Questions and Answers.pdf
PDF 2 MB Posted
- Attached to
- Clean Agent System Repairs
- Solicitation number
- 12444526Q0058
- Issued by
-
Department of Agriculture Forest Service
About this file
This document is a Questions and Answers (Q&A) file for a federal contract opportunity related to clean agent and dry chemical fire suppression system repairs at the Forest Products Laboratory.
The solicitation (1244526Q0058) addresses repairs to fire suppression systems across multiple buildings. Building 34 contains SHP Pro Fike control panels using 3M Novec 1230 clean agent and requires troubleshooting of solenoid assemblies in Room 215, panel programming review for horn-strobes in Rooms G11, G9, and G4, replacement of junction box covers in Room 209, and system rearm with documentation. The Hazardous Waste Building contains two 50-pound ABC dry-chemical tanks (either AutoPulse Z-10 or Ansul Automan II-C models, last hydro-tested December 2013) requiring removal, internal inspection, cleaning, rebuild of valve assemblies, refilling, recharging, and reinstallation, plus replacement of batteries and firing cartridges. All work, including discovery of additional failed components during troubleshooting, is to be included in a single firm-fixed-price bid. Prior certification occurred July 2, 2026, with all clean agent systems using 3M Novec 1230 and control panels being SHP Pro Fike model 10-063 Series. A pre-award site visit is permitted, and the Government requires one firm-fixed-price amount for the entire project rather than separate item-level pricing.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| C04b_Attachment B - Schedule of Items_12444526Q0058.xlsx | XLSX spreadsheet | |
| C04b_Attachment B - Schedule of Items_12444526Q0058.xlsx | XLSX spreadsheet | |
| C04a_Attachment A - Statement of Work_12444526Q0058.pdf | ||
| C04c_Attachment C - Wage Determination_12444526Q0058.pdf | ||
| C04d_Attachment D - Continuation of 1449_124445260058.pdf | ||
| C04b_Attachment B - Schedule of Items_12444526Q0058.xlsx | XLSX spreadsheet | |
| C04_12444526Q0058.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1244526Q0058 Forest Products Laboratory Clean Agent Systems Repairs
Questions and Answer
1. Please provide the manufacturer and model of the Building 34 clean-agent control panels and identify the clean agent used.
Panel: Single Hazard Panel (SHP) Pro Fike, Agent: 3M Novec 1230
2. Are the prior inspection or deficiency reports, wiring diagrams, panel programming records, or equipment information available?
Diagrams and equipment info is available if needed. Newer systems have only been inspected twice so far.
3. For Rooms G11, G9, and G4, should replacement of any failed horn-strobes, wiring, modules, or other components identified during troubleshooting be included in the firm-fixed price, or handled separately if discovered? Included.
4. Please provide the manufacturer, model, serial numbers, manufacture dates, and latest maintenance or hydrostatic-test dates for the two 50-pound ABC dry-chemical tanks in Building 46, if available.
Manufacturer: either AutoPulse or Ansul
Model: either Z-10 or Automan II-C
Serial #: 196623
Manuf. Dates: N/A
Last Hydro: December 2013 (not sure why previous inspections in previous years didn’t identify this issue)
5. Will a pre-award site visit be permitted? Yes
6. Are the prior certification dates, reports, equipment inventory, manufacturer/model information, cabinet classifications, or room locations available?
Prior certification occurred on July 2, 2026.
I’m awaiting a response from the company that performed the work as I have not received the written reports.
All the clean agent systems use 3M Novec 1230 for the extinguishant. All control panels are SHP Pro from Fike model 10-063 Series. Don’t have cabinet classifications. See attached clean agent/dry chemical system list.
7. First, the Schedule of Items contains multiple item lines, but most of the pricing fields are left blank. Should oƯerors provide separate pricing for each item associated with each building, or does the Government require one firm-fixed-price amount for the entire project under a single line item? ONE FIRM FIXED PRICE
8. Second, could you please provide the inspection report(s) covering the deficiencies identified for Building 34? We are particularly interested in the issue described under Item 5 concerning the horn/strobes in Rooms G11, G9, and G4 that did not operate correctly during the inspection.
Building 34 Clean Agent Fire Systems
1. Disarm Building 34 Clean agent fire suppression system panels
2. Room 215 remove solenoid assembly from fire system tank and troubleshoot wire and connections for proper locations per manufacture manual
3. Room 215 review panel program and make adjustment as needed for proper operation of panel release circuit
4. Room 215 once above work has been completed function test solenoid for proper operation and reinstall on fire system tank.
5. Room G11, G9, and G4 review panel programming and wiring to horn strobes that did not operate correctly during inspection and replace as necessary.
6. Room 209 provide and replace 5-mising 4 X 4 Junction box covers on fire system conduit wiring.
8. Rearm system and provide documentation of the above repairs and or proposal for the replacement of solenoid in room 215 if needed.
Hazardous Waste Building Dry Chemical Fire System
1. Disarm Ansul Dry system at control box before starting below repairs
2. Remove actuation and supply Line piping to 2- 50# Dry Chemical fire system ranks and remove from mounting brackets
3. Return to shop discharge, and internally inspect 2 -50#ABC dry chemical fire system tanks, clean and rebuild valve assembly, fill tanks and recharge to operating pressure
4. Return to site and reconnect tanks to existing actuation and supply lines, and wall brackets.
5. Provide and install 2- new 12v 7ah batteries in electrical fire suppression panel
6. Provide new 101-10 Ansul firing cartridge in Ansul actuation control box.
7. Rearm system and provide documentation of the above repairs.
Operation and Maintenance Manual
USDA - FPL
1 Gifford Pinchot Madison, WI 53726
NOVEC Fire Suppression System
763-536-3950 24 Hours
September 9, 2024
SECTION 1
PANEL OPERATION
SECTION 2
SYSTEM MANUAL
SOLUTIONS
Fire Protection
Explosion Protection
Overpressure Protection
Pressure Activation
PRODUCT MANUAL
CONVENTIONAL FIRE ALARM AND SUPPRESSION SYSTEM
Doc. P/N 06‐297 Rev. 5 / July, 2017
COPYRIGHT INFORMATION
© Copyright 2003, Fike Corporation. All rights reserved. Printed in the U.S.A.
This document may not be reproduced, in whole or in part, by any means without the prior written consent of Fike. All Fike documentation and hardware are copyrighted with all rights reserved.
TRADEMARKS
Fike and SHP‐Pro® are registered trademarks of Fike. All other trademarks, trade names or company names referenced herein are the property of their respective owners.
ERRORS AND OMMISSIONS
While every precaution has been taken during the preparation of this document to ensure the accuracy of its content, Fike assumes no responsibility whatsoever for errors or omissions.
Fike reserves the right to change product designs or specifications without obligation and without further notice in accordance with our policy of continuing product and system improvement.
