SPECIFICATIONS
Section 21201 - Signs
Section 24100 – Waste Material Disposal
Section 33020 – Concrete From Packaged Dry Mix For Minor Structures
Section 55204 – Repair Concrete
Section 60700 – Cleaning of Structures
Section 63401 – Pavement Markings
Section 70000 – Sheet Metal Flashing and Trim
Section 90000 – Water Distribution Systems
SECTION 21201 - SIGNS
USDA FOREST SERVICE, R-8
SIERRA PALM PICNIC AREA MINOR REPAIR MAINTENANCE PROJECT
SECTION 21201 - SIGNS
PART 1 - GENERAL
1.1 This item shall consist of furnishing and installing signs as shown on the Drawings. The location for sign installations shall be as shown on the Drawings and at locations staked by the Contractor and approved by the Contracting Officer in the field. The Contractor shall furnish all posts, concrete, signs, and hardware required to complete the full installation.
1.2 REFERENCE SPECIFICATIONS - The publication listed below form a part of this specification to the extent referenced. The publication is referred to in the text by the basic designation only.
A. EM 7100-15 Sign and Poster Guidelines for the Forest Service.
1.3 SUBMITTAL
A. Sign List Submittal: The Contractor shall submit a list of signs proposed for the project.
The list shall include detailed drawings showing the size of the sign, size of letters, colors, materials, sign texts, and location for installation. The Contracting Officer shall approve the submitted list, prior to the Contractor ordering the signs.
1.4 METHOD OF MEASUREMENT
A. The quantity to be measured shall be the number of signs furnished, installed and accepted as shown in the Schedule of Items.
PART 2 - PRODUCTS
2.1 SIGN PANELS
A. General:
1. Sign panels shall be panels of one-piece construction.
2. Signs shall conform to current editions of the Manual of Uniform Traffic Control
Devices (MUTCD) and the Forest Service Manual - EM 7100-15, Standards for Forest Service Signs.
B. HDO Plywood Panels:
1. Shall be fabricated using 100% heat activated retro-reflectorized material applied to ¾-inch thick 7-ply HDO plywood meeting the requirements of the current edition of the National Bureau of Standards PS 1.
2. Shall be edge tape with clear vinyl film.
3. Shall be furnished with predrilled holes for installation.
C. Aluminum Panels:
1. Shall be fabricated using 100% heat activated retro-reflectorized material.
2. Shall be furnished with predrilled holes for installation.
3. All sign sheets and plates shall meet the requirements of ASTM B 209, alloy 6061-
T6, or 5052-H38 and shall be of the minimum thickness shown below.
Sign Width (inches) Sheet Aluminum Thickness (inches) Less than 8 0.022
8-12 0.040 13-19 0.063 20-30 0.080 31-48 0.100 over 48 0.125
2.2 POSTS
A. Wood Posts - 4”X 4” and 4”X6” posts shall be rough sawn standard and better hemlock fir or pine. All lumber shall be pressure treated using the “Empty Cell Process” as required by the American Wood Preservers Association (AWPA), with copper naphthenate solution. The copper naphthenate solution shall contain not less that 6% or more than 8% copper in the form of copper naphthenate, in petroleum oil, AWPA P9, conforming to AWPA P8 and C1 for oil-born preservatives.
2.3 FASTENER BOLTS
A. Vandal-Proof Bolts and hardware shall be galvanized or cadmium plated steel. Bolts shall be 5/16” carriage bolts. Nuts installed with wood posts shall be NTPAFN fluted nuts. Nuts installed with tubular steel posts shall be vandal-proof tufnuts or approved equal. A known supplier is Intermountain Traffic Safety, West Valley City, Utah, phone
(801) 972-6515.
2.4 CONCRETE
A. Concrete for installing sign posts shall conform to the requirement of Section 33020.
PART 3 - EXECUTION
3.1 POST SETTING
A. Post holes not larger than 18-inch diameter shall be excavated to a depth as shown on the drawings. Backfill shall be hand tamped around the wood posts so as to make the post solid and plumb. Any loose posts shall be removed and re-installed. Concrete shall be used to backfill tubular steel posts when shown on the drawings.
3.2 SIGN MOUNTING
A. Signs shall be mounted as shown on the drawings. Bolt holes shall be neatly drilled in the signs so as to prevent splintering and drilling through letters or delaminate sheathing.
Sign face sheathing or coverings shall not be broken.
3.3 GRADING AND CLEANUP
A. The area around the post shall be graded to the desired contour. When the installation is completed, the general area shall be cleaned up by removing all debris and material not utilized.
END OF SECTION 21201
SEPTEMBER 2018
SECTION 24100 - WASTE MATERIAL DISPOSAL
SIERRA PALM PICNIC AREA MINOR REPAIR MAINTENANCE PROJECT
SECTION 24100 - WASTE MATERIAL DISPOSAL
PART 1 - GENERAL
1.1 SUMMARY
A. This Section includes the loading, handling, hauling, and placing of excess material, unsuitable material, and construction and demolition debris.
1.2 MEASUREMENT AND PAYMENT
A. There will be no separate measurement or payment for work in this Section. Waste material disposal is considered incidental to other items of work shown in the Schedule of Items.
PART 2 - PRODUCTS – NOT APPLICABLE
PART 3 - EXECUTION
3.1 WASTE MATERIAL TO BE HAULED TO A LANDFILL
A. All demolition materials, garbage, and other refuse generated shall be removed from the project site and legally disposed off of Government property in an approved landfill.
END OF SECTION 24100
September 2018
SECTION 33020 - CONCRETE FROM PACKAGED DRY MIX FOR MINOR STRUCTURES
SIERRA PALM PICNIC AREA MINOR REPAIR MAINTENANCE PROJECT
SECTION 33020 - CONCRETE FROM PACKAGED DRY MIX FOR MINOR STRUCTURES
PART 1 - GENERAL
1.1 SUMMARY
A. This Section includes constructing small concrete structures such as thrust blocks, pipe supports, setting sign posts, and test hole fillers.
