELECTRICAL CLOSET/ROOM

E213 ENLARGED PLANS - 6th FLOOR WEST ELECTRICAL CLOSET/ROOM

E214 ENLARGED PLANS - ROOF/PENTHOUSE PANELS

E300 ELECTRICAL SINGLE-LINE DIAGRAM - EXISTING

E301 ELECTRICAL SINGLE-LINE DIAGRAM - NEW

E400 DETAILS - GROUNDING AND BONDING

E401 DETAILS - CABLE TRAY AND BUS DUCT ANCHORAGE

E402 DETAILS - ELECTRICAL EQUIPMENT ANCHORAGE

E403 DETAILS - WALL PENETRATIONS

A. RISK CATEGORY – II

B. SEISMIC DESIGN CATEGORY – D

C. SEISMIC SITE CLASS – D

D. SEISMIC IMPORTANCE FACTOR – 1.00

E. SEISMIC COEFFICIENTS – SDS = 0.510, SD1 = 0.530

SEISMIC PARAMETERS

A. CONCRETE (UP TO 15% FLYASH SUBSTITUTION FOR

PORTLAND CEMENT)

1. FOUNDATIONS AND WALLS – 3,000 PSI, 145PCF

NORMAL WEIGHT, W/C RATIO = .58

2. SLAB ON GRADE AND CURBS – 3,500 PSI, 145PCF

NORMAL WEIGHT, W/C RATIO = .45

3. CONCRETE FLATWORK AND PAVING – 2,500 PSI,

145PCF NORMAL WEIGHT

B. CONCRETE REINFORCING:

1. ASTM A615 GRADE 60

2. ASTM A706 GRADE 60 AT WELDED BARS

C. ANGLES, CHANNELS, PLATES, ETC.:

1. ASTM A36 (36 KSI)

2. ASTM A572 GRADE 50 (50 KSI)

D. LIGHT GAGE METAL INCLUDING STUDS, ANGLES, ETC.

1. ASTM A653 (33 KSI OR 50 KSI)

E. POST INSTALLED ANCHORS

1. HILTI KB-TZ2

STRUCTURAL MATERIALS

PROJECT SCOPE INCLUDES, BUT IS NOT LIMITED TO, INTERIOR WORK WITHIN PORTIONS OF AN EXISTING BUILDING:

- ELECTRICAL UPGRADES INCLUDE DISCONNECTING AND REPLACEMENT OF EXISTING SWITCHGEAR, SWITCHBOARDS, DISTRIBUTION PANELBOARDS, TRANSFORMERS, PANELBOARDS, DISCONNECT SWITCHES, BUSWAY, AND SELECTIVE FEEDERS THROUGHOUT, AND REPLACEMENT OF BUSWAY FROM SMUD VAULT TO MAIN ELECTRICAL ROOM. MUCH OF THE CONDUIT SHALL BE REUSED. WHERE IT IS KNOWN THAT CONDUITS NEED TO BE REROUTED OR ADJUSTED WE HAVE DENOTED. ASSUME ALL ELECTRICAL EQUIPMENT IS TO BE REPLACED

UNLESSDENOTED AS EXISTING TO REMAIN.

- INSTALLATION OF ALL NEW EQUIPMENT, INCLUDING ANCHORAGE AS REQUIRED.

- CIRCUIT TRACING AND DEVELOPMENT OF RECORD DOCUMENTS AS DESCRIBED ON E002.

- UPS IS TO BE REPLACED AS SHOWN ON E212. THE UPS IS REPLACING AN EXISTING UNIT AND IS

SERVING JUST IT LOADS. THIS IS NOT AN EMERGENCY SOURCE. THE VALVE-REGULATED LEAD- ACID (VRLA) BATTERY ENERGY CAPACITY IS BELOW THE 70 KWH CALIFORNIA FIRE CODE (CFC)

SECTION 1207.1.1 THRESHOLD FOR SPECIAL OCCUPANCY.

TEMP POWER IS REQUIRED PRIOR TO DISCONNECTING SERVICE TO THE FACILITY FOR THE FOLLOWING SYSTEM. THE TEMPORARY POWER SHALL PROVIDE POWER WITH NO INTERRUPTION OF SERVICE TO ASSURE THE

EMERGENCY LOADS ARE ALWAYS ACTIVE.

- SECURITY

- SERVER ROOM / INCLUDING HVAC AND UPS LOADS

- FREIGHT ELEVATOR

- PUMPS (DOMESTIC WATER)

- FIRE ALARM & FIRE SUPRESSION

- EXIT SIGNS AND EGRESS LIGHTING

FOLLOW THE APPROVED SEQUENCING PLAN AS DESCRIBED IN CONTRACT DOCUMENTS.

*EXEMPT FROM ACCESSIBLE PATH OF TRAVEL REQUIREMENTS PER CBC 11B-202.4, EXCEPTION 7.

CONTRACTOR TO CONFIRM NO EGRESS ROUTES ARE OBSTRUCTED OR OCCUPANCY SAFETY IS

COMPROMISED BY ELECTRICAL WORK OR PROTECTION BARRIERS.

Per CBC Table 601: for Type I-A construction, primary structural frame has 3-hour protection and floor construction requires 2-hour protection.

Any penetrations in floor/deck assemblies must be fire-stopped to maintain or restore the required 2-hour rating.

Information on existing wall ratings is limited; field investigation is required to identify any rated wall assembly locations that may be impacted by the scope of work. All penetrations through rated walls must be fire-stopped to maintain or restore the existing assembly continuity.

PER ORIGINAL AS-BUILT DRAWINGS:

(E) STEEL COLUMNS NOT ENCASED IN CONCRETE HAVE 3-HOUR FIREPROOFING WITH PUTTY

COAT FINISH ON 1 3/8" LIGHTWEIGHT AGGREGATE PLASTER AND SELF-FURRING METAL LATH.

(E) 2-HOUR WALLS ARE 1" PLASTER & LATH BOTH SIDES OF 4" METAL STUDS AT 16" OC.

(E) GYP BOARD WALLS ARE NON-RATED WITH 3 5/8" METAL NAILING STUDS (M.N.S.) AT 24" OC.

NOTE: NOT TO SCALE

CONTRACTOR STAGING / LAY DOWN AREA

PROJECT LOCATION

1 2025/03/02 SFM RESUBMITTAL

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

4/21/2026

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-3911

2026-06-30

V3

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

7/2/2026

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-3911

ISSUE DATE: JULY 14, 2026

A

AFI

AF

AFF

AIC

AL

AT

ATS

C

CEC

CL

CT

CU

D

(E)

EC

EF

EPO

EMT

F

(F)

FACP

FLA

FMC

G

GB

GFCI

GND

GRC

IG

IMC

K

KAIC

KCMIL

KO

LCP

MBGB

MCB

MLO

MTC

MTS

(N)

NC

NF

NIEC

NL

NO

NTS

OC

OFCI

PNL

PT

PVC

(R)

(RR)

TC

TP

SPD

TX

TYP

UON

UPS

V

VA

VFD

WP

Y

1Ø

3Ø

1P

2P

3P

3W

4W

ABBREVIATIONS

AMPERES

ARC FAULT CIRCUIT INTERRUPTER

AMPERE OVERCURRENT FRAME SIZE

(WHEN APPLIED TO CIRCUIT

BREAKERS) OR AMPERE FUSE SIZE

(WHEN APPLIED TO FUSES)

ABOVE FINISHED FLOOR

ASYMMETRIC INTERRUPTING CURRENT

ALUMINUM

AMPERE OVERCURRENT TRIP (WHEN

APPLIED TO CIRCUIT BREAKERS)