READER QUESTIONS AND RESPONSES
If you have any questions regarding the information contained in this document, or if you have any other inquiries regarding Fike products, please call Fike’s Customer Support Department at (800)‐979‐FIKE (3453), option 21.
Fike encourages input from our distributors and end users on how we can improve this manual and even the product itself. Please direct all calls of this nature to Fike’s Customer Support Department at (800)‐979‐FIKE (3453), option 21.
Any communication received becomes the property of Fike.
TERMS AND CONDITIONS OF SALE
Because of the many and varied circumstances and extreme condition under which Fike’s products are used, and because Fike has no control over this actual use, Fike makes no warranties based on the contents of this document.
FIKE MAKES NO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A SPECIFIC PURPOSE. Refer to www.fike.com/terms‐conditions for Fike’s full TERMS AND CONDITIONS OF SALE.
TERMS OF USE
Do not alter, modify, copy, or otherwise misappropriate any Fike product, whether in whole or in part. Fike assumes no responsibility for any losses incurred by you or third parties arising from such alteration, modification, copy or otherwise misappropriation of Fike products.
Do not use any Fike products for any application for which it is not intended. Fike shall not be in any way liable for any damages or losses incurred by you or third parties arising from the use of any Fike product for which the product is not intended by Fike.
You should install and use the Fike products described in this document within the range specified by Fike, especially with respect to the product application, maximum ratings, operating supply voltage range, installation and other product characteristics. Fike shall have no liability for malfunctions or damages arising out of the use of Fike products beyond such specified ranges.
You should install and use the Fike products described in this document in compliance with all applicable laws, standards, and regulations. Fike assumes no liability for damages or losses occurring as a result of your noncompliance with applicable laws and regulations.
It is the responsibility of the buyer or distributor of Fike products, who distributes, disposes of, or otherwise places the product with a third party, to notify such third party in advance of the contents and conditions set forth in this document. Fike assumes no responsibility for any losses incurred by you or third parties as a result of unauthorized use of Fike products.
QUALITY NOTICE
Fike has maintained ISO 9001 certification since 1996. Prior to shipment, we thoroughly test our products and review our documentation to assure the highest quality in all respects.
PAGE / 1
REVISION HISTORY
ORIGINAL RELEASE DATE: .................................................................................................................................... October, 2003
REVISION / DESCRIPTION OF CHANGE REVISION DATE
REV 1 ALL SECTIONS, UL 9TH
EDITION REVISIONS...................................................................................................... JULY, 2006
REV 2 ALL SECTIONS, UL 9TH
EDITION REVISIONS..................................................................................................... APRIL, 2008
REV 3 SECTIONS 3, 4 AND 6, CHANGED AGENT RELEASE CIRCUIT EOL VALUE TO 2.4K ............................................... AUGUST, 2008
REV 4 SECTIONS 2 THRU 6, ADDED IRM AS COMPATIBLE RELEASING DEVICE ............................................................. MARCH, 2010
REV 5 ALL SECTIONS, UPDATED TO NEW FIKE DOCUMENT STANDARDS AND ADDED NEW HOCHIKI SOC DETECTORS ............. JULY, 2017
PAGE / 2 Doc. P/N 06‐297
TABLE OF CONTENTS
Section Page No.
Revision History
Table of Contents
List of Figures
1. General Information
1.1. About This Manual
1.2. Product Support
1.3. Terms Used in this Manual
1.4. Symbols Used in this Manual
1.5. Safety Notices
1.6. FCC Compliance
2. Product Overview
2.1. Description
2.2. Listings and Approvals
2.3. Agency Compliance and Standards
2.4. Related Documentation
2.5. SHP‐Pro Features
3. Main Panel Hardware
3.1. SHP‐Pro Control System
3.1.1. SHP‐Pro Controller
3.1.2. Class‐A Input Module
3.1.3. Class‐A Output Module
3.1.4. CRM4 Relay Module
3.1.5. Standby Batteries
3.1.6. 33 AH Battery Enclosure
3.1.7. 75 AH Battery Enclosure
3.2. Compatible Input/Output Devices
3.3. Ancillary Devices
3.4. Spare Parts
4. Hardware Specifications
4.1. SHP‐Pro Control Board
4.1.1. Detector Base Selection
4.1.2. Circuit Impedance Limitations
4.2. Class‐A Input Card
4.3. Class‐A Output Card
4.4. CRM4 Relay Card
4.5. Enclosure
5. Installation
5.1. Enclosure
5.2. Modules
5.2.1. Optional Modules
5.2.1.1. Class‐A Input Module
5.2.1.2. Class‐A Output Module
5.2.1.3. CRM4 Relay Module
5.2.2. SHP‐Pro Control Board
5.3. AC Transformer
PAGE / 3
TABLE OF CONTENTS
Section Page No.