1.2 MEASUREMENT AND PAYMENT
A. There will be no separate measurement or payment for work in this Section. Concrete from packaged dry mix is considered incidental to other items of work shown in the Schedule of Items.
PART 2 - PRODUCTS
2.1 MATERIALS
A. Concrete Dry Mix:
1. Design: ASTM C 387, made using dry pre-portioned, blended and bagged mix.
2. Minimum 28-day Compressive Strength: 3000 psi
3. Product: Sakrete Concrete Mix, as manufactured by US Mix Products Company, or an approved equal.
B. All reinforcement bars shall be deformed billet steel conforming to the requirement of ASTM A615, Grade 60.
C. Water: Clean and free from alkali and other deleterious materials.
PART 3 - EXECUTION
3.1 CONCRETE INSTALLATION
A. Mixing:
1. Mix dry concrete and water thoroughly according to the manufacturer.
2. Mixing Equipment: Mechanical mixer or wheel barrow.
3. Place concrete while fresh; any concrete in which initial set has begun shall be wasted.
B. Placing: Place the fresh concrete in the forms and work as necessary to remove the air pockets.
C. Finishing: Apply medium trowel finish to exposed concrete surfaces.
SECTION 33020 - CONCRETE FROM PACKAGED DRY MIX FOR MINOR STRUCTURES
D. Protection From Cold: Keep the air temperature surrounding the fresh concrete above 40ºF for a period of five days after the concrete is placed.
E. Curing: If determined necessary by the Contracting Officer, cover exposed surfaces with plastic sheeting after the concrete has taken its initial set.
END OF SECTION 33020
SECTION 55204 – REPAIR CONCRETE
PART 1 - GENERAL
1.1 SUMMARY
A. This work shall consist of repairing concrete spalls, cracks, and repairing reinforced concrete structures
B. All concrete repair requirements shall comply with manufactures recommendations to epoxy resin adhesives, polymer concrete and mortar, Class A (AE) concrete, and all other apparatus to repair damaged reinforced concrete structures.
C. Contractor will be responsible for their own quality assurance and shall perform their own inspections and record the results in their Quality Control Plan.
D. If a hazardous material containing lead or chromium is found on site and to be removed, comply with the following:
(a) SSPC Guide 6 – Guide for Containing Surface Preparation Debris Generated During Paint Removal Operations;
(b) SSPC Guide 7 – Guide to the Disposal of Lead-Contaminated Surface Preparation Debris;
(c) 29 CFR 1926.62 – Lead (OSHA Safety and Health Regulations for Construction);
(d) 40 CFR 50.6 – EPA National Primary and Secondary Ambient Air Quality Standards for PM10 (EPA);
(e) 40 CFR 50.12 – EPA National Primary and Secondary Ambient Air Quality Standards for Lead; and
(f) 42 U.S.C. §6901 – Resource Conservation and Recovery Act (RCRA).
Collect and dispose of material including waste water that is used in preparing, cleaning, or painting according to the requirements of FAR Clause 52.236-7 Permits and Responsibilities.
Comply with applicable laws, ordinances, safety codes, regulations, orders, and decrees.
Protect and indemnify the Government and its representatives against claim or liability arising from or based on the alleged violation of the same.
Comply with permits and agreements obtained by the Government for performing the work that is included in the contract. Obtain additional permits or agreements and modifications to Government-obtained permits or agreements that are required by the Contractor's methods of operation. Submit copies of permits and agreements.
1.2 DEFINITIONS
A. S.F.: SQUARE FEET
1.3 SUBMITTALS
A. Product Data: For each type of product and material indicated. Include technical data, psi strength, epoxy resin adhesives, polymer concrete and mortar, concrete class and strength, tagged and marked reinforcement bar(s) according to Manual of Standard Practice (CRSI), and tested physical and performance properties.
B. Ship marking material in appropriate bundles and containers plainly marked with the following information, as appropriate, for the material being furnished:
i) Manufacturer's name and address;
ii) Name of product;
iii) Manufacturing process;
iv) Heat numbers;
v) Net mass and volume of contents;
vi) Sizes
vii) Specifications
viii) Date of manufacture;
ix) Date of expiration;
x) Statement of contents (if mixing of components is required);
xi) Mixing proportions and instructions; and
xii) Safety information.
1.4 DELIVERY, STORAGE, AND HANDLING
A. Deliver materials to Project site in original packages and bundles with seals unbroken and bearing manufacturer's labels containing brand name and type of material, size, date of manufacture, and directions for storage.
1.5 PROJECT CONDITIONS
A. Project is located on the Rain Forest of the El Yunque National Forest. Contractor can expect rainy days and humidity. Manufacture recommendations should be considered for these conditions.
1.6 MEASUREMENT AND PAYMENT
A. The quantity of repaired surface areas are in square feet (S.F.) and to be paid for shall be the number of square feet (S.F.) of repaired areas measured along the square footage completed and accepted.
PART 2 - PRODUCTS
2.1 MATERIALS
A. Reinforcement Bars: Furnish deformed, Grade 60 (420) bars conforming to AASHTO
M 31 or AASHTO M 322.
B. Epoxy-coated Reinforcing Bars: Furnish bars conforming to Section 2.1(A) located above. Conform to ASTM A775.
Inspect the reinforcing bars after the near white blast cleaning. Reject bars with steel slivers or scabs. Selective sorting and rejection at the fabricator's shop may avoid unnecessary delays and subsequent rejection of bars during the precoating inspection at the coating applicator's shop.
Coat epoxy-coated reinforcing steel in a plant certified by CRSI as a fusion bonded epoxy applicator.
C. Polymer Concrete and Mortar: Furnish a polymer binder and fine aggregate in the proportions recommended by the polymer manufacturer with a minimum compressive strength of 3,500 pounds per square inch (25 megapascals) in 4 hours. Conform to the following:
a) Epoxy mortar. Conform to ACI 503.4
b) Other polymer concrete or mortar. Conform to ASTM C1438, Type II
D. Epoxy Resin Adhesives: Furnish epoxy resin adhesives conforming to AASHTO M 235 for structural concrete injection and crack repair.
