C04 Attachment 3 Drawings.pdf
PDF 18 MB Posted
- Solicitation number
- 1232SA26Q0885
About this file
This document is a comprehensive design package for the replacement of Building 7 Greenhouse 3 at the Jamie Whitten Delta States Research Center in Stoneville, Mississippi, prepared for the U.S. Department of Agriculture Agricultural Research Service. The project involves the complete demolition and reconstruction of an existing greenhouse facility, with design drawings covering architectural, mechanical, plumbing, and electrical systems. Key project components include the demolition of three existing greenhouse structures, removal of asbestos-containing building materials and lead paint, and construction of a new climate-controlled greenhouse facility with 16 million liters of polycarbonate glazing, integrated environmental controls, heating and cooling systems, roof and side vents, evaporative cooling walls, and comprehensive utility infrastructure including hot water piping, drainage systems, ductwork, and electrical distribution.
The project specifications detail an extensive HVAC system with multiple air handling units, boilers with 1999.9 MBH capacity each, primary and secondary hot water circulation pumps, exhaust fans, and an automated greenhouse environmental control system (Micro Grow controller) that manages temperature, humidity, ventilation, and lighting. The mechanical design includes eight evaporative cooling pads (13-foot length, 3-foot height), eight greenhouse bays with individual plant room configurations, and a "Bid Option #1" that adds supplemental HVAC equipment including additional air handling units and exhaust fans. Plumbing systems provide domestic cold water, reverse osmosis treated water for cooling pads, and sanitary drainage with existing below-slab piping to be reused. Electrical work encompasses four new 100-amp panelboards serving individual greenhouse bays, grow lighting circuits controlled by contactors, general lighting with LED vapor-tight fixtures, and connections for mechanical equipment with motors sized up to 30 horsepower. The document includes detailed schedules for all mechanical equipment, electrical panels, lighting fixtures, and controls, with notes indicating contractor coordination requirements with the greenhouse manufacturer and compliance with the Buy American Act.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TomTaylor Stamp
BREAK
STORAGE
SPRAY ROOM
SEE ELECTRICAL
FOR WORK IN THIS
AREA
PLANT ROOMPLANT ROOMPLANT ROOMPLANT ROOM
CORRIDOR
001002003004
3 3
ENVIRONMENTAL GENERAL NOTES:
1. THE CONTRACTOR SHALL REMOVE AND DISPOSE OF ALL ASBESTOS CONTAINING BUILDING
MATERIALS (ACBM) AS HAZARDOUS ASBESTOS WASTE IN ACCORDANCE WITH ALL LOCAL, STATE AND
FEDERAL REGULATIONS.
2. THE CONTRACTOR SHALL NOTIFY THE MISSISSIPPI STATE DEPARTMENT OF HEALTH AND
ENVIRONMENT A MINIMUM OF 10 DAYS PRIOR TO ANY DEMOLITION WORK AT THE FACILITY.
3. THE HEADHOUSE AND OTHER GREENHOUSES WILL BE OCCUPIED DURING CONSTRUCTION. PROVIDE PROPER CONTAINMENT AND VENTILATION DURING HAZARDOUS MATERIAL ABATEMENT PROCEDURES
AS DIRECTED BY SPECIFICATIONS.
4. ASSUME THAT ALL PAINT COATINGS CONTAIN SOME LEVEL OF LEAD. PROVIDE OSHA REQUIRED PROTECTION FOR WORKERS DISTURBING EXISTING PAINT COATINGS REQUIRED TO PERFORM THE
WORK.
ACBM PANEL LOCATIONS
ENVIRONMENTAL KEY NOTES:
THE SOLID PANELS IN THE PROJECT AREA GREENHOUSE SYSTEM ARE
ASBESTOS CONTAINING MATERIAL. REMOVE AND DISPOSE OF AS ASBESTOS CONTAINING
MATERIAL.
REMOVE DRYWALL CEILING OF LAB 140 AND LAB 141. DISPOSE OF AS ASBESTOS CONTAINING
MATERIAL. ALL EXISTING LIGHT FIXTURES, REGISTERS, GRILLES AND CEILING-MOUNTED ITEMS SHALL BE CLEANED OF ASBESTOS CONTAMINATION AND REINSTALLED IN THE NEW CEILING SYSTEM. (BID
OPTION 1)
ASSUME THAT ALL GLAZING COMPOUND CONTAINS ASBESTOS. REMOVE AND
DISPOSE OF AS ASBESTOS CONTAINING BUILDING MATERIALS (ACBM) WASTE IN ACCORDANCE
WITH ALL LOCAL, STATE AND FEDERAL REGULATIONS.
STORAGE
LAB
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
JAMIE WHITTEN DELTA STATES RESEARCH CENTER
DESIGN TO REPLACE BLDG. 7 GREENHOUSE 3
STONEVILLE, MISSISSIPPI
HAZARDOUS MATERIALS PLAN
HM101
2 422/24/2026
RPP
TGT
DRL
MID SOUTH AREA
STONEVILLE, MS
K. MAGEE
SCALE:
HAZARDOUS MATERIALS PLAN - GREENHOUSE 3
3/16"=1'-0"
HM101
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
SCALE:
HAZARDOUS MATERIALS RCP - LAB 140
3/16"=1'-0"
HM101
KEYPLAN
NTS
16 MIL GLAZING BAR
16 MIL POLYCARBONATE PANEL
GLAZING BAR CAP
PANEL TERMINATOR STRIP
EXISTING STRUCTURE
BEYOND
EXISTING STRUCTURE
BEYOND
16 MIL SILL
16 MIL BASE SILL --
ANCHOR TO CMU
WALL PER
MANUFACTURER
INSTRUCTIONS
16 MIL POLYCARBONATE
VENT PANEL
16 MIL VENT MULLION
VENT TOP RAIL
GLAZING BAR CAP
VENT BOTTOM RAIL
VENT BOTTOM RAIL CAP
16 MIL VENT SILL ADAPTOR
16 MIL GLAZING BAR
16 MIL POLYCARBONATE PANEL
GLAZING BAR CAP
EXISTING STRUCTURE
BEYOND
EXISTING STRUCTURE
BEYOND
16 MIL BASE SILL --
ANCHOR TO CMU WALL
PER MANUFACTURER
INSTRUCTIONS
PANEL TERMINATOR STRIP
GIRT CLIP
GIRT STRAP
ANGLE GIRT
16 MIL GLAZING BAR
16 MIL POLYCARBONATE PANEL
GLAZING BAR CAP
INSECT SCREEN
8" CMU KNEE WALL
CONT. # 5 REBAR IN GROUT
FILLED BOND BEAM
CONT. SEALANT
CONT. SEALANT
8" MIN. #4 DOWELS @ 16" O.C --
EPOXY INTO SLAB
HORIZONTAL JOINT
REINFORCEMENT @
16" O.C. VERTICAL
8" MIN. #4 DOWELS @ 16" O.C --
EPOXY INTO SLAB
EXISTING FOUNDATION
AND SLAB
EXISTING FOUNDATION
AND SLAB
HORIZONTAL JOINT
REINFORCEMENT @
16" O.C. VERTICAL
8" CMU KNEE WALL
CONT. # 5 REBAR IN GROUT
FILLED BOND BEAM
HORIZONTAL JOINT
REINFORCEMENT @
16" O.C. VERTICAL
HORIZONTAL JOINT
REINFORCEMENT @
16" O.C. VERTICAL
FILL ALL CMU
CELLS WITH
GROUT (TYP.)
FILL ALL CMU
CELLS WITH
GROUT (TYP.)
8" CMU BOND BEAM
8" CMU BOND BEAM
FLASHING FLASHING
DOOR AND FRAME SCHEDULE
DOOR # TYPE WD HGT THK
SIZE
MAT'L
DOOR
TYPE MAT'L DETAIL
FRAME FIRE
RATING
LABEL
HDW
SET
NO
REMARKS
B A A A A
5'-6" 3'-0" 3'-0" 3'-0" 3'-0"
7'-0" 7'-0" 7'-0" 7'-0" 7'-0"
1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4"
MTL
MTL
MTL
MTL
MTL
B A A A A
MTL
MTL
MTL
MTL
MTL
4/A501 3/A501 3/A501 3/A501 3/A501
PAIR OF DOORS
A
2"
B
DOOR AND FRAME TYPES
AS SCHED. AS SCHED.
AS
S
C H
ED
2" 2"2" 2"
AS
S
C H
ED
2"
16 MIL GLAZING BAR
16 MIL POLYCARBONATE PANEL
GLAZING BAR CAP
EXISTING STRUCTURE
BEYOND
EXISTING STRUCTURE
BEYONDPANEL TERMINATOR STRIP
GIRT CLIP
GIRT STRAP
ANGLE GIRT
16 MIL GLAZING BAR
16 MIL POLYCARBONATE PANEL
GLAZING BAR CAP
DOOR - SEE SCHEDULE
16 MIL GLAZING BAR
16 MIL POLYCARBONATE PANEL
GLAZING BAR CAP
EXISTING STRUCTURE
BEYOND
EXISTING STRUCTURE
BEYONDPANEL TERMINATOR STRIP
GIRT CLIP
GIRT STRAP
ANGLE GIRT
16 MIL GLAZING BAR
16 MIL POLYCARBONATE PANEL
GLAZING BAR CAP
DOOR - SEE SCHEDULE
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
JAMIE WHITTEN DELTA STATES RESEARCH CENTER
DESIGN TO REPLACE BLDG. 7 GREENHOUSE 3
STONEVILLE, MISSISSIPPI
WALL SECTION DETAILS
AND DOOR SCHEDULE
A501 13 422/24/2026
RPP
TGT
DRL
MID SOUTH AREA
DETAIL
3"=1'-0"
A501 SCALE:
DETAIL
3"=1'-0"
A501
2' -8
2' -8
SCALE:
DOOR HEAD DETAIL - INTERIOR
3"=1'-0"
A501 SCALE:
DOOR HEAD DETAIL - EXTERIOR
3"=1'-0"
A501
SCALE: 3"=1'-0"
3"0 6" 1'
R O
R O
R O
R O
SS D
C
W
SS D
C
W
SS D
C
W
TOILET
& SHOWER
RM
ROOM
STORAGE
WORK AREA
TOILET
STORAGE
STORAGE
CORRIDOR MECHANICAL
WORK AREA
WORK AREA
STORAGE
RM
RM
EQUIP. STO.