5.4. Standby Batteries
5.5. Field Wiring
5.5.1. Wire Selection
5.5.2. Wiring Verification
5.5.3. Initial Power‐Up
5.5.4. Wiring Diagrams
5.5.4.1. AC Power and Chassis Wiring
5.5.4.2. Battery Wiring
5.5.4.3. Relay Wiring
5.5.4.4. Detection and Input Circuits Wiring
5.5.4.5. Auxiliary Power Circuit Wiring
5.5.4.6. Audible and Releasing Circuits Wiring
5.5.4.7. Class‐A Input Module Wiring
5.5.4.8. Class‐A Output Module Wiring
5.5.4.9. CRM4 Relay Module Wiring
6. System Configuration
6.1. Application Details
6.1.1. Application #1 Detail – Clean Agent Release Only
6.1.2. Application #2 Detail – Clean Agent and Sprinkler Protection
6.1.3. Application #3 Detail – Preaction Sprinkler/Deluge
6.1.4. Application #4 Detail – Industrial Solenoid
6.2. Audible Options
6.3. Abort Types
7. System Checkout
8. Operation
8.1. Controls and Indicators
8.2. Diagnostic LED Code Designators
8.3. Latching Versus Non‐latching Troubles
8.4. Supervision Response Times
8.5. Low Power Conditions
8.6. Linear Heat Detection Cable
8.7. Typical System Operation
8.8. SHP‐Pro Input/Output Matrix
9. Servicing
10. Maintenance
11. Troubleshooting
Appendix 1 – Battery Calculations
Appendix 2 – System Operation Posting
PAGE / 4 Doc. P/N 06‐297
LIST OF FIGURES
Figure 1 SHP‐Pro Block Diagram Figure 2 SHP‐Pro Control System Figure 3 Ordering Information Figure 4 SHP‐Pro Controller Figure 5 Class A Input Module Figure 6 Class A Output Module Figure 7 CRM4 Relay Module Figure 8 SLA Battery Figure 9 33 AH Battery Enclosure Figure 10 75 AH Battery Enclosure Figure 11 Table of Compatible Input Devices Figure 12 Table of Compatible Ancillary Devices Figure 13 Table of Spare Parts Figure 14 SHP‐Pro Controller Figure 15 SHP‐Pro Controller Circuit Specifications Figure 16 SHP‐Pro Controller Circuit Specifications – Continued Figure 17 SHP‐Pro Controller Circuit Specifications – Continued Figure 18 Detector Base Selection Guide Figure 19 Field Wiring Resistance Limitations Figure 20 Class A Input Card Figure 21 Class‐A Input Card Specifications Figure 22 Class A Output Card Figure 23 Class‐A Input Card Specifications Figure 24 CRM4 Relay Card Figure 25 CRM4 Relay Card Specifications Figure 26 Enclosure Dimensions Figure 27 Optional Module Mounting Locations Figure 28 Class‐A Input Module Mounting Figure 29 Class‐A Output Module Mounting Figure 30 CRM4 Module Mounting Figure 31 SHP‐Pro Board Mounting Figure 32 Power Limited vs. Non‐Power Limited Wire Segregation Figure 33 Conductor Properties Figure 34 Maximum Circuit Current Figure 35 AC Power and Transformer Wiring Figure 36 Standby Battery Wiring Figure 37 Common Relay Wiring Figure 38 Detection and Input Circuits Wiring Figure 39 0 Ω Jumper Locations Figure 40 Auxiliary Power Circuit Wiring Figure 41 Audible and Release Circuit Wiring Figure 42 Solenoid Circuit Disconnect Wiring Figure 43 Class A Detection Input #1 and #2 Wiring Figure 44 Class A Input #3, #4 and #5 Wiring Figure 45 Class A Audible Outputs #1 Thru #3 Wiring Figure 46 Class A Agent Release Output Wiring Figure 47 Class a Solenoid Output Wiring Figure 48 CRM4 Relay Module Wiring Figure 49 UL Non‐complying Features Figure 50 Dip‐Switch Configuration Table Figure 51 Table of Audible Options Figure 52 SHP‐Pro Control Switches and Status LEDs Figure 53 Control Switches and Status LEDs Descriptions Figure 54 Control Switches and Status LEDs Descriptions – Continued Figure 55 Diagnostic LED Codes Figure 56 Fault Resolutions Figure 57 Fault Resolutions – Continued
PAGE / 5
1. GENERAL INFORMATION
1.1. About This Manual
This manual is intended to be a complete reference for the installation, operation, and service of the Fike Single Hazard Panel Professional (SHP‐Pro) Fire Alarm/Suppression Control System. The information contained in this manual must be utilized by the factory trained Fike distributor in order to properly install, test and service the SHP‐ Pro. This manual can also be used by the end user as an Operations Manual for the SHP‐Pro.
Before you refer to any section in this manual, and before you attempt to install or use the SHP‐Pro, be sure to read the important safety notices in Section 1.5.
This manual is divided into sections for easy reference. The first‐time installer and/or user should thoroughly read and understand the instructions contained within this manual before using this device. These instructions must be followed to avoid possible damage to the SHP‐Pro itself or adverse operating conditions caused by improper installation and programming.
1.2. Product Support
If you have a question or encounter a problem not covered in this manual, you should first try to contact the distributor that installed the protection system. Fike has a worldwide distribution network. Each distributor sells, installs, and services Fike equipment. Look on the inside of the door, left side, there should be a sticker with an indication of the distributor who sold the system. If you cannot locate the distributor, please call Fike Customer Service for locating your nearest distributor, or go to our web‐site at www.fike.com. If you are unable to contact your installing distributor or you simply do not know who installed the system you can contact Fike Product Support at
(800) 979‐FIKE (3453), Monday through Friday, 8:00 a.m. to 4:30 p.m. CST.
1.3. Terms Used in This Manual
The following are various terms used in this manual with a brief description of each:
‐ Symbol for “ohm”. Unit of resistance.
AC Normal State (“AC Normal” Green LED ON) ‐ The system is in the AC Normal state when appropriate AC power is being applied to the system.
Abort ‐ An input to a suppression system to prevent an unwanted discharge of fire suppressant agent. The SHP‐Pro has several different abort types.
Alarm State (“Alarm” Red LED ON, Piezo pulsing) ‐ The alarm occurs when an input circuit configured for alarm operation has been activated. Activation typically initiated by a detector or contact device. The system leaves the alarm state upon entry into the pre‐discharge or release state.
Class A wiring ‐ Input circuits capable of transmitting an alarm signal during a single open or a non‐simultaneous single ground fault on a circuit conductor shall be designated as Style D or Class A. Similarly, output circuits capable of activating during a single open or a non‐simultaneous ground fault on a circuit conductor shall be designated as Style Z or Class A. Commonly referred to as redundant or 4‐wire connection; this manual refers to 4‐wire connections as Class A wiring.
Class B wiring ‐ Input circuits incapable of transmitting and alarm signal beyond the location of the fault condition (listed for Class A wiring above) shall be designated as Style B or Class B. Similarly, output circuits incapable of operating beyond the location of the fault condition shall be designated as Style Y or Class B. This manual refers to 2‐ wire connections as Class B wiring
Initiating Device ‐ A system component that originates transmission of a change‐of‐state condition, such as in a smoke detector, manual fire alarm box, or supervisory switch. This manual interchanges the terms initiating device and input device.
PAGE / 6 Doc. P/N 06‐297
1.3 Terms Used in This Manual – Continued
Initiating Device Circuit ‐ A circuit to which automatic or manual initiating devices are connected where the signal received does not identify the individual device operated. This manual interchanges the terms initiating device circuit and input circuit.
Normal State (“Trouble” Yellow LED OFF) ‐ The system is in the normal state when the power supply and all circuits are configured properly, connected, and responding properly. The system remains in normal state until a trouble condition occurs.
Cross‐zone Detection ‐ A detection scheme where two detectors must activate before the system enters into the pre‐ discharge state: at least one detector from each detection initiating circuit must be active.
Notification Appliance ‐ A fire alarm system component such as a bell, horn, speaker, light, or textual display that provides audible, tactile, or visible output, or any combination thereof. The device notifies building occupants of system status. This manual interchanges the terms notification and audible appliance.
Notification Appliance Circuit ‐ A circuit or path directly connected to a notification appliance(s). This manual interchanges the terms notification appliance circuit and audible circuit.
Non‐Power Limited ‐ A circuit designation given for wiring purposes. The amount of current flowing through the circuit is unlimited vs. being limited, or power limited. AC power and Battery wiring is Non‐Power Limited.
Power Limited ‐ A circuit designation given for wiring purposes. The amount of current flowing through the circuit is limited (typically by fuse) vs. being unlimited, or non‐power‐limited. The SHP‐Pro input and output circuits are power‐ limited. The circuit has a maximum power that flows through it or it current limits and opens the circuit.