AUTOMATIC TRANSFER SWITCH

CONDUIT

CALIFORNIA ELECTRICAL CODE

CURRENT LIMITING CIRCUIT BREAKER

OR FUSE

CURRENT TRANSFORMER

COPPER

DELTA

EXISTING TO REMAIN

ELECTRICAL CONTRACTOR

EXHAUST FAN

EMERGENCY POWER OFF

ELECTRICAL METALLIC TUBING

FUSED

FUTURE

FIRE ALARM CONTROL PANEL

FULL LOAD AMPERES

FLEXIBLE METAL CONDUIT

GROUND

GROUND BUS

GROUND FAULT CIRCUIT INTERRUPTER

GROUND

GALVANIZED RIGID CONDUIT

ISOLATED GROUND

INTERMEDIATE METAL CONDUIT

KILO

KILO AIC

KILO CIRCULAR MIL

CONDUIT KNOCKOUT

LIGHTING CONTROL PANEL

MAIN BUILDING GROUND BUS

MAIN CIRCUIT BREAKER

MAIN LUGS ONLY

EMPTY CONDUIT

MANUAL TRANSFER SWITCH

NEW

NORMALLY CLOSED

NON-FUSED

NOT IN ELECTRICAL CONTRACT

NIGHT LIGHT, UNSWITCHED

NORMALLY OPEN

NOT TO SCALE

ON CENTER

OWNER FURNISHED CONTRACTOR

INSTALLED

PANEL

POTENTIAL TRANSFORMER

POLYVINYL CHLORIDE

EXISTING TO BE REMOVED

REMOVE AND RELOCATE

TIME CLOCK

TWISTED-PAIR

SURGE PROTECTION DEVICE

TRANSFORMER

TYPICAL

UNLESS OTHERWISE NOTED

UNINTERRUPTIBLE POWER SUPPLY

VOLTS

VOLTS-AMPS

VARIABLE FREQUENCY DRIVE

WEATHERPROOF

WYE

1-PHASE

3-PHASE

1-POLE

2-POLE

3-POLE

3-WIRE

4-WIRE

R

ELECTRICAL

E E

NI

GN

E

LANOISSEFORP

DERET

SI

G

E R

C A L I F ORN

I A

S T A T E

O F

707 Third Street, Suite 4-105

Architecture & Engineering Sections

Project Management & Development Branch Real Estate Services Division

State of California

West Sacramento, California 95605

Department of General Services

CONSULTING ENGINEERS

ALAMEDA | AUBURN | LOS ANGELES

https://www.engent.com

NEOSHO | SAN DIEGO | SANTA BARBARA

JJ

AS NOTED

V1

C o p y ri g h t

C a lif o rn ia D e p a rt m e n t o f G e n e ra l S e rv ic e s

R e a l E s ta te S e rv ic e s D iv is io n

PROFESSIONAL

STAMP

0 1 2 3

Issue

DateNo. Description

Project

DSA App No.

Supervisor

Sheet Title

Designed

Sheet Number

Sheet Scale

Reference North

Project Number

Drawn

OSFM Permit No. 25-N-3911-C

12533

SWSW

1227 O STREET

SACRAMENTO, CA 95814

#E015491 Exp. 06/30/27

SCOTT WHEELER

PERMIT APPLICATION NO.

25-N-3911-C

SYMBOLS AND

ABBREVIATIONS

E001

CalVet Electrical Upgrades

SOME OF THESE SYMBOLS SHOWN MAY NOT BE USED ON THIS PROJECTSYMBOLS LIST

EXISTING TO REMAIN

EXISTING TO BE REMOVED (R) OR RELOCATED (RR)

NEW CONSTRUCTION

AREA NOT IN SCOPE

IN ELEVATIONS, EXISTING LOCATION OF EQUIPMENT THAT IS TO BE RELOCATED OR

REMOVED

LINESTYLES

POWER DISTRIBUTION

SWITCHGEAR, SWITCHBOARD, DISTRIBUTION BOARD, SUBSTATION OR MOTOR CONTROL

CENTER, FLOOR MOUNTED ON CONCRETE HOUSEKEEPING PAD WHERE INDICATED ON

DRAWINGS. DOUBLE LINE INDICATES FRONT FACE OF GEAR.

DISTRIBUTION BOARD, SURFACE MOUNTED ON WALL.

PANELBOARD, 277/480V, SURFACE MOUNTED ON WALL.

PANELBOARD, 277/480V, FLUSH MOUNTED IN WALL.

PANELBOARD, 120/208V, SURFACE MOUNTED ON WALL.

PANELBOARD, 120/208V, FLUSH MOUNTED IN WALL.

DRY-TYPE STEP-DOWN TRANSFORMER, FLOOR MOUNTED 480-120/208V 3Ø, UON. DOUBLE

LINE INDICATES FRONT FACE OF TRANSFORMER.

PULLBOX OR HANDHOLE, SIZE AND TYPE AS NOTED ON PLANS.

SAFETY DISCONNECT SWITCH, 3 POLE, UON. ADJACENT NUMBER INDICATES FUSE SIZE

WHEN APPLICABLE. LABELING CONVENTION AS FOLLOWS:

A: 30A, NON-FUSED AF: 30A, FUSED

B: 60A, NON-FUSED BF: 60A, FUSED

C: 100A, NON-FUSED CF: 100A, FUSED

D: 200A, NON-FUSED DF: 200A, FUSED

E: 400A, NON-FUSED EF: 400A, FUSED

F: 600A, NON-FUSED FF: 600A, FUSED

G: 800A, NON-FUSED GF: 800A, FUSED

MAGNETIC MOTOR STARTER WITH INTEGRAL OVERCURRENT PROTECTION. ADJACENT

NUMBER INDICATES NEMA SIZE OF STARTER. "HANDLE" DENOTES INTEGRAL DISCONNECT.

VARIABLE FREQUENCY DRIVE FURNISHED UNDER ANOTHER DIVISION. INSTALL VFD AND

PROVIDE POWER SERVICE CONNECTION UNDER THIS DIVISION. "HANDLE" DENOTES

INTEGRAL DISCONNECT.

ELECTRONICALLY COMMUTATED MOTOR CONTROLLER FURNISHED UNDER ANOTHER

DIVISION. INSTALL ECM AND PROVIDE POWER SERVICE CONNECTION UNDER THIS

DIVISION. "HANDLE" DENOTES INTEGRAL DISCONNECT.

PACKAGE MOTOR CONTROLLER OR STARTER FURNISHED AND INSTALLED UNDER

ANOTHER DIVISION WITH EQUIPMENT CONTROLLED. PROVIDE SINGLE-POINT POWER

SERVICE CONNECTION UNDER THIS DIVISION AS NOTED ON PLANS.

DRIVEN GROUND ROD.

DRIVEN GROUND ROD IN GROUND WELL WITH COVER.

CABLE TO BUS TERMINATION LUGS.

BOLTED PRESSURE OR HIGH PRESSURE CONTACT OR FUSED SWITCHES.

GROUP MOUNTED MOLDED CASE CIRCUIT BREAKER.

INDIVIDUALLY FIXED MOUNTED INSULATED-CASE OR POWER CIRCUIT BREAKER.

INDIVIDUALLY DRAW-OUT MOUNTED INSULATED-CASE OR POWER CIRCUIT BREAKER.

MEDIUM-VOLTAGE, INDIVIDUALLY DRAW-OUT MOUNTED VACUUM CIRCUIT BREAKER.

MEDIUM-VOLTAGE LOAD INTERRUPTER SWITCH, FUSED TYPE.

MEDIUM-VOLTAGE LOAD INTERRUPTER SWITCH, NON-FUSED TYPE.

GROUND FAULT RELAY INTEGRAL WITH CIRCUIT BREAKER.

ELECTRICALLY OPERATED CIRCUIT BREAKER, INTEGRAL.

SHUNT-TRIP INTEGRAL WITH OVERCURRENT PROTECTION DEVICES.

KIRK-KEY INTERLOCK INTEGRAL WITH OVERCURRENT PROTECTION DEVICES. ADJACENT

NUMBER CORRESPONDS WITH DEVICE INTERLOCK.

PRIVATE METER, MOUNTED INTEGRAL WITH OVERCURRENT PROTECTION OR SEPARATE

WITHIN SWITCHGEAR.

UTILITY METER, MOUNTED IN UTILITY METER SECTION OF SWITCHGEAR OR

SWITCHBOARDS.

PRIVATE METER, MOUNTED IN SEPARATE ENCLOSURE FROM SWITCHGEAR OR

SWITCHBOARDS.

GROUND FAULT RELAY WITH SHUNT TRIP.

GROUND FAULT ALARM, NO SHUNT TRIP.

TRANSFORMER.

CONNECTION TO GROUND.

AUTOMATIC OR MANUAL TRANSFER SWITCH.

AUTOMATIC TRANSFER & BY-PASS ISOLATION SWITCH.

EMERGENCY GENERATOR.

BATTERIES.

NEUTRAL SERVICE DISCONNECT LINK.

SURGE PROTECTION DEVICE, 'SPD'.

CONTROL CONTACTOR.

NORMALLY OPEN CONTACT.

NORMALLY CLOSED CONTACT.

DIGITAL METERING UNIT.

GROUND BUS AS SHOWN ON SINGLE LINE DIAGRAMS.

GROUND BUS AS SHOWN ON PLAN VIEWS.

NEUTRAL BUS.NEU

DMU

GND

C

SPD

G

GFA

GFR

K

ST

EO

M

G

M

WIRING DEVICES

JUNCTION BOX, WALL MOUNTED, +18" UON.

JUNCTION BOX, MOUNTED IN FLUSH FLOOR BOX.

JUNCTION BOX, MOUNTED FLUSH IN CEILING.

JUNCTION BOX, SURFACE OR PENDANT MOUNTED TO BOTTOM OF STRUCTURE IN

ACCESSIBLE CEILING SPACE OR EXPOSED IN OPEN CEILING AREAS.

JUNCTION BOX, MOUNTED ON CONDUIT STANCHION FLOOR PENETRATION, +12" UON.

SINGLE-PLEX CONVENIENCE RECEPTACLE DEVICE, WALL MOUNTED, +18" UON.