OFFICE
OFFICE
BREAK
STORAGE
STORAGE
METAL
COLD ROOM
WORK AREA
BLDG
WET LAB
DRY LAB
COVERED AREA
SPRAY ROOM
10124
108109
126 125
PLANT ROOM PLANT ROOM
PLANT ROOM PLANT ROOM
PLANT ROOM PLANT ROOM
PLANT ROOM PLANT ROOM
PLANT ROOM
PLANT ROOM
PLANT ROOM
PLANT ROOM
OVENOVEN
GREENHOUSE 1GREENHOUSE 2
GREENHOUSE 3
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
JAMIE WHITTEN DELTA STATES RESEARCH CENTER
DESIGN TO REPLACE BUILDING 7 GREENHOUSE 3
STONEVILLE, MISSISSIPPI
PLUMBING DEMOLITION PLAN
PD100
14 422/24/2026
RPP
SME
DRL
SOUTHEAST AREA
PLUMBING DEMOLITION PLAN
3/32"=1'-0"
PD100
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
KEYED NOTES
1. EXISTING PIPING AND INSULATION UPSTREAM OF THE
SHOWN POINT OF CONNECTION MUST REMAIN UNDAMAGED
IN PLACE AND BE TEMPORARILY CAPPED UNTIL
RECONNECTION.
2. DEMOLISH EXISTING RO WATER PIPING AND FITTINGS.
3. DEMOLISH EXISTING DOMESTIC COLD WATER PIPING AND
FITTINGS.
4. EXISTING SANITARY SEWER PIPING AND FITTINGS TO
REMAIN.
DEMOLISH EXISTING
DOMESTIC COLD
WATERDEMOLISH EXISTING
RO WATER
DEMOLISH EXISTING HOSE BIB
(TYP.)
EXISTING FLOOR
DRAIN TO HAVE
COVER REMOVED
AND REPLACED.
(TYP.)
LEGEND:
POINT OF
CONNECTION/
DEMOLITION
X
GENERAL NOTES
1. INTENT OF DEMOLITION IS TO REMOVE ALL EXISTING
UTILITIES SERVING EXISTING GREENHOUSE #3. THIS
INCLUDES, BUT IS NOT LIMITED TO, DOMESTIC WATER,RO
WATER, ABOVE-GRADE SANITARY, VENT PIPING, FITTINGS,
VALVES, SUPPORTS, INSULATION, AND ASSOCIATED
APPURTENANCES.
2. EXISTING SANITARY SEWER PIPING LOCATED BELOW THE
SLAB MUST REMAIN IN PLACE AND MUST BE REUSED TO
SERVE THE RENOVATED GREENHOUSE #3. CONTRACTOR
MUST PROTECT ALL EXISTING BELOW-SLAB SANITARY
PIPING AND VENT CONNECTIONS DURING DEMOLITION AND
CONSTRUCTION. ANY PIPING DAMAGED BY THE
CONTRACTOR MUST BE REPAIRED OR REPLACED AT NO
ADDITIONAL COST TO THE GOVERNMENT.
3. ALL ABOVE-GRADE SANITARY VENT PIPING MUST BE
REMOVED AND REPLACED AS REQUIRED TO ACCOMMODATE
THE RENOVATED GREENHOUSE CONSTRUCTION AND NEW
UTILITY ROUTING.
Dylan Mitchell New Stamp
R O
R O
R O
R O
SS D
C
W
SS D
C
W
SS D
C
W
TOILET
& SHOWER
RM
ROOM
STORAGE
WORK AREA
TOILET
STORAGE
STORAGE
CORRIDOR MECHANICAL
WORK AREA
WORK AREA
STORAGE
RM
RM
EQUIP. STO.
OFFICE
OFFICE
BREAK
STORAGE
STORAGE
METAL
COLD ROOM
WORK AREA
BLDG
WET LAB
DRY LAB
COVERED AREA
SPRAY ROOM
10124
108109
126 125
PLANT ROOM PLANT ROOM
PLANT ROOM PLANT ROOM
PLANT ROOM PLANT ROOM
PLANT ROOM PLANT ROOM
PLANT ROOM
PLANT ROOM
PLANT ROOM
PLANT ROOM
OVENOVEN
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
JAMIE WHITTEN DELTA STATES RESEARCH CENTER
DESIGN TO REPLACE BUILDING 7 GREENHOUSE 3
STONEVILLE, MISSISSIPPI
PLUMBING PLAN
P100 15 422/24/2026
RPP
SME
DRL
PLUMBING PLAN
3/32"=1'-0"
P100
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
EXIST.
SSWR
1" DCW
1" PVC RO
WATER
HB
HB
HB
HB
KEYED NOTES
1. PROVIDE HAND OPERATED SHUTOFF VALVE.
2. ROUTE DCW DOWN TO SERVE EVAPORATIVE COOLING PAD .
PROVIDE WITH SHUTOFF VALVE.
3. ROUTE RO PIPING DOWN BELOW EVAPORATIVE COOLING
PAD AND PROVIDE HOSE BIBB FOR CONNECTION.
1 1
EXISTING FLOOR
DRAIN TO HAVE
COVER REMOVED
AND REPLACED.
(TYP.)
3/4"
DCW
1"
DCW
1-1/2"
DCW
GENERAL NOTES
1. CONTRACTOR MUST REMOVE AND REPLACE EXISTING
FLOOR DRAIN COVERS THROUGHOUT EXISTING
GREENHOUSE. CONTRACTOR MUST PHYSICALLY CLEAN
AND UNBLOCK AND AND ALL EXISTING GREENHOUSE
SANITARY PIPING BACK TO MAIN. CONTRACTOR MUST
ENSURE THAT EACH EXISTING FLOOR DRAIN LOCATED IN
THE GREENHOUSE FUNCTIONS WITH NO IMPAIRMENTS
THROUGHOUT THE EXISTING SANITARY SYSTEM.
2. ALL PIPING LOCATED IN GREENHOUSE MUST BE ROUTED AT
ROOF STRUCTURE AND PROVIDED WITH EXTERIOR GRADE
INSULATION AND UV PROTECTION SHIELDING.
LEGEND:
POINT OF
CONNECTION
X
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
JAMIE WHITTEN DELTA STATES RESEARCH CENTER
DESIGN TO REPLACE BUILDING 7 GREENHOUSE 3
STONEVILLE, MISSISSIPPI
PLUMBING SCHEDULES AND DETAILS
P600 16 422/24/2026
RPP
SME
DRL
MARK DESCRIPTION CW HW MIN. WASTE REMARKSVENTMIN. TRAP
PLUMBING FIXTURE SCHEDULE
HB - -3/4" - - PRIER C-144 ANTI-SIPHON DESIGN WALL-HYDRANT.HOSE BIBB
INTERIOR WALL
TERMINATED
SLEEVE FLUSH
WITH FINISHED
WALL SURFACES.
SEAL OR CAULK
SLEEVES THRU FIRE
WALLS IN A SMOKE
TIGHT MANNER,
WITH FIRE STOP
MATERIAL.
PIPE AND
INSULATION TO BE
CENTERED IN
SLEEVE. DO NOT
SUPPORT PIPE FROM
SLEEVE.
BACK UP MATERIAL
FINISHED WALL
WHERE EXPOSED, PROVIDE FINISHED
ESCUTCHEON PLATE FLUSH AGAINST
WALL, AND OF SIZE TO COMPLETELY
COVER OPENING.
STEEL PIPE SLEEVE OF
SIZE TO PASS PIPE AND
INSULATION.
SCALE:
TYPICAL PIPE SLEEVES THROUGH WALLS
N.T.S
P600
PROVIDE SHUTOFF
VALVE IN
ACCESSIBLE
LOCATION PER IPC
SECTION 6.
3/4" PVC RO PIPING
STRAP PIPE TO FLANGE OF
GREENHOUSE STRUCTURE
90 DEG
ELBOW
WALL HYDRANT
PER SCHEDULE
MOUNT AT 48" AFF
UNLESS NOTED
OTHERWISE REFER TO
PLANS
SCALE:
TYPICAL HOSE BIBB DETAIL
N.T.S
P600
GREENHOUSE
STRUCTURE
3/4" PVC RO PIPING UP TO
ROOF STRUCTURE
H W
R H
W S
H W
R H
W S
R O
R O
R O
R O
H W
R H
W S
H W
R H
W S
TOILET
& SHOWER
RM
ROOM
STORAGE
WORK AREA
TOILET
STORAGE
STORAGE
CORRIDOR
MECHANICAL
WORK AREA
WORK AREA
STORAGE
RM
RM
EQUIP. STO.
OFFICE
OFFICE
BREAK
STORAGE
STORAGE
METAL
COLD ROOM
WORK AREA
BLDG
WET LAB
DRY LAB
COVERED AREA
SPRAY ROOM
103 102
108109
126 125
PLANT ROOM PLANT ROOM
PLANT ROOM PLANT ROOM
PLANT ROOM PLANT ROOM
PLANT ROOM PLANT ROOM
PLANT ROOM
PLANT ROOM
PLANT ROOM
PLANT ROOM
OVENOVEN
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
JAMIE WHITTEN DELTA STATES RESEARCH CENTER
DESIGN TO REPLACE BUILDING 7 GREENHOUSE 3
STONEVILLE, MISSISSIPPI
MECHANICAL DEMOLITION PLAN
MD100
17 422/24/2026
RPP
SME
DRL
MECHANICAL DEMOLITION PLAN
3/32"=1'-0"
MD100
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
KEYED NOTES
1. EXISTING BOILER MUST REMAIN IN PLACE FOR CONTINUED
USE.
2. EXISTING PUMP MUST REMAIN IN PLACE FOR CONTINUED
USE.
3. DEMOLISH EXISTING PUMP AND ALL APPURTENANCES.
4. DEMOLISH EXISTING BOILER AND ALL APPURTENANCES.
5. EXISTING HYDRONIC PIPING AND INSULATION MUST BE
PROTECTED FROM DAMAGE IN PLACE FOR CONTINUED USE.
6. EXISTING EXPANSION TANK MUST REMAIN IN PLACE FOR
CONTINUED USE.
7. DEMOLISH EXISTING GREENHOUSE EXHAUST FAN, LOUVER,
GRILLE, DUCTWORK, CONTROLS, AND ALL APPURTENANCES.
8. DEMOLISH EXISTING SUPPLY AND RETURN PIPING AND
FITTINGS.
X
EXISTING
AHU-7 TO
REMAIN
EXISTING 3" HWS &
HWR PIPING TO
REMAIN (TYP.)
EXISTING AHU-5
TO REMAIN
EXISTING
AHU-4 TO
REMAIN
EXISTING
AHU-2 TO
REMAIN
EXISTING 1"
HWS AND HWR
EXISTING 3"
HWS AND
HWR
EXISTING 3"
HWS AND
HWR
EXISTING
1-1/4" HWS
AND HWR
EXISTING 3" HWS
AND HWR TO REMAIN
EXISTING
AHU-6 TO
REMAIN
EXISTING
AIR
SEPARATOR
TO REMAIN
EXISTING 6" HWS AND
HWR TO REMAIN
EXISTING
AHU-3 TO
REMAIN
EXISTING AHU-1
TO REMAIN
DEMOLISH
EXISTING
FIN-TUBED
RADIATORS AND
PIPING (TYP.)