Pre‐discharge Delay ‐ The time (in seconds) that the system will delay entering the release state after the zone’s detection type has been satisfied. Activation of an abort switch will have an effect on this value, depending upon the abort type selected.
Pre‐discharge State (“Alarm” Red LED ON, Piezo chirping) ‐ The pre‐discharge state occurs when the zone’s detection type input conditions are satisfied (Cross‐zone Detection, Sequential Alarm Detection, or Single Detector Release).
Upon time delay countdown completion (unless delayed by a pertinent activated abort input), the system leaves the pre‐discharge state and enters the release state.
Release State (“Alarm” Red LED ON, Piezo chirping) ‐ The release state occurs upon completion of the pre‐discharge state or upon activation of a manual release input. At the start of the release state, output circuits configured for releasing shall operate
Sequential Detection ‐ A detection scheme where the sum total of active detectors on the detection initiating circuits must be two or more before the system will enter the pre‐discharge state.
Single Detector Release Detection ‐ A detection scheme where activation of one detector causes the system to enter the pre‐discharge state. SDR (Single Detector Release) detector(s) are installed on initiating circuits setup for sequential detection.
Solenoid On Time ‐ The time (in minutes) that the solenoid is activated upon entering the release state. Reset of the system overrides this value.
Supervisory State (“Supervisory” Yellow LED ON, Piezo Warble) ‐ The supervisory state occurs upon activation of a supervisory input circuit. The supervisory state is non‐latching and will follow the status of the supervisory input contact.
Trouble State (“Trouble” Yellow LED ON, Piezo Constant) ‐ The trouble state occurs upon any detectable condition which could impair system operation including connection problems, ground faults, hardware problems, power problems, configuration problems, or prematurely activated abort inputs. Certain trouble conditions are latching;
others allow the system to reset upon trouble condition removal. Depending upon the type of trouble condition, the system may or may not remain operational. When the system is in trouble state, it is not in the normal state.
PAGE / 7
1.4. Symbols Used in This Manual
The following cautions and warnings appear in this manual. Be certain to read all of the following warning and cautions before attempting to install or use this device. Personal injury or accidental release of the suppression system may result if these warnings and cautions are NOT followed!
Warning Symbol – This symbol is used in this manual to warn of possible injury or death from improper use or application of the product under noted conditions.
Caution Symbol – This symbol warns of possible personal injury or equipment damage under noted conditions. Follow all safety standards of professional practice and the recommendations in this manual. Using equipment in ways other than described in this manual can present serious safety hazards or cause equipment damage.
Notes – This symbol indicates the message is important, but is not of a Warning or Caution category. These notes can be of great benefit to the user and should be read.
Tips – Tips provide advice that may save time during a procedure, or help to clarify an issue. Tips may include additional reference.
1.5. Safety Notices
Be certain to read all the following warnings and cautions before installing or using this device. Accidental damage to the device could result if these warnings and cautions are NOT heeded!
CAUTION: The SHP‐Pro contains static sensitive components. Handle the electronics by the edges only and avoid touching the integrated components. Keep the electronics in the protective static bags it was shipped in until time for installation. Always ground yourself with a proper wrist strap before handling the module(s). If the installer is properly grounded at all times, damage due to static discharge will not occur. If the module requires repair or return to Fike, it must be shipped in an anti‐static bag.
CAUTION: To ensure proper system operation after installation of the SHP‐Pro, this device must be tested in accordance with NFPA 72. Re‐acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
WARNING: Failure to disconnect power to the releasing circuit(s) and completely disarm the solenoid(s) or any other "critical operation" contacts prior to system testing may cause accidental activation of the system.
1.6. FCC Compliance
This equipment has been tested and found to comply with the limits for Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at this own expense.
PAGE / 8 Doc. P/N 06‐297
2. PRODUCT OVERVIEW
2.1. Description
The Fike SHP‐Pro (P/N 10‐063 Series) is a compact, cost‐effective, conventional fire alarm and suppression releasing panel. The SHP‐Pro is designed for use with Fike Clean Agent Fire Suppressant, CO2, sprinkler (pre‐action/deluge), or other industrial solenoid‐based suppression systems. The SHP‐Pro controller is shipped from the factory pre‐ configured for Clean Agent suppression operation.
The main controller contains all electronics required for a complete detection and control system suitable for most applications. Optional modules, which plug into the main circuit board, are available to add increased functionality to the system.
Figure 1 SHP‐Pro Block Diagram
2.2. Listings and Approvals
Approval Agency File Number
Underwriters Laboratories S2203
Type: Local, Remote Station, Central Station PPU Service Type: A‐Automatic Fire Alarm, M‐Manual Fire Alarm WF‐Water‐flow Alarm, SS‐Sprinkler Supervisory, Releasing, DACT
Type Signaling: Non‐coded
Factory Mutual (FM) 3017159
California State Fire Marshall 7165‐0900:135
City of New York (MEA) 461‐04‐E
Hong Kong 206/0877 VII
Smoke and
Thermal
Detectors
Waterflow and
Sprinkler Supervisory
Manual Fire Alarm or Manual
Releasing Stations
Sprinkler
Operation
Clean Agent, CO2, or Watermist
Release
Audible and
Visual Alarm
Signals
Notification
Appliances
PAGE / 9
2.3. Agency Compliance Standards
This fire alarm control panel complies with the following NFPA and UL Standards:
NFPA 72 – National Fire Alarm Code UL 864 – Control Units and Accessories for Fire Alarm Systems
Related Fire Alarm Standards:
National Fire Protection Association (NFPA) Codes:
NFPA 12 – Carbon Dioxide Extinguishing Systems (High Pressure Only) NFPA 12A – Halon 1301 Extinguishing Systems
NFPA 13 – Sprinkler Systems NFPA 15 – Water Spray Fixed Systems NFPA 16 – Deluge, Foam‐water and Foam‐water Spray Systems NFPA 70 – National Electrical Code (NEC) NFPA 70, Article 300 – Wiring Methods NFPA 70, Article 760– Fire Protective Signaling Systems NFPA 72 – National Fire Alarm Code NFPA 101 – Life Safety Code NFPA 110 – Emergency Standby Power Systems NFPA 2001 – Clean Agent Fire Extinguishing Systems
Underwriters Laboratories (UL) Standards:
UL 38 – Manually Actuated Signaling Boxes UL 217 – Smoke Detectors, Single and Multiple Station UL 228 – Door Closers – Holders for Fire Protective Signaling Systems UL 268 – Smoke Detectors for Fire Protective Signaling Systems UL 268A – Smoke Detectors for Duct Applications UL 346 – Waterflow Indicators for Fire Protective Signaling Systems UL 464 – Audible Signaling Appliances UL 521 – Heat Detectors for Fire Protective Signaling Systems UL 1481 – Power Supplies for Fire Protective Signaling Systems UL 1638 – Visual Signaling Appliances UL 1971 – Visual Signaling Appliances
Factory Mutual (FM) Standards:
FMRC 1011 and 1012 – Deluge and Pre‐action Sprinkler Systems FMRC 3820 – Electrical Utilization Equipment
Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction
2.4. Related Documentation
To obtain a complete understanding of the specific features of the SHP‐Pro or to become familiar with related functions in general, refer to the documentation listed below. Please reference the most current version or the version noted on the label located on the product.
