About this file

Specs Vol 2

View the file

Other files

File Type Posted
ARTC_Salinas_CA_Cancellation_Notice.pdf PDF
Sol_1232SA19B0001_Amd_0002.pdf PDF
Salinas_ARTC_1232SA19B0001_Amd_001.pdf PDF
Vol-2_Greehouse.pdf PDF
_10-Lab-Special_Systems.pdf PDF
_8-Lab-Electrical.pdf PDF
_9-Lab-Telecom.pdf PDF
_1-Lab-General.pdf PDF
Specifications_Vol_1.pdf PDF
_3-Lab-Landscape.pdf PDF
Davis_Bacon_CA190018_1-4-19.pdf PDF
_2-Lab-Civil.pdf PDF
_6-Lab-Mechanical.pdf PDF
_7-Lab-Plumbing.pdf PDF
Attachments.pdf PDF
_5-Lab-Architectural.pdf PDF
_4-Lab-Structural.pdf PDF
ARTC_Salinas_DBB_Solicitation.pdf PDF
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

THE AGRICULTURAL RESEARCH

TECHNOLOGY CENTER

SALINAS, CALIFORNIA

GREENHOUSE / HEADHOUSE SPECIFICATIONS

CONSTRUCTION PHASING / ALTERNATES REVISION

SUBMISSION

SEPTEMBER 28, 2018

Prepared by:

Setty & Associates, Ltd.

3040 Williams Drive, Suite 600

Fairfax, Virginia 22031 S&A No SAG16056.01

USDA Agricultural Research Technology Center Sept 28,2018 Greenhouse Specifications (VOL. 2) Construction Phasing / Alternates Revisions

PROJECT TABLE OF CONTENTS

DIVISION 01 - GENERAL REQUIREMENTS

01 33 29 SUSTAINABILITY REPORTING

DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES

06 10 00 ROUGH CARPENTRY

06 18 00 GLUED-LAMINATED CONSTRUCTION

DIVISION 07 - THERMAL AND MOISTURE PROTECTION

07 05 23 PRESSURE TESTING AN AIR BARRIER SYSTEM FOR AIR TIGHTNESS

07 14 00 FLUID-APPLIED WATERPROOFING

07 22 00 ROOF AND DECK INSULATION

07 27 10.00 10 BUILDING AIR BARRIER SYSTEM

07 42 13 METAL WALL PANELS

07 43 10 EXTERIOR REAL WOOD COMPOSITE WALL PANELS

07 60 00 FLASHING AND SHEET METAL

07 61 14.00 20 STEEL STANDING SEAM ROOFING

07 81 00 SPRAY-APPLIED FIREPROOFING

07 84 00 FIRESTOPPING

07 92 00 JOINT SEALANTS

DIVISION 08 - OPENINGS

08 11 13 STEEL DOORS AND FRAMES

08 11 16 ALUMINUM DOORS AND FRAMES

08 14 00 WOOD DOORS

08 36 13 SECTIONAL OVERHEAD DOORS

08 44 00 CURTAIN WALL AND GLAZED ASSEMBLIES

08 51 13 ALUMINUM WINDOWS

08 60 45 SKYLIGHTS

08 71 00 DOOR HARDWARE

08 81 00 GLAZING

08 91 00 METAL LOUVERS

DIVISION 09 - FINISHES

09 22 00 SUPPORTS FOR PLASTER AND GYPSUM BOARD

DIVISION 10 - SPECIALTIES

10 21 13 TOILET COMPARTMENTS

10 22 26.13 ACCORDION FOLDING PARTITIONS

10 26 00 WALL AND DOOR PROTECTION

10 28 13 TOILET ACCESSORIES

10 44 16 FIRE EXTINGUISHERS

10 51 13 STEEL CLOTHING LOCKERS

10 56 13 STEEL SHELVING

DIVISION 11 - EQUIPMENT

11 71 00 WARMING CABINETS, STERILIZERS, AND ASSOCIATED EQUIPMENT

DIVISION 13 - SPECIAL CONSTRUCTION

13 34 20 STRUCTURE AND GLAZING/GREENHOUSE

PROJECT TABLE OF CONTENTS Page 1

13 34 21 ISOLATION UNITS PREENGINEERED SHED

DIVISION 18 -

18 00 02 COMMISSIONING OF GREENHOUSE/HEADHOUSE SYSTEMS

DIVISION 22 - PLUMBING

22 00 00 PLUMBING, GENERAL PURPOSE

22 00 01 PLUMBING SYSTEMS/GREENHOUSE

22 15 14.00 40 GENERAL SERVICE COMPRESSED-AIR SYSTEMS, LOW PRESSURE

DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)

23 00 01 SPECIAL EQUIPMENT AND SYSTEM/GREENHOUSE

23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC

23 09 01 GREENHOUSE CONTROL

23 09 23.01 DIRECT DIGITAL CONTROL SYSTEMS

23 22 26.00 20 STEAM SYSTEM AND TERMINAL UNITS

23 31 13.00 40 METAL DUCTS

23 52 49.00 20 STEAM BOILERS AND EQUIPMENT (500,000 - 18,000,000 BTU/HR)

23 54 16.00 10 HEATING SYSTEM; GAS-FIRED HEATERS

23 74 33.00 40 AIR HANDLING UNITS

23 81 00.00 20 UNITARY AIR CONDITIONING EQUIPMENT

23 82 02.00 AIR HANDLING EQUIPMENT/GREENHOUSE

DIVISION 26 - ELECTRICAL

26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS

26 00 00.01 BASIC ELECTRICAL MATERIALS AND METHODS

26 05 01.00 GENERAL ELECTRICAL PROVISIONS / GREENHOUSE

26 05 05 CONTROL/INSTRUMENTATION WORK FOR GREENHOUSES

26 05 48.00 10 SEISMIC PROTECTION FOR ELECTRICAL EQUIPMENT

26 09 23.00 40 LIGHTING CONTROL DEVICES

26 09 43 NETWORK LIGHTING CONTROLS - LUTRON QUANTUM

26 20 00 INTERIOR DISTRIBUTION SYSTEM

26 24 13 SWITCHBOARDS

26 24 19.00 40 MOTOR STARTERS CABINETS (MSC)