DEMOLISH
EXISTING
EVAPORATIVE
COOLING WALL
(TYP.)
EXISTING
RO SYSTEM
EXISTING 3"
HWS AND
HWR
EXISTING
HVAC UNIT
TO REMAIN
LEGEND:
POINT OF
DEMOLITION
x1
48x12
12x6
12x8
12x8
12x8
36x1230x1224x1220x1218x12
16x1614"Ø
"Ø
"Ø12 "Ø
"Ø
10x10
10x10
36x18 x1
24x12 x1
18x1212x12 x6
12x12
12x12
12x12 x1
10"Ø
6"Ø
10"Ø
6" Ø
6"Ø
STOR.
NOT IN USE
CHAMBER CHAMBER ELECTRICAL PANELS
TOILET
& SHOWER
RM
ROOM
STORAGE
WORK AREA
TOILET
STORAGE
STORAGE
CORRIDOR MECHANICAL
WORK AREA
WORK AREA
STORAGE
RM
RM
EQUIP. STO.
OFFICE
OFFICE
BREAK
STORAGE
STORAGE
METAL
COLD ROOM
WORK AREA
BLDG
WET LAB
DRY LAB
COVERED AREA
SPRAY ROOM
10124
108109
126 125
PLANT ROOM PLANT ROOM
PLANT ROOM PLANT ROOM
PLANT ROOM PLANT ROOM
PLANT ROOM PLANT ROOM
PLANT ROOM
PLANT ROOM
PLANT ROOM
PLANT ROOM
OVENOVEN
GREENHOUSE 1GREENHOUSE 2GREENHOUSE 3
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
JAMIE WHITTEN DELTA STATES RESEARCH CENTER
DESIGN TO REPLACE BUILDING 7 GREENHOUSE 3
STONEVILLE, MISSISSIPPI
MECHANICAL DEMOLITION PLAN
BID OPTION #1
MD101
18 422/24/2026
RPP
SME
DRL
MECHANICAL DEMOLITION PLAN - BID OPTION #1
3/32"=1'-0"
MD100
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
KEYED NOTES
1. DEMOLISH EQUIPMENT, THERMOSTATS, CONTROLS, ALL
DUCTWORK, FITTINGS, AND ALL APPURTENANCES TO POINT
SHOWN. EXISTING PIPING TO BE CAPPED FOR FUTURE
CONNECTIONS. CONTRACTOR MUST PROTECT ALL EXISTING
HVAC EQUIPMENT, DUCTWORK, DIFFUSERS, ETC. FROM ANY
DAMAGE OR CONTAMINATION. OPEN ENDS OF ALL
DUCTWORK (EXISTING AND NEW) MUST BE COVERED
DURING CONSTRUCTION. CONTRACTOR MUST
MECHANICALLY CLEAN ALL HVAC SYSTEM IN WORK AREA TO
REMOVE ALL VISIBLE CONTAMINANTS, SUCH THAT SYSTEMS
ARE CAPABLE OF PASSING NADCA CLEANING VERIFICATION
TESTING STANDARDS ONCE CONSTRUCTION IS COMPLETE.
2. DEMOLISH EXISTING FUME HOOD, DUCTWORK, CONTROLS,
AND ALL APPURTENANCES. DEMOLISH AND CAP ALL
EXISTING UTILITIES CONNECTED TO EXISTING FUME HOOD.
DEMOLISH EXISTING ASSOCIATED EXHAUST FAN LOCATED
ON ROOF AND SEAL EXISTING PENETRATION WATER TIGHT.
DEMOLITION OF EXISTING SYSTEM WILL REQUIRE ASBESTOS
ABATEMENT.
X
EXISTING
AHU-7 TO
REMAIN
DEMOLISH
EXISTING AHU-5
DEMOLISH
EXISTING
AHU-4
EXISTING
AHU-6 TO
REMAIN
EXISTING
AIR
SEPARATOR
TO REMAIN
EXISTING AHU-3
TO REMAIN
DEMOISH
EXISTING AHU-1
DEMOLISH
EXISTING
AHU-2
TYP. EXISTING 3"
HWS & HWR PIPING
TO REMAIN
EXISTING 1" HWS
AND HWR TO BE
DEMOLISHED
EXISTING 3"
HWS AND
HWR TO BE
DEMOLISHED
EXISTING 3"
HWS AND HWR
EXISTING 3"
HWS AND
HWR
EXISTING
1-1/4" HWS
AND HWR
EXISTING 3"
HWS AND
HWR TO
REMAIN
EXISTING 6" HWS
AND HWR TO
REMAIN
TYP. EXISTING
DUCTWORK TO
REMAIN
BASE BID
WORK (SEE
MD100)
DEMOLISH EXISTING
RETURN DUCTWORK
AND GRILLE
EXISTING
HVAC UNIT
TO REMAIN
DEMOLISH
EXISTING
ACCU-4
DEMOLISH EXISTING
RETURN DUCTWORK
AND GRILLE
DEMOLISH EXISTING EXHAUST FAN.
TEMPORARILY SEAL EXISTING PENETRATION
WATER TIGHT UNTIL RECONNECTION.
DEMOLISH EXISTING
DUCTWORK UP TO
ROOFTOP EXHAUST FAN
DEMOLISH
EXISTING AIR
TERMINALS
LEGEND:
POINT OF
CONNECTION
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
JAMIE WHITTEN DELTA STATES RESEARCH CENTER
DESIGN TO REPLACE BUILDING 7 GREENHOUSE 3
STONEVILLE, MISSISSIPPI
MECHANICAL ROOF DEMOLITION PLAN
BID OPTION #1
MD102
19 422/24/2026
RPP
SME
DRL
MECHANICAL ROOF DEMOLITION PLAN - BID OPTION #1
3/32"=1'-0"
MD102
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
KEYED NOTES
1. DEMOLISH EXISTING FUME HOOD EXHAUST FAN LOCATED
ON ROOF. EXISTING CURB MUST BE CAPPED AND SEALED
WATER TIGHT.
X
EXISTING FUME
HOOD
EXHAUST FAN
TO BE
DEMOLISHED
DEMOLISH EXISTING AHU-2 OUTDOOR AIR
INTAKE. EXISTING ROOF CURB MUST REMAIN
AND BE TEMPORARILY CAPPED WATER TIGHT
UNTIL RECONNECTION.
DEMOLISH EXISTING RESTROOM
EXHAUST FAN, DUCTWORK, AIR
TERMINALS, CONTROLS, AND ALL
APPURTENANCES. EXISTING ROOF
CURB MUST REMAIN AND BE
TEMPORARILY CAPPED WATER TIGHT
UNTIL RECONNECTION.
EXISTING
ROOFTOP
PACKAGED
UNIT TO
REMAIN
EXISTING
ROOFTOP FAN
TO REMAIN
EXISTING
INTAKE TO
REMAIN
EXISTING ROOFTOP
FAN TO REMAIN
EXISTING FUME HOOD
EXHAUST FAN TO REMAIN
R H W
S
HWS
HWR
EXIST.
AHU-1
35.0 GPM
350 MBH
EXIST.
AHU-3
9.2 GPM
92.0 MBH
HWR
HWS
HWR
HWS
HWS
H W
S
HWR
H W
R
EXIST.BOILER
1496.5 MBH
EXIST. BOILER
1530 MBH
EXIST. PUMP
87 GPM
EXIST. PUMP
81 GPM
H W
R H W
S
EXIST.
AHU-7
0.9 GPM
9.0 MBH
EXIST.
AHU-5
7.0 GPM
70.3 MBH
EXIST.
AHU-2
35.0 GPM
350 MBH
H W
S H W
R
EXIST.
AHU-6
0.9 GPM
9.0 MBH
EXIST.
AHU-4
5.0 GPM
5.0 MBH
EXIST. CHEMICAL
FEEDER
ET-1 ET-2
EXIST. PUMP
452 GPM
(VFD)
EXIST. AS-1
DCW
HWS
HWR
H W
R H W
S
EXISTING EXPANSION
TANKS TO REMAIN
RELIEF VALVE (TYP.)
H W
S
H W
R
119.67 GPM
89.75 GPM
EXIST.
GREENHOUSE
BAY
29.92 GPM
216.8 MBH
59.83 GPM
119.67 GPM
89.75 GPM
EXIST.
GREENHOUSE
BAY
29.92 GPM
216.8 MBH
59.83 GPM
119.67 GPM
89.75 GPM
59.83 GPM
126.67 GPM
EXISTING 3" HWS&R
EXISTING 2" HWS&R
EXISTING 3" HWS&R
EXISTING 3" HWS&R
EXISTING
THERMOMETER (TYP.)
EXISTING 6" HWS&R
161.67 GPM
167.56
GPM
168.47 GPM
452 GPM239.34 GPM
EXIST.BOILER
1496.5 MBH
EXIST. PUMP
81 GPM
EXIST. PUMP
452 GPM
(VFD)
EXIST.
GREENHOUSE
BAY
29.92 GPM
216.8 MBH
EXIST.
GREENHOUSE
BAY
29.92 GPM
216.8 MBH
EXIST.
GREENHOUSE
BAY
29.92 GPM
216.8 MBH
EXIST.
GREENHOUSE
BAY
29.92 GPM
216.8 MBH
EXIST.
GREENHOUSE
BAY
29.92 GPM
216.8 MBH
EXIST.
GREENHOUSE
BAY
29.92 GPM
216.8 MBH
EXIST.
GREENHOUSE
BAY
29.92 GPM
216.8 MBH
EXIST.
GREENHOUSE
BAY
29.92 GPM
216.8 MBH
EXIST.
GREENHOUSE
BAY
29.92 GPM
216.8 MBH
EXIST.
GREENHOUSE
BAY
29.92 GPM
216.8 MBH
EXIST. PRESSURE
REDUCING VALVE
EXIST. 3/4" DOMESTIC
COLD WATER TO REMAIN
EXIST. BACKFLOW PREVENTER
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
JAMIE WHITTEN DELTA STATES RESEARCH CENTER
DESIGN TO REPLACE BUILDING 7 GREENHOUSE 3
STONEVILLE, MISSISSIPPI
HOT WATER PIPING
DEMOLITION DIAGRAM
MD800
20 422/24/2026
RPP
SME
DRL
HOT WATER PIPING DEMOLITION DIAGRAM
NOT TO SCALE
MD800
KEYED NOTES
1. DEMOLISH EXISTING PUMP, PIPING, CONTROLS, AND ALL
APPURTENANCES.
2. DEMOLISH EXISTING BOILER, PIPING, CONTROLS, AND ALL
APPURTENANCES.
3. EXISTING AIR HANDLER, PIPING, CONTROLS, AND ALL
APPURTENANCES TO BE DEMOLISHED UNDER BID OPTION
#1.