06‐106 – Agent Release Module (ARM III) Manual
06‐186 – Compatible Notification and Releasing Devices
06‐159 – DACT/Fire Communicator Addendum
06‐160 – DACT/Fire Communicator Manual
02‐11060 – SHP‐Pro System Operation Posting
06‐552 – Impulse Releasing Module Product Manual
PAGE / 10 Doc. P/N 06‐297
2.5. SHP‐Pro Features
General
Microprocessor‐controlled
Power‐limited on all circuits except power connections (P1)
Four operational modes:
1. Clean agent release (10‐2452‐1)
2. Clean agent release with sprinkler operation (10‐2452‐1)
3. Sprinkler operation (10‐2452‐1, 10‐2452‐2)
4. Industrial releasing (10‐2452‐1)
Ten system status LEDs to provide positive indication of system status
Seven segment diagnostic LED for trouble and event occurrences
System configuration via dip‐switches
Local piezo with distinct event tones
Reset switch
Audible silence switch
Disable Mode for audible and release circuits, and relays
Alarm and trouble resound
Power
Integral power supply at 24VDC nominal; 1.0 Amp total normal standby / 4.0 Amp alarm
Selection of 120, or 240VAC power input at 50 or 60 hertz
Re‐settable and non‐re‐settable special application power output
Battery/Earth fault supervision
7 AH to 40 AH battery options, up to 90 hours (Factory Mutual) standby
Enclosure
Steel enclosure 21” high by 14.35” wide by 4” deep (Back‐box dimensions)
Enclosure is equipped with a .50” wide lip to facilitate flush mounting
Removable door for easy installation
Enclosure is available in Red or Gray
Initiating Device Circuits
Up to two Style B initiating device circuits capable of sequential alarm, cross‐zone, or single detector release operation with an overall system capacity of 50 detectors maximum
Three Style B initiating device circuits capable of monitoring closed contact devices Optional Class A module that converts all five initiating device circuits to Style D wiring and operation
Notification Appliance Circuits
Three Style Y notification appliance circuits rated at 2.0 amps each Optional Class A module that converts all five output circuits to Style Z (3 NAC, 2 releasing)
Releasing Circuits
One Agent Release circuit with maximum of 6 ARM’s or IRM’s (any combination) One Solenoid release circuit which can activate one 24V or two 12V solenoids Model 10‐063‐1 provides option to use both releasing circuits simultaneously
Relays
General Alarm, Supervisory and Trouble relays Two Optional CRM4 modules to add eight more SPDT dry relay contact outputs
Sprinkler Monitoring Points
Waterflow input Supervisory input
PAGE / 11
3. MAIN PANEL HARDWARE
3.1. SHP‐Pro Control System
The 10‐063, SHP‐Pro Control System (Figure 2) includes the main controller, transformer, and steel enclosure with red or gray finish. The enclosure is equipped with a removable door to facilitate installation of the enclosure back box. The door is fitted with a standard Fike key‐lock and a viewing window covered with clear Lexan. The enclosure back‐box is 21” (533
mm) high x 14.35“ (364 mm) wide x 4“ (102 mm) deep. It also includes a 0.5” (13 mm) lip around the back box to facilitate flush mounting. The enclosure includes space for installing up to 18 AH batteries (ordered separately).
Refer to Section 4.5 for a complete detail of the back‐box features and dimensions.
The basic part numbers for the components covered in further detail in this section are as follows:
Part Number Description
10‐063‐m‐c‐p
SHP‐Pro Control System m: 1 = all modes 2 = sprinkler mode only c: R = red, G = gray p: 1 = 120VAC, 2 = 240VAC
10‐2452 ‐ m
SHP‐Pro Controller Printed Circuit Board m: 1 = all modes 2 = sprinkler mode only
Compatibility Identifier for this product is “SHP‐PRO”
10‐2450 Class A Input Module
10‐2448 Class A Output Module
10‐2204 CRM4 Relay Module
10‐2190‐b Battery Assembly (AH selection: b: 1 = 7 AH, 2 = 18 AH)
NOTE: Assembly includes 10‐2192 wire assembly
02‐3468 Battery, 12VDC, 35 AH
10‐2154‐C Battery Enclosure, 33 AH, where C= R for Red; G for Gray
A02‐0252 Battery, 12 VDC, 40 AH (requires 75 AH enclosure)
10‐2236‐C Battery Enclosure, 75 AH, where C= R for Red; G for Gray
Figure 3 Ordering Information
Figure 2 SHP‐Pro Control System
PAGE / 12 Doc. P/N 06‐297
3.1.1. SHP‐Pro Controller (P/N 10‐2452)
The SHP‐Pro controller (Figure 4) is the heart of the SHP‐Pro control panel. It contains the system’s central processing unit, power supply, and other primary components. It also includes the electronics required to support the optional Class A modules and CRM4 Relay modules.
3.1.2. Class‐A Input Module (P/N 10‐2450)
The optional Class‐A Input Module (See Figure 5) allows all of the five initiating device circuits to be wired Class A (Style D) versus the standard Class B (Style B). The Class A module mounts directly onto the SHP‐Pro Controller at P6 utilizing two standoffs supplied with the module.
3.1.3. Class‐A Output Module (P/N 10‐2448)
The optional Class A Output Module allows all of the three notification appliance and both releasing circuits to be wired Class A (Style Z) versus the standard Class B (Style Y). The Class A module mounts directly onto the SHP‐Pro Controller at P7 utilizing two standoffs supplied with the module.
3.1.4. CRM4 Relay Module (P/N 10‐2204)
The optional CRM4 Relay Module provides four SPDT dry contact relays, which activate upon selected events per the configuration switches. The CRM4 Relay modules mount directly onto the SHP‐Pro Controller at P8 or P9 utilizing four stand‐offs supplied with the module.
3.1.5. Standby Batteries
Batteries are required for alarm systems for maintaining emergency back‐up power. Two each 12V batteries are required and are to be wired in series for maintaining a 24VDC back‐up. Most systems require at least a 24 hour standby current with 5 minutes alarm current for determining minimum battery size. Refer to Appendix 1 for Battery Calculation form for determining required battery size for system.