26 28 00.00 10 MOTOR CONTROL CENTERS, SWITCHBOARDS AND PANELBOARDS

26 28 21.00 40 AUTOMATIC TRANSFER SWITCHES

26 51 00 INTERIOR LIGHTING

DIVISION 27 - COMMUNICATIONS

27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM

27 21 00.00 20 INTERCOMMUNICATION SYSTEM

DIVISION 28 - ELECTRONIC SAFETY AND SECURITY

28 31 64.00 10 FIRE DETECTION AND ALARM SYSTEM, ADDRESSABLE

DIVISION 40 - PROCESS INTERCONNECTIONS

40 18 00.00 40 VACUUM SYSTEMS PROCESS PIPING

-- End of Project Table of Contents --

PROJECT TABLE OF CONTENTS Page 2

SECTION 01 33 29

SUSTAINABILITY REPORTING

02/17

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ASTM INTERNATIONAL (ASTM)

ASTM D 2369 (2010; E 2011) Volatile Content of Coatings

ASTM D 6886 (2014) Standard Test Method for Determination of the Weight Percent Individual Volatile Organic Compounds in Waterborne Air-Dry Coatings by Gas Chromatography

AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING

ENGINEERS (ASHRAE)

ASHRAE 189.1 (2014) Standard for the Design of High-Performance Green Buildings Except Low-Rise Residential Buildings

COUNCIL ON ENVIRONMENTAL QUALITY (CEQ) (WHITE HOUSE)

HPSB Guiding Principles (2016) Guiding Principles for Sustainable Federal Buildings and Determining Compliance with the Guiding Principles for Sustainable Federal Buildings

SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL ASSOCIATION

(SMACNA)

ANSI/SMACNA 008 (2007) IAQ Guidelines for Occupied Buildings Under Construction, 2nd Edition

U.S. DEPARTMENT OF AGRICULTURE (USDA)

FSRIA 9002 Farm Security and Rural Investment Act Section 9002 (USDA Biopreferred Program)

U.S. DEPARTMENT OF ENERGY (DOE)

Energy Star (1992; R 2006) Energy Star Energy Efficiency Labeling System (FEMP)

U.S. ENVIRONMENTAL PROTECTION AGENCY (EPA)

SNAP (2016) EPA's Significant New Alternatives Policy Program

SECTION 01 33 29 Page 1

U.S. GREEN BUILDING COUNCIL (USGBC)

LEED BDC Ref Guide (2013) USGBC LEED Reference Guide for Building Design and Construction, v4

U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

40 CFR 247 Comprehensive Procurement Guideline for Products Containing Recovered Materials

1.2 SUMMARY

This specification includes general requirements and procedures for this project to be constructed and documented per the federally mandated HIgh Performance and Sustainable Building or HPSB Guiding Principles (GP), Third Party Certification (TPC) requirements, High Performance and Sustainable Building Requirements, and other requirements identified in this specification.

1.3 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to this section. Submit the following in accordance with Section 01 33 00

SUBMITTAL PROCEDURES:

SD-01 Preconstruction Submittals

Preliminary High Performance and Sustainable Building Checklist; G

Preliminary Sustainability eNotebook; G

SD-11 Closeout Submittals

Final High Performance and Sustainable Building Checklist; G

Final Sustainability eNotebook; G

Amended Final Sustainability Notebook; G

1.4 GUIDING PRINCIPLES VALIDATION (GPV)

Provide construction related sustainability documentation to verify achievement of HPSB Guiding Principles Validation (GPV). Provide the following for GPV:

a. Refer to Attachment 1, HPSB Checklist at the end of this specification section. (Multiple checklists indicate multiple buildings that require HPSB tracking.)

b. Obtain approval of any changes to the HPSB Checklist from the Contracting Officer at the Preconstruction Conference. Contracting Officer's approval establishes identified HPSB Guiding Principles Requirements as the project's sustainability goals.

No variations or substitutions to the HPSB Checklist are allowed

SECTION 01 33 29 Page 2 without written consent from the Contracting Officer. Immediately bring to the attention of the Contracting Officer any changes that impact meeting the approved HPSB Guiding Principles Requirements for this project and demonstrate that change will not incur additional construction cost or increase the life cycle cost.

c. Provide all work, including "S" submittals, required to incorporate the applicable HPSB Guiding Principles Requirements indicated on the HPSB Checklist and in this contract.

d. Provide Sustainability Action Plan

e. Provide construction related documentation for the project Sustainability eNotebook, and keep updated with regularly-scheduled construction meetings. Include construction related documentation containing the following components;

(1) HPSB Checklist

(2) Sustainability Action Plan

(3) Documentation illustrating HPSB Guiding Principles Requirements compliance (including "S" submittals)

1.4.1 Sustainability Action Plan

Include the following information in the Sustainability Action Plan:

a. Planned method to achieve each construction related GP requirement.

b. For each designated construction related HPSB Guiding Principles Requirements that is not achieved, provide narrative explaining how mission or activity precludes achieving specific sustainability requirement or goal. Provide analysis of particular requirement and level to which project is able to comply. Final government-approved narrative(s) must be included with the HPSB Checklist submittal.

c. Name and contact information for: POC responsible for ensuring sustainability goals are accomplished and documentation is assembled.

d. Include the Indoor Air Quality plan with the Sustainability Action Plan.

1.4.2 Costs

Bear all costs associated with constructing and demonstrating that project complies with approved HPSB Guiding Principles Requirements.

1.4.3 Calculations

Provide calculations, product data, labels and certifications required in this section to demonstrate compliance with the HPSB Guiding Principles Requirements.

1.4.4 Third Party Certification (TPC) Documentation

This project has been designed for, and must be constructed to attain a

SECTION 01 33 29 Page 3 sustainability rating of LEED BDC Ref Guide Silver Certified. Project is already registered with the TPC Organization. Provide construction related sustainability documentation, in the format required by the TPC Organization, to the Contracting Officer for approval, and for final approval by the TPC organization. Third Party Certification is met when Government receives TPC organization certificate or validation. Include the following:

a. Refer to the TPC Checklist.

b. Obtain approval of the TPC Checklist from the Contracting Officer at the Pre-Construction Conference.

No variations or substitutions to the approved TPC checklist are allowed without written consent from the Contracting Officer.

Immediately bring to the attention of the Contracting Officer any project changes that impact meeting the approved TPC Requirements for this project. Demonstrate that change will not: incur additional construction cost; increase the life cycle cost; impact previous TPC Design Review; impact required TPC level.

c. Complete all work required to incorporate the applicable TPC Requirements.

d. Maintain the construction related information, and provide replacement pages, in the Sustainability eNotebook pertaining to additions and changes to the approved sustainability requirements. Maintain the Sustainability eNotebook in electronic format. For more explanation, refer to paragraph SUSTAINABILITY eNOTEBOOK. Provide the following components in the Sustainability eNotebook, in addition to the GPV components above:

(1) TPC Checklist

(2) Completed TPC documentation for each identified requirement.