4. DEMOLISH EXISTING HYDRONIC PIPING, HEATING
EQUIPMENT, CONTROLS, AND ALL APPURTENANCES
LOCATED IN GREENHOUSE.
X
LEGEND:
POINT OF
CONNECTION
R H
W S
H W
R H
W S
R O
R O
R O
R O
H W
R H
W S
H W
R H
W S
TOILET
& SHOWER
RM
ROOM
STORAGE
WORK AREA
TOILET
STORAGE
STORAGE
CORRIDOR MECHANICAL
WORK AREA
WORK AREA
STORAGE
RM
RM
EQUIP. STO.
OFFICE
OFFICE
BREAK
STORAGE
STORAGE
METAL
COLD ROOM
WORK AREA
BLDG
WET LAB
DRY LAB
COVERED AREA
SPRAY ROOM
10124
108109
126 125
PLANT ROOM PLANT ROOM
PLANT ROOM PLANT ROOM
PLANT ROOM PLANT ROOM
PLANT ROOM PLANT ROOM
PLANT ROOM
PLANT ROOM
PLANT ROOM
PLANT ROOM
OVENOVEN
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
JAMIE WHITTEN DELTA STATES RESEARCH CENTER
DESIGN TO REPLACE BUILDING 7 GREENHOUSE 3
STONEVILLE, MISSISSIPPI
MECHANICAL FLOOR PLAN
M100 21 422/24/2026
RPP
SME
DRL
MECHANICAL PLAN
3/32"=1'-0"
M100
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
EXISTING
AHU-7
EXISTING 3" HWS &
HWR PIPING
KEYED NOTESX
B-1&2
HTWP-1&2
EXISTING AHU-5
EXISTING AHU-4
EXISTING AHU-2
EXISTING 1" HWS AND HWR
EXISTING 3" HWS AND HWR
EXISTING 3" HWS AND HWR
EXISTING 3" HWS AND
HWR
EXISTING 3" HWS
AND HWR
EXISTING AHU-6
EXISTING
BOILER
EXISTING AIR
SEPARATOR TO REMAIN
EXISTING 6" HWS
AND HWR
EXISTING
AHU-3
EXISTING
AHU-1
ECP-1
EF-1
ECP-2
ECP-3
ECP-4
ECP-5
ECP-6
ECP-7
ECP-8
EF-2
EF-3
EF-4
EF-5
EF-6
EF-7
EF-8
LEGEND:
POINT OF
CONNECTION
1. CONNECT PIPING FROM HTWP-1&2 AND B-1&2 TO EXISTING
HWS AND HWR PIPING.
2. PROVIDE MODULATING CONTROL VALVE FOR EACH
GREENHOUSE BAY.
3. PROVIDE AUTOMATIC AIR VENT/BLEED VALVE.
4. PROVIDE MICRO-GROW GROW MASTER CONTROLLER
SYSTEM OR APPROVED EQUAL. MASTER CONTROLLER
SYSTEM MUST BE MOUNTED ON APPROXIMATELY 4'-0" X 4'-0"
MARINE-GRADE PLYWOOD BASE AND MUST BE COMPLETE
WITH RELAYS, CONTACTORS, ALL SENSORS, AND
APPURTENANCES FOR A COMPLETE OPERATIONAL SYSTEM.
PROVIDE CONTROL OF ENTIRE GREENHOUSE AND
HEATING/COOLING EQUIPMENT SPECIFIED HEREIN
INCLUDING EXHAUST FANS, EVAPORATIVE COOLERS, &
ROOF/SIDE VENTS. SEE SHEET M600 FOR CONTROLS.
TESTING: CHECK THE COMPUTERIZED CLIMATE
CONTROLLER, ADJUST EQUIPMENT AND COMPUTER FOR
PROPER OPERATION AND DEMONSTRATE OPERATION TO
CONTRACTING OFFICER.
5. PROVIDE DRIVE UNIT AND APPURTENANCES FOR ROOF
VENT FOR AUTOMATIC OPERATION OF VENT SYSTEM.
PROVIDE DRIVE UNIT INCLUDING GEAR MOTOR, ROLLER
BEARING PIPE HANGERS, GALVANIZED PIPE, ARM AND ROD
LINKAGE, OPEN AND CLOSE LIMIT SWITCHES, SCREENS,
THERMOSTAT AND OTHER COMPONENTS AS REQUIRED FOR
A COMPLETE OPERATING SYSTEM WITH EMERGENCY
RELEASE MECHANISM: QUICK DISCONNECT-RELEASE OF
ELECTRIC-MOTOR DRIVE SYSTEM, PERMITTING MANUAL
OPERATION IN THE EVENT OF OPERATING FAILURE.
MOTORIZED VENT MUST BE THE FULL LENGTH OF THE
GREENHOUSE BAY. INTER-COMPONENT WIRING BY THE
CONTRACTOR; 110V POWER WIRING TO COMPONENTS BY
ELECTRICAL. GEAR MOTORS MUST BE
HIGH-STARTING-TORQUE, REVERSIBLE, CONTINUOUS-DUTY,
CLASS A INSULATED, ELECTRIC MOTORS, COMPLYING WITH
NEMA MG 1, WITH THERMAL-OVERLOAD PROTECTION; SIZED
TO OPEN AND OPERATE SIZE AND WEIGHT OF ROOF VENT
WITHOUT EXCEEDING NAMEPLATE RATINGS OR
CONSIDERING SERVICE FACTOR, WITH THE FOLLOWING
SPECIFICATIONS:
··· SERVICE FACTOR: ACCORDING TO NEMA MG 1,
UNLESS OTHERWISE INDICATED.
··· ENCLOSURE: OPEN DRIP PROOF, UNLESS
OTHERWISE INDICATED.
··· MOTORS: SINGLE PHASE, 110V, 60 HZ.
··· LIMIT SWITCHES: ADJUSTABLE SWITCHES,
INTERLOCKED WITH MOTOR CONTROLS AND SET
TO AUTOMATICALLY STOP ROOF VENT AT OPEN
AND CLOSED POSITIONS.
6. PROVIDE CHEMICAL FILTER FEEDER CAPABLE OF
INTERCONNECTION WITH EXISTING CHEMICAL SHOT
SYSTEM. PROVIDE ALL SUPPORTS, WIRING, PIPING, AND ALL
OTHER APPURTENANCES REQUIRED FOR A FULLY
FUNCTIONING SYSTEM.
EXISTING RO
SYSTEM
1-1/4" COPPER HEATING
ELEMENT, 4-1/4"X4-1/4" FIN
SIZE, 2 ROWS AT 6" SPACING
50 FINS/FOOT (TYP.)
5 5
5 5
GENERAL NOTES
1. COORDINATE ALL GREENHOUSE SYSTEMS WITH
GREENHOUSE MANUFACTURER.
PROVIDE NEW TOUCH SCREEN
MASTER CONTROLLER
EXISTING 3"
HWS AND HWR
EXISTING 1-1/4" HWS AND HWR
CFF-1 6
24x1218x1212x12 x6
10x10
10x10
16x1614"Ø
"Ø
"Ø12 "Ø
"Ø x2
10"Ø
10"Ø x1
48x12
12x6
12x8
12x8
12x8
36x1230x1224x1220x1218x1212x12
12x12
12x12
6"Ø
"Ø44x46
6x
10x10 x1
6"Ø
6"Ø
10"Ø
6" Ø
24x22
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
JAMIE WHITTEN DELTA STATES RESEARCH CENTER
DESIGN TO REPLACE BUILDING 7 GREENHOUSE 3
STONEVILLE, MISSISSIPPI
MECHANICAL PLAN
BID OPTION #1
M101 22 422/24/2026
RPP
SME
DRL
MECHANICAL PLAN BID OPTION #1
3/32"=1'-0"
M101
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
KEYED NOTES
1. PROVIDE AHU AND CONNECT TO EXISTING HOT WATER
SUPPLY AND RETURN PIPING. MODIFY PIPING AS REQUIRED
TO SUIT NEW HEATER LOCATION.
2. ROUTE DUCTWORK DOWN FROM AHU TO RAG-2. PROVIDE
ADEQUATE SPACE TO ALLOW FOR THE CONNECTION OF THE
OUTDOOR AIR DUCT ROUTED FROM L-1.
3. PROVIDE EXHAUST FAN, CONTROLS, AND ALL
APPURTENANCES IN EXISTING WALL PENETRATION.
CONTRACTOR MUST FIELD VERIFY EXISTING PENETRATION
DIMENSIONS PRIOR TO BEGINNING OF CONSTRUCTION.
X
AHU-5
AHU-3
AHU-1
EXISTING 3" HWS &
HWR
1" HWS AND
HWR
3" HWS AND
HWR
EXISTING 3"
HWS AND
HWR
EXISTING
1-1/4" HWS
AND HWR
EXISTING 6" HWS
AND HWR
AHU-4
EXISTING
INTAKE LOUVER
BALANCE EXISTING
SUPPLY TO 425 CFM
BALANCE EXISTING
SUPPLY TO 305 CFM
BALANCE
EXISTING
SUPPLY TO 475
CFM
BALANCE
EXISTING SUPPLY
TO 635 CFM
BALANCE EXISTING
SUPPLY TO 650 CFM
BALANCE EXISTING
SUPPLY TO 635 CFM
BALANCE
EXISTING
SUPPLY TO
635 CFM
EXISTING
AHU-7
EXIST.
AHU-6
BALANCE EXISTING
RETURN TO 275 CFMBALANCE EXISTING
SUPPLY TO 315 CFM
AHU-2
RAG-1
280 CFM
EXISTING
HVAC UNIT
PROVIDE ACCU-4
ON EXISTING
EQUIPMENT PAD
EXISTING 3"
HWS AND
HWR
EF-9
BALANCE
EXISTING
SUPPLY TO 330
CFM (TYPICAL
OF 14) BALANCE
EXISTING
SUPPLY TO 255
CFM
BALANCE
EXISTING
SUPPLY TO 255
CFM
BALANCE
EXISTING
SUPPLY TO 170
CFM
BASE BID
WORK (SEE
M-100)
L-1
DUCTWORK
ROUTED TO
L-1
RAG-2
4885 CFM
PROVIDE DUCTWORK DOWN
FROM EXISTING ROOF INTAKE.
SEE DETAIL 6/M501
PROVIDE
DAMPER. SEE
DETAIL 6/M501
PROVIDE RAG-3.