02‐2018 ‐ (1) 7AH, 12 VDC battery
02‐2820 – (1) 18AH, 12 VDC battery
02‐3468 – (1) 35AH, 12 VDC battery
A02‐0252 – (1) 40AH, 12 VDC battery
Figure 4 SHP‐Pro Controller
Figure 5 Class A Input Module
Figure 6 Class A Output Module
Figure 7 CRM4 Relay Module
Figure 8 SLA Battery
PAGE / 13
3.1.6. 33 AH Battery Enclosure (P/N 10‐2154‐R/G)
The 33 AH Enclosure is a heavy gauge metal enclosure (21”w x 11”h x 5”d) and is large enough to house two each 33 AH batteries. Conduit knockouts are provided for entry of battery wiring. The box lid is installed onto the back‐box using the 4 mounting screws provided.
Refer to Fike document 06‐534 for installation instructions.
3.1.7. 75 AH Battery Enclosure (P/N 10‐2236‐R/G)
The 75 AH Enclosure is a heavy gauge metal enclosure (26 1/4”w x 14”h x 7”d) and is large enough to house two each 40 AH batteries. Conduit knockouts are provided to provide entry of battery wiring. The box lid is installed onto the back‐box using the 4 mounting screws provided.
Refer to Fike document 06‐535 for installation instructions.
Figure 9 33 AH Battery Enclosure
Figure 10 75 AH Battery Enclosure
PAGE / 14 Doc. P/N 06‐297
3.2. Compatible Input/Output Devices
The following table lists devices that are approved for use with the SHP‐Pro’s input circuits. Other devices such as contact closure input devices, contact closure detectors, notification appliances, and Solenoids are listed in the Fike Compatibility Document, P/N 06‐186. Refer to Section 4.1.1 for selecting the appropriate detector base for system operation.
Mfg Replacement P/N Part Number Mfg Model Number Description
Sy st e m S e n so r
63‐1015 1 2451 Photoelectric Detector
63‐1017 1 2451TH Photo/heat Detector
67‐1025 1 1451 Ionization Detector
60‐1027 3 5151 135 Thermal Detector
63‐1014 2151 Photoelectric Detector, Low Profile
67‐1040 1151 Ionization Detector, Low Profile
67‐1023 1151 Ionization Detector
67‐1026 1,6 B401BR 470 base, 6‐inch
67‐1029 6 B110RLP 470 Low Profile Base, 6‐inch
67‐1031 6 B401B 0 Base, 6‐inch
H o ch ik i
63‐1024 1 SLR‐24V Photoelectric Detector
67‐1033 1 SIJ‐24 Ionization Detector
63‐1025 SLR‐24H Photo/Thermal Detector
63‐1307 4 SOC‐24V Photoelectric Detector
63‐1308 4 SOC‐24VN Photoelectric Detector, no test feature
60‐1020 3 DFE‐135 135 F Fixed Temperature Heat Detector
60‐1022 3 DFE‐190 190 F Fixed Temperature Heat Detector
60‐1029 3 DCD‐135 135 F Fixed, Rate of Rise Heat Detector 60‐1030 3 DCD‐190 190 F Fixed, Rate of Rise Heat Detector 67‐1034 5,7 NS6‐224 430 Base, 6‐inch
67‐1036 5,7 NS4‐224 430 Base, 4‐inch
67‐1035 5,7 NS6‐220 220 Base, 6‐inch
67‐1037 5,7 NS4‐220 220 Base, 4‐inch
67‐1034 5,7 67‐1027 1 HSB‐224 430 Base, 6‐inch
67‐1036 5,7 67‐1028 1 YBA‐M224 430 Base, 4‐inch
67‐1035 5,7 67‐1010 1 HSB‐220 220 Base, 6‐inch
67‐1037 5,7 67‐1017 1 YBA‐M220 220 Base, 4‐inch
Li n e ar H e at D e te ct io n C ab lin g
(S e e n o te s a n d
63‐1067 TC155 155°F, 0.05Ω/Ft , 500 ft. spool length
63‐1107 TC155 155°F, 0.05Ω/Ft , 1500 ft. spool length
63‐1108 TC155 155°F, 0.05Ω/Ft , 3000 ft. spool length
63‐1068 TC172 172°F, 0.05Ω/Ft , 500 ft. spool length
63‐1109 TC172 172°F, 0.05Ω/Ft , 1500 ft. spool length
63‐1110 TC172 172°F, 0.05Ω/Ft , 3000 ft. spool length
63‐1065 TC190 190°F, 0.05Ω/Ft , 500 ft. spool length
63‐1111 TC190 190°F, 0.05Ω/Ft , 1500 ft. spool length
63‐1112 TC190 190°F, 0.05Ω/Ft , 3000 ft. spool length
63‐1066 TC220 220°F, 0.05Ω/Ft , 500 ft. spool length
63‐1113 TC220 220°F, 0.05Ω/Ft , 1500 ft. spool length
63‐1114 TC220 220°F, 0.05Ω/Ft , 3000 ft. spool length
Figure 11 Table of Compatible Input Devices
NOTES:
1. Device has been discontinued by manufacturer. Listed for retrofit compatibility.
2. UL approved up to 8,800 ft. (2,682 m) and FM approved up to 10,000 ft. (3,048 m) for Alarm state only. 5,500 ft. (1,676 m) for Pre‐ discharge/SDR operation.
3. Heat detectors are for property protection only, not Life Safety!
4. UL listed only. Not FM approved.
5. Base provides terminals for connection to conventional graphic panel.
6. Base is compatible with all System Sensor detectors listed.
7. Base is compatible with all Hochiki detectors listed.
PAGE / 15
3.3. Ancillary Devices
The following table lists several ancillary devices that can be used in conjunction with the SHP‐Pro panel to provide increased system flexibility and performance. For detailed wiring instructions for each of these devices refer to the appropriate product manual.
P/N Manual P/N Description Function
10‐2256 (obsolete)
06‐159 Digital Alarm Communicator Transmitter (DACT).
Complies with NFPA 72‐Supervising Station Fire Alarm System.
The SHP‐Pro panel is capable of communicating to a central station via the DACT (optional). The DACT monitors the relay outputs of the SHP‐Pro.
This model provides 4 channel inputs; 3 standard inputs with one programmable selection. It is necessary to program the DACT with the 10‐2257 programmer and 10‐2258 cable or 10‐2259 modem and 06‐151 software.
10‐2476 5 Zone Digital Alarm Communicator Transmitter (DACT).
Complies with NFPA 72‐Supervising Station Fire Alarm System.
The 5 zone DACT contains inputs configurable for one of the seven types of conditions: Fire Alarm, Waterflow Alarm, Supervisory, Monitor Alarm, System Fault, AC Failure, and Low Battery. It is programmable using the 10‐2477 programmer.