(3) Copy of all correspondence with the TPC organization.

e. Provide the following information in the Sustainability Action Plan.

Provide this TPC information in addition to the GPV Action Plan items above:

(1) Planned method to achieve each TPC requirement.

(2) For each TPC requirement that is attempted but not achieved, provide narrative explaining how mission or activity precludes achieving specific sustainability requirement or goal. Provide analysis of particular requirement and level to which project is able to comply.

(3) Provide name and contact information for: Sustainability POC and other names of sustainability professionals responsible for ensuring TPC sustainability goals are accomplished and documentation is assembled. Sustainability POCs are also responsible for ensuring GPV required in paragraph GUIDING PRINCIPLES VALIDATION (GPV) above.

f. Bear all costs associated with constructing and demonstrating that project complies with approved TPC requirements, including but not

SECTION 01 33 29 Page 4 limited to:

(1) TPC coordination with Government's AE and other consultants, TPC website requirements, and management for construction related documentation.

(2) Construction work required to incorporate TPC requirements.

(3) Submittals required to demonstrating compliance with Government approved TPC checklists.

(4) Documentation illustrating compliance with TPC requirements and additional documentation required by the TPC.

g. Provide all calculations, product data, and certifications required in this contract to demonstrate compliance with the TPC Requirements of this section.

1.5 SUSTAINABILITY SUBMITTALS

Provide HPSB Checklist and other documentation in the Sustainability eNotebook to indicate compliance with the sustainability requirements of the project.

1.5.1 High Performance Sustainable Building (HPSB) Checklist

Provide construction documentation that provides proof of and supports compliance with the completed HPSB Checklist.

1.5.1.1 HPSB Checklist Submittals

Submit updated HPSB Checklist with each Sustainability eNotebook submittal. Attach final HPSB Checklist to draft final DD1354 Real Property Record Submittal.

1.5.2 "S" Submittals for Sustainability Documentation

Submit the GPV and TPC sustainability documentation required in this specification as "S" submittals in all affected UFGS Sections. Highlight GPV and TPC compliance data in "S" submittal.

1.5.3 Sustainability eNotebook

Provide and maintain a comprehensive Sustainability eNotebook to document compliance with the sustainability requirements identified in the approved HPSB and TPC Checklist. Sustainability eNotebook must contain all required data to support full compliance with the HPSB Guiding Principles Requirements, including HPSB checklist, Sustainable Action Plan, calculations, labels, certifications and TPC requirements.

Sustainability eNotebook is in the form of an Adobe PDF file; bookmarked at each HPSB Guiding Principles Requirement, TPC requirement,and sub-bookmarked at each document. Match format to HPSB Guiding Principles numbering system indicated herein. Maintain up to date information, spreadsheets, templates, and other required documentation with each current submittal. For TPC projects, provide a second Table of contents using TPC numbering system, for maintaining documentation unique to TPC.

Contracting Officer may deduct from the monthly progress payment accordingly if Sustainability eNotebook information is not current, until

SECTION 01 33 29 Page 5 information is updated and on track per project goals.

1.5.3.1 Sustainability eNotebook Submittal Schedule

Provide Sustainability eNotebook Submittals at the following milestones of the project:

a. Preliminary Sustainability eNotebook

Submit preliminary Sustainability eNotebook for approval at the Pre-construction conference. Include Preliminary High Performance and Sustainable Building Checklist.

b. Construction Progress Meetings. Update GP and TPC documentation in the Sustainability eNotebook for each meeting.

c. Final Sustainability eNotebook

Submit updated Sustainability eNotebook at the Beneficial Occupancy Date (BOD). Final progress payment retainage may be held by Contracting Officer until final sustainability documentation is complete. Submit three electronic copies of the Final Sustainability eNotebook on DVDs to the Government. Include Final High Performance and Sustainable Building Checklist.

d. Amended Final Sustainability eNotebook

Amend and resubmit the Final Sustainability eNotebook to include post-occupancy corrections, updates, and requirements. Include Amended Final High Performance and Sustainable Building Checklist.

Final progress payment retainage may be held by Contracting Officer until amended final sustainability documentation is complete. Submit three (3) final electronic copies of the Amended Final Sustainability eNotebook Submittal on DVDs to the Government no longer than 30 days after the GP, TPC designated data collection period.

1.6 LEED Description

This project has been designed for, and shall be constructed for a sustainable rating of no less than Silver in accordance with LEED Rating System for Healthcare Version v2009.

The table below summarizes the LEED prerequisites and credits required for implementation on this project and identifies where specific requirements to meet the LEED criteria are addressed in the technical specifications and general conditions.

a. Where the reference indicates "Design", the criteria for that listed LEED credit or prerequisite shall be met through the efforts of the design team and, unless otherwise noted, is not the direct responsibility of the General Contractor or their subcontractors.

b. General Contractor and their subcontractors are responsible for ensuring the designer's intent behind their LEED implementation strategy is not modified or omitted through substitutions or proposed alternates to design without prior approval of the Government and Project Architect.

c. No variations or substitutions to the LEED credits identified for

SECTION 01 33 29 Page 6 this contract shall be allowed without written consent from the Contracting Officer. Should there be a case where there is any problem meeting the full requirements of a LEED credit identified for this project, the Contractor must bring this to the attention of the Contracting Officer immediately.

LEED Prerequisites and Points

Design/Specification Section

Sustainable Sites Prerequisite 1

Construction Activity Pollution Prevention

Design

Credit 1 Site Selection Design

Credit 2 Development Density & Community Connectivity

Design

Credit 4.1 Alternative Transportation, Public Transportation Access

Design

Credit 4.2 Alternative Transportation, Parking Capacity

Design

Credit 4.3 Alternative Transportation, Low-Emitting and Fuel-Efficient Vehicles

Design

Credit 4.4 Alternative Transportation, Parking Capacity

Design

Credit 5.2 Site Development, Maximize Open Space

Design

Credit 6.1 Stormwater Design, Quantity Control

Design

Credit 7.1 Heat Island Effect, Non-Roof 32 16 13

Credit 7.2 Heat Island Effect, Roof 07 54 23

Credit 8 Light Pollution Reduction Design

Water Efficiency Prereg 1 Water Use Reduction 22 00 70

Credit 1 Water Efficient Landscaping Design

Credit 3 Water Use Reduction 22 00 70

Energy & Atmosphere Prereg 1 Fundamental Commissioning of Building Energy Systems