BALANCE TO 165
CFM
BALANCE EXISTING
SUPPLY TO 300 CFM
BALANCE EXISTING
SUPPLY TO 50 CFM
BALANCE EXISTING
SUPPLY TO 135 CFM
SAG-1
CFM
EAG-1
70 CFM
EAG-1
140 CFM
ROUTE DUCTWORK UP
TO EF-10 ON ROOF
PROVIDE RAG-2
BALANCE TO 3960
CFM
LEGEND:
POINT OF
CONNECTION
1 1
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
JAMIE WHITTEN DELTA STATES RESEARCH CENTER
DESIGN TO REPLACE BUILDING 7 GREENHOUSE 3
STONEVILLE, MISSISSIPPI
MECHANICAL ROOF PLAN
BID OPTION #1
M102 23 422/24/2026
RPP
SME
DRL
MECHANICAL ROOF PLAN - BID OPTION #1
3/32"=1'-0"
M102
SCALE: 3/32" = 1'-0"
16' 8' 0 16'
KEYED NOTES
1. PROVIDE EXHAUST FAN ON EXISTING ROOF CURB. PROVIDE
ALL DUCTWORK, INSULATION, AIR TERMINALS, CONTROLS,
AND ALL APPURTENANCES.
2. PROVIDE PENTHOUSE INTAKE LOUVER ON EXISTING CURB.
CONTRACTOR MUST FIELD VERIFY EXISTING CURB
DIMENSIONS PRIOR TO ANY CONSTRUCTION. PROVE
MANUFACTURE RECOMMENDED BRACING AND FLASH SHEET
METAL FROM EXISTING ROOF CURB TO PENTHOUSE LOUVER.
CONTRACTOR MUST SEAL CONNECTION WATER TIGHT. SEE
DETAIL 7/M501.
X
L-2
EF-10
EXISTING
ROOFTOP
PACKAGED
UNIT
EXISTING
ROOFTOP FAN
EXISTING
INTAKE
EXISTING
ROOFTOP FAN
EXISTING FUME
HOOD
EXHAUST FAN
SEE ARCHITECTURAL
FOR EXISTING CURB CAP
NORTH
4-1/2"
-1
/2
48"
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
JAMIE WHITTEN DELTA STATES RESEARCH CENTER
DESIGN TO REPLACE BUILDING 7 GREENHOUSE 3
STONEVILLE, MISSISSIPPI
MECHANICAL DETAILS
M500 24 422/24/2026
RPP
SME
DRL
SOLAR
K-LUX
WALL
BRACKETS
FIXED TO
GREENHOUSE
STRUCTURE
GREENHOUSE
STRUCTURE
COPPER/ALUMINUM
FINNED TUBING
EXPANDED METAL (18 GA.
MIN.) COVER, BAKED OR
POLYESTER POWDER, OAT
FINISH
SCALE:
WEATHER STATION DETAIL
NOT TO SCALE
M500
SCALE:
EVAPORITIVE COOLING WALL & PUMP DETAIL
NOT TO SCALE
M500SCALE:
WALL FAN MOUNTING DETAIL
NOT TO SCALE
M500
SCALE:
FINNED TUBE RADIATION DETAIL
NOT TO SCALE
M500
STRAIGHT RACK
& PINION
INSECT SCREEN
RIDGE VENT MOTOR
ROOF VENT
SCALE:
ROOF VENT DETAIL
NOT TO SCALE
M500
P
P
PUMP
DISCHARGE
PIPING (SEE
PLANS)
PUMP SUCTION
PIPING (SEE
PLANS)
PRESSURE
GAUGE
PRESSURE
GAUGE
THERMOMETER
BUTTERFLY VALVE
BUTTERFLY
VALVE
MOTORIZED FLOW
CONTROL VALVE
CHECK VALVE
FLEX CONNECTION
CONCENTRIC REDUCER
BASE MOUNTED PUMP
SUCTION
DIFFUSER
DRAIN WITH
BALL VALVE
EXISTING FLOOR
HOUSEKEEPING PAD
PUMP BASE
STAINLESS STEEL
BRAIDED FLEX
CONNECTION
STRAINER WITH
BLOWDOWN
PETES PLUG
(TYP.)
SUCTION DIFFUSER
SUPPORT
SCALE:
BASE MOUNTED PUMP DETAIL
NOT TO SCALE
M500
HOSE BIBB
SUMP PUMP
FLOAT
SUMP TANK
FLOAT VALVE
1/2" MAKE-UP
WATER
SHUT-OFF
VALVE
120V POWER TO
STARTER
2-1/2" DRAIN
HOSE BIBB
PVC BALL VALVE
PVC UNION
MEDIA
PIPE SIZED PER
MANUFACTURER'S
RECOMMENDATIONS
MANUFACTURER
PROVIDED FRAME
SUPPORT (TYP.)
EXTERIOR
WALL
BACKDRAFT
DAMPER/SHUTTER
GREENHOUSE
EXHAUST FAN
FAN SUPPORT AS PER
MANUFACTURER'S
RECOMMENDATIONS
SECURELY MOUNT THE OUTDOOR
SENSOR AT THE HIGHEST
UNOBSTRUCTED POINT ON THE
GREENHOUSE. OBSERVE NORTH
POSITIONING. INSTALL SENSOR
PER MANUFACTURER'S AND
GREENHOUSE MANUFACTURER'S
RECOMMENDATIONS.
OUTDOOR
TEMPERATURE
SOLAR
K-LUX
RAIN
WIND
SPEED
WIND
DIRECTION
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
JAMIE WHITTEN DELTA STATES RESEARCH CENTER
DESIGN TO REPLACE BUILDING 7 GREENHOUSE 3
STONEVILLE, MISSISSIPPI
MECHANICAL DETAILS
BID OPTION #1
M501 25 422/24/2026
RPP
SME
DRL
AIR FLOW 5
KEYED NOTES
PROVIDE BALANCING VALVE WITH
MINIMUM OF 3 STRAIGHT PIPE
DIAMETERS UPSTREAM AND 1
STRAIGHT PIPE DIAMETER
DOWNSTREAM.
MAINTAIN 6" MINIMUM CLEARANCE
ABOVE TEST PLUG TO ALLOW
GAUGE TO BE INSERTED. DO NOT
COVER PLUG WITH INSULATION.
PROVIDE SWING JOINTS AT COIL
CONNECTIONS.
CONNECT BRANCH LINES FROM
COIL INTO TOP OR SIDE OF SUPPLY
AND RETURN MAINS. CONNECTING
INTO BOTTOM OF MAIN IS NOT
ACCEPTABLE.
PROVIDE COILS WITH INLET
STRAINERS AND CAPPED HOSE
CONNECTION BLOW DOWN VALVES.
PROVIDE MANUAL AIR VENTS IN
SUPPLY AND RETURN COIL BRANCH
PIPING AS FOLLOWS:
A) IN PIPING HIGH POINT WHEN
PIPING IS ABOVE MAIN.
B) CLOSE TO COIL WHEN PIPING IS
NOT ABOVE MAIN (SIDE
CONNECTION).
NC
NO
C
HTWS
SHUT-OFF VALVE (TYP.)
HTWR
BALANCING VALVE
3-WAY CONTROL VALVE
DIRECT ACTING SIGNAL
PLUG VALVE, ADJUST
TO EQUAL GPM THRU
COIL AT DESIGN FLOW
TEST PLUG (TYP.)
1/2" PLUGGED DRAIN VALVE COIL
MANUAL AIR VENT,
3/8" BALL VALE (TYP.)
SCALE:
3-WAY HEATING WATER COIL DETAIL
N.T.S
M501
AIR FLOW
KEYED NOTES
PROVIDE BALANCING VALVE WITH
MINIMUM OF 3 STRAIGHT PIPE
DIAMETERS UPSTREAM AND 1
STRAIGHT PIPE DIAMETER
DOWNSTREAM.
MAINTAIN 6" MINIMUM CLEARANCE
ABOVE TEST PLUG TO ALLOW GAUGE
TO BE INSERTED. DO NOT COVER
PLUG WITH INSULATION.
PROVIDE SWING JOINTS AT COIL
CONNECTIONS.
CONNECT BRANCH LINES FROM COIL
INTO TOP OR SIDE OF SUPPLY AND
RETURN MAINS. CONNECTING INTO
BOTTOM OF MAIN IS NOT
ACCEPTABLE.
PROVIDE COILS WITH INLET
STRAINERS AND CAPPED HOSE
CONNECTION BLOW DOWN VALVES.
PROVIDE MANUAL AIR VENTS IN
SUPPLY AND RETURN COIL BRANCH
PIPING AS FOLLOWS:
A) IN PIPING HIGH POINT WHEN
PIPING IS ABOVE MAIN.
B) CLOSE TO COIL WHEN PIPING IS
NOT ABOVE MAIN (SIDE
CONNECTION).
NO
6HTWS
SHUT-OFF VALVE (TYP.)
HTWR
BALANCING VALVE
2-WAY CONTROL VALVE
REVERSE ACTING SIGNAL
TEST PLUG (TYP.)
1/2" PLUGGED DRAIN VALVE COIL
MANUAL AIR VENT,
3/8" BALL VALE (TYP.)
SCALE:
2-WAY HEATING WATER COIL DETAIL
N.T.S
M501
3"
CABLE WRAP
AROUND BEAM
AND BAR JOIST
CL20
DUCTMATE
CLUTCHERS
WR20 CABLE
DUCT
DUCT
INSULATION
THREADED ROD
DOUBLE NUT
UNISTRUT OR
ANGLE
UNISTRUT BAR
BAR JOIST
CL20
DUCTMATE
CLUTCHER OR
EQUAL
DUCTMATE
WR20 CABLE
OR EQUAL
MINIMUM 3/8"
DIA. THREADED
ROD
12 GAUGE
GALVANIZED
STEEL
DUCT
DUCT
INSULATION
DOUBLE NUT
DUCT
EXTERNAL INSULATION WHERE
SPECIFIED
NOTE: FOR SIZES UP TO 60"
WITH 10' MAXIMUM SPACING.
NOTE: SEMI-CIRCLE
HANGER. 61"-72" DIAMETER
WITH 10' MAXIMUM
SPACING.
END VIEW ELEVATION VIEW
2"3 1/2" 1"
NOTE: FOR SIZES UP TO 60"
WITH 10' MAXIMUM SPACING.
SINGLE
DOUBLE
NOTE: 10' MAXIMUM SPACING.
97-120
85-96
72-84
61-72
DUCT SIZE (IN.) STRUT SIZE
1 5/8 X 1 5/8 X 12 GA
N/A
N/A
N/A
2 1/2 X 2 1/2 X 1/4
2 X 2 X 1/4
N/A
ANGLE SIZE
3 X 3 X 1/4
3/8
ROD SIZE
3/8
3/8
3/8
SCALE:
DUCT HANGER DETAILS
N.T.S
M501
PROVIDE MANUAL OPPOSED DAMPER IN EACH BRANCH LINE
UNLESS OTHERWISE NOTED ON DRAWINGS. DAMPERS SHALL
BE INSTALLED IN ACCESSIBLE LOCATION NEAR TRUNK DUCT
AND MINIMUM OF 5'-0" FROM ANY AIR INLET OR OUTLET
DEVICE. COORDINATE W/ ACCESS DOORS IN NON-ACCESSIBLE
CEILINGS.