DUPLEX CONVENIENCE RECEPTACLE DEVICE, WALL MOUNTED, +18" UON. LETTERING

ADJACENT TO THE DEVICE ON THE PLANS INDICATE THE FOLLOWING FOR THOSE

RECEPTACLES.

A: ARC FAULT CURRENT INTERRUPTER (AFCI)

G: GROUND FAULT CURRENT INTERRUPTER (GFCI)

IG: ISOLATED GROUND

TR: TAMPER RESISTANT

U: INTEGRAL USB PORTS

WP: WEATHER-RESISTANT, GROUND FAULT CURRENT INTERRUPTER (GFCI) WITH

WEATHERPROOF "IN USE" COVER

DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, WALL MOUNTED, +18" UON.

DUPLEX CONVENIENCE RECEPTACLE DEVICE, WALL MOUNTED OVER COUNTER, 6"

ABOVE BACK SPLASH UON, BUT NO HIGHER THAN ADA REQUIREMENTS.

DUPLEX CONVENIENCE RECEPTACLE DEVICE, SPLIT-WIRED, WALL MOUNTED, +18" UON.

DUPLEX CONVENIENCE RECEPTACLE DEVICE, ON BACK-UP POWER SYSTEM, WALL

MOUNTED, +18" UON.

DUPLEX, OR DOUBLE DUPLEX, CONVENIENCE RECEPTACLE DEVICE, CONTROLLED PER

T24, WALL MOUNTED, +18" UON.

DUPLEX CONVENIENCE RECEPTACLE DEVICE, HORIZONTALLY WALL MOUNTED, +18"

UON.

SPECIALTY OUTLET DEVICE, NEMA CONFIGURATION TYPE AS NOTED ON PLANS, WALL

MOUNTED, +18" UON.

DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FLUSH FLOOR BOX.

DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FLUSH FLOOR BOX.

COMBINATION POWER/TELECOMMUNICATION DEVICE, MOUNTED IN FLUSH FLOOR BOX.

TYPE AS NOTED ON PLANS OR IN SPECIFICATIONS.

DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FIRE-RATED POKE-THRU

FLOOR FITTING.

DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FIRE-RATED POKE-

THRU FLOOR FITTING.

COMBINATION POWER/TELECOMMUNICATION DEVICE, MOUNTED IN FIRE-RATED POKE-

THRU FLOOR FITTING. TYPE AS NOTED ON PLANS OR IN SPECIFICATIONS.

DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED FLUSH IN CEILING.

DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED FLUSH IN CEILING.

DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED ON CONDUIT STANCHION

FLOOR PENETRATION, +12" UON.

DUPLEX CONVENIENCE RECEPTACLE DEVICE, CORD OR REEL HUNG FROM STRUCTURE

ABOVE. TYPE AS NOTED ON PLANS.

ELECTRIFIED FURNITURE PARTITION POWER FEED, WALL MOUNTED, +18" UON.

CONSISTS OF 4 11/16" SQ. X 2 1/8" DEEP JUNCTION BOX, SINGLE GANG RING, AND

STAINLESS STEEL COVER PLATE WITH KO TO ACCEPT FURNITURE WHIP.

ELECTRIFIED FURNITURE PARTITION COMBINATION POWER/TELECOMMUNICATION

FEEDS, MOUNTED IN FIRE-RATED POKE-THRU FLOOR FITTING WITH KO'S OR THREADED

HUB IN COVER TO ACCEPT FURNITURE WHIPS

ELECTRIFIED FURNITURE PARTITION POWER FEED, MOUNTED IN FIRE-RATED POKE-

THRU FLOOR FITTING WITH KO OR THREADED HUB IN COVER TO ACCEPT FURNITURE

WHIP.

POWER/TELECOMMUNICATION POLE, MOUNTED TO EXTEND FROM FLOOR TO CEILING.

TYPE AS NOTED ON PLANS.

SINGLE-POLE, MANUAL DISCONNECT SWITCH WITH THERMAL OVERLOAD ELEMENT,

MOUNTED ADJACENT TO MOTOR.

SINGLE-POLE, FRACTIONAL HORESPOWER MOTOR STARTER/DISCONNECT SWITCH,

MOUNTED ADJACENT TO MOTOR.

SWITCH FURNISHED UNDER ANOTHER DIVISION, BUT INSTALLED AND WIRED UNDER

THIS DIVISION, WALL MOUNTED, +42" UON.

LINE-VOLTAGE THERMOSTAT, NIEC, WALL MOUNTED +48" UON. INSTALLED AND WIRED

BY ELECTRICAL.

CONTROL STATION, WALL MOUNTED, +42" UON.

NUMBERED NOTE, APPLIES TO ALL DRAWINGS.

NUMBERED SHEET NOTE, APPLIES TO DRAWING CONTAINING NOTES ONLY.

OVERCURRENT PROTECTIVE DEVICE NUMBER IDENTIFICATION TAG. REFERS TO

LOCATION OF PROTECTIVE OR CONTROL DEVICE WITHIN SWITCHBOARDS,

DISTRIBUTION BOARDS, MOTOR CONTROL CENTERS, ETC.

EQUIPMENT IDENTIFICATION TAG: ITEM FURNISHED AND INSTALLED UNDER

ANOTHER DIVISION AND WIRED UNDER THIS DIVISION.

FEEDER TAG. REFER TO FEEDER SCHEDULE.

DETAIL REFERENCE:

DETAIL DESIGNATION

SHEET NUMBER

LUMINAIRE IDENTIFICATION TAG:

LUMINAIRE TYPE

QUANTITY

UNDERGROUND CONDUIT DESIGNATION:

CONDUIT SIZE IN INCHES

CONDUIT SYSTEM DESIGNATION

P: PRIMARY POWER

S: SECONDARY POWER

T: TELECOMMUNCATIONS

QUANTITY OF CONDUITS

EQ

E-801

2 - F3

CONVENTIONS

RACEWAYS

CONDUIT RUN EXPOSED ON WALL OR CEILING.

CONDUIT RUN CONCEALED IN SLAB, UNDER SLAB OR UNDERGROUND.

CONDUIT RUN CONCEALED IN WALL OR ABOVE CEILING.

CONDUIT HOMERUN, CONTINUOUS RUN TO PANEL OR EQUIPMENT CABINET.

HOMERUN CAN OCCUR ON ANY OF THE ABOVE ROUTING CONDITIONS.

CONDUIT TURNED UP, CAN OCCUR ON ANY OF THE ABOVE ROUTING

CONDITIONS.

CONDUIT TURNED DOWN, CAN OCCUR ON ANY OF THE ABOVE ROUTING

CONDITIONS.

CONDUIT CAPPED OR STUBBED WITH INSULATED BUSHINGS, CAN OCCUR ON

ANY OF THE ABOVE ROUTING CONDITIONS.

CONDUIT SLEEVE, WITH INSULATING BUSHINGS.

FLEXIBLE METALLIC CONDUIT, EQUIPMENT CONNECTION.

CROSSMARKS ON BRANCH CIRCUIT CONDUIT RUNS INDICATE THE QUANTITY OF

CONDUCTORS AS FOLLOWS (GROUND CONDUCTORS ARE NOT NOTED, BUT

SHOULD BE INCLUDED IN EVERY CONDUIT WITH POWER CONDUCTORS):

1. NO CROSSMARKS INDICATES TWO #12 AWG CONDUCTORS, UON.

2. THREE TO SIX CROSSMARKS INDICATES THE QUANTITY OF #12 AWG

CONDUCTORS, UON.

3. SEVEN OR MORE CROSSMARKS INDICATES THE QUANTITY OF #10

AWG CONDUCTORS, UON.

SURFACE RACEWAY; TYPE, DEVICE SPACING AND MOUNTING AS NOTED ON

PLANS.

CABLE TRAYS/RUNWAYS, REFER TO PLANS AND/OR SPECS FOR SIZE AND

MOUNTING.

A AF

1 1

VFD

VFD

ECM

ECM

LINE VOLTAGE LIGHTING CONTROL

SINGLE-POLE, SINGLE-THROW SWITCH, WALL MOUNTED, +42" UON.

THREE-WAY SWITCH, WALL MOUNTED, +42" UON.

FOUR-WAY SWITCH, WALL MOUNTED, +42" UON.

SINGLE-POLE, SINGLE-THROW SWITCH, KEY-OPERATED, WALL MOUNTED, +42" UON.

SINGLE-POLE, SINGLE-THROW SWITCH, WITH PILOT LIGHT, WALL MOUNTED, +42" UON.

WALLBOX DIMMER SWITCH, +42" UON. SIZED PER CONNECTED LOAD ON PLANS AND

FURNISHED FOR LAMP SOURCE SERVED. PROVIDED FOR DERATING WHEN INSTALLED

GANGED LOCATIONS.

SINGLE-POLE, TIMER CONTROLLED SWITCH, WALL MOUNTED, +42" UON.

SINGLE-POLE, SINGLE-THROW SWITCH, EXPLOSION PROOF, WALL MOUNTED, +42" UON.