01 91 00.15

Prereg 2 Minimum Energy Performance Design

Prereg 3 Fundamental Refrigerant Management

Design

Credit 1 Optimize Energy Performance Design

SECTION 01 33 29 Page 7

LEED Prerequisites and Points

Design/Specification Section

Credit 2 On-Site Renewable Energy Design

Credit 3 Enhanced Commissioning

Credit 4 Enhanced Refrigerant Management

01 941 00.15

Credit 5 Measurement & Verification Design

Materials & Resources Prereg 1

Storage and Collection of Recyclables

Design

Credit 2 Construction Waste Management

01 74 19

Credit 4 Recycled Content 01 33 29

Credit 5 Regional Materials 01 33 29

Credit 7 Certified Wood 01 33 29

Indoor Environmental Quality Prereg 1

Minimum Indoor Air Quality Performance

01 33 29

Prereg 2 Environmental Tobacco Smoke Design

Credit 1 Outdoor Air Delivery Monitoring

Design

Credit 2 Increased Ventilation Design

Credit 3.1 Construction Indoor Air Quality Management Plan - During Construction

01 33 29

Credit 3.2 Construction Indoor Air Quality Management Plan - Before Occupancy

01 33 29

Credit 4.1 Low-Emitting Materials - Adhesives and Sealants

01 33 29

Credit 4.2 Low-Emitting Materials - Paints and Coatings

01 33 29

Credit 4.3 Low-Emitting Materials - Flooring Systems

01 33 29

Credit 4.4 Low-Emitting Materials - Composite Wood and Agrifiber Products

01 33 29

Credit 5 Indoor Chemical and Pollutant Source Control

Design

Credit 6.1 Controllability of Systems

- Lighting

Design

Credit 6.2 Controllability of Systems

- Thermal Comfort

Design

Credit 7.1 Thermal Comfort - Design Design

SECTION 01 33 29 Page 8

LEED Prerequisites and Points

Design/Specification Section

Credit 7.2 Thermal Comfort - Verification

Design

Credit 8.1 Daylight and Views - Daylight

Design

Credit 8.2 Daylight and Views - Views Design

Innovation in Design Credit 1.1

MRc2 Exemplary Performance 01 33 29

Credit 1.2 MRc7 Exemplary Performance 01 33 29

Credit 1.3 Green Cleaning Policy Design

Credit 1.4 Integrated Pest Management Policy

Design

Credit 2 LEED AP Design

Regional Priority Credit 1.1 IEQc8.1 Design

Credit 1.2 SSc5.2 Design

1.7 DOCUMENTATION REQUIREMENTS

a. Incorporate each of the following HPSB Guiding Principles Requirements into project construction; and provide documentation that proves compliance with each listed requirement. Items below are organized according to the HPSB Guiding Principles . For life-cycle cost analysis requirements, one document with all analyses is acceptable, with Contracting Officer approval.

b. For each of the following paragraphs that require the use of products listed on Government-required websites, provide documentation of the process used to select products, or process used to determine why listed products do not meet project performance requirements.

1.7.1 Commissioning

Submit approved Final Commissioning Report required by Section 01 91 00.15 TOTAL BUILDING COMMISSIONING as proof of this tracking requirement.

1.7.2 Energy Efficient Products

Provide only energy-using products that are Energy Star rated, or have the Federal Energy Management Program (FEMP) recommended efficiency. Where Energy Star or FEMP recommendations have not been established, provide most efficient products that are life-cycle cost effective. Provide only energy using products that meet FEMP requirements for low standby power consumption. Energy efficient products can be found at:

https://energy.gov/eere/femp/federal-energy-management-program and https://www.energystar.gov/ . Provide the following documentation:

Proof that products are labeled energy efficient and comply with the cited requirements.

SECTION 01 33 29 Page 9

1.7.3 Indoor Water Use

Provide only water-consuming products that are EPA WaterSense labeled, or the most efficient water fixtures available that meet the requirements of ASHRAE 189.1 Section 6.3.2, when EPA Watersense products are not available. Provide the following documentation:

For products available with EPA WaterSense labeling, proof that fixtures are labeled EPA WaterSense or Energy Star ; for all other fixtures, proof they comply with the cited efficiency requirements.

1.7.4 Reduce Volatile Organic Compounds (VOC) (Low Emitting Materials)

Meet the requirements of Table 3-1 at the end of this specification.

Provide the following documentation:

Provide certifications or labels that demonstrate compliance with cited requirements.

a. Demonstrate that materials do not exceed maximum VOC emissions of cited standards. VOC averaging is allowed where coatings are subject to human contact or harsh environmental conditions.

b. Demonstrate that flooring materials comply with VOC emissions of cited standards.

c. Demonstrate that composite wood and agrifiber products and associated laminating adhesives contain no added urea-formaldehyde.

d. Demonstrate that furniture and seating complies with low emissions requirements.

e. Create and maintain a list of above listed products used on the project within the building vapor barrier. Demonstrate how product meets cited standards.

f. For Adhesives and Sealants applied inside the weatherproofing system and applied onsite, comply with following VOC content limits as adopted by South Coast Air Quality Management District (SCAQMD) Rule #1168 for TPC.

(1) Wood Glues: 30 g/L.

(2) Metal-to-Metal Adhesives: 30 g/L.

(3) Adhesives for Porous Materials (Except Wood): 50 g/L.

(4) Subfloor Adhesives: 50 g/L.

(5) Plastic Foam Adhesives: 50 g/L.

(6) Carpet Adhesives: 50 g/L.

(7) Carpet Pad Adhesives: 50 g/L.

(8) VCT and Asphalt Tile Adhesives: 50 g/L.

(9) Cove Base Adhesives: 50 g/L.

(10)Gypsum Board and Panel Adhesives: 50 g/L.

(11)Rubber Floor Adhesives: 60 g/L.

(12)Ceramic Tile Adhesives: 65 g/L.

(13)Multipurpose Construction Adhesives: 70 g/L.

(14)Fiberglass Adhesives: 80 g/L.

(15)Contact Adhesive: 80 g/L.

(16)Structural Glazing Adhesives: 100 g/L.

(17)Wood Flooring Adhesive: 100 g/L.

(18)Structural Wood Member Adhesive: 140 g/L.

SECTION 01 33 29 Page 10

(19)Single-Ply Roof Membrane Adhesive: 250 g/L.