TRUNK
DUCT
OVAL BRANCH
DUCT
45° CLINCH COLLAR PER SMACNA
USE AT ALL BRANCH TAPS
UNLESS
SPLITTER DAMPERS ARE
INDICATED.
BELL-MOUTH
FITTING
NOTE:
DAMPERS SHALL BE PROVIDED IN ALL BRANCH RUN-OUTS TO DIFFUSERS, R.A AND EXHAUST GRILLES, UNLESS SPECIFICALLY NOTED OTHERWISE ON DRAWINGS.
LOCATE DAMPERS SO THEY ARE ACCESSIBLE FROM LAY-IN CEILING OR ACCESS DOORS.
ROUND
DUCT
TURNING VANES, TYPICAL
TURNS 45° OR LARGER
RUNNER
INSTALL VANES
TANGENT TO
AIRSTREAM
DOUBLE SIDED TURNING
VANES REQUIRED WHERE
DUCT HEIGHT IS 24" OR
GREATER.
TOP RUNNER NOT SHOWN FOR
CLARITY.
NUMBER AND CONFIGURATION OF
VANES PER SMACNA STANDARDS.
SCALE:
TURNING VANE DETAIL
N.T.S
M501
SCALE:
BRANCH DUCT TAP DETAIL
N.T.S
M501
DUCTWORK DOWN
FROM ROOF
10" X 10"
DUCTWORK TO
RETURN OF AHU-2
6" X 6" DUCTWORK
TO RETURN OF
AHU-4
CAPPED
DUCTWORK
GRILLE OBTAINING
RETURN AIR FOR
AHU-4 FROM
CORRIDOR
MANUALLY OPERATED
CONTROL DAMPER. SET
DAMPER TO SCHEDULED
OUTDOOR AIR VALUE
MANUALLY OPERATED
CONTROL DAMPER. SET
DAMPER TO SCHEDULED
OUTDOOR AIR VALUE
SCALE:
AHU-2 AND AHU-4 OUTDOOR AIR CONNECTION DETAIL
N.T.S
M501
L-2
EXISTING ROOF
SCALE:
ROOF MOUNTED EXHAUST FAN DETAIL
N.T.S
M501
EXHAUST FAN
(SEE SCHEDULE)
BACKDRAFT DAMPER
FLASHING CAULK
WATER TIGHT
EXISTING ROOF CURB TO
BE MODIFIED AS NEEDED.
SEE ARCH.
EXISTING ROOF
EXISTING ROOF CURB
PROVIDE CURB ADAPTER FOR
TRANSITION FROM EXISTING ROOF CURB
TO PENTHOUSE LOUVER.
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
JAMIE WHITTEN DELTA STATES RESEARCH CENTER
DESIGN TO REPLACE BUILDING 7 GREENHOUSE 3
STONEVILLE, MISSISSIPPI
BASE BID
MECHANICAL SCHEDULE
M600 26 422/24/2026
RPP
SME
DRL
FAN SCHEDULE
MARK MANUFACTURER MODEL TYPE RPM
EF-1 GREENHECK AER-42-03-0305-VG SIDEWALL 7,800 855
EF-2
0.27"
AIRFLOW
(CFM)
E.S.P.
(IN W.G.)
DRIVE
DIRECT
ELECTRICAL
HP
VOLTS
PHASE
REMARKS
SEE NOTES
EF-3
EF-4
EVAPORATIVE COOLING PAD
MARK MANUFACTURER MODEL LENGTH GPM
ECP-1 13'
REMARKS
SEE NOTES
HEIGHT
3'
EAT
DB(°F) WB(°F)
97 77.2
MEDIA
THICKNESS
6"
MAX. FACE
VELOCITY
ECP-2
ECP-3
ECP-4
TEMPERATURE SENSOR
GREENHOUSE BAY
CONTROLLER INPUT/
OUTPUT SUMMARY
AN
AL
O G
IN
PU
T
AN
AL
O G
O U
TP
U
T
BI
N
AR
Y
IN
PU
T
BI
N
AR
Y
O U
TP
U
T
HUMIDITY SENSOR
FAN #1 START/STOP
FAN #2 START/STOP (LOW SPEED)
FAN #2 START/STOP (HIGH SPEED)
VENT WALL MOTOR (OPEN)
VENT WALL MOTOR (CLOSE)
EVAPORATING COOLING WALL START/STOP
HEATING VALVE
WALL VENT WALL OPEN LIMIT
WALL VENT CLOSE WALL LIMIT
X
X
X
X
X
X
X
X
X
X
X
10.0
10.0
10.0
VENT ROOF MOTOR (OPEN)
VENT ROOF MOTOR (CLOSE)
X
X
ROOF VENT WALL OPEN LIMIT
ROOF VENT CLOSE WALL LIMIT
X
X
NOTE: PROVIDE CONTROLLERS AS REQUIRED FOR THE
INPUT/OUTPUT/OUTPUT SUMMARY ABOVE.
RAIN
WEATHER STATION
CONTROLLER INPUT/
OUTPUT SUMMARY
AN
AL
O G
IN
PU
T
AN
AL
O G
O U
TP
U
T
BI
N
AR
Y
IN
PU
T
BI
N
AR
Y
O U
TP
U
T
WIND DIRECTION
WIND SPEED
SOLAR K-LUX
OUTDOOR TEMPERATURE
X
X
X
X
X
NOTE: PROVIDE CONTROLLERS AS REQUIRED FOR THE
INPUT/OUTPUT/OUTPUT SUMMARY ABOVE. WEATHER STATION
CONTROLLER TO BE BY SAME MANUFACTURER TO GREENHOUSE
BAY CONTROLLER.
ACME OR EQUAL
ACME OR EQUAL
ACME OR EQUAL
ACME OR EQUAL
OCCUPIED COOLING: STEPS TO MAINTAIN ADJUSTABLE
SETPOINT AS MEASURED BY TEMPERATURE SENSOR
STEP 1: OPEN SIDE VENTS.
STEP 2: COOLING 1 - ACTIVATE LOW SPEED OF TWO
SPEED FANS.
STEP 3: COOLING 2 - ACTIVATE HIGH SPEED OF TWO
SPEED FANS.
STEP 4: COOLING 3 - ACTIVATE EVAPORATIVE
COOLING WALL SYSTEM.
HEATING: STEPS TO MAINTAIN ADJUSTABLE SETPOINT
STEP 1: CLOSE ROOF AND SIDE VENTS.
STEP 2: HEATING 1 - MODULATE THE NEW
ELECTRONIC VALVE ACTUATOR TO MAINTAIN
TEMPERATURE SETPOINT.
CONTROL SYSTEM SHALL MONITOR INDOOR AIR
TEMPERATURE AND HUMIDITY, OUTDOOR AIR TEMPERATURE,
RAIN CONDITIONS, WIND DIRECTION AND SPEED, AND SOLAR
KLUX. CONTROL SYSTEM SHALL PROTECT GREENHOUSE
VENTILATION SYSTEMS FROM HIGH WINDS AND RAIN DAMAGE.
PROVIDE MANUAL OVERRIDE FOR ROOF VENTS.
COORDINATION OF CONTROLS TO GROW LIGHTS SHOWN ON
ELECTRICAL IS REQUIRED. PROVIDE ALL WIRING AND
CONTROLS FOR A COMPLETE OPERATIONAL SYSTEM.
SEQUENCE OF OPERATION
NOTES:
1. PROVIDE WITH TWO-SPEED MOTOR AND UNIT MOUNTED STARTER.
2. PROVIDE WITH INLET MOUNTED GRAVITY SHUTTERS TO CLOSE WHEN FAN IS NOT IN OPERATION.
3. PROVIDE DRY CONTACT FOR REMOTE START/STOP OF EXHAUST FAN TO INTERFACE WITH GREENHOUSE CONTROL SYSTEM.
4. PROVIDE WITH WALL-MOUNTED SWITCH FOR ACTIVATION.
EF-5
EF-6
EF-7
EF-8
ECP-5 10.0
ECP-6
ECP-7
ECP-8
10.0
10.0
10.0
ACME OR EQUAL
ACME OR EQUAL
ACME OR EQUAL
ACME OR EQUAL
3'
3'
3'
3'
3'
3'
3'
MOP
SCCRFLA MCA
16.2 5 KA13
SONES
GREENHECK AER-42-03-0305-VG SIDEWALL 7,800 855 0.27" DIRECT 1 1152516.2 5 KA13 30
GREENHECK AER-42-03-0305-VG SIDEWALL 7,800 855 0.27" DIRECT 1 1152516.2 5 KA13 30
GREENHECK AER-42-03-0305-VG SIDEWALL 7,800 855 0.27" DIRECT 1 1152516.2 5 KA13 30
GREENHECK AER-42-03-0305-VG SIDEWALL 7,800 855 0.27" DIRECT 1 1152516.2 5 KA13 30
GREENHECK AER-42-03-0305-VG SIDEWALL 7,800 855 0.27" DIRECT 1 1152516.2 5 KA13 30
GREENHECK AER-42-03-0305-VG SIDEWALL 7,800 855 0.27" DIRECT 1 1152516.2 5 KA13 30
GREENHECK AER-42-03-0305-VG SIDEWALL 7,800 855 0.27" DIRECT 1 1152516.2 5 KA13 30
NOTES:
1. PROVIDE MAKE-UP WATER AS RECOMMENDED BY MANUFACTURER TO EACH COOLING WALL.
2. PROVIDE MANUFACTURER PROVIDED TANK AND PUMPING SYSTEM.
3. PROVIDE CONTROLS TO ALLOW FOR AUTOMATED EVAPORATIVE COOLING PAD DRYING EVERY 24
HOURS IN ACCORDANCE WITH MANUFACTURER'S REQUIREMENTS AND RECOMMENDATIONS.