LINE VOLTAGE SINGLE RELAY VACANCY SENSOR, WALL MOUNTED, +42" UON.

SINGLE-POLE, SINGLE-THROW SWITCH WITH WEATHERPROOF COVER, WALL MOUNTED,

+42" UON.

SINGLE-POLE SWITCH WITH AUTOMATIC HUMIDITY CONTROL, WALL MOUNTED, +42" UON.

DUAL LEVEL OCCUPANCY SENSOR SWITCH, WALL MOUNTED, +42" UON.

SINGLE LEVEL OCCUPANCY SENSOR SWITCH, WALL MOUNTED, +42" UON.

COMBINATION OCCUPANCY SENSOR AND DIMMER SWITCH, WALL MOUNTED, +42" UON.

OCCUPANCY SENSOR FOR AREA COVERAGE, CEILING MOUNTED.

PHOTOELECTRIC CELL SENSOR, CEILING MOUNTED.

EGRESS LIGHTING TRANSFER DEVICE.

BYPASS DEVICE FOR CONTROLLED EMERGENCY LIGHTING.

S

WP

S V

S

EP

S

TC

S D

S P

S K

S

S

S

OS

PC

S

DM

S M1

S M

S H

J

J

J

J

J

ETD

T

P

P

7S4

S F

S

MS

S T

M

P

V2

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

4/21/2026

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-3911

2026-06-30

V3

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

7/2/2026

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

1. ELECTRICAL SCOPE SHALL COMPLY WITH THE LATEST ADOPTED EDITIONS OF THE CALIFORNIA

ELECTRIC CODE (CEC), CALIFORNIA BUILDING CODE (CBC), CALIFORNIA FIRE CODE (CFC),

CALIFORNIA MECHANICAL CODE (CMC), NATIONAL FIRE PROTECTION ASSOCIATION (NFPA 72) AND

THE CALIFORNIA ENERGY CODE.

2. THE CONTRACTOR SHALL VISIT THE JOBSITE AND VERIFY ALL EXISTING CONDITIONS PRIOR TO

BIDDING THE PROJECT AND SHALL INCLUDE IN THEIR BID THE NECESSARY COSTS TO

CONSTRUCT THIS PROJECT IN ACCORDANCE WITH THE DRAWINGS, SPECIFICATIONS, AND ALL

APPLICABLE CODES.

3. DRAWINGS INDICATE GENERAL ARRANGEMENT OF ELECTRICAL SYSTEMS AND WORK. FOLLOW

THE DRAWINGS IN LAYING OUT WORK AND VERIFY EXACT LOCATIONS WITH ARCHITECTURAL

FLOOR PLAN AND RCP DRAWINGS. ALSO, CHECK DRAWINGS OF OTHER TRADES TO VERIFY

LOCATIONS OF EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS AND COORDINATE SPACE

CONDITIONS WITH THEIR INSTALLATION. FINAL LOCATIONS SHALL BE ADJUSTED TO MEET FIELD

CONDITIONS.

4. NOT EVERY ELECTRICAL RACEWAY, BOX, CONDUCTOR, ETC., FOR A COMPLETE ELECTRICAL

INSTALLATION IS SHOWN ON THESE DRAWINGS. THIS IS DONE FOR CLARITY PURPOSES AND

EASE OF INTERPRETING DRAWINGS. PROVIDE ALL ADDITIONAL ITEMS REQUIRED TO MAKE THE

ELECTRICAL SYSTEMS COMPLETE AND OPERATIONAL.

5. WORK PERFORMED UNDER THIS CONTRACT SHALL CONFORM TO THESE DRAWINGS AND SHALL

ALSO COMPLY WITH THE ELECTRICAL SPECIFICATIONS. IN THE EVENT THAT THERE IS A

DISCREPANCY BETWEEN THE DRAWINGS AND SPECIFICATIONS, THE MORE STRINGENT OF THE

REQUIREMENTS SHALL TAKE PRECEDENT.

6. ALL NEW ELECTRICAL MATERIALS AND EQUIPMENT SHALL BE UNDERWRITER’S LABORATORIES (UL) LISTED OR ELECTRICAL TESTING LABORATORIES (ETL) LISTED AND BEAR THEIR LABELS.

7. ALL ELECTRICAL MATERIALS SHALL BE NEW AND UNUSED, AND THE SAME MANUFACTURER OF

LIKE EQUIPMENT AND/OR SYSTEMS.

8. CONTRACTOR SHALL REMOVE ALL LEFTOVER CONDUIT, WIRE, SCRAPS, ETC. AND LEAVE

PREMISES CLEAN AND FREE OF TRASH AND DEBRIS RESULTING FROM THEIR WORK.

9. COORDINATE ALL INCOMING ELECTRICAL SERVICE WORK WITH THE SERVING POWER UTILITY

COMPANY PRIOR TO ANY INSTALLATION.

10. ALL ON-SITE INFRASTRUCTURE FOR SERVICE ENTRANCE INSTALLATION WORK OF POWER UTILITY

COMPANY SHALL BE PROVIDED UNDER THIS CONTRACT. COORDINATE INSTALLATION WITH

POWER UTILITY COMPANY’S STANDARDS AND SPECIFICATIONS.

11. ALL EQUIPMENT, DEVICES, AND RACEWAYS SHOWN AS SOLID LINEWORK ON THESE DRAWINGS

ARE NEW CONSTRUCTION.

12. THE EXISTING INSTALLATION SHOWN ON THESE DRAWINGS WAS DEVELOPED FROM VARIOUS

SOURCES, WHICH WERE NOT ALL FIELD VERIFIED AND NOT ALL CONDITIONS ARE SHOWN.

CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS PRIOR TO CONSTRUCTION.

13. CONTRACTOR SHALL DISCONNECT AND REMOVE ALL EQUIPMENT, DEVICES, AND RACEWAYS

DENOTED TO BE DEMOLISHED ON THESE DRAWINGS. LEGALLY DISPOSE OF ALL MATERIALS THAT

THE OWNER DOES NOT WANT.

14. RECONNECT EXISTING TO REMAIN DEVICES WHERE CIRCUITS HAVE BEEN INTERRUPTED BY

DEMOLITION WORK TO MAINTAIN CONTINUITY. PROVIDE NEW CONNECTIONS TO ANOTHER

EXISTING DEVICE OR NEW CIRCUIT BREAKER FROM PANELBOARD. VERIFY CIRCUIT LOADING ON

EXISTING CIRCUITS BEFORE MAKING THESE CONNECTION.

15. WHERE EXISTING DEVICES TO BE REMOVED ARE SHOWN ON THESE DRAWINGS, THE

CONTRACTOR SHALL ALSO REMOVE ALL WIRING, CONDUIT, AND BOXES SERVING THE DEVICES,

UNLESS CONDUIT AND BOXES CAN BE REUSED IN NEW CONSTRUCTION.

16. WHEN A DEVICE IS REMOVED FROM AN EXISTING WALL TO REMAIN, PATCH WALL TO MATCH

EXISTING OR NEW WALL FINISHES.

17. MOUNTING HEIGHTS FOR ALL NEW DEVICES SHALL BE LOCATED TO MATCH EXISTING TO REMAIN

DEVICES, UNLESS OTHERWISE NOTED.

18. WHERE ADDITIONAL CIRCUITS ARE REQUIRED AND EXISTING PANELBOARDS HAVE AVAILABLE

SPACE, PROVIDE NEW CIRCUIT BREAKERS IN EXISTING PANELBOARDS TO MATCH THE AIC

RATINGS AND THE MANUFACTURER OF THE EXISTING BREAKERS.

19. ALL GROUNDING ELECTRODES WITHIN BUILDING OR STRUCTURE SHALL BE BONDED TOGETHER

TO FORM A SINGLE GROUNDING ELECTRODE SYSTEM.

20. ALL SEPARATELY DERIVED SYSTEMS SHALL COMPLY WITH CODE, CEC 250.104, FOR BONDING TO

METAL WATER PIPING AND STRUCTURAL METAL.

21. FURNISH, INSTALL, AND CONNECT A CODE SIZED INSULATED OR BARE COPPER GROUND

CONDUCTOR IN ALL BRANCH CIRCUITS AND FEEDER CONDUITS.

22. WHERE UNGROUNDED CONDUCTORS ARE INCREASED IN SIZE TO ACCOMMODATE VOLTAGE

DROP, THE EQUIPMENT GROUND CONDUCTOR SHALL ALSO BE INCREASED IN SIZE

PROPORTIONATELY, ACCORDING TO THE CIRCULAR MIL AREA OF UNGROUNDED CONDUCTORS.

23. ALL EQUIPMENT CONNECTED BY PERMANENT WIRING METHODS SHALL BE GROUNDED.

24. BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED TO PREVENT VOLTAGE DROP EXCEEDING 3% AT

THE FARTHEST OUTLET OR DEVICE. THE MAXIMUM VOLTAGE DROP ALLOWED ON COMBINED

FEEDERS AND BRANCH CIRCUITS SHALL NOT EXCEED 5% TO THE FARTHEST OUTLET OR DEVICE.