E. Nonshrink grout. Conform to ASTM C1107. Provide a minimum compressive strength of 5,000 pounds per square inch (35 megapascals) in 3 days.
3.1 GENERAL
A. Saw cut structures when partial removal is required.
Construct structurally adequate debris shields to contain debris within the construction limits. Do not allow debris to enter waterways, or areas designated not to be disturbed.
Handle material with lead paint contamination according to Section 1.1D.
Raze and remove obstructions interfering with the work and not designated to remain.
Concrete removal in repair areas. Saw cut ¾ inch (19 millimeters) deep along boundaries of repair areas. Use power-driven hand tools to remove existing concrete. Do not damage concrete designated to remain in place.
Where the bond between existing concrete and reinforcing steel is destroyed, remove concrete adjacent to the steel to provide at least ¾-inch (19-millimeter) clearance for the new concrete to bond to the reinforcing steel. Use care to prevent damage to remaining concrete when achieving the final surface.
Clean exposed concrete surfaces that will be in contact with repair material. Provide a residue free surface.
B. Concrete Repair. For concrete repairs, remove existing or new defective concrete according to Subsection 3.1 (A) above. After removal of deteriorated or unsound concrete, shotblast exposed structural steel, reinforcing steel, and concrete surfaces which will be in contact with repair material until free of rust and foreign material. Clean the sound concrete surface by flushing with clean water from a high pressure water jet or compressed air. Remove and replace deteriorated reinforcing steel. Before placing repair concrete, thoroughly flushing with clean water under pressure or compressed air. If compressed air is used, provide a filter in airline to ensure that the air is oil-free. If there is an interval of more than 24 hours between cleaning of the sound concrete surfaces that have been contaminated by substances detrimental to good bonding, clean by abrasive shot blasting and pressurized water flushing or remove the concrete.
For vertical and overhead concrete repairs and those horizontal repairs to areas less than 5 inches (130 millimeters) in depth; use a non-shrink grout patching compound placed according to the manufacturer’s recommendations.
For other repairs patches greater than 5 inches (130 millimeters) in depth, apply a bonding coat of an epoxy resin adhesive to the surfaces of the sound existing concrete immediately before placing new concrete against it. Follow the manufacturer’s recommendations for the epoxy resin adhesive. Repair areas using Class A(AE) concrete.
3.2 DISPOSAL
A. Dispose of debris and unsuitable and excess material as follows:
Remove from project. Recycle or dispose of material legally off the project. Submit a statement documenting the nature and quantity of material processed or sold for recycling. Otherwise, submit a signed copy of the disposal agreement before disposal begins.
B. Hazardous Material: Submit a copy of disposal permits. Dispose of material according to Federal, state, and local regulations.
Dispose of lead contaminated steel either by transporting to an approved scrap facility for recycling or remelt; or remove and dispose of lead contamination in an appropriate waste facility.
1) Disposal plan. Submit a detailed disposal plan that includes how material will be handled, loaded, and transported to the disposal facility. Include the name and address of the facility where the material will be taken. Describe steps that will be taken to ensure that lead contamination will be contained throughout the process.
Measures may include additional steps or precautions when lifting and handling the steel on site.
2) Transport and delivery. Include the material safety data sheet (MSDS) with the material to the disposal facility. Ensure that loads transported from the site are adequately contained and covered to prevent dispersion en route to the disposal facility. Submit a copy of the receiving report from the disposal facility specifically acknowledging that the material being delivered is contaminated with lead paint.
3) Lead paint removal. If the Contractor chooses to salvage the steel members, the paint may be removed subject to the following requirements:
a) Remove lead contaminated paint in an appropriate containment facility;
b) Comply with the requirements as listed in Subsection 563.05; and
c) Manifest and dispose of lead contaminated waste according to the requirements of 40 CFR 260 through 268 – Resource Conservation and Recovery Act (RCRA).
END OF SECTION 55204
SECTION 60700 – CLEANING OF STRUCTURES
SIERRA PALM PICNIC AREA MINOR REPAIR MAINTENANCE PROJECT
SECTION 60700 – CLEANING OF STRUCTURES
PART 1 - GENERAL
1.1 SUMMARY
A. This work includes all labor, wages, oversight, and materials associated with cleaning existing structures interior and exterior and pressure washing interior and exterior of each structure including fireplaces, pressure washing roofs, and roof drains of each structure, including removing all dirt, debris, grime, and mildew of each structure as shown in drawings and repair schedule until Final Acceptance by C.O.. Contractor shall conform to OSHA requirements for all work identified in the specifications, drawings, and repair schedule.
B. Contractor shall submit methods of cleaning to C.O. for approval.
1.2 REFERENCE SPECIFICATIONS - Not Applicable
1.3 RELATED WORK
A. The work shall be in accordance with the contract Schedule of Items, specifications, and drawings repair schedule.
B. The work shall be in accordance with the following subsidiary specifications. The subsidiary specifications are referred to in the text by the Section designation only.
SECTION 21400 – WASTE MATERIAL DISPOSAL
1.4 MEASUREMENT AND PAYMENT
A. Measurement and Payment shall be “Each” Actual Quantity (AQ) as shown in the Schedule of Items for the cleaning of structure. Payment shall include all summary as specified in Section 1.1A above. The bid shall include all components to provide a complete job for all work identified in Schedule of Items, specification, drawings, and repair schedule.
SECTION 60700 – CLEANING OF STRUCTURES
2.1 DETERGENT AND SOLUTIONS
A. All detergents and solutions and mixtures shall be submitted to C.O. for approval in its entirety prior to contractor using it. DO NOT use ammonia or vinegar as these may damage the finish.
2.2 BRUSHES
A. The use of a metal-bristle brush IS NOT ALLOWED.
A. Work shall be completed in accordance with the contract specifications, manuactures recommendations, and according to C.O.’s approval.