10.0
SEE NOTES
SEE NOTES
SEE NOTES
SEE NOTES
SEE NOTES
SEE NOTES
SEE NOTES
VOLT
AMPS
2.9
HP
1/3
ELECTRICAL
13' SEE NOTES97 77.2 6" 200 115 2.91/3
13' SEE NOTES97 77.2 6" 200 115 2.91/3
13' SEE NOTES97 77.2 6" 200 115 2.91/3
13' SEE NOTES97 77.2 6" 200 115 2.91/3
13' SEE NOTES97 77.2 6" 200 115 2.91/3
13' SEE NOTES97 77.2 6" 200 115 2.91/3
13' SEE NOTES97 77.2 6" 200 115 2.91/3
KOOL-CEL CSBG
KOOL-CEL CSBG
KOOL-CEL CSBG
KOOL-CEL CSBG
KOOL-CEL CSBG
KOOL-CEL CSBG
KOOL-CEL CSBG
KOOL-CEL CSBG
PUMP SCHEDULE
SERVICEMARK
HTWP-1 PRIMARY
HOT WATER
GPM FT HD
FLOW DESIGN
HEAD
111 25
HP RPM
1.5 1,800
V/PH
MOTOR
POWER
MOTOR
SPEED
MOTOR
VOLTAGE
208/3
TYPE
BASE MOUNTED
END SUCTION
30%
GLYCOL
FLUID
SEE NOTES
REMARKS
NOTES:
1. PROVIDE WITH BUNA-N SEALS.
2. PROVIDE STRAIGHT THROUGH SUCTION DIFFUSER.
3. CONNECT BOILER TO EXISTING BOILER CONTROL PANEL IN MECHANICAL ROOM.
4. PUMPS MUST BE SUITABLE FOR OUTDOOR INSTALLATION AND CONTINUOUS EXPOSURE TO AMBIENT WEATHER CONDITIONS.
5. PUMPS, MOTORS, COUPLINGS, BEARINGS, SEALS, AND ALL ASSOCIATED COMPONENTS MUST BE RATED FOR OUTDOOR SERVICE AND MUST BE CAPABLE OF OPERATING IN FREEZING TEMPERATURES
TYPICAL OF THE PROJECT LOCATION. PROVIDE WEATHERPROOF MOTOR ENCLOSURES (MINIMUM NEMA 3R UNLESS OTHERWISE REQUIRED), CORROSION-RESISTANT COATINGS, AND FREEZE
PROTECTION MEASURES AS REQUIRED FOR A COMPLETE AND OPERABLE INSTALLATION.
BASIS OF DESIGN
BELL & GOSSETT,
SERIES: E-1510
HTWP-2
BOILER SCHEDULE
SERVICEMARK
B-1 HOT WATER
GPM
FLOW
FLA
30% GLCOL
FLUID
SEE NOTES.
REMARKS
NOTES:
1. PROVIDE WITH HIGH LIMIT AQUASTAT SET FOR 200°F.
2. PROVIDE WITH PRESSURE RELIEF VALVE SET FOR 75 PSIG.
3. PROVIDE WITH FACTORY FLOW SWITCH.
4. PROVIDE WITH MANUFACTURER'S SEQUENCER CONTROL SYSTEM FOR OUTDOOR AIR RESET.
5. PROVIDE WITH MINIMUM 95% THERMAL EFFICIENCY AT FACTORY CONDITIONS AND ENERGY STAR RATING .
6. PROVIDE WITH OUTSIDE MANUFACTURER'S VENT AND INLET AIR ATTACHMENT FOR OUTDOOR INSTALLATION.
7. CONNECT BOILER TO EXISTING BOILER CONTROL PANEL IN MECHANICAL ROOM.
BASIS OF DESIGN
MAGNATHERM FT 2000
ELECTRICAL
MBH
INPUT
MIN./MAX.
100/1999.9
MBH
OUTPUT
MIN./MAX.
95/1900N. GAS
FUEL
°F
E.W.T.
°F
L.W.T.
PRIMARY
HOT WATER
B-2 HOT WATER 111 30% GLCOL SEE NOTES.MAGNATHERM FT 2000100/1999.9 95/1900N. GAS 165 200
111 25 1.5 1,800 208/3 BASE MOUNTED
END SUCTION
30%
GLYCOL SEE NOTESBELL & GOSSETT,
SERIES: E-1510
MCA MOP V/PH
7.8 9.7 20 120/1
7.8 9.7 20 120/1
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
JAMIE WHITTEN DELTA STATES RESEARCH CENTER
DESIGN TO REPLACE BUILDING 7 GREENHOUSE 3
STONEVILLE, MISSISSIPPI
MECHANICAL SCHEDULE AND DETAILS
BID OPTION #1
M601 27 422/24/2026
RPP
SME
DRL
OA
FLOW
(CFM)
ESP
(IN H2O)
TSP
(IN H2O)
FAN
SPEED
(RPM)
VOLTS/
PHASE
OPER.
WEIGHT
(LBS) REMARKS
MARK MOTOR
HP
AIRFLOW DATA
1. ALL UNITS TO BE DOUBLE WALL WITH HINGED ACCESS DOORS.
2. EQUIPMENT SHALL COMPLY "BUY AMERICAN ACT". EQUIPMENT SHOWN IN SCHEDULE TO ESTABLISH A STANDARD OF QUALITY, NOT TO LIMIT COMPETITION. EQUIVALENT EQUIPMENT BY OTHER MANUFACTURER'S SHALL BE
ACCEPTABLE.
3. MODIFY EXISTING PIPING AND DUCTWORK AS NEEDED FOR CONNECTION TO NEW EQUIPMENT.
FAN
TYPE FILTER
BASIS
OF DESIGN MOP
ELECTRICAL
TOTAL
MBH
EAT °F
(DB)
APD
(IN WC)
EWT
(°F)
FLOW
(GPM)
WPD
(FT)
ROWSLAT °F
(DB)
LWT
(°F)
HEATING COIL
CAPACITY AIR SIDE WATER SIDE
FLUID
HEATING ONLY AIR HANDLING UNIT SCHEDULE
NOTES:
MCA
AHU-2 GREENHECK
MSX-P116-H22-MF ALL NOTES APPLY340 1.0 1.254 1686 2 208/1 931MERV 8294.7 45 108.3 200 180 30.3 0.2 2WATER
AHU-5 ALL NOTES APPLY750 0.4 - - 0.333 208/1 38562.3 22.9 99.4 200 180 6.0 6.14 1WATER
SA
FLOW
(CFM)
750 MERV 8DAIKIN
UAHF9H07 3-SPEED 156.3
MARK SYSTEM DESCRIPTION GRILLE
SIZE MATERIAL COLOR
MAX
PRESSURE DROP
(in-wg)
AIR TERMINALS SCHEDULE
RAG-2 ALUMINUM MATCH CEILING 0.09CEILING MOUNTED
RAG-1 RETURN 24" x 24" ALUMINUM MATCH CEILING 0.09CEILING MOUNTED
RETURN
AHU-1 GREENHECK
MSX-P122-H22-D1 ALL NOTES APPLY415 1.0 1.351 1144 2 208/1 1098DIRECT MERV 8 30337.9 45 103.9 - 200 180 34.8 0.27 2WATER 175300
AIR COOLED CONDENSING UNIT SCHEDULE
VOLTS/
PHASE
OPER.
WEIGHT
(LBS) REMARKS
MARK TYPE
NOTES:
1. PROVIDE WITH MANUFACTURER PROVIDE LINE SET AND INSULATION.
2. EXTERIOR PIPING INSULATION MUST BE COVERED BY ALUMINUM JACKETING.
MCABASIS OF
DESIGNLOCATION
NOMINAL
SIZE
(TONS)
SEER2
RATING
CONDENSER
AMBIENT
REFRIGERANT
TYPE
MOCP
COOLING
ONLYACCU-4 208/3 183 SEE NOTES16.6DAIKIN 4.0 13.4 105 R-32 25OUTDOOR
OA
FLOW
(CFM)
ESP
(IN H2O)
TSP
(IN H2O)
FAN
SPEED
(RPM)
VOLTS/
PHASE
OPER.
WEIGHT
(LBS) REMARKS
MARK MOTOR
HP
AIRFLOW DATA
1. ALL UNITS TO BE DOUBLE WALL WITH HINGED ACCESS DOORS.
2. EQUIPMENT SHALL COMPLY "BUY AMERICAN ACT". EQUIPMENT SHOWN IN SCHEDULE TO ESTABLISH A STANDARD OF QUALITY, NOT TO LIMIT COMPETITION. EQUIVALENT EQUIPMENT BY OTHER MANUFACTURER'S SHALL BE ACCEPTABLE.
3. MODIFY EXISTING PIPING AND DUCTWORK AS NEEDED FOR CONNECTION TO NEW EQUIPMENT.
FAN
TYPE FILTER
BASIS
OF DESIGN MROPD
ELECTRICAL
TOTAL
MBH
EAT °F
(DB)
EWT
(°F)
FLOW
(GPM)
WPD
(FT)
ROWSLAT °F
(DB)
LWT
(°F)
HEATING COIL
CAPACITY AIR SIDE WATER SIDE
FLUID
AIR HANDLING UNIT SCHEDULE
NOTES:
MCA
AHU-4 ALL NOTES APPLY55 1.0 1.56 1339 1/2 208/1 39771.8 45 127.0 200 180 7.4 13.9 1WATER
SA
FLOW
(CFM)
800 MERV 8DAIKIN
BCHD0101
DIRECT
DRIVE 155.2
TOTAL
BTU/HR
CAPACITY
36995
SENS.
BTU/HR
24503 81.2
EAT °F
(DB)
67.8
EAT °F
(WB)
53.2
LAT °F
(DB)
52.7
LAT °F
(WB)
DX COOLING COIL
DRAIN
(INCH)
3/4"
EXHAUST FAN SCHEDULE
BASIS
OF DESIGN MAX
SONES
VOLTS/
PHASE
OTHER AS
NOTED
OPER.
WEIGHT
(LBS)
MARK
RPMDRIVES.P.CFM
FAN DATA
POWER
HP
CONTROL INTERLOCKS
SWITCH
REMARKSFAN
TYPE FLA MCA MOP
ELECTRICAL DATA
EF-9 GREENHECK
CUBE-120-4 CONSTANTNO 761/47.110480.5 ALL800 BELT CENTRIFUGAL 115/1 5.8 7.25 15
NOTES: 1. PROVIDE WITH MAGNETIC MOTOR STARTER WITH COIL VOLTAGE MATCHING OUTPUT OF THE BUILDING MANAGEMENT SYSTEM. PROVIDE POWER TRANSFORMERS AS REQUIRED.