25. ALL CONDUCTORS ON THIS PROJECT SHALL BE COPPER.

26. CONDUCTORS 600VOLT OR LESS RATED SHALL UTILIZE THE AMPACITY OF THE 60-DEGREE C

COLUMN OF CEC TABLE 310.16 FOR CONDUCTOR SIZES #14 AWG THROUGH #1 AWG. FOR

CONDUCTOR SIZES OVER #1 AWG, UTILIZE AMPACITY FROM THE 75-DEGREE C COLUMN OF CEC

TABLE 310.16.

27. MULTIWIRE BRANCH CIRCUITS SHALL ORIGINATE FROM THE SAME PANELBOARD.

28. MULTIWIRE BRANCH CIRCUITS SHALL BE PROVIDED WITH A MEANS TO SIMULTANEOUSLY

DISCONNECT ALL UNGROUNDED CONDUCTORS AT THE POINT WHERE THE BRANCH CIRCUIT

ORIGINATES, I.E. HANDLE TIES OR MULTIPOLE CIRCUIT BREAKERS.

29. ALL MULTIWIRE BRANCH CIRCUITS SHOWN WITH THREE (3) CONSECUTIVE PHASE CONDUCTORS (E.G., 1,3,5 OR 4,6,8), NONE SHARING THE SAME PHASE, SHALL INCLUDE A DEDICATED NEUTRAL CONDUCTOR, THREE (3) HOTS AND ONE (1) NEUTRAL. CIRCUITING OUT OF PHASE ORDER (E.G., 1,5,7 OR 4,6,10) WILL REQUIRE AN ADDITIONAL NEUTRAL CONDUCTOR, TWO (2) HOTS AND ONE (1)

NEUTRAL PLUS ONE (1) HOT AND ONE (1) NEUTRAL.

30. BRANCH CIRCUIT CONDUCTOR HOMERUNS SHALL BE INSTALLED IN CONDUIT. MC TYPE CABLE

SHALL NOT BE USED FOR ANY HOMERUNS ON THIS PROJECT.

FEEDER CONDUCTORS SHALL BE INSTALLED IN CONDUIT, UNLESS OTHERWISE NOTED.

31. PROVIDE FEEDER CONDUCTOR SUPPORT IN VERTICAL RACEWAYS AS REQUIRED BY CODE, CEC 300.19.

32. WHERE MORE THAN THREE UNGROUNDED CONDUCTORS ARE ROUTED WITHIN A RACEWAY, THE

CONTRACTOR SHALL APPLY THE DERATING FACTOR REQUIRED BY CODE.

33. MINIMUM CONDUIT TRADE SIZE FOR INTERIOR APPLICATIONS SHALL BE 0.5”, UNLESS OTHERWISE

NOTED.

34. CONDUIT ROUTING ON DRAWINGS IS ESSENTIALLY DIAGRAMMATIC. CONTRACTOR SHALL LAYOUT

RUNS TO SUIT FIELD CONDITIONS, LIMITING BENDS AND BOXES, AND SHALL COORDINATE

INSTALLATION WITH WORK OF OTHER TRADES.

35. PENETRATIONS OF PIPES, CONDUITS, ETC. IN RATED ASSEMBLIES SHALL BE FIRE-STOPPED. FIRE-

STOPPING SHALL BE AN APPROVED MATERIAL AS PRESCRIBED BY THE STATE FIRE MARSHAL

STANDARDS PROTECTION DETAILS OF THRU-PENETRATIONS THROUGH FIRE RATED PARTITIONS

SHALL BE UL/WH LISTED AND COMPLY WITH CBC, SECTION 714. PROTECTION DETAILS OF

MEMBRANE PENETRATIONS THROUGH FIRE PARTITIONS SHALL COMPLY WITH CBC SECTION

714.4.2. ALL FIRE STOPPING MATERIAL SHALL BE RED IN COLOR.

36. PROVIDE INSULATING BUSHINGS OR INSULATED THROAT CONNECTORS AT BOTH ENDS OF ALL

CONDUIT SLEEVES.

37. ALL JUNCTION AND PULL BOXES SHALL BE SIZED PER CODE TO ACCOMMODATE NUMBER OF

CONDUITS AND/OR CONDUCTORS ROUTED TO AND FROM BOXES.

38. RACEWAYS ROUTED IN EXPOSED CEILING AREAS SHALL BE RUN PARALLEL AND AT RIGHT

ANGLES TO WALLS WITHIN SPACES. MC CABLE IS NOT ALLOWED IN EXPOSED CEILING SPACES.

39. PROVIDE A PULL WIRE/TAPE IN ALL EMPTY CONDUIT RUNS OVER 15’ IN LENGTH.

40. NO PIPING, DUCTWORK, OR EQUIPMENT FOREIGN TO ELECTRICAL EQUIPMENT SHALL BE

ALLOWED WITHIN THE DEDICATED SPACE ABOVE ELECTRICAL EQUIPMENT.

41. REQUIRED ELECTRICAL EQUIPMENT WORKING SPACE DEPTH SHALL NOT BE LESS THAN THAT INDICATED IN CEC TABLE 110.26(A)(1). THE WIDTH OF THE WORKING SPACE IN FRONT OF THE

ELECTRICAL EQUIPMENT SHALL BE THE WIDTH OF THE EQUIPMENT OR 30", WHICHEVER IS

GREATER. THIS REQUIREMENT ALSO APPLIES TO DISCONNECT SWITCHES.

42. FOR EQUIPMENT RATED 1200AMPS OR MORE AND OVER 6.5’ WIDE, CONTAINING OVERCURRENT, SWITCHING, AND CONTROL DEVICES, THERE SHALL BE ONE ENTRANCE TO AND EGRESS FROM

THE REQUIRED WORKING SPACE LOCATED AT EACH END OF THE WORKING SPACE, NOT LESS

THAN 24” WIDE AND 6.5’ HIGH. A SINGLE ENTRANCE TO AND EGRESS FROM THE REQUIRED

WORKING SPACE SHALL BE PERMITTED WHERE EITHER UNOBSTRUCTED EGRESS OR EXTRA

WORKING SPACE IS PROVIDED IN CONFORMANCE WITH THE CEC.

43. FOR EQUIPMENT RATED 800AMPS OR MORE, CONTAINING OVERCURRENT, SWITCHING, AND

CONTROL DEVICES, WHERE THERE IS A PERSONNEL DOOR(S) INTENDED FOR ENTRANCE TO AND

EGRESS FROM THE WORKING SPACE WHICH IS LESS THAN 25’ FROM THE NEAREST EDGE OF THE

WORKING SPACE, THE DOOR(S) SHALL OPEN IN THE DIRECTION OF EGRESS AND BE EQUIPPED

WITH LISTED PANIC HARDWARE.

PROJECT GENERAL NOTES PROJECT GENERAL NOTES (cont.)

44. NO ELECTRICAL EQUIPMENT SHALL BE RELEASED FOR SHIPMENT OR INSTALLED ON-SITE PRIOR

TO ENGINEER’S REVIEW OF THE POWER SYSTEM STUDY AND APPROVED ADJUSTMENTS TO

ELECTRICAL EQUIPMENT SUBMITTALS.

45. CONTRACTOR SHALL PROVIDE ARC FLASH LABELS FOR ALL ELECTRICAL EQUIPMENT WITHIN THE

SCOPE OF THIS PROJECT. THESE LABELS SHALL BE GENERATED BY THE CONTRACTOR FROM

THE POWER SYSTEM STUDY AND SUBMITTED WITH THE POWER SYSTEM STUDY SUBMITTAL FOR

ENGINEER’S REVIEW. THIS INCLUDES ALL FIELD MARKING OF AIC VALUES ON ALL BOARDS PER

THE CEC.

46. PROVIDE ENGRAVED NAMEPLATES FOR ALL ELECTRICAL PANELBOARDS, SWITCHBOARDS,

SWITCHGEAR, TRANSFORMERS, AND DISCONNECT SWITCHES, AS DESCRIBED IN THE

SPECIFICATIONS.

47. CONTRACTOR SHALL ENSURE THAT THE ELECTRICAL EQUIPMENT PROVIDED UNDER THEIR

CONTRACTOR WILL FIT WITHIN THE ELECTRICAL ROOMS AND SPACES PROVIDED IN THE BID

DOCUMENTS, WHETHER PROVIDED BY THE SPECIFIED EQUIPMENT MANUFACTURER OR NOT. NO

ADDITIONAL COMPENSATION WILL BE CONSIDERED IF CONTRACTOR NEEDS TO ADJUST

EQUIPMENT PACKAGE TO OBTAIN REDUCED DIMENSIONS.