(20)Special-Purpose Contact Adhesive (Contact adhesive used to bond melamine-covered board, metal, unsupported vinyl, rubber, or wood veneer 1/16 IN or less in thickness to surface): 250 g/L.

(21)Top and Trim Adhesive: 250 g/L.

(22)Plastic Cement Welding Compounds: 250 g/L.

(23)ABS Welding Compounds: 325 g/L.

(24)CPVC Welding Compounds: 490 g/L.

(25)PVC Welding Compounds: 510 g/L.

(26)Adhesive Primer for Plastic: 550 g/L.

(27)Sheet-Applied Rubber Lining Adhesive: 850 g/L.

(28)Aerosol Adhesive, General-Purpose Mist Spray: 65 percent by weight.

(29)Aerosol Adhesive, General-Purpose Web Spray: 55 percent by weight.

(30)Special-Purpose Aerosol Adhesive: 70 percent by weight.

(31)Other Adhesives: 250 g/L.

(32)Architectural Sealants: 250 g/L.

(33)Non-membrane Roof Sealants: 300 g/L.

(34)Single-Ply Roof Membrane Sealants: 450 g/L.

(35)Other Sealants: 420 g/L.

(36)Sealant Primers for Nonporous Substrates: 250 g/L.

(37)Sealant Primers for Porous Substrates: 775 g/L.

(38)Modified Bituminous Sealant Primers: 500 g/L.

(39)Other Sealant Primers: 750 g/L.

g. For Paints and Coatings applied inside the weatherproofing system and applied onsite, comply with following VOC content limits as adopted by Green Seal GS-11, Green Seal GC-03 and SCAQMD Rule 1113 for TPC.

(1) Flat Paints and Coatings: 50 g/L.

(2) Nonflat Paints and Coatings: 150 g/L.

(3) Primers, Sealers, and Undercoaters: 200 g/L.

(4) Anticorrosive and Antirust Paints: 250 g/L.

(5) Pretreatment Wash Primers: 420 g/L.

(6) Clear Wood Finishes, Varnishes: 350 g/L.

(7) Clear Wood Finishes, Lacquers: 550 g/L.

(8) Clear Wood Finishes, Sanding Sealers: 350 g/L.

(9) Clear Brushing Lacquer: 680 g/L.

(10)Floor Coatings: 100 g/L.

(11)Shellacs, Clear: 730 g/L.

(12)Shellacs, Pigmented: 550 g/L.

(13)Stains: 250 g/L.

(14)Concrete Curing Compounds: 350 g/L.

(15)Japans/ Faux Finishing Coatings: 350 g/L.

(16)Magnesite Cement Coatings: 450 g/L.

(17)Pigmented Lacquer: 550 g/L.

(18)Waterproofing Sealers: 250 g/L.

(19)Waterproofing Concrete/ Masonry Sealers: 400 g/L.

(20)Wood Preservatives: 350 g/L.

(21)Low-Solids Coatings: 120 g/L.

h. Flooring shall comply with one of following as applicable to the project scope:

(1) Option 1:

(a) Meets the testing and product requirements of the Carpet and Rug Institute Green Label Plus program.

(b) Maximum VOC concentrations are less than or equal to those specified in California Department of Health Services Standard

SECTION 01 33 29 Page 11

Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers, including 2004 Addenda, using the office scenario as defined in Table 7.5 within the practice. Meet additional VOC concentration limits listed in Section 9.1.

(c) Maximum VOC concentrations meet the California requirements specified above based on the California Department of Public Health (CDPH) Standard Method V1.1-2010 using test results obtained at the 14 day time point.

(d) Carpet cushion installed in the building interior shall meet the requirements of the Carpet and Rug Institute Green Label program.

(e) Carpet adhesive shall meet the requirements of IEQ Credit 4.1:

Adhesives and Sealants, which includes a volatile organic compound (VOC) limit of 50 g/L (0.4 lb/gal).

(f) Hard surface flooring installed in building interior shall meet one of following requirements:

(1) Meet the requirements of the FloorScore standard, current as of date of rating system, or more stringent version, as shown with testing by independent third-party.

(2) Demonstrate maximum VOC concentrations less than or equal to those specified in the California Department of Health Services Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers, including 2004 Addenda, using office scenario as defined in Table

7.5 within the practice.

(3) maximum VOC concentrations meet California requirements specified above based on California Department of Public Health (CDPH) Standard Method V1.1-2010 using test results obtained at 14 day time point.

(g) Mineral based finish flooring products such as tile, masonry, terrazzo, and cut stone without integral organic-based coatings and sealants and unfinished/untreated solid wood flooring qualify for credit without any IAQ testing requirements.

(1) Associated site-applied adhesives, grouts, finishes and sealers shall be compliant for a mineral-based or unfinished/untreated solid wood flooring system to qualify for credit.

(2) Concrete, wood, bamboo and cork floor finishes such as sealer, stain and finish shall meet requirements of South Coast Air Quality Management District SCAQMD) Rule 1113, Architectural Coatings, rules in effect on January 1, 2004.

(3) Tile setting adhesives and grout shall meet South Coast Air Quality Management District (SCAQMD) Rule 1168. VOC limits correspond to an effective date of July 1, 2005 and rule amendment date of January 7, 2005.

(4) For carpet adhesive, concrete, wood, bamboo and cork floor finishes, and tile setting adhesives, compliance can be demonstrated with test results of: Total volatiles fraction, based on one of following, provided water and exempt compounds are subtracted from total volatiles test results and mass VOC content is calculated consistent with SCAQMD Rule 1113 and Rule 1168: ASTM D 2369 , EPA method 24, ISO 11890-1.

(5) Total volatile organic compounds fraction, based on one of following, provided VOCs with a boiling point up to 536 degF are included, and exempt compounds are subtracted from total volatiles test results and the mass VOC content is calculated consistent with SCAQMD Rule 1113 and Rule 1168: ASTM D 6886 , ISO 11890-2.

(2) Option 2:

SECTION 01 33 29 Page 12

(a) Flooring elements installed in building interior shall meet testing and product requirements of the California Department of Health Services Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers, including 2004 Addenda.

(b) Mineral-based finish flooring products such as tile, masonry, terrazzo, and cut stone without integral organic based coatings and sealants and unfinished/untreated solid wood flooring qualify for credit without any IAQ testing requirements.

(c) Associated site-applied adhesives, grouts, finishes and sealers shall be compliant for a mineral-based or unfinished/untreated solid wood flooring system to qualify for credit.