3.2 CONSTRUCTION ENVIRONMENT
A. Contractor shall maintain a clean, trash-free construction environment throughout the progress of work.
3.3 CLEANUP
A. Cleanup shall include disposal of waste materials in accordance with Section 24100.
END OF SECTION
SECTION 63401 - PAVEMENT MARKINGS
1.1 SUMMARY
A. This item shall consist of furnishing and applying the paint markings for parking stalls, directional arrows, and accessible symbols for the control of traffic, at locations as shown on the drawings, marked in the field, or as directed by the Contracting Officer.
B. All work to be performed Mondays through Fridays, between the hours of 0800 and 1700.
Contractor may coordinate with the C.O.R. to complete proposed work in phases due to parking of Forest Service personnel/employees.
C. All requirements shall comply with the direction in the Manual of Uniform Traffic
Control Devices (MUTCD).
D. Contractor shall perform their own inspections and record the results in their Quality
Control Plan. COR will review Contractor quality records.
1.2 DEFINITIONS
A. L.F.: Linear Foot
B. Foot: Linear Foot
C. Each: Each Particular Item
1.3 SUBMITTALS
A. Product Data: For each type of product indicated. Include technical data and tested physical and performance properties.
B. Ship marking material in appropriate containers plainly marked with the following information, as appropriate, for the material being furnished:
i) Manufacturer's name and address;
ii) Name of product;
iii) Lot/batch numbers;
iv) Color;
v) Net mass and volume of contents;
vi) Date of manufacture;
vii) Date of expiration;
viii) Statement of contents (if mixing of components is required);
ix) Mixing proportions and instructions; and
x) Safety information.
1.4 DELIVERY, STORAGE, AND HANDLING
A. Deliver pavement-marking materials to Project site in original packages with seals unbroken and bearing manufacturer's labels containing brand name and type of material, date of manufacture, and directions for storage.
B. Store pavement-marking materials in a clean, dry, protected location within temperature range required by manufacturer. Protect stored materials from direct sunlight.
1.5 PROJECT CONDITIONS
A. Proceed with pavement marking only on clean, dry surfaces and at a minimum ambient or surface temperature of 50 deg F (10 deg C) for water-based materials, and not exceeding 95 deg F (35 deg C).
1.6 MEASUREMENT AND PAYMENT
A. The quantity of 3" – 4” wide striping (Type C reflectorized and color as shown on the
Schedule of Items), to be paid for shall be the number of linear feet (LF) of stripes measured along the center line of the painted strips completed and accepted with no deduction for the unpainted area caused by broken stripe.
B. The quantity of International Symbol of Accessibility parking (Reflectorized Symbol, White on Blue Background), to be paid for shall be the number of such symbols designated In the Schedule of Items, completed and accepted.
C. The quantity of curb stops (Reflectorized, White), to be paid for shall be the number of each curb stop designated in the Schedule of Items, completed and accepted.
D. The accepted quantities will be paid for at the contract unit price for each pay item shown in the Schedule of Items.
2.1 MATERIALS
A. Waterborne Traffic Paint (Type C): Apply paint when the pavement and air temperatures are above 50 ºF. Spray paint at 15 mil minimum wet film thickness before glass beads or at a rate of 107 square feet per gallon.
1) Type C. Immediately apply type 3 glass beads on the paint at a minimum rate of 12 pounds per gallon of paint.
2) On new asphalt pavements or new asphalt surface treatments, apply two coats. Apply each coat at 210 square feet per gallon.
B. Waterborne Traffic Paint: Furnish an acrylic water-based, ready-mixed paint for use on asphalt and rigid pavements conforming to the following:
(a) Composition. Furnish a paint composed of resin solids of 100 percent acrylic polymer with the exact formulation determined by the manufacturer. Conform to the following:
(1) Pigment, % by mass, ASTM D 3723 45% to 55%
(2) Lead, chromium, cadmium, or barium 0%
ASTM D 3335 & D3718
(3) Volatile organic compounds, 20.0 ounces per gallon max.
ASTM D 2369
(4) Mass of paint, 12.0 pounds per gallon min.
ASTM D 1475
(b) Viscosity. ASTM D 562 75-90 Krebs units
(c) Drying time.
(1) Dry to no pickup, ASTM D 711 10 minutes max.
(2) Drying to no track, 6 pounds per gallon, 90 seconds max.
type 1 waterproofed glass beads, 15±1 mil wet film thickness at 130 ºF
(d) Flexibility. ASTM D 522, using the 1/4-inch No cracking or flaking cylindrical mandrel
(e) Dry opacity. ASTM D 2805, contrast ratio at 0.96 min. 319 square feet per gallon spreading rate
(f) Color.
(1) White, ASTM D 1729 Match FHWA standard highway white
(2) Yellow, ASTM D 1729 Match FHWA standard highway yellow
(3) Blue, ASTM D 1729 Match FHWA standard highway blue
(g) Daylight reflectance. (Without glass beads)
(1) White, FTMS 141 method 6121
84% relative to ASTM E 1347 magnesium oxide standard
(2) Yellow, FTMS 141 method 6121 ASTM E 1347
55% relative to magnesium oxide standard
(h) Bleeding ratio. ASTM 969. 0.96 min. Determine reflectance according to
ASTM D 1347 immediately after drying. Divide the average of 3 reflectance readings of the paint over the bleeding surface by the average of 3 readings over the non-bleeding surface to determine the bleeding ratio.
(i) Scrub resistance. ASTM D 2486 300 cycles min.
(j) Freeze-thaw stability. ASTM D 2243
1) Change in viscosity ±5 Krebs units max.
2) Decrease in scrub resistance -10% max.
(k) Storage stability. During a 12-month storage period, conform to the following:
1) No excessive setting, caking, or increase in viscosity; and
2) Readily stirred to a consistency for use in the striping equipment.
C. Glass Beads: Conform to AASHTO M 247 for the type specified. Table 1, Gradation of
Glass Beads in AASHTO M 247 is supplemented by Table 718-2. Treat glass beads with an adherence coating as recommended by manufacturer.
Table 718-2
Gradation of Glass Beads
Sieve Size
Percent by Mass Passing Designated
Sieve (ASTM D 1214)
Grading Designation
Type 3
No. 8
No. 10
No. 12 100
No. 14 95 - 100
No. 16 80 - 95
No. 18 10 - 40
No. 20 0 - 5
No. 25 0 - 2
For type 3 glass beads, also conform to the following:
a) Treat beads with a reactive adherence coating as recommended by the manufacturer.
b) Roundness, FLH T 520 70% min. per sieve size
c) Refractive index, AASHTO M 247 1.50 - 1.55
2.2 COLORS
A. Colors for commonly used lines, marking, and symbols are as follows:
1. Parking stall lines - yellow.
2. Directional Arrows - yellow.
3. International symbol of accessibility - white on blue background.
A. The Contractor shall be responsible for preliminary spotting of the lines to be painted and approval by the Contracting Officer must be obtained before applying pavement-marking paint.
B. At least 7 days before applying pavement markings, furnish a written copy of the marking
Manufacturer’s recommendations for use. A field demonstration may be required to verify the adequacy of recommendations.
C. Sweep and clean surface to eliminate all loose material including: pine needles, pine straws, moss, pollen, grass, loose soils, dust etc. The area to be painted shall be dry, clean, and free of loose particles. Remove loose particles, dirt, tar, grease, and other deleterious material from the surface to be marked. Remove temporary pavement markings the same day permanent pavement markings are applied. Apply markings to a clean, dry surface according to the MUTCD.
D. Apply paint with mechanical equipment to produce pavement markings, of required dimensions, with uniform, straight edges. Apply at manufacturer's recommended rates to provide a minimum wet film thickness of 15 mils (0.4 mm). The equipment shall include a mechanical bead dispenser that will distribute the glass beads uniformly into the wet pavement markings at a rate of 6 lb/gal. (0.72 kg/L).
E. Stripes shall be 4 inches wide. Broken line segments (dashed or skip traffic strip) shall be 10 feet in length with 30-foot gaps, or 2 feet in length with 4-foot gaps.
F. Arrows and letters shall be of the dimensions as shown on the drawings or existing pavement markings.
G. The painted area shall be protected from traffic until the paint is thoroughly dry. Protect marked areas from traffic until the markings are dried to no-tracking condition. Remove all tracking marks, spilled marking material, markings in unauthorized areas, and defective markings.
H. All markings shall present a clean-cut, uniform appearance. All markings which fail to have a uniform appearance, either day or night, shall be corrected by the Contractor.
3.2 DISPOSAL
A. Dispose of debris and unsuitable and excess material as follows:
(1) Remove or dispose of material legally off the project
B. Contractor shall dispose of all hazardous materials according to Federal, State, and local regulations.
END OF SECTION 63401
August 2018
SECTION 70000 - SHEET METAL FLASHING AND TRIM
1.1 SUMMARY
A. This Section includes the following sheet metal flashing and trim:
1. Formed steep-slope roof sheet metal fabrications.
1.2 PERFORMANCE REQUIREMENTS
A. General: This work includes all labor, fees and materials associated with installing a new metal roof, soffit and fascia as shown in the drawings and specifications. Work includes removing the existing roofing down to the existing sheathing, installing new underlayment system, installing new flashing, metal roofing, and fascia, and following directions as described in the drawings and specifications.
B. Install sheet metal flashing and trim to withstand wind loads, structural movement, thermally induced movement, and exposure to weather without failing, rattling, leaking, and fastener disengagement.
C. Fabricate and install flashing, roofing, and all its apparatus capable of resisting design speeds of 175 mph (78 m/s):
1. Risk Category III-IV: Velocity pressures, perimeter uplift force, corner uplift force, and outward force shall conform to IBC for Puerto Rico.
2. New metal roof shall be in accordance to the latest IBC for Puerto Rico and shall accommodate a risk Category III-IV: 3-sec peak gust in mph of 175. Metal roofing system shall last a minimum of 40 years with specified gauge.
D. Thermal Movements: Provide sheet metal flashing and trim that allow for thermal movements resulting from the following maximum change (range) in ambient and surface temperatures by preventing buckling, opening of joints, hole elongation, overstressing of components, failure of joint sealants, failure of connections, and other detrimental effects.
Provide clips that resist rotation and avoid shear stress as a result of sheet metal and trim thermal movements. Base engineering calculation on surface temperatures of materials due to both solar heat gain and nighttime-sky heat loss.
1. Temperature Change (Range): 120 deg F, ambient; 180 deg F, material surfaces.
E. Water Infiltration: Provide sheet metal flashing and trim that do not allow water infiltration to building interior.
1.3 SUBMITTALS
A. Product Data: For each type of product indicated. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes.
B. Samples for Initial Selection: For each type of sheet metal flashing and trim indicated with factory-applied color finishes.
1. Include similar Samples of trim and accessories involving color selection.
1.4 QUALITY ASSURANCE
A. Sheet Metal Flashing and Trim Standard: Comply with Sheet Metal and Air Conditioning Contractors' National Association (SMACNA) conforming to dimensions and profiles shown unless more stringent requirements are indicated.
1.5 DELIVERY, STORAGE, AND HANDLING
A. Deliver sheet metal flashing materials and fabrications undamaged. Protect sheet metal flashing and trim materials and fabrications during transportation and handling.
B. Unload, store, and install sheet metal flashing materials and fabrications in a manner to prevent bending, warping, twisting, and surface damage.
C. Stack materials on platforms or pallets, covered with suitable weathertight and ventilated covering. Do not store sheet metal flashing and trim materials in contact with other materials that might cause staining, denting, or other surface damage.
1.6 COORDINATION
A. Coordinate installation of sheet metal fascia, flashing and trim with interfacing and adjoining construction to provide a leakproof, secure, and noncorrosive installation.
1.7 MEASUREMENT AND PAYMENT
A. There will be no separate measurement or payment for work in this section. Payment will be included in the contract unit price for items shown in the schedule of items.
PART 2 - PRODUCTS
2.1 SHEET METALS
A. General: Protect mechanical and other finishes on exposed surfaces from damage by applying a strippable, temporary protective film before shipping.
B. Metallic-Coated Steel Sheet: Restricted flatness steel sheet, metallic coated by the hot-dip process and prepainted by the coil-coating process to comply with
ASTM A 755/A 755M.
1. Zinc-Coated (Galvanized) Steel Sheet: ASTM A 653/A 653M, G90 coating designation; structural quality.
2. Aluminum-Zinc Alloy-Coated Steel Sheet: ASTM A 792/A 792M, Class AZ50 coating designation, Grade 40; structural quality.
3. Surface: Smooth, flat.
4. Exposed Coil-Coated Finish:
a. Three-Coat Fluoropolymer: AAMA 621. Fluoropolymer finish containing not less than 70 percent PVDF resin by weight in both color coat and clear topcoat. Prepare, pretreat, and apply coating to exposed metal surfaces to comply with coating and resin manufacturers' written instructions.
5. Color: As selected by Contracting Officer from manufacturer's full range.
6. Concealed Finish: Pretreat with manufacturer's standard white or light-colored acrylic or polyester backer finish, consisting of prime coat and wash coat with a minimum total dry film thickness of 0.5 mil.
2.2 UNDERLAYMENT MATERIALS (Select from the following as indicated or required)
A. Polyethylene Sheet: 6-mil- thick polyethylene sheet complying with ASTM D 4397.
B. Felt: ASTM D 226, Type II (No. 30), asphalt-saturated organic felt, nonperforated.
C. Self-Adhering, High-Temperature Sheet: Minimum 30 to 40 mils thick, consisting of slip-resisting polyethylene-film top surface laminated to layer of butyl or SBS-modified asphalt adhesive, with release-paper backing; cold applied. Provide primer when recommended by underlayment manufacturer.
1. Thermal Stability: ASTM D 1970; stable after testing at 240 deg F.
2. Low-Temperature Flexibility: ASTM D 1970; passes after testing at minus 20 deg F.
3. Products: Subject to compliance with requirements, provide one of the following:
a. Carlisle Coatings & Waterproofing Inc.; CCW WIP 300HT.
b. Grace Construction Products, a unit of W. R. Grace & Co.; Ultra.
c. Henry Company; Blueskin PE200 HT.
d. Metal-Fab Manufacturing, LLC; MetShield.
e. Owens Corning; WeatherLock Metal High Temperature Underlayment.
f. Approved equal.
D. Slip Sheet: Building paper, 3-lb/100 sq. ft. minimum, rosin sized.
2.3 MISCELLANEOUS MATERIALS
A. General: Provide materials and types of fasteners, solder, welding rods, protective coatings, separators, sealants, and other miscellaneous items as required for complete sheet metal flashing and trim installation.
B. Fasteners: Wood screws, annular threaded nails, self-tapping screws, self-locking rivets and bolts, and other suitable fasteners designed to withstand design loads.
1. Exposed Fasteners: Heads matching color of sheet metal by means of plastic caps or factory-applied coating.
2. Fasteners for Flashing and Trim: Blind fasteners or self-drilling screws, gasketed, with hex washer head.
3. Blind Fasteners: High-strength aluminum or stainless-steel rivets.
C. Sealing Tape: Pressure-sensitive, 100 percent solids, polyisobutylene compound sealing tape with release-paper backing. Provide permanently elastic, nonsag, nontoxic, nonstaining tape.
D. Elastomeric Sealant: ASTM C 920, elastomeric polyurethane polymer sealant; of type, grade, class, and use classifications required to seal joints in sheet metal flashing and trim and remain watertight.
E. Butyl Sealant: ASTM C 1311, single-component, solvent-release butyl rubber sealant, polyisobutylene plasticized, heavy bodied for hooked-type expansion joints with limited movement.
F. Epoxy Seam Sealer: Two-part, noncorrosive, aluminum seam-cementing compound, recommended by aluminum manufacturer for exterior nonmoving joints, including riveted joints.
G. Bituminous Coating: Cold-applied asphalt mastic, SSPC-Paint 12, compounded for 15-mil dry film thickness per coat. Provide inert-type noncorrosive compound free of asbestos fibers, sulfur components, and other deleterious impurities.
H. Asphalt Roofing Cement: ASTM D 4586, asbestos free, of consistency required for application.
2.4 FABRICATION, GENERAL
A. General: Custom fabricate sheet metal fascia, flashing and trim to comply with recommendations in SMACNA's "Architectural Sheet Metal Manual" that apply to design, dimensions, metal, and other characteristics of item indicated. Shop fabricate items where practicable. Obtain field measurements for accurate fit before shop fabrication.
B. Fabricate sheet metal flashing and trim in thickness or weight needed to comply with performance requirements, but not less than that specified for each application and metal.
C. Fabricate sheet metal flashing and trim without excessive oil canning, buckling, and tool marks and true to line and levels indicated, with exposed edges folded back to form hems.
1. Seams for Other Than Aluminum: Fabricate nonmoving seams in accessories with flat-lock seams. Tin edges to be seamed, form seams, and solder.
D. Sealed Joints: Form nonexpansion but movable joints in metal to accommodate elastomeric sealant to comply with SMACNA recommendations.
E. Expansion Provisions: Where lapped or bayonet-type expansion provisions in the Work cannot be used, form expansion joints of intermeshing hooked flanges, not less than 1 inch deep, filled with elastomeric butyl sealant concealed within joints.
F. Conceal fasteners and expansion provisions where possible on exposed-to-view sheet metal flashing and trim, unless otherwise indicated.
G. Fabricate cleats and attachment devices from same material as accessory being anchored or from compatible, noncorrosive metal.
1. Thickness: As recommended by SMACNA's "Architectural Sheet Metal Manual" and FMG Loss Prevention Data Sheet 1-49 for application but not less than thickness of metal being secured.