48. CONTRACTOR IS RESPONSIBLE FOR SUBMITTING REVISED LAYOUTS OF DISTRIBUTION

EQUIPMENT IN ELECTRICAL ROOMS AND/OR SPACES, FOR APPROVAL BY ENGINEER, IF

PROPOSED INSTALLATION DIFFERS FROM CONSTRUCTION DOCUMENTS. SUBMISSION MUST BE

REVIEWED PRIOR TO RELEASE OF EQUIPMENT ORDER AND PRIOR TO INSTALLATION.

49. WHERE NEW EQUIPMENT IS REPLACING THE EXISTING EQUIPMENT IN THE SAME LOCATION ONLY THE NEW EQUIPMENT IS SHOWN. UTILIZE EXISTING CONDUIT AND BRANCH CIRCUIT CONDUIT &

WIRING. REMOVE EXISTING FEEDER WIRE AND THE EQUIPMENT. INSTALL THE NEW EQUIPMENT

AND RECONNECT EXISTING BRANCH CONDUIT AND WIRE. CONNECT EXISTING FEEDER CONDUIT

AND PULL NEW FEEDER WIRE. IF NEW EQUIPMENT IS TO BE IN A NEW LOCATION, WE HAVE

SHOWN THAT ON THE PLANS AND ELEVATIONS, INCLUDING THE REVISED WORK REQUIRED FOR

THE RELOCATION. CONTRACTOR SHALL SURVEY EACH EQUIPMENT LOCATION AND DETERMINE

NEW EQUIPMENT INSTALLATION REQUIREMENTS PRIOR TO RELEASE OF EQUIPMENT.

50. ALL WORK ASSOCIATED WITH THE NEW AND EXISTING UPS SYSTEMS AND ASSOCIATED

DISTRIBUTION SHALL BE COORDINATED WITH CALVET. ASSUME ALL WORK REQUIRING A POWER

OUTAGE WILL BE PERFORMED OUTSIDE OF NORMAL BUSINESS HOURS ON WEEKENDS OR

HOLIDAYS. NOTE, THE OWNER MAY PERFORM WORK WITHIN THE DATA CENTER DURING THE

OUTAGE REQUIRED TO CONNECT THE NEW UPS EQUIPMENT, WHICH IS WHY IT IS IMPERATIVE TO

CLOSELY COORDINATE ANY OUTAGE.

51. WIRING SPACE IN PANELBOARD'S, DISTRIBUTION BOARDS, SWITCHBOARDS, AND SWITCHGEAR

SHALL BE DEDICATED TO CONDUCTORS TERMINATED IN THAT ENCLOSURE AND SHALL NOT BE

USED AS PULL AND/OR SPLICE BOXES FOR CONDUCTORS THAT TERMINATE IN OTHER

ENCLOSURES.

52. ALL CIRCUIT BREAKERS SERVING THE FIRE ALARM CONTROL PANEL AND FIRE ALARM SYSTEM

COMPONENTS SHALL HAVE LOCKABLE HANDLES AND SHALL BE RED IN COLOR, FOR EASE IN

IDENTIFICATION.

53. PROVIDE PROTECTION FROM PHYSICAL DAMAGE FOR ALL ELECTRICAL EQUIPMENT, LUMINARIES, WIRING DEVICES, ETC., DURING THE CONSTRUCTION OF THE PROJECT.

54. MOUNTING HEIGHTS OF ALL WIRING DEVICES ARE DIMENSIONED TO THE CENTER OF THE DEVICE, UNLESS OTHERWISE NOTED.

55. DURING CONSTRUCTION, PROVIDE TEMPORARY POWER TO EXISTING SYSTEMS AS DESCRIBED IN SPECIFICATION 260090, SECTION 3.05. SYSTEMS INCLUDED, BUT NOT LIMITED TO THE FOLLOWING:

A. SECURITY

B. SERVER ROOM / UPS LOADS / COOLING WITHIN THE SERVER ROOM

C. FREIGHT ELEVATOR

D. PUMPS ( DOMESTIC WATER)

E. FIRE ALARM & FIRE SUPPRESSION

F. EXIT SIGNS & EGRESS LIGHTING

56. EXISTING CONDUIT OR GUTTER RACEWAYS SHALL BE ADJUSTED TO ENTER THE NEW

SWITCHBOARD, PANELS, GUTTERS, ETC. AS REQUIRED TO ACCOMODATE NEW EQUIPMENT.

57. PANEL AND EQUIPMENT SCHEDULES ARE SHOWN FOR NEW EQUIPMENT (EQUIPMENT REPLACING EXISTING). EXISTING TO REMAIN EQUIPMENT IS NOT SCHEDULED AS IT REMAINS AND IS NOT

ALTERED.

58. COORDINATE ALL PROJECT SEQUENCING WITH OWNER OR AS SPECIFIED AND/OR SHOWN ON

THE DRAWINGS.

59. GENERAL CONTRACTOR SHALL FOLLOW REQUIREMENTS FOR FIRE SAFETY DURING

CONSTRUCTION. REFER TO CALIFORNIA FIRE CODE CHAPTER 33.

60. PROVIDE FIRE DEPARTMENT ACCESS AND A SAFE MEANS OF EGRESS THROUGH AND/OR

AROUND THE BUILDING AND SITE PER APPLICABLE CODES AT ALL TIMES DURING THE

CONSTRUCTION PROCESS. MINIMIZE DISRUPTION TO ADJACENT AREAS/FLOORS AS MUCH

AS POSSIBLE.

61. MAINTAIN EGRESS FROM EXISTING OCCUPIED SPACES AND SURROUNDING BUILDING AREAS AS

INDICATEDAND AS REQUIRED BY AUTHORITIES HAVING JURISDICTION.

62. PER CFC 3312.2, REQUIRED MEANS OF EGRESS SHALL BE MAINTAINED DURING CONSTRUCTION

AND DEMOLITION, REMODELING, OR ALTERATIONS TO ANY BUILDING. EXCEPTION: APPROVED

TEMPORARY MEANS OF EGRESS.

63. PROVIDE AND MAINTAIN FIRE EXTINGUISHERS IN AREA OF WORK, IN ACCORDANCE WITH

REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION.

64. PROVIDE TEMPORARY BARRIERS AND ENCLOSURES AS REQUIRED TO PROTECT MATERIALS

AND PEOPLE (REF CFC 3305). PREVENT DUST, FUMES, AND ODORS FROM ENTERING OCCUPIED

AREAS. MAINTAIN AND RELOCATE TEMPORARY BARRIERS AND ENCLOSURES AS REQUIRED BY

THE PROGRESS OF THE WORK. REMOVE TEMPORARY BARRIERS AND ENCLOSURES AT

COMPLETION OF WORK.

65. PRIOR TO STARTING DEMOLITION, VERIFY EXISTING CONDITIONS AND DIMENSIONS. COORDINATE

EXTENT OF DEMOLITION WORK AND EXITING CONSTRUCTION TO REMAIN WITH NEW WORK.

NOTIFY [ENGINEER/DESIGN TEAM] IF CONFLICTS OR DISCREPANCIES.

SEQUENCE OF WORK

THE PROCUREMENT OF THE EQUIPMENT SHALL BEGIN AFTER PROJECT AWARD, WITH SUBMITTALS, APPROVALS, PROCUMENT, ETC. COORDINATE THE SEQUENCING WITH THE

OWNER. SUBMIT PROJECT SCHEDULE FOR APPROVAL UPON AWARD.

THE CIRCUIT TRACING AND DOCUMENTATION (DESCRIBED BELOW) SHALL BE PERFORMED DURING THE PROCUREMENT SEQUENCE.

UPS AND ASSOCIATED EQUIPMENT SHALL BE PROCURED AT THE BEGINNING OF THE PROJECT WITH THE GOAL OF INSTALLATION OCCURRING AS SOON AS POSSIBLE.

THE MAIN CONSTRUCTION SEQUENCE SHALL BEGIN ONCE ALL EQUIPMENT AND MATERIALS ARE DELIVERED. THIS SHALL BE COORDINATED WITH THE OWNER AS THE INTENT IS FOR THE OCCUPANTS TO VACATE THE BUILDING DURING THIS SEQUENCE. AS DENOTED IN THE GENERAL CONDITIONS, THE CONSTRUCTION PORTION OF THIS PROJECT NEEDS TO BE

COMPLETED IN 55 WORKING DAYS OR LESS.

CIRCUIT TRACING SCOPE OF WORK

THE CONTRACTOR IS RESPONSIBLE FOR CIRCUIT TRACING WITH THE INTENT THAT AN AS-BUILT REVIT MODEL AND AUTOCAD FILES WILL BE PROVIDED AT THE CONCLUSION OF THE

PROJECT. THIS SHALL ENTAIL, BUT NOT BE LIMITED TO:

A. DOCUMENTING LOCATIONS OF ALL DEVICES THAT ARE POWERED IN A REVIT MODEL. A COPY OF THE MODEL WITH THE FLOOR PLANS WILL BE FURNISHED BY THE ENGINEER.

