Attachment 9 - RFI Submittal Form QA.xlsx
XLSX spreadsheet 11 KB Posted
- Attached to
- Installation of Cold Storage Room
- Solicitation number
- 1232SA25Q0201
About this file
This document is a Request for Information (RFI) Submittal Form containing eight detailed technical questions about a cold storage room installation project. The solicitation (1232SA25Q0201) is for installing a cold storage room at a University Park, Pennsylvania location, with a project magnitude between $25,000 and $100,000 and a 120-calendar day performance period. The procurement is a 100% small business set-aside under NAICS code 493120, with a small business size standard of $36.5 million.
The RFI questions seek specific technical clarifications including cold room requirements for external dimensions, temperature specifications, humidity ranges, insulation, electrical service, shelving provisions, surface materials, and installation logistics. Questions address critical technical details such as target operating temperature, desired humidity set point, electrical service specifications, and site-specific installation considerations. Potential vendors must submit RFIs by close of business on July 28, 2025, to the USDA Agricultural Research Service contact, with responses to be posted on www.sam.gov. Contractors must also comply with various federal requirements including SAM registration, E-Verify, veterans' employment reporting, and environmental management systems standards.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| 1232SA25RQ0201 Installation of Cold Storage Room | ||
| Question | Answer | |
| 1 | Please provide Cold Room requirements for external dimensions, temperature requirements, humidification requirements/ranges, insulated floor requirement, controller requirement, lighting, and receptacle/outlet requirements. | |
| 2 | Is Cold Room shelving to be provided by CR mfg, or lab casework supplier? | |
| 3 | Section 13 21 26, 2.3, Page 4 mentions providing refrigeration equipment as per manufactures recommendations that meets requirements of drawings and design. What is the target operating temperature and tolerance for the cold storage room as I do not see if mentioned any where else? | |
| 4 | Section 13 21 26, 2.1.1.M, Page 4 mentions a remotely mounted chemical dryer unit implying the room has a desired humidity set point. What (if any), is the target Rh% and tolerance? | |
| 5 | Section 13 21 26, 2.1.1.C, Page 3 - Would 22 ga smooth, white galvanized be acceptable in lieu of smooth aluminum exposed surfaces? Smooth aluminum is more susceptible to damage during transit, installation and throughout the life of the room | |
| 6 | Section 13 21 26 / Att. 5 - What is the electrical service available for compressor and evaporator? Are we to follow electrical listed on page 22 and 23 on Attachment #5 Cold Storage? | |
| 7 | Section 13 21 26 - Installation Questions: What floor is the cold room located on? |
Is there a loading dock at the facility to receive full size tractor trailer?
Is there a fork lift or lull onsite to assist in unloading materials?
| 8 |
| 9 |
| 10 |
| 11 |
| 12 |