Life Safety Inventories.xlsx
XLSX spreadsheet 35 KB Posted
- Solicitation number
- 12318726Q0082
- Issued by
-
Department of Agriculture Forest Service
About this file
This is a Life Safety Inventories spreadsheet documenting fire extinguisher inventory and maintenance schedules across multiple buildings and equipment at what appears to be a Job Corps training facility. The inventory includes approximately 120 fire extinguishers distributed across 32 buildings and structures, including dormitories (Palace, Alamo), educational facilities (MLK Education, Student Services, Education Building), operational buildings (Dining Hall, Gym, Theater, Health and Wellness), trade training facilities (Welding, Carpentry, Brick Trade, Paint Trade, HEO Trade, Fire Cache), and support structures (Warehouse, Maintenance, Admin). The extinguishers are predominantly 10-pound ABC-rated units manufactured by Amerex, Buckeye, and Sentry, with specialized 6-pound K-rated units in the culinary kitchen and dining hall, and 5-pound ABC units on select equipment and vehicles.
All fire extinguishers were installed in February 2025 with annual inspection due dates of December 2025 or 2026 and five-year service due dates of 2030, except for three units identified as requiring replacement or service: extinguisher CM2 (Sentry, 10lb ABC) at Center Maintenance due for 5-year service in December 2025; extinguisher WB2 (Sentry, 10lb ABC) at Warehouse Bays due in 2026; and extinguisher PA3 (Sentry, 10lb ABC) at Paint Trade due in 2026. Additionally, the inventory includes fire extinguishers on 24 pieces of equipment and vehicles, primarily 2.5-pound Kiddie ABC units with select 5-pound units on vans and buses, all scheduled for annual inspection in December 2025-2026 and five-year maintenance in 2030. Several entries contain incomplete data, including missing manufacturer information and five-year due dates for units BR2 and PA2.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire Exting. Inventory Building
| Total # 120 exting including Fleet | Building | Location | Manufacture Type and Size | Extinguisher ID | Annual Due | 5 yr Due | Status If non-compliant | Remarks |
| 32/ CTT | ||||||||
| North Entrance | Buckeye | CTT1 | Dec-26 | 2030 | Installed Feb 2025 | |||
| 10lb ABC | ||||||||
| West Entrance | Buckeye | CTT2 | Dec-26 | 2030 | Installed Feb 2025 | |||
| 10lb ABC | ||||||||
| East Entrance | Amerex | CTT3 | Dec-26 | 2030 | Installed Feb 2025 | |||
| 10lb ABC | ||||||||
| Culinary Kitchen | Amerex 6lb K | CTT4 | Dec-26 | 2030 | Installed Feb 2025 |
| 57/ Warehouse | ||||||
| Laundry Room West Entrance | Amerex | WL1 | Dec-26 | 2030 | Installed Feb 2025 | |
| 10lb ABC | ||||||
| Laundry Room East Entrance | Sentry | WL2 | Dec-26 | 2030 | Installed Feb 2025 | |
| 10lb ABC | ||||||
| Laundry Mechanical Room | Amerex | WL3 | Dec-26 | 2030 | Installed Feb 2025 | |
| 10lb ABC | ||||||
| Student Issue South Wall | Sentry | WI1 | Dec-26 | 2026 | ||
| 10lb ABC | ||||||
| 57/ Warehouse Bays | ||||||
| Bay1 West Wall | Amerex | WB1 | Dec-26 | 2030 | Installed Feb 2025 | |
| 10lb ABC | ||||||
| Bay 2 North Wall | Sentry | WB2 | Dec-26 | 2026 | ||
| 10lb ABC | ||||||
| Outside east wall propane tank | Buckeye 51b ABC | WB3 | Dec-26 | 2030 | Installed Feb 2025 | |
| 13A/ Admin | ||||||
| Front Entrance | Amerex | AD1 | Dec-26 | 2030 | Installed Feb 2025 | |
| 10lb ABC | ||||||
| East Entry/Exit | Amerex | AD2 | Dec-26 | 2030 | Installed Feb 2025 | |
| 10lb ABC | ||||||
| Server/Copier Room | Amerex | AD3 | Dec-26 | 2030 | Installed Feb 2025 | |
| 10lb ABC | ||||||
| 51/ MLK Education | ||||||
| South Entrance | Buckeye | CPP1 | Dec-26 | 2030 | Installed Feb 2025 | |
| 10lb ABC | ||||||
| Southwest Entrance | Amerex | CPP2 | Dec-26 | 2030 | Installed Feb 2025 | |
| 10lb ABC | ||||||
| Northwest Entrance | Buckeye | CPP3 | Dec-26 | 2030 | Installed Feb 2025 | |
| 10lb ABC | ||||||
| North Entrance | Buckeye | CPP4 | Dec-26 | 2030 | Installed Feb 2025 | |
| 10lb ABC | ||||||
| Mechanical Room | Buckeye | CPP5 | Dec-26 | 2030 | Installed Feb 2025 | |
| 10lb ABC | ||||||
| 61/ Waste-Water | ||||||
| Office Entrance | Buckeye | WTR1 | Dec-26 | 2030 | Intstalled Feb 2025 | |
| 10lb ABC |
| Building | Location | Manufacture Type and Size | Extinguisher ID | Annual Due | 5 yr Due | Status If non-compliant | Remarks |
| 60/ Residential Office | |||||||
| South Entrance Metal Detector | Buckeye | RL1 | Dec-26 | 2030 | Installed Feb 2025 | ||
| 10lb ABC | |||||||
| North Entrance | Buckeye | RL2 | Dec-26 | 2030 | Installed Feb 2025 | ||
| 10lb ABC | |||||||
| 70/ Student Services | |||||||
| West Entrance | Amerex | CO1 | Dec-26 | 2030 | Installed Feb 2025 | ||
| 10lb ABC | |||||||
| East Entrance | Amerex | CO1 | Dec-26 | 2030 | Installed Feb 2025 | ||
| 10lb ABC | |||||||
| 70/ Canteen | |||||||
| Lobby Area | Buckeye | Can1 | Dec-26 | 2030 | Installed Feb 2025 | ||
| 10lb ABC | |||||||
| Food Storage | Amerex | Can 2 | Dec-26 | 2030 | Installed Feb 2025 | ||
| 10lb ABC | |||||||
| 53/ Palace Dorm | |||||||
| Front Entrance | Buckeye | P