THE MODEL FROM THE ENGINEER WILL NOT BE POPULATEED WITH DEVICES, MECHANICAL/PLUMBING EQUIPMENT, LIGHTING FIXTURES, SWITCHES, ETC. VERIFY ALL POWERED ITEMS IN THE MODEL AS WELL AS ALL POWERED ITEMS NOT SHOWN IN THE MODEL, INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING:

•RECEPTACLES – FLOOR RECEPTACLES AND WHIPS ONLY IF VISIBLE, NOT COVERED BY CARPET

•LIGHTING FIXTURES/TIMERS, INCLUDING EXTERIOR FIXTURES

•SWITCHES – (LIGHT SWITCHES, SWITCHES CONTROLLING DEVICES SUCH AS GARBAGE DISPOSALS/PROJECTION SCREENS, ETC)

•FIRE SMOKE DAMPERS

•DRINKING FOUNTAINS

•EMERGENCY POWER SYSTEM

•EXIT/EGRESS LIGHTS

•SECURITY/ACCESS SYSTEM EQUIPMENT

•BACK-UP GENERATOR LOADS

•MECH & PLUMBING EQUIP, “INCLUDING BUT NOT LIMITED TO”:

•FIRE ALARM SYSTEM EQUIPMENT

•MIXING BOXES

•HVAC SYSTEM AND COMPONENTS

•EXHAUST FANS

•BOOSTER PUMPS

•ELEVATORS

•GARAGE DOOR

•POWERED DOORS (EXAMPLE, ADA FRONT DOORS)

•HEAT EXCHANGER

B. TRACE AND IDENTIFY ALL CIRCUITS FOR DEVICES AND EQUIPMENT. DOCUMENT CIRCUITS AT THE DEVICES AND EQUIPMENT WITHIN THE REVIT MODEL.

C. PROVIDE PDF FOR REVIEW AND UPDATE THE MODEL PER COMMENTS FROM THE ENGINEER AND OWNER. REVIEW DOCUMENTS SHALL ALSO INCLUDE PANEL SCHEDULES.

D. PROVIDE LABELS AND NAMEPLATES FOR ALL EXISTING AND NEW DEVICES AND EQUIPMENT AND ADHERE TO DEVICE COVERS, DISCONNECTS, ETC PER SPECIFICATIONS.

E. PROVIDE JUNCTION BOX IDENTIFICATION WITH CIRCUITS.

F. PROVIDE UPDATED PANELS DIRECTORIES COMPLIANT WITH CEC ARTICLE 408.4 AND PLACE IN EACH PANELBOARD.

G. PROVIDE PDF, AUTOCAD FILES AND REVIT MODEL TO ENGINEER AND OWNER AS RECORD DOCUMENT.

NOTES:

1. THE CIRCUIT TRACING WORK WITHIN THE BUILDING SHALL BE CONDUCTED DURING NON WORK HOURS. IT SHALL BEGIN UPON AWARD AND BE

COMPLETED AS NOTED IN DIVISION 00 & 01.

2. REFER TO SPECIFICATION SECTION 26 05 53 FOR ADDITIONAL LABELING AND IDENTIFICATION INFORMATION.

3. CONTRACTOR TO COORDINATE BUILDING ACCESS TO PERFORM CIRCUIT TRACING SCOPE OF WORK WITH CALVET.

R

ELECTRICAL

E E

NI

GN

E

LANOISSEFORP

DERET

SI

G

E R

C A L I F ORN

I A

S T A T E

O F

707 Third Street, Suite 4-105

Architecture & Engineering Sections

Project Management & Development Branch Real Estate Services Division

State of California

West Sacramento, California 95605

Department of General Services

CONSULTING ENGINEERS

ALAMEDA | AUBURN | LOS ANGELES

https://www.engent.com

NEOSHO | SAN DIEGO | SANTA BARBARA

JJ

AS NOTED

V1

C o p y ri g h t

C a lif o rn ia D e p a rt m e n t o f G e n e ra l S e rv ic e s

R e a l E s ta te S e rv ic e s D iv is io n

PROFESSIONAL

STAMP

0 1 2 3

Issue

DateNo. Description

Project

DSA App No.

Supervisor

Sheet Title

Designed

Sheet Number

Sheet Scale

Reference North

Project Number

Drawn

OSFM Permit No. 25-N-3911-C

12533

SWSW

1227 O STREET

SACRAMENTO, CA 95814

#E015491 Exp. 06/30/27

SCOTT WHEELER

PERMIT APPLICATION NO.

25-N-3911-C

FEEDER

SCHEDULE,

NOTES, & TABLES

E002

CalVet Electrical Upgrades

FEEDER SCHEDULE

FEEDER SCHEDULE GENERAL NOTES

1. COPPER FEEDER SIZES SHOWN IN THIS SCHEDULE ARE BASED ON CONDUCTORS WITH THHN/THWN-2 INSULATION IN EMT CONDUIT.

2. FEEDER SIZES SHOWN IN THIS SCHEDULE ARE BASED ON AN AMBIENT TEMPERATURE OF 30 DEGREES C (86 DEGREES F).

3. FEEDERS CONSISTING OF MULTIPLE SETS OF CONDUCTORS AND CONDUITS ARE TO BE PROVIDED WITH THE INDICATED SIZE GROUND CONDUCTOR

IN EACH CONDUIT.

4. PER CEC ARTICLE 110.14, ALL FEEDERS SIZED AT #2 AWG OR LESS ARE CALCULATED PER 60 DEGREE TABLE. FEEDERS GREATER THAN #2 AWG

ARE RATED 75 DEGREE. 90 DEGREE COLUMN IS USED WHEN APPLYING DERATING FACTORS.

FEEDER SCHEDULE REMARKS

A. OVERSIZED 150% NEUTRAL, SUITABLE FOR SERVICE FROM K-13 RATED TRANSFORMERS.

B. FEEDER APPROVED FOR USE WITH SEPARATELY DERIVED SYSTEM; GROUNDING AS REQUIRED BY CEC ARTICLES 240 AND 250.

C. FEEDER GROUND AND BONDING JUMPER SHALL HAVE AN AREA NOT LESS THAN 12.5% OF THE AREA OF THE LARGEST PHASE CONDUCTOR.

D. INCREASE CONDUIT TO THE NEXT LARGER TRADE SIZE WHEN USING SCHEDULE 40 OR 80 PVC CONDUIT.

E. PER CEC SECTION 240.4(B), FOR OVERCURRENT DEVICES RATED 800A OR LESS, THE NEXT HIGHER STANDARD OVERCURRENT DEVICE RATING (ABOVE THE

AMPACITY OF THE CONDUCTORS) CAN BE USED. RULE CAN NOT BE APPLIED IF 100% RATED BREAKERS ARE USED.

F. PER CEC 240.21(C), THE PROVISIONS OF 240.4(B) SHALL NOT BE PERMITTED FOR TRANSFORMER SECONDARY CONDUCTORS.

G. USE EXTRA-FLEXIBLE CONDUCTORS (CLASS I OR K STRANDING) WITH TERMINATIONS RATED FOR THE EXTRA-FLEXIBLE

CONDUCTORS.