10‐1832 06‐106 ARM‐III (Agent Release Module) Provides a releasing means for Fike’s Clean Agent suppression systems with GCA valves
The SHP‐Pro panel is capable of supporting up to 6 ARM’s on the single Agent Release Output Circuit. The ARM is required for each Clean Agent Suppressant Container equipped with a GCA valve.
Refer to the ARM manual, 06‐106 for detailed instructions on the ARM.
Conventional Graphic Annunciator
GEMCOM, Inc.
8028 S. Archer Ave.
Willow Springs, Il.
60480‐1204 Toll Free: 888‐4‐GEMCOM
Graphic Annunciators provide a graphic display of the protected area using LED’s to indicate the location of the smoke detectors. The LED will illuminate when the detector is in alarm.
Hochiki NS4 and NS6 detector bases must be used for graphic panel interface.
10‐2748 06‐552 Impulse Releasing Module Provides a releasing means for Fike’s Clean Agent suppression systems with Impulse valves.
The SHP‐Pro panel is capable of supporting up to 6 IRM’s on the single Agent Release Output Circuit. The IRM is required for each Clean Agent Suppressant Container equipped with an Impulse valve.
Refer to the IRM manual, 06‐552 for detailed instructions on the IRM.
06‐588 Compatible Surge Protection Devices Provides a complete list of Emerson Power surge suppression devices approved for use with the SHP‐Pro.
Figure 12 Table of Compatible Ancillary Devices
PAGE / 16 Doc. P/N 06‐297
3.4. Spare Parts
The following table lists spare parts used with the SHP‐Pro control system.
Description Part Number
Keylock with cam 02‐1606
Panel Key Only (without cam) 02‐12025
Battery, 7 Amp‐Hour 02‐2018
Battery, 18 Amp‐Hour 02‐2820
Battery, 35 Amp‐Hour 02‐3468
Battery, 40 Amp‐Hour A02‐0252
Wire Assembly, 7/18 AH Batteries 10‐2192
Standoff and lock washer/hex nut kit (30 each) 02‐4035
Transformer, 110VAC 02‐10881
Transformer, 240 VAC 02‐10882
Releasing circuit EOL assembly, 2.4K, 1W 5% 02‐12281
Switch circuit 3,4 & 5 EOL assembly, 20K 10‐2461
Detection circuit 1 & 2 circuit EOL assembly, 4.3K 10‐2318
Audible output circuit EOL assembly, 1.2K 10‐2570
Fuse, 10 Amp, Mini Auto, Fast Acting (For F1 & F2) 02‐4173
Fuse, 4 Amp, Mini Auto, Fast Acting (For F3 & F4) 02‐11412
Flashbulb (for testing ARM III release) 12/box 02‐3799
End Of Line Relay ‐ Hochiki 02‐4667
End Of Line Relay – System Sensor 02‐4981
Touch‐Up Paint (Not available from Fike)
Sherwin Williams, Signal Red, RAL 3001 per RAL 840‐HR (matt finish)
Sherwin Williams, Light Gray, RAL 7035 per RAL 840‐HR
Figure 13 Table of Spare Parts
PAGE / 17
4. HARDWARE SPECIFICATIONS
NOTE: All electronics are rated 32 ‐ 120°F (0 ‐ 49°C), 93% relative humidity.
4.1. SHP‐Pro Control Board (P/N 10‐2452)
Figure 14 SHP‐Pro Controller
Figure 15 SHP‐Pro Controller Circuit Specifications
Index Terminal Description Specifications
1 Transformer H1 and H2
Primary AC power input to Transformer Primary
AC line power must originate from a dedicated circuit at the main building power distribution center.
Circuit breaker shall be equipped with a lockout mechanism and be clearly labeled as a “Fire Protection Control Circuit”.
Power Input:
− 120 VAC, 50/60 Hertz, 2.6 A, 250 VA − 240 VAC, 50/60 Hertz, 1.5 A, 250 VA
2 P1‐1 and P1‐2 Transformer Secondary to SHP‐Pro AC Secondary
The SHP‐Pro’s internal power supply provides 4.135 amps of 24 VDC power.
Controller power consumption = 0.135 amps at 24 VDC in the normal standby mode.
Voltage: 20.5 – 28.1 VAC
Non‐power limited and supervised
Fused by F1, 10 A field replaceable (P/N 02‐4173)
PAGE / 18 Doc. P/N 06‐297
Figure 16 SHP‐Pro Controller Circuit Specifications ‐ Continued
Index Terminal Description Specifications
3 P1‐3+ and P1‐4‐ Standby battery input Sealed lead acid batteries only
Charging capacity: 40 AH maximum
Voltage: 24 VDC nominal
Supply current: 8 A @ 27 VDC maximum
Charge current: 1.5 A @ 27 VDC maximum
Non‐power limited and supervised
Fused by F2, 10 A field replaceable fuse (P/N 02‐4173)
4 P2‐1 thru 3 Alarm Relay Non‐programmable, common Alarm relay that switches when any Alarm input is activated
Style: Form C, SPDT
Contact Rating (DC operation): 2 A @ 30 VDC (pf = .35)
Contact Rating (AC operation): 0.5 A @ 250 VAC (pf = .35)
Non‐supervised
Can be connected to power limited or non‐power limited source
5 P2‐4 thru 6 Supervisory Relay Non‐programmable, common Supervisory relay that switches when any Supervisory input is activated
Style: Form C, SPDT
Contact Rating (DC operation): 2 A @ 30 VDC (pf = .35)
Contact Rating (AC operation): 0.5 A @ 250 VAC (pf = .35)
Non‐supervised
Can be connected to power limited or non‐power limited source
6 P2‐7 thru 9 Trouble Relay Non‐programmable, common Trouble relay that switches on any Trouble condition or when panel is de‐energized
Style: Form C, SPDT
Contact Rating (DC operation): 2 A @ 30 VDC (pf = .35)
Contact Rating (AC operation): 0.5 A @ 250 VAC (pf = .35)
Non‐supervised
Can be connected to power limited or non‐power limited source
7 P3‐1 thru 5 Detect #1 and Detect #2 Inputs
Compatible with conventional detectors and linear heat detection cable listed in Section 3.2 or contact closure type devices listed for fire alarm use.
Wire configuration: Class B (Class A with optional 10‐2450 module)
Detector voltage: 19.9 – 27.5 VDC
Current: 360 mA maximum
Maximum wire resistance: 20 Ω detectors; 440 Ω linear heat detection or contact closure
End of line resistor: 4.3 Ω (banding: yellow/orange/red)
Power limited and supervised
Capable of Sequential, Cross‐zone (Detect #1 & #2), or Single detector release detection methods
Appropriate “0 ohm” jumper must be clipped if using 0 ohm bases or contact closure device on Detect #1 or #2 circuits in order to limit the circuit current to 100 mA.
If using linear heat detection cable (LHD) on Detect #1 or #2 circuits, do NOT clip the “0 ohm” jumpers
Refer to Section 4.1.1 for detector base selection
PAGE / 19
Figure 17 SHP‐Pro Controller Circuit Specifications ‐ Continued
Index Terminal Description Specifications
8 P3‐1 thru 13 Input #3, #4 and #5 Compatible with contact closure inputs (i.e., manual release, abort, heat detection devices, waterflow and supervisory devices listed for fire alarm use)
Wire configuration: Class B (Class A with optional 10‐2450 module)
Voltage: 5 VDC maximum
Current: 0.5 mA maximum
Wire resistance: 100 Ω maximum
End of line resistor: 20k Ω (banding: red/black/orange)
Power limited and supervised
9 P4‐1 and P4‐2 Resettable AUX Output Voltage: 24 VDC nominal (range = 19.8 – 27.3 VDC)
Current: 2 A maximum, special application
Fused by F3, 4 A field replaceable fuse (P/N 02‐11412)
Supervised and power limited
Resettable and Continuous AUX outputs share the same negative and shield terminals
P4‐2 and P4‐3 Continuous AUX Output Voltage: 24 VDC nominal (range = 19.8 – 27.3 VDC)
Current: 2 A maximum, special application
Fused by F4, 4 A field replaceable fuse (P/N 02‐11412)
Supervised and power limited
Resettable and Continuous AUX outputs share the same negative and shield terminals
10 P5‐1 thru 8 Audible #1, #2 and #3 Refer to Fike’s Device Compatibility document P/N 06‐186 for a list of compatible notification appliances.
Wiring: Class B (Class A with optional module P/N 10‐2448)
Output Voltage: 24 VDC nominal, 27.9 VDC maximum (16 – 33 maximum RMS)
Output Current: 2 A maximum, regulated
Wire Resistance: Refer to Section 4.1.2
End of line resistor: 1.2 kΩ (banding: brown/red/red)
Supervised and power limited
11 P5‐9 and P5‐10 Agent Release Wiring: Class B (Class A with optional module P/N 10‐2448)
Output Voltage: 24 VDC nominal, special application
Output Current: 2 A maximum
Wire Resistance: 35 Ω maximum
End of line resistor: 2.4 kΩ (banding: red/yellow/red)
Supervised and power limited
Compatible Devices: ARM III (P/N 10‐1832) and IRM (P/N 10‐ 2748), maximum 6 any combination
12 P5‐11 and P5‐12 Solenoid Wiring: Class B (Class A with optional module P/N 10‐2448)
Output Voltage: 24 VDC nominal, special application
Output Current: 2 A maximum
Wire Resistance: Refer to Section 4.1.2
End of line resistor: None required. Circuit is supervised through coil for wiring integrity.
Compatible Devices: Refer to Fike’s Device Compatibility document P/N 06‐186
Testing: Install 200 Ω, 5 watt resistor (P/N 02‐2686) to simulate solenoid resistance
PAGE / 20 Doc. P/N 06‐297
4.1.1. Detector Base Selection
The following table identifies the maximum number of detector bases that can be connected to the SHP‐Pro’s Detection input circuits and the detection scheme that is available with the base model being used. Bases of different models/manufacturers shall not be mixed on the system.
Maximum Bases per Circuit
Fike P/N Size Manufacturer Mfg. P/N Manufacturer Compatibility
ID
Sequential
Cross‐ zone
Single Detector Release
67‐1027 2 6” 430 Hochiki HSB‐224 HB‐53 25 25 N/A
67‐1028 2 4” 430 Hochiki YBA‐M224 HB‐5 25 25 N/A
67‐1010 2 6” 220 Hochiki HSB‐220 HB‐56 N/A 25 25
67‐1017 2 4” 220 Hochiki YBA‐M220 HB‐3 N/A 25 25
67‐1034 3 6” 430 Hochiki NS6‐224 HB‐5 25 25 N/A
67‐1036 3 4” 430 Hochiki NS4‐224 HB‐5 25 25 N/A
67‐1035 3 6” 220 Hochiki NS6‐220 HB‐3 N/A 25 25
67‐1037 3 4” 220 Hochiki NS4‐220 HB‐3 N/A 25 25
67‐10262 6” 470 System Sensor B401BR470 61‐093‐02A 25 25 N/A
67‐1029 6” 470 System Sensor B110RLP 61‐093‐02A 25 25 N/A
67‐1031 6” 0 System Sensor B401B 61‐093‐02A N/A Note 1 Note 1
Figure 18 Detector Base Selection Guide
NOTES:
1. 0 ohm bases do not have a current limiting resistor. They provide a contact closure input to the detection circuit(s) they are connected to. Depending upon controller configuration, they are capable of providing either single detector release or cross‐zoned detection operation. The number of bases that can be connected to the circuit is limited by the circuit specifications. If using 0 ohm bases on the detection circuit(s), appropriate “0 ohm” jumper must be clipped in order to limit the circuit current to 100 mA. See Section 5.5.4.4.
2. Device has been discontinued by manufacturer. Listed for retrofit compatibility.
3. Base provides terminals for connection to conventional graphic panel. Replaces Hochiki HSB and YBA bases.
4.1.2. Circuit Impedance Limitations
The following table can be used to estimate the maximum allowable circuit impedance based on the total current draw of all devices connected to the circuit. First, determine the maximum amount of current flowing through the circuit; then use the table to find the corresponding maximum impedance allowed for the circuit wiring based on a maximum circuit voltage drop of 2.4 volts.
Max Current (Amps) 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1.0 1.5 2.0
Audibles 1‐3 (Max s) 24 12 8 6 4.8 4.0 3.0 2.4 1.6 1.2
Solenoid (Max s) 12 6 4 3 2.4 2.0 1.5 1.2 0.8 0.6
Figure 19 Field Wiring Resistance Limitations
PAGE / 21
4.2. Class-A Input Card (P/N 10-2450)
The Class A Input Card (Figure 20) mounts directly to the SHP‐Pro control board and receives its control and operating power directly from the board via the P6 terminal connection. If the Class A Input card is installed, all five input circuits must be wired Class A, rather than Class B.
Figure 20 Class A Input Card
Figure 21 Class‐A Input Card Specifications
Index Terminal Description Specifications 1 P3A‐1 thru 4 Detect #1 and Detect #2
Inputs Compatible with conventional detectors listed in Section 3.2, linear heat detection cabling or contact closure type devices listed for fire alarm use.
Detector voltage: 19.9 – 27.5 VDC
Current: 360 mA maximum
Maximum wire resistance: 20 Ω detectors; 440 Ω linear heat and contact closure
Supervised and power limited
2 P3A‐6 thru 13 Input #3, #4 and #5 Compatible with contact closure inputs (manual…