RFI RESPONSES - SOLICITATION NO. 1232SA26Q0655.pdf

PDF 193 KB Posted

Attached to
Chiller #2 Repairs - National Agricultural Library
Solicitation number
1232SA26Q0655
Issued by

About this file

This document is a Request for Information (RFI) Responses for Solicitation No. 1232SA26Q0655, issued May 26, 2026. The RFI addresses clarifications regarding building maintenance and cooling system work. Key technical clarifications include confirmation that the 8-inch butterfly valve replacement is the correct size (not 6-inch as stated in conflicting documentation), that contractors may perform work on weekends with advanced notice to the Contract Specialist, and that pipe freeze kits may be used upstream of the valve to minimize system downtime by avoiding complete condenser water loop draining. The response confirms that building maintenance personnel or service providers are responsible for draining the cooling tower and associated piping for valve replacement.

Additional technical specifications clarified include belt specifications (DAYTON Banded V-Belt 4/B100, 4 ribs, 103.8 inches outside length), pulley diameters of 6.5 and 16.5 inches with 4 grooves (requiring contractor field verification prior to ordering), and requirements for the condenser water pump No. 1 repair. The response confirms that both bearing assembly bearings and motor bearings must be replaced. The RFI also specifies that contractors must provide an initial leak search proposal for paragraph C.1.3.1, with an additional repair proposal to follow based on findings, and confirms there is no operational isolation valve associated with the 8-inch valve replacement.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RFI RESPONSES - SOLICITATION NO. 1232SA26Q0655

May 26, 2026

1. Will the building maintenance personnel or service provider be responsible for draining the cooling tower and associated piping for replacement of 8" butterfly valve? Yes

2. Replacing the 8" butterfly valve will require shutting down entire cooling system so work will need to take place after hours on weekdays or weekends. Can the work be performed on the weekend? Yes, with advanced notice submitted to the Contract Specialist.

3. Can the condenser water piping upstream of 8" butterfly valve be frozen using pipe freeze kit to prevent draining of the entire condenser water loop to cooling tower which will save downtime? Yes

4. Please find the following questions regarding the statement of work All pertaining to paragraph C.1.3.1.

a. Is the intent of this paragraph we provide a leak search proposal and there will be a follow up proposal to repair the leak(s)? Yes, provide an additional proposal based on findings.

b. Is there an operational isolation valve allowing for 100% shut off to condenser water pump one to enable replacement of the 8-inch butterfly valve? No there is no isolation valve associated with the 8-inch valve replacement.

c. Can we confirm the shut off valve is in fact, 8 inch and not 6 inch as there is conflicting information in the statement of Work? The valve is an 8-inch shut-off valve.

d. Can we confirm the belt size, the pulley diameter, and the number of grooves of the belt?

i. Belt size – Current belts onsite are DAYTON Banded V-Belt: 4/B100, 4 Ribs, 103.8 in Outside Lg, 2 43/64 in Top Wd, 1/2 in Thick from Grainger.

ii. Pully diameter – 6.5” & 16.5”. Contractor must field verify prior to ordering.

iii. Groove number - 4

5. Regarding the condenser water pumps No. 1 repair: The pump/motor assembly has bearings in bearing assembly and the motor also. Is the request to replace the bearing assembly bearings or the motor bearings? Yes, replace both bearing assembly & motor bearings.