FEEDER

TAG

FEEDER

DESCRIPTION

CONDUIT

FEEDER CONDUCTORS

SEPARATELY DERIVED

SYSTEM

REMARKS

PHASE/NEUTRAL GROUND

GROUNDING

ELECTRODE

SYSTEM

BONDING

JUMPER

604 55 AMP, 4 WIRE SEE E301

SHEET

4 #6 CU 1 #10 CU

- - E

704 70 AMP, 4 WIRE SEE E301

SHEET

4 #4 CU 1 #8 CU

1003 95 AMP, 3 WIRE SEE E301

SHEET

3 #2 CU 1 #8 CU

- - E

1004 95 AMP, 4 WIRE SEE E301

SHEET

4 #2 CU 1 #8 CU

- - D,E

1254 130 AMP, 4 WIRE SEE E301

SHEET

4 #1 CU 1 #6 CU

T1504 150 AMP, 4 WIRE SEE E301

SHEET

4 #1/0 CU 1 #6 CU

#6 CU IN 0.75" C. #6 CU B,F

1753 175 AMP, 3 WIRE SEE E301

SHEET

3 #2/0 CU 1 #6 CU

1754 175 AMP, 4 WIRE SEE E301

SHEET

4 #2/0 CU 1 #6 CU

2003 200 AMP, 3 WIRE SEE E301

SHEET

3 #3/0 CU 1 #6 CU

2004 200 AMP, 4 WIRE 1-2.00" 4 #3/0 CU 1 #6 CU - - -

2253 230 AMP, 3 WIRE SEE E301

SHEET

3 #4/0 CU 1 #4 CU

2254 230 AMP, 4 WIRE SEE E301

SHEET

4 #4/0 CU 1 #4 CU

2504 255 AMP, 4 WIRE SEE E301

SHEET

4 #250 KCMIL CU 1 #4 CU

T2504 255 AMP, 4 WIRE SEE E301

SHEET

4 #250 KCMIL CU 1 #2 CU

#2 CU IN 0.75" C. #2 CU B,F

4003 380 AMP, 3 WIRE SEE E301

SHEET

3 #500 KCMIL CU 1 #2 CU

- - D,E

4004 380 AMP, 4 WIRE SEE E301

SHEET

4 #500 KCMIL CU 1 #2 CU

- - D,E

T4004 400 AMP, 4 WIRE SEE E301

SHEET

2 SETS OF 4 #3/0 CU 1 #1/0 CU/SET

#1/0 CU IN 0.75" C, #1/0 CU B,F

6003 600 AMP, 3 WIRE SEE E301

SHEET

2 SETS OF 3 #400 KCMIL CU 1 #1 CU

- - D

16004 1680 AMP, 4 WIRE 4-3.50" 4 SETS OF 4 #600 KCMIL CU 1 #4/0 CU/SET - - D,G

1 2025/03/02 SFM RESUBMITTAL

V2

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

4/21/2026

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-3911

2026-06-30

V3

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

7/2/2026

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

R

ELECTRICAL

E E

NI

GN

E

LANOISSEFORP

DERET

SI

G

E R

C A L I F ORN

I A

S T A T E

O F

707 Third Street, Suite 4-105

Architecture & Engineering Sections

Project Management & Development Branch Real Estate Services Division

State of California

West Sacramento, California 95605

Department of General Services

CONSULTING ENGINEERS

ALAMEDA | AUBURN | LOS ANGELES

https://www.engent.com

NEOSHO | SAN DIEGO | SANTA BARBARA

JJ

AS NOTED

V1

C o p y ri g h t

C a lif o rn ia D e p a rt m e n t o f G e n e ra l S e rv ic e s

R e a l E s ta te S e rv ic e s D iv is io n

PROFESSIONAL

STAMP

0 1 2 3

Issue

DateNo. Description

Project

DSA App No.

Supervisor

Sheet Title

Designed

Sheet Number

Sheet Scale

Reference North

Project Number

Drawn

OSFM Permit No. 25-N-3911-C

12533

SWSW

1227 O STREET

SACRAMENTO, CA 95814

#E015491 Exp. 06/30/27

SCOTT WHEELER

PERMIT APPLICATION NO.

25-N-3911-C

TITLE 24

E003

CalVet Electrical Upgrades

V2

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

4/21/2026

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-3911

2026-06-30

V3

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

7/2/2026

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

1A 1B

1P

1LA 1LB

R

ELECTRICAL

E E

NI

GN

E

LANOISSEFORP

DERET

SI

G

E R

C A L I F ORN

I A

S T A T E

O F

707 Third Street, Suite 4-105

Architecture & Engineering Sections

Project Management & Development Branch Real Estate Services Division

State of California

West Sacramento, California 95605

Department of General Services

CONSULTING ENGINEERS

ALAMEDA | AUBURN | LOS ANGELES

https://www.engent.com

NEOSHO | SAN DIEGO | SANTA BARBARA

JJ

AS NOTED

V1

C o p y ri g h t

C a lif o rn ia D e p a rt m e n t o f G e n e ra l S e rv ic e s

R e a l E s ta te S e rv ic e s D iv is io n

PROFESSIONAL

STAMP

0 1 2 3

Issue

DateNo. Description

Project

DSA App No.

Supervisor

Sheet Title

Designed

Sheet Number

Sheet Scale

Reference North

Project Number

Drawn

OSFM Permit No. 25-N-3911-C

12533

SWSW

1227 O STREET

SACRAMENTO, CA 95814

#E015491 Exp. 06/30/27

SCOTT WHEELER

PERMIT APPLICATION NO.

25-N-3911-C

SCHEDULES -

PANELBOARDS -

1ST FLOOR

E005

CalVet Electrical Upgrades

{1} CONNECT EXISTING NITE LITES TO EXISTING CIRCUIT.

Notes:

Code Demand Amps: 0 A

Code Demand Load: 0 kVA

Connected Amps: 0 A

Connected Load: 0.00 kVA

Load Classification Conn. Load Demand Factor Code Demand Panel Totals

0 A 0 A 0 A

0 kVA 0 kVA 0 kVA

0 kVA 0 kVA 0 kVA

-- (N) SPARE 20 A 1 11 0.00 0.00 12 1 20 A (N) SPARE --

-- (N) SPARE 20 A 1 9 0.00 0.00 10 1 20 A (N) SPARE --

-- {1} (E) LTG FRONT STAIRS 20 A 1 7 0.00 0.00 8 1 20 A (E) LOAD --

-- (E) LOAD 20 A 1 5 0.00 0.00 6 1 20 A (E) LTG REAR STAIRS --

-- (E) LTG S.E. 20 A 1 3 0.00 0.00 4 1 20 A (E) LTG HALL --

-- (E) LTG N.E. 20 A 1 1 0.00 0.00 2 1 20 A (E) LTG REST RMS --

LC Load Served Amp P # A (kVA) B (kVA) C (kVA) # P Amp Load Served LC

Mounting: SURFACE Volts: 277/480 Wires 4 Main Type: MCB Main Rating: 50 A

Location: LEVEL 1 EAST ELEC. CLOSET Served From MDB Phases 3 A.I.C. Rating: 65KAIC Bus Rating 50 A

Branch Panel: PANEL 1A

{1} CONNECT EXISTING EXIT LTS TO EXISTING CIRCUIT

Notes:

Code Demand Amps: 0 A

Code Demand Load: 0 kVA

Connected Amps: 0 A

Connected Load: 0.00 kVA

Load Classification Conn. Load Demand Factor Code Demand Panel Totals

0 A 0 A 0 A

0 kVA 0 kVA 0 kVA

0 kVA 0 kVA 0 kVA

-- (N) SPARE 20 A 1 11 0.00 0.00 12 1 20 A (N) SPARE --

-- (N) SPARE 20 A 1 9 0.00 0.00 10 1 20 A (N) SPARE --

-- {1} (E) LOAD 20 A 1 7 0.00 0.00 8 1 20 A (E) LOAD --

-- (E) LTG GARAGE 20 A 1 5 0.00 0.00 6 1 20 A (E) LTG AVDT. --

-- (E) LTG WEST 20 A 1 3 0.00 0.00 4 1 20 A (E) LTG HALL --

-- (E) LTG SOUTH 20 A 1 1 0.00 0.00 2 1 20 A (E) LTG EXCERCISE RM. --

LC Load Served Amp P # A (kVA) B (kVA) C (kVA) # P Amp Load Served LC

Mounting: SURFACE Volts: 277/480 Wires 4 Main Type: MCB Main Rating: 50 A

Location: L1 WEST ELEC. CLOSET 115 Served From MDB Phases 3 A.I.C. Rating: 65KAIC Bus Rating 50 A

Branch Panel: PANEL 1B

{1} SEE PROJECT GENERAL SHEET NOTE 52 ON SHEET E002.

Notes:

Code Demand Amps: 0 A

Code Demand Load: 0 kVA

Connected Amps: 0 A

Connected Load: 0.00 kVA

Load Classification Conn. Load Demand Factor Code Demand Panel Totals

0 A 0 A 0 A

0 kVA 0 kVA 0 kVA

0 kVA 0 kVA 0 kVA

-- (N) SPARE 20 A 1 53 0.00 0.00 54 1 20 A (N) SPARE --

-- (N) SPARE 20 A 1 51 0.00 0.00 52 1 20 A (N) SPARE --

-- (N) SPARE 20 A 1 49 0.00 0.00 50 1 20 A (N) SPARE --

47 0.00 -- 48 1 -- space --

45 0.00 0.00 46 1 20 A (E) SPARE ---- (E) MAIN 100 A 3

43 0.00 0.00 44 1 20 A (E) SPARE --

-- (E) LOBBY TRACK LITES 20 A 1 41 0.00 0.00 42

-- (E) LOBBY TRACK LITES 20 A 1 39 0.00 0.00 40

-- (E) LOBBY TRACK LITES 20 A 1 37 0.00 0.00 38

3 20 A (E) GARAGE DOOR OPENER --

-- (E) LOBBY TRACK LITES 20 A 1 35 0.00 0.00 36 1 20 A (E) RECEPT. EXISTING --

-- (E) LOBBY TRACK LITES 20 A 1 33 0.00 0.00 34 1 20 A (E) RECEPT. EXISTING --

-- (E) DRINK. FOUNTAIN &... 30 A 1 31 0.00 0.00 32 1 20 A (E) RECEPT. EXISTING --

-- (E) FURNITURE PARTITIONS 20 A 1 29 0.00 0.00 30 1 20 A (E) RECEPT. EXISTING --

-- (E) FURNITURE PARTITIONS 20 A 1 27 0.00 0.00 28 1 20 A (E) HVAC TRANS. RECEPT. EAST --

-- (E) FURNITURE PARTITIONS 20 A 1 25 0.00 0.00 26 1 20 A (E) LOAD --

-- (E) FURNITURE…