1.7.5 Indoor Air Quality During Construction

Prior to construction, create indoor air quality plan. Implement IAQ plan during construction and flush building air before occupancy.

For new construction and for renovation of unoccupied existing buildings, indoor air quality plan must meet the requirements of ASHRAE 189.1 Section

10.3.1.4. (Indoor Air Quality (IAQ) Construction Management), with maximum outdoor air consistent with achieving relative humidity no greater than 60 percent. For renovation of occupied existing buildings, comply with ANSI/SMACNA 008 IAQ Guidelines for Occupied Buildings Under Construction.

Provide documentation showing that after construction ends and prior to occupancy, HVAC filters were replaced and building air was flushed out in accordance with the cited standard.

1.7.6 Recycled Content

Comply with 40 CFR 247 . Refer to https://www.epa.gov/smm/comprehensive-procurement-guidelines-construction-products for assistance identifying products cited in 40 CFR 247 . Selected products must comply with non-proprietary requirements of the Federal Acquisition Regulation, and must meet performance requirements. Provide the following documentation:

a. Manufacturers’ documents stating the recycled content by material, or written justification for claiming one of the exceptions allowed on the cited website.

b. Substitutions: Submit for Government approval, proposed alternative products or systems that provide equivalent performance and appearance and have greater contribution to project recycled content requirements. For all such proposed substitutions, submit with the Sustainability Action Plan accompanied by product data demonstrating equivalence.

1.7.7 Bio-Based Products

Provide products and material composed of the highest percentage of biobased materials (including rapidly renewable resources and certified sustainably harvested products), consistent with FSRIA 9002 USDA Biopreferred Program, to the maximum extent possible without jeopardizing the intended end use or detracting from the overall quality delivered to the end user. Use only supplies and materials of a type and quality that conform to applicable specifications and standards.

SECTION 01 33 29 Page 13

Comply with FSRIA 9002 USDA BioPreferred Program. Refer to https://www.biopreferred.gov/BioPreferred/ for the product categories and BioPreferred Catalog. Selected products must comply with non-proprietary requirements of the Federal Acquisition Regulation, and must meet performance requirements. Provide the following documentation:

USDA Biopreferred label for each product; for bio-based products used on project but not listed with Biopreferred program, provide bio-based content and percentage.

1.7.8 Ozone Depleting Substances

Meet the requirements of ASHRAE 189.1 Section 9.3.3 Refrigerants for no CFC-based refrigerants in heating ventilation, air conditioning and refrigeration systems (except for fire suppression system requirements, covered elsewhere in this specification). Where feasible, use products from U.S. EPA Significant New Alternatives Policy (SNAP) ( https://www.epa.gov/snap ) or meet the criteria of SNAP. Provide the following documentation:

a. MSDS sheets for all refrigerants.

b. Provide label for each product meeting the cited standards.

1.7.9 Regional Materials

Document materials to indicate minimum of twenty (20) percent, by dollar value, of materials and products for project are extracted, harvested or recovered, and manufactured, within five-hundred (500) mile radius of project site.

a. Total amount of regional material contained in building materials as a percentage of total cost of all building materials on the project (mechanical, electrical, and plumbing components, fire protection equipment and transportation are excluded).

b. Substitutions: Contractor may submit for Government approval, proposed alternative products or systems that provide equivalent performance and appearance and have greater contribution to project regional material requirements. For all such proposed substitutions, submit with the Sustainability Action Plan accompanied by product data demonstrating equivalence.

1.7.10 Certified Wood

a. Document materials to indicate percentage, by dollar value, of permanently installed virgin wood-based materials and products for project are certified in accordance with FSC STD 40-004 V2-1.

b. Minimum of fifty (50) percent is required.

c. Determine amount of FSC-certified project materials by method described in applicable LEED Reference Guide.

d. Vendor invoices for permanently-installed wood products, both FSC certified and not, purchased by project contractor and subcontractors shall be compiled.

(1) Total cost of wood products, both FSC certified and not, on appropriate LEED document, e.g., MRc7 template.

(2) Wood products not FSC certified and those identified on invoices as "FSC Pure" and "FSC Mixed Credit" shall be valued at 100 percent of product cost.

(3) Value wood products identified as "FSC Mixed (X) percent" at

SECTION 01 33 29 Page 14 indicated percentage of their cost.

(4) Value products identified as "FSC Mixed 75 percent," at 75 percent of cost.

(5) Wood products identified as "FSC Recycled" or "FSC Recycled

Credit" qualify only as recycled content products.

e. Each vendor invoice must conform to following requirements:

(1) Identify each wood product on a line-item basis;

(2) Identify FSC products as such on a line-item basis;

(3) Show dollar value of each line item;

(4) Show vendor's COC certificate number on invoices including FSC products.

(a) Each wood product vendor that invoices FSC certified products shall be COC certified by FSC accredited certifier.

f. Wood-based materials include, but not limited to, materials when made from wood, engineered wood products, or wood-based panel products.

1.7.11 Waste Material Management (Recycling – Construction)

Divert construction debris from landfill disposal where markets or on-site recycling exists, and provide documentation in accordance with Section

01 74 19 CONSTRUCTION AND DEMOLITION WASTE MANAGEMENT.

1.7.12 Additional Sustainability Requirements

1.7.12.1 Validation and Certification Restrictions

Purchase of renewable energy certificates (RECs) specifically to meet project sustainability goals is prohibited.

PART 2 PRODUCTS

Not used.

PART 3 EXECUTION

3.1 SUSTAINABILITY COORDINATION

3.1.1 Coordinating Sustainability Documentation Progress

Provide sustainability focus and coordination at the following meetings to achieve sustainability goals. The designated TPC accredited sustainability professional responsible for GP and TPC documentation must participate in the following meetings to coordinate documentation completion.

a. Pre-Construction Conference: Discuss the following: TPC and HPSB Checklists, Sustainability Action Plan, Construction submittal requirements and schedule, individuals responsible for achieving each Guiding Principle Requirement and TPC prerequisite and credit.

b. Construction Progress Meetings: Review GP and TPC sustainability requirements with project team including contractor and sub-contractor representatives. Demonstrate GP and TPC documentation is being collected and updated to the Sustainability eNotebook and TPC Online tool.

(1) Facility Turnover Meetings: Review Sustainability eNotebook, and TPC Online submission for completeness and identify any

SECTION 01 33 29 Page 15 outstanding issues relating to final documentation requirements.

(2) Final Sustainability eNotebook Review

-- End of Section --

SECTION 01 33 29 Page 16

SECTION 06 10 00

ROUGH CARPENTRY

08/16

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

AMERICAN FOREST FOUNDATION (AFF)

ATFS STANDARDS (2015) American Tree Farm System Standards of Sustainability 2015-2020

AMERICAN HARDBOARD ASSOCIATION (AHA)

AHA A135.4 (1995; R 2004) Basic Hardboard

AMERICAN INSTITUTE OF TIMBER CONSTRUCTION (AITC)

AITC 111 (2005) Recommended Practice for Protection of Structural Glued Laminated Timber During Transit, Storage and Erection

AITC TCM (2012) Timber Construction Manual, 5th Edition

ANSI/AITC A190.1 (2007) American National Standard, Structural Glued Laminated Timber

AMERICAN LUMBER STANDARDS COMMITTEE (ALSC)

ALSC PS 20 (2015) American Softwood Lumber Standard

AMERICAN RAILWAY ENGINEERING AND MAINTENANCE-OF-WAY ASSOCIATION

(AREMA)

AREMA Eng Man (2015) Manual for Railway Engineering

AMERICAN WOOD COUNCIL (AWC)

AWC NDS (2012) National Design Specification (NDS) for Wood Construction

AWC WFCM (2012) Wood Frame Construction Manual for One- and Two-Family Dwellings

AMERICAN WOOD PROTECTION ASSOCIATION (AWPA)

AWPA M2 (2016) Standard for the Inspection of Preservative Treated Wood Products for Industrial Use

AWPA M6 (2013) Brands Used on Preservative Treated

SECTION 06 10 00 Page 1

Materials

APA - THE ENGINEERED WOOD ASSOCIATION (APA)

APA E30 (2011) Engineered Wood Construction Guide

APA E445 (2002) Performance Standards and Qualification Policy for Structural-Use Panels (APA PRP-108)

APA EWS R540 (2013) Builder Tips: Proper Storage and Handling of Glulam Beams

APA EWS T300 (2007) Technical Note: Glulam Connection Details

APA F405 (19) Product Guide: Performance Rated Panels

APA L870 (2010) Voluntary Product Standard, PS 1-09, Structural Plywood

APA S350 (2014) PS 2-10, Performance Standard for Wood-Based Structural-Use Panels

ASME INTERNATIONAL (ASME)

ASME B18.2.1 (2012; Errata 2013) Square and Hex Bolts and Screws (Inch Series)

ASME B18.2.2 (2010) Nuts for General Applications:

Machine Screw Nuts, Hex, Square, Hex Flange, and Coupling Nuts (Inch Series)

ASME B18.5.2.1M (2006; R 2011) Metric Round Head Short Square Neck Bolts

ASME B18.5.2.2M (1982; R 2010) Metric Round Head Square Neck Bolts

ASME B18.6.1 (2016) Wood Screws (Inch Series)

ASTM INTERNATIONAL (ASTM)

ASTM A153/A153M (2016) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware

ASTM A307 (2014) Standard Specification for Carbon Steel Bolts and Studs, 60 000 PSI Tensile Strength

ASTM A653/A653M (2015; E 2016) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process

ASTM C1136 (2012) Standard Specification for Flexible, Low Permeance Vapor Retarders

SECTION 06 10 00 Page 2 for Thermal Insulation

ASTM C1396/C1396M (2014a) Standard Specification for Gypsum Board

ASTM C208 (2012) Cellulosic Fiber Insulating Board

ASTM D1435 (2013) Standard Practice for Outdoor Weathering of Plastics

ASTM D198 (2015) Standard Test Methods of Static Tests of Lumber in Structural Sizes

ASTM D2344/D2344M (2016) Standard Test Method for Short-Beam Strength of Polymer Matrix Composite Materials and Their Laminates

ASTM D2898 (2010) Accelerated Weathering of Fire-Retardant-Treated Wood for Fire Testing

ASTM D3498 (2003; R 2011) Adhesives for Field-Gluing Plywood to Lumber Framing for Floor Systems

ASTM D6108 (2013) Standard Test Method for Compressive Properties of Plastic Lumber and Shapes

ASTM D6109 (2013) Standard Test Methods for Flexural Properties of Unreinforced and Reinforced Plastic Lumber and Related Products

ASTM D6111 (2013a) Standard Test Method for Bulk Density and Specific Gravity of Plastic Lumber and Shapes by Displacement

ASTM D6112 (2013) Compressive and Flexural Creep and Creep-Rupture of Plastic Lumber and Shapes

ASTM D6117 (2016) Standard Test Methods for Mechanical Fasteners in Plastic Lumber and Shapes

ASTM D696 (2016) Standard Test Method for Coefficient of Linear Thermal Expansion of Plastics Between -30 degrees C and 30 degrees C With a Vitreous Silica Dilatometer

ASTM E96/E96M (2016) Standard Test Methods for Water Vapor Transmission of Materials

ASTM F1667 (2013) Driven Fasteners: Nails, Spikes, and Staples

ASTM F547 (2006; R 2012) Nails for Use with Wood and Wood-Base Materials

SECTION 06 10 00 Page 3

CALIFORNIA AIR RESOURCES BOARD (CARB)

CARB 93120 (2007) Airborne Toxic Control Measure (ATCM) to Reduce Formaldehyde Emissions from Composite Wood Products

CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)

CDPH SECTION 01350 (2004; Add 2004-01) Standard Practice for the Testing Of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers

COMPOSITE PANEL ASSOCIATION (CPA)

CPA A208.1 (2016) Particleboard

CSA GROUP (CSA)

CSA Z809-08 (R2013) Sustainable Forest Management

FM GLOBAL (FM)

FM 4435 (2013) Roof Perimeter Flashing

FOREST STEWARDSHIP COUNCIL (FSC)

FSC STD 01 001 (2000) Principles and Criteria for Forest Stewardship

GREEN SEAL (GS)

GS-36 (2011) Commercial Adhesives

INTERNATIONAL CODE COUNCIL (ICC)

ICC IBC (2015) International Building Code

NATIONAL HARDWOOD LUMBER ASSOCIATION (NHLA)

NHLA Rules (2011) Rules for the Measurement & Inspection of Hardwood & Cypress

NORTHEASTERN LUMBER MANUFACTURERS ASSOCIATION (NELMA)

NELMA Grading Rules (2013) Standard Grading Rules for Northeastern Lumber

PROGRAMME FOR ENDORSEMENT OF FOREST CERTIFICATION (PEFC)

PEFC ST 2002:2013 (2015) PEFC International Standard Chain of Custody of Forest Based Products Requirements

REDWOOD INSPECTION SERVICE (RIS) OF THE CALIFORNIA REDWOOD

ASSOCIATION (CRA)

RIS Grade Use (1998) Redwood Lumber Grades and Uses

SECTION 06 10 00 Page 4

SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)

SCAQMD Rule 1168 (1989; R 2005) Adhesive and Sealant Applications

SOUTHERN CYPRESS MANUFACTURERS ASSOCIATION (SCMA)

SCMA Spec (1986; Supple. No. 1, Aug 1993) Standard Specifications for Grades of Southern Cypress

SOUTHERN PINE INSPECTION BUREAU (SPIB)

SPIB 1003 (2002) Standard Grading Rules for Southern Pine Lumber

SUSTAINABLE FOREST INITIATIVE (SFI)

SFI 2015-2019 (2015) Standards, Rules for Label Use, Procedures and Guidance

TRUSS PLATE INSTITUTE (TPI)

TPI 1 (2007; R 2006) National Design Standard for Metal Plate Connected Wood Truss Construction; Commentary and Appendices

TPI HIB (1991) Commentary and Recommendations for Handling, Installing and Bracing Metal Plate Connected Wood Trusses

U.S. DEPARTMENT OF COMMERCE (DOC)

DOC/NIST PS56 (1973) Structural Glued Laminated Timber

DOC/NIST PS58 (1973) Basic Hardboard (ANSI A135.4)

U.S. GENERAL SERVICES ADMINISTRATION (GSA)

CID A-A-1923 (Rev A; Notice 2) Shield, Expansion (Lag, Machine and Externally Threaded Wedge Bolt Anchors)

CID A-A-1924 (Rev A; Notice 2) Shield, Expansion (Self Drilling Tubular Expansion Shell Bolt Anchors

CID A-A-1925 (Rev A; Notice 2) Shield Expansion (Nail Anchors)

FS UU-B-790 (Rev A; Notice 2) Building Paper Vegetable Fiber: (Kraft, Waterproofed, Water Repellent and Fire Resistant)

UNDERWRITERS LABORATORIES (UL)

UL 2818 (2013) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings

SECTION 06 10 00 Page 5

WEST COAST LUMBER INSPECTION BUREAU (WCLIB)

WCLIB 17 (2004) Standard Grading Rules

WESTERN WOOD PRODUCTS ASSOCIATION (WWPA)

WWPA G-5 (2011) Western Lumber Grading Rules

1.2 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are [for Contractor Quality Control approval.][for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-02 Shop Drawings

[ Structural Glued Laminated Members; G

][ Trussed Rafters; G

][ Trussed Joists; G

][ Fabricated Structural Members; G

] Modifications of Structural Members; G

Drawings of structural laminated members, fabricated wood trusses, engineered wood joists and rafters, and other fabricated structural members indicating materials, shop fabrication, and field erection details; including methods of fastening.

[ Nailers and Nailing Strips; G

Drawings of field erection details, including materials and methods of fastening nailers in conformance with Factory Mutual wind uplift rated systems specified in other Sections of these specifications.

] SD-03 Product Data

[ Underlayment

] Plastic Lumber

Fiberboard Wall Sheathing

Cellulose Honeycomb Panels

Fire-retardant Treatment

Structural-use and OSB Panels

Oriented Strand Board

Adhesives

SECTION 06 10 00 Page 6

SD-05 Design Data

Modifications of Structural Members; G

Design analysis and calculations showing design criteria used to accomplish the applicable analysis.

SD-06 Test Reports

Preservative-treated Lumber and Plywood

SD-07 Certificates

[ Certificates of Grade

] Certified Sustainably Harvested Wood; G

Preservative Treatment

Indoor Air Quality

SD-10 Operation and Maintenance Data

Take-back Program

Include contact information, summary of procedures, and the limitations and conditions applicable to the project. Indicate manufacturer's commitment to reclaim materials for recycling or reuse.

1.3 SUSTAINABLE DESIGN REQUIREMENTS

1.3.1 Final Sustainability Notebook Submittal

Refer to Section 01 33 29 SUSTAINABILITY REPORTING for federal sustainability product and documentation requirements.

1.3.2 LEED Documentation Notebook

Refer to Section 01 33 29 SUSTAINABILITY REPORTING for additional contract compliance requirements, including but not limited to, performance and submittal requirements that may apply to any product herein specified.

1.4 DELIVERY AND STORAGE

Deliver materials to the site in an undamaged condition. Store, protect, handle, and install prefabricated structural elements in accordance with manufacturer's instructions and as specified. Store materials off the ground to provide proper ventilation, with drainage to avoid standing water, and protection against ground moisture and dampness. Store materials with a moisture barrier at both the ground level and as a cover forming a well ventilated enclosure. Store wood I-beams and glue-laminated beams and joists on edge. Adhere to requirements for stacking, lifting, bracing, cutting, notching, and special fastening requirements. [ Handle and store laminated timber in accordance with AITC 111 or APA EWS R540. ] Do not use materials that have visible

SECTION 06 10 00 Page 7 moisture or biological growth. Remove defective and damaged materials and provide new materials. Store separated reusable wood waste convenient to cutting station and area of work.

1.5 GRADING AND MARKING

1.5.1 Lumber

Mark each piece of framing and board lumber or each bundle of small pieces of lumber with the grade mark of a recognized association or independent inspection agency. Such association or agency must be certified by the Board of Review, American Lumber Standards Committee, to grade the species used. Surfaces that are to be exposed to view must not bear grademarks, stamps, or any type of identifying mark. Hammer marking will be permitted on timbers when all surfaces will be exposed to view.

1.5.2 Structural Glued Laminated Timber

Mark each member with the mark of a recognized association or independent inspection agency that maintains continuing control over the quality of structural glued laminated timber products. The marking must indicate compliance with ANSI/AITC A190.1 and must include all identification information required by ANSI/AITC A190.1 . [Structurally end-jointed lumber must also be certified and grade marked in accordance with

ANSI/AITC A190.1 .]

1.5.3 Plywood

Mark each sheet with the mark of a recognized association or independent inspection agency that maintains continuing control over the quality of the plywood. The mark must identify the plywood by species group or span rating, exposure durability classification, grade, and compliance with APA L870 . Surfaces that are to be exposed to view must not bear grademarks or other types of identifying marks.

1.5.4 Structural-Use and OSB…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it.