2. PROVIDE SPARK B RESISTANT EXPLOSION PROOF FANS.
3. EXHAUST FAN MUST OPERATE CONTINUOUSLY.
NOTES:
1. PROVIDE LOUVER WITH ALUMINUM INSECT SCREEN.
2. INTAKE LOUVERS SHALL NOT BE SIZED FOR ANY MORE THAN 80% OF THE LOUVER MANUFACTURER'S BPWP RATING.
MARK DESCRIPTION REMARKSAPPLICATION WIDTH
(IN)
HEIGHT
(IN)
FREE
AREA
(SF)
VOLUME
(CFM)
PRESSURE
DROP
(IN WG)
FREE
AREA
VELOCITY
(FPM)
BEGINNING POINT
OF WATER
PENETRATION,
BPWP (FPM)
L-1 ALL
BASIS
OF
DESIGN
MAKE
BASIS
OF
DESIGN
MODEL
3" DRAINABLE 16 GREENHECK EVH-302OUTSIDE AIR
INTAKE
16 0.5
LOUVER SCHEDULE
DEPTH
(IN)
NECK SIZE
48" x 24"
10"
48" x 24"
RAG-3 ALUMINUM MATCH DUCT 0.09DUCT MOUNTEDRETURN 10" x 4"10" x 4"
SAG-1 ALUMINUM MATCH DUCT 0.09DUCT MOUNTEDSUPPLY 12" x 10" 12" x 10"
EF-10 GREENHECK
CUE-070-VG CONSTANTNO 381/602.913130.2 1,3210 DIRECT CENTRIFUGAL 115/1 1.3 1.6 15
DIRECT 3017
EAG-1 ALUMINUM 0.09EXHAUST CEILING MOUNTED 24" x 24" MATCH CEILING10"
415 0.12 841
NOTES:
1. PROVIDE LOUVER WITH ALUMINUM INSECT SCREEN.
2. INTAKE LOUVERS SHALL NOT BE SIZED FOR ANY MORE THAN 80% OF THE LOUVER MANUFACTURER'S BPWP RATING.
MARK DESCRIPTION REMARKSAPPLICATION WIDTH
(IN)
HEIGHT
(IN)
THROAT
AREA
(SF)
VOLUME
(CFM)
PRESSURE
DROP
(IN WG)
THROAT
AREA
VELOCITY
(FPM)
BEGINNING POINT
OF WATER
PENETRATION,
BPWP (FPM)
L-2 ALL
BASIS
OF
DESIGN
MAKE
BASIS
OF
DESIGN
MODEL
PENTHOUSE 26 GREENHECK ESD-635PDOUTSIDE AIR
INTAKE
24 1
PENTHOUSE LOUVER SCHEDULE
LENGHT
(IN)
26 395 0.06 395
CHEMICAL FILTER FEEDER (CFF-1)
1. PROVIDE ONE (1) FILTER FEEDER FOR THE HEATING WATER LOOP WITH THE CAPABILITY TO INTEGRATE WITH THE EXISTING SHOT FEEDER.
2. BASIS OF DESIGN - JL WINGERT 5HD
3. FURNISH AND INSTALL A PACKAGED, CHEMICAL FILTER FEEDER UNIT FOR DISPENSING PRE-MIXED CHEMICAL TREATMENT TO MAINTAIN
CONSTANT MIXTURE IN HEATING WATER LOOP.
4. THE UNIT MUST CONSIST OF A BASE, 5 GALLON CAPACITY (MAXIMUM) FILTER FEEDER.
NOTES:
OUTDOORS
ROOM
EF-DPS
L H
120 VAC NH
EXHAUST FAN TERMINALS
HAND OFF
AUTO
EF
STR
COIL
OVERLOADS
SEQUENCE OF OPERATION
EXHAUST FAN MUST BE IN OPERATION
CONTINUOUSLY.
FUNCTION
PROOFS
& SAFETIES
EF-S EXHAUST FAN STATUS ON/OFF EXHAUST FAN FAILED TO START INFO
START/STOP EF-SS EXHAUST FAN START/STOP COMMAND ON/OFF
NOTES:
1. THE CONTRACTOR MUST COMPLETE THE POINTS SCHEDULE AS INDICATED IN THE SPECIFICATION AND IN ACCORDANCE WITH THIS DRAWING.
SCALE:
EXHAUST FAN CONTROLS
NTS
DDC
EF-SS
EF-S
POINT NAME DESCRIPTION
SETTING
(WITH UNITS)
RANGE
(WITH UNITS)
IO
TYPE
ALARM CONDITION
(SEE NOTES)
ALARM
PRIORITY
ALARMING
BI
BO
M700
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
c P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA AGRICULTURAL RESEARCH SERVICE
JAMIE WHITTEN DELTA STATES RESEARCH CENTER
DESIGN TO REPLACE BUILDING 7 GREENHOUSE 3
STONEVILLE, MISSISSIPPI
MECHANICAL CONTROLS
BID OPTION #1
M700 28 422/24/2026
RPP
SME
DRL
AIR
OUTSIDE
AIR
SUPPLY
INTAKE DISCHARGE
OA-FLT-P-HL
H LP
FUNCTION
PROOFS
SAFETIES
SF-S
START/STOP
TEMPERATURE
CONTROL
NOTES:
1. THE CONTRACTOR MUST COMPLETE THE POINTS SCHEDULE AS INDICATED IN THE SPECIFICATION AND IN ACCORDANCE WITH THIS DRAWING.
2. UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR MUST SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW.
3. UNIT STATUS: SERVES AS A MONITORED POINT AT THE M&C SOFTWARE (FRONT-END) AND AS A HEATING/COOLING REQUEST TO THE BOILER
AND/OR CHILLER SERVING THIS SYSTEM.
4. THE UNIT CONTROLS MUST INITIATE ALARM UPON DETECTION OF COOLING COIL LEAVING AIR TEMPERATURE BEING EQUAL TO OR GREATER
THAN 5 DEG ABOVE DESIGN DEWPOINT TEMPERATURE.
5. TEMPERATURE SENSORS MUST BE ACCURATE TO 1%. HUMIDITY SENOSR MUST BE ACCURATE TO WITHIN 2.5%.
6. "TBD" = TO BE DETERMINED DURING TAB
SUPPLY FAN STATUS ON/OFF
INLET TEMPERATURE / HUMIDITY
SF-SS SUPPLY FAN START/STOP
ENABLE/DISABLE
FAN CONTROL
SF-C SUPPLY FAN COMMAND
ON/OFF
SA-T/RH
OA-T/RH
SUPPLY AIR DISCHARGE TEMPERATURE /
HUMIDITY
60°F-110°F
15-60% RH
0-130°F/0-100% RH
45-95°F/0-100% RH
SCHEDULED
OA-RH
OA-RH OUTDOOR AIR RELATIVE HUMIDITY ALM/NORMAL
SA-DP SUPPLY AIR DEW POINT TEMPERATURE ALM/NORMAL
OA-F OUTSIDE AIR FLOW MEASURING STATION ALM/NORMAL
OA-FLT-F-HL
H LP
SEQUENCE OF OPERATION
AHU-5:
RUN CONDITIONS - SCHEDULED:
THE UNIT MUST RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE FOLLOWING MODES:
· OCCUPIED MODE: THE UNIT MUST MAINTAIN
· A 60°F (ADJ.) HEATING SETPOINT.
ALARMS MUST BE PROVIDED AS FOLLOWS:
· LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS LESS THAN THE HEATING SETPOINT BY -6 DEGF (ADJ.).
SUPPLY FAN:
IN THE OCCUPIED MODE, THE SUPPLY FAN MUST OPERATE CONTINUOUSLY. VFD MUST MODULATE FAN TO MAINTAIN STATIC PRESSURE SETPOINT SET BY TAB PERSONNEL. IF THE SUPPLY FAN FAILS TO PROVE STATUS FOR 30 SECONDS (ADJ.), THE FAN MUST BE DISABLED AND AN ALARM MUST BE ANNUNCIATED AT THE BAS. A MANUAL SOFTWARE RESET MUST BE REQUIRED TO RESTART THE FAN. A HARDWIRED, HIGH STATIC PRESSURE CUT-OFF SWITCH MUST BE ELECTRICALLY INTERLOCKED WITH THE SUPPLY FAN VARIABLE SPEED DRIVE. IF THE HIGH STATIC PRESSURE CUT-OFF SWITCH IS TRIPPED, THE FAN MUST BE DISABLED, THE OUTSIDE AIR DAMPER MUST CLOSE, ALL HEATING MUST BE DISABLED, AND AN ALARM MUST BE ANNUNCIATED AT THE A MANUAL RESET OF THE HIGH STATIC PRESSURE CUT-OFF SWITCH MUST BE REQUIRED TO RESTART THE FANS.
ZONE SETPOINT ADJUST:
THE OCCUPANT MUST BE ABLE TO ADJUST THE ZONE TEMPERATURE HEATING SETPOINTS AT THE ZONE SENSOR.
OCCUPIED PERIODS
THE SUPPLY FAN MUST RUN CONTINUOUSLY. OUTDOOR AIR DAMPER MUST MODULATE TO THE OPEN POSITION DETERMINED BY THE TAB PERSONNEL. WHEN STARTING UNIT IN SUB-FREEZING WEATHER, THE HEATING WATER VALVE WILL BE COMMANDED OPEN FOR 1 MINUTE BEFORE
THE UNIT BEGINS THE STARTUP SEQUENCE.
DISCHARGE AIR TEMPERATURE:
THE CONTROLLER MUST MONITOR THE DISCHARGE AIR TEMPERATURE.
ALARMS MUST BE PROVIDED AS FOLLOWS:
· HIGH DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS GREATER THAN 120°F (ADJ.).
FREEZE PROTECTION:
A HARDWIRED, LOW LIMIT TEMPERATURE SWITCH MUST BE ELECTRICALLY INTERLOCKED WITH THE VARIABLE SPEED DRIVE. IF THE LOW LIMIT TEMPERATURE SWITCH IS TRIPPED 38.0 DEG. F (ADJ.), THE FAN MUST BE COMMANDED OFF. ALL VALVES MUST BE COMMANDED OPEN TO 100% (ADJUST PER CLIMATE). AN ALARM MUST ANNUNCIATE AT THE BAS AND MANUAL RESET OF THE LOW LIMIT TEMPERATURE
SWITCH MUST BE REQUIRED TO RESTART THE FAN.
FILTER STATUS:
A DIFFERENTIAL PRESSURE SWITCH MUST MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE FILTER(S) WHEN THE FAN IS RUNNING. IF THE SWITCH CLOSES DURING NORMAL OPERATION A DIRTY FILTER ALARM MUST ANNUNCIATE AT THE BAS. CONDENSATE OVERFLOW MONITORING: IF THE CONDENSATE LEVEL REACHES THE TRIP POINT, A CONDENSATE OVERFLOW DIAGNOSTIC MUST ANNUNCIATE AT THE BAS. TO PREVENT THE CONDENSATE DRAIN PAN FROM OVERFLOWING AND CAUSING WATER DAMAGE TO THE BUILDING THE FAN MUST BE DISABLED AND THE CHILLED
WATER VALVE MUST CLOSE.
H
HTG-V-S
NO NC HTG-V-C
HTWR
HTWS
HTG-V-S HEATING VALVE POSITION STATUS 0-100% OPEN
HTG-V-C HEATING VALVE COMMAND 0-100% OPEN AO
POINT NAME DESCRIPTION
SETTING
(WITH UNITS)
RANGE (WITH
UNITS)
IO TYPE ALARM CONDITION
(SEE NOTES)
ALARM
PRIORITY
AI
AI
BO
BI
BI
BI
BI
AI
BI ALM
ALARMING
ALM
ALM
INFO
INFO
CRITICAL
INFO
INFO
INFO
OA-F
SA-T
SA-RH
OA-T
HTG-T DISCHARGE TEMPERATURE 100°F 0-130°F AI INFO
INFO
OA-FLT-P-HL…