2.5 STEEP-SLOPE ROOF SHEET METAL FABRICATIONS
A. Apron, Step, Cricket, and Backer Flashing: Fabricate from the following materials:
1. Aluminum-Zinc Alloy-Coated Steel: 0.022 inch thick.
B. Counterflashing: Fabricate from the following materials:
1. Aluminum-Zinc Alloy-Coated Steel: 0.022 inch thick.
C. Flashing Receivers: Fabricate from the following materials:
1. Aluminum-Zinc Alloy-Coated Steel: 0.022 inch thick.
D. Roof-Penetration Flashing: Fabricate from the following materials:
1. Prefinished Aluminum-Zinc Alloy-Coated Steel: 0.028 inch thick.
2.6 WALL SHEET METAL FABRICATIONS
A. Opening Flashings in Frame Construction, where indicated or required: Fabricate head, sill, jamb, and similar flashings to extend 4 inches beyond wall openings. Form head and sill flashing with 2-inch- high, end dams. Fabricate from the following materials:
1. Prefinished Aluminum-Zinc Alloy-Coated Steel: 0.022 inch thick.
2.7 MISCELLANEOUS SHEET METAL FABRICATIONS
A. Equipment Support Flashing, not provided by Division 15: Fabricate from one of the following material:
1. Galvanized Steel: 0.0276 inch thick.
2. Aluminum-Zinc Alloy-Coated Steel: 0.0276 inch thick.
3. Prepainted, Metallic-Coated Steel, where exposed to public view: 0.0276 inch thick.
2.8 FINISHES
A. Comply with NAAMM's "Metal Finishes Manual for Architectural and Metal Products" for recommendations for applying and designating finishes.
B. Protect mechanical and painted finishes on exposed surfaces from damage by applying a strippable, temporary protective covering before shipping.
C. Appearance of Finished Work: Variations in appearance of abutting or adjacent pieces are acceptable if they are within one-half of the range of approved Samples. Noticeable variations in the same piece are not acceptable. Variations in appearance of other components are acceptable if they are within the range of approved Samples and are assembled or installed to minimize contrast.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates, areas, and conditions, with Installer present, to verify actual locations, dimensions and other conditions affecting performance of work.
1. Verify that substrate is sound, dry, smooth, clean, sloped for drainage, and securely anchored.
2. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION, GENERAL
A. General: Anchor sheet metal flashing and trim and other components of the Work securely in place, with provisions for thermal and structural movement. Use fasteners, solder, welding rods, protective coatings, separators, sealants, and other miscellaneous items as required to complete sheet metal flashing and trim system.
1. Torch cutting of sheet metal flashing and trim is not permitted.
B. Metal Protection: Where dissimilar metals will contact each other or corrosive substrates, protect against galvanic action by painting contact surfaces with bituminous coating or by other permanent separation as recommended by fabricator or manufacturers of dissimilar metals.
1. Coat side of uncoated aluminum, stainless-steel and lead sheet metal flashing and trim with bituminous coating where flashing and trim will contact wood, ferrous metal, or cementitious construction.
2. Underlayment: Where installing metal flashing directly on cementitious or wood substrates, install a course of felt underlayment and cover with a slip sheet or install a course of polyethylene underlayment.
3. Bed flanges in thick coat of asphalt roofing cement where required for waterproof performance.
C. Install exposed sheet metal flashing and trim without oil canning, buckling, and tool marks.
D. Install sheet metal flashing and trim true to line and levels indicated. Provide uniform, neat seams with minimum exposure of solder, welds, and elastomeric butyl sealant.
E. Install sheet metal flashing and trim to fit substrates and to result in watertight performance. Verify shapes and dimensions of surfaces to be covered before fabricating sheet metal.
1. Space cleats not more than 12 inches apart. Anchor each cleat with two fasteners.
Bend tabs over fasteners.
F. Expansion Provisions: Provide for thermal expansion of exposed flashing and trim.
Space movement joints at a maximum of 10 feet with no joints allowed within 24 inches of corner or intersection. Where lapped or bayonet-type expansion provisions cannot be used or would not be sufficiently watertight, form expansion joints of intermeshing hooked flanges, not less than 1 inch deep, filled with elastomeric butyl sealant concealed within joints.
G. Fasteners: Use fasteners of sizes that will penetrate substrate not less than 1-1/4 inches for nails and not less than 3/4 inch for wood screws.
1. Galvanized or Prepainted, Metallic-Coated Steel: Use stainless-steel fasteners.
H. Seal joints with elastomeric butyl sealant as required for watertight construction.
1. Where sealant-filled joints are used, embed hooked flanges of joint members not less than 1 inch into sealant. Form joints to completely conceal sealant. When ambient temperature at time of installation is moderate, between 40 and 70 deg F, set joint members for 50 percent movement either way. Adjust setting proportionately for installation at higher ambient temperatures. Do not install sealant-type joints at temperatures below 40 deg F.
2. Prepare joints and apply sealants to comply with requirements in Division 7 Section "Joint Sealants."
I. Soldered Joints, where required: Clean surfaces to be soldered, removing oils and foreign matter. Pretin edges of sheets to be soldered to a width of 1-1/2 inches except where pretinned surface would show in finished Work.
1. Do not solder prepainted, metallic-coated steel and aluminum sheet.
2. Pretinning is not required for lead-coated copper, zinc-tin alloy-coated stainless steel and lead.
3. Stainless-Steel Soldering: Pretin edges of uncoated sheets to be soldered using solder recommended for stainless steel and phosphoric acid flux. Promptly wash off acid flux residue from metal after soldering.
4. Copper Soldering: Tin uncoated copper surfaces at edges of sheets using solder recommended for copper work.
5. Where surfaces to be soldered are lead coated, do not tin edges, but wire brush lead coating before soldering.
6. Lead-Coated Copper Soldering: Wire brush edges of sheets before soldering.
7. Do not use open-flame torches for soldering. Heat surfaces to receive solder and flow solder into joints. Fill joints completely. Completely remove flux and spatter from exposed surfaces.
3.3 ROOF FLASHING INSTALLATION
A. General: Install sheet metal roof flashing and trim to comply with performance requirements, sheet metal manufacturer's written installation instructions, and SMACNA's "Architectural Sheet Metal Manual." Provide concealed fasteners where possible, set units true to line, and level as indicated. Install work with laps, joints, and seams that will be permanently watertight.
B. Pipe or Post Counterflashing: Install counterflashing umbrella with close-fitting collar with top edge flared for butyl sealant, extending a minimum of 4 inches over base flashing. Install stainless-steel draw band and tighten.
C. Counterflashing: Coordinate installation of counterflashing with installation of base flashing. Insert counterflashing in reglets or receivers and fit tightly to base flashing.
Extend counterflashing 4 inches over base flashing. Lap counterflashing joints a minimum of 4 inches and bed with butyl sealant.
1. Secure in a waterproof manner by means of snap-in installation and sealant or interlocking folded seam or blind rivets and sealant or anchor and washer at 36-inch centers.
D. Roof-Penetration Flashing: Coordinate installation of roof-penetration flashing with installation of roofing and other items penetrating roof. Install flashing as follows:
1. Turn lead flashing down inside vent piping, being careful not to block vent piping with flashing.
2. Seal with butyl sealant and clamp flashing to pipes penetrating roof except for lead flashing on vent piping.
3.4 WALL FLASHING INSTALLATION
A. General: Install sheet metal wall flashing to intercept and exclude penetrating moisture according to SMACNA recommendations and as indicated. Coordinate installation of wall flashing with installation of wall-opening components such as windows, doors, and louvers.
3.5 MISCELLANEOUS FLASHING INSTALLATION
A. Equipment Support Flashing: Coordinate installation of equipment support flashing with installation of roofing and equipment. Weld or seal flashing with butyl sealant to equipment support member.
3.6 CLEANING AND PROTECTION
A. Clean exposed metal surfaces of substances that interfere with uniform oxidation and weathering.
B. Clean and neutralize flux materials. Clean off excess solder and sealants.
C. Remove temporary protective coverings and strippable films as sheet metal flashing and trim are installed. On completion of installation, clean finished surfaces, including removing unused fasteners, metal filings, pop rivet stems, and pieces of flashing.
Maintain in a clean condition during construction.
D. Replace sheet metal flashing and trim that have been damaged or that have deteriorated beyond successful repair by finish touchup or similar minor repair procedures.
END OF SECTION 70000
SECTION 90000 - WATER DISTRIBUTION SYSTEMS
SIERRA PALM PICNIC AREA MINOR REPAIR MAINTENANCE PROJECT
SECTION 90000 - WATER DISTRIBUTION SYSTEMS
PART 1 - GENERAL
1.1 SUMMARY
A. This Section shall consist of furnishing and installing the following:
1. Potable water distribution pipe and fittings.
B. This Section shall also include the flushing, testing and disinfection of waterlines.
C. Related Sections include the following:
1. Section 24100 “Waste Material Disposal.”
2. Section 33020 “Concrete From Package Dry Mix for Minor Structures.”
1.2 DEFINITIONS
A. GSP: Galvanized Steel Pipe.
B. HDPE: High Density Polyethylene plastic.
C. PVC: Polyvinyl chloride plastic.
1.3 SUBMITTALS
A. Product Data: For the following:
1. Pipe and fittings.
2. Drain and vent screens.
B. Plan for disposal of water used for testing and disinfection of waterlines.
C. Water System Operations and Maintenance Manual.
1.4 QUALITY ASSURANCE
A. All work is to be completed according to applicable Federal, State and Local codes. This work includes, but is not limited to, materials, installation, testing and disinfection
B. Piping materials shall bear label, stamp, or other markings of specified testing agency.
C. NSF Compliance:
1. Comply with NSF 14 for plastic potable-water-service piping. Include marking "NSF-pw" on piping.
2. Comply with NSF 61 for materials for water-service piping and specialties for domestic water.
1.5 MINIMUM SYSTEM REQUIREMENTS
A. Unless otherwise noted, the minimum working pressure for piping and specialties shall be 160 psig.
1.6 DELIVERY, STORAGE AND HANDLING
A. Deliver piping with factory-applied end caps. Maintain end caps through shipping, storage, and handling to prevent pipe-end damage and to prevent entrance of dirt, debris, and moisture.
B. Protect stored piping from moisture and dirt. Elevate above grade.
C. Protect flanges, fittings, and specialties from moisture and dirt.
D. Store plastic piping protected from direct sunlight. Support to prevent sagging and bending.
E. Handle Meters to avoid damage to exposed parts.
1.7 PROJECT CONDITIONS
A. Existing Utilities: Do not interrupt utilities serving facilities occupied by the Government or others unless permitted under the following conditions and then only after arranging to provide temporary utility services according to requirements indicated:
1. Notify the Contracting Officer not less than two days in advance of proposed utility interruptions.
2. Do not proceed with utility interruptions without the Contracting Officer’s written permission.
1.8 COORDINATION
A. Coordinate connection to existing waterlines with Contracting Officer.
B. Verify piping materials, sizes, entry locations and pressure requirements are compatible with connection point.
C. Coordinate other utility impacts.
1.9 MEASUREMENT AND PAYMENT
A. Payment will be as listed for the following items:
1. Pipeline: Linear Feet (LF) of pipe of each type and size designated, including fittings, trench, drains, tracer wire and test stations, non-potable and sewerline crossings, and connections to existing waterlines.
2. Pipe Sleeves: Linear Feet of pipe sleeve, of the type and size indicated.
3. Drains: Each type and size of drain indicated in the schedule of items and as shown on the drawings, and including all work within 10 feet of the drain outlet or pumpout drain.
4. Water System Operations and Maintenance Manual: This item is considered incidental to this section and will not be paid for separately.
PART 2 - PRODUCTS
2.1 GENERAL
A. All waterlines, pipes, and fittings shall be new and unused, of the type, pressure rating or class, and size specified and as shown on the Drawings.
2.2 PIPES AND FITTINGS
A. HDPE:
1. Pipe, AWWA C901:
a. Material Designation: PE 3408 resin
b. Material Classification: ASTM D1248
c. Minimum Cell Classification: ASTM D 3350, 345434C
d. Dimension Ratio and Minimum Pressure Rating: DR11, 160 psig.
2. Fittings:
a. Molded HDPE Fittings: ASTM D 3350, PE 3408 resin, butt-fusion type, made to match HDPE pipe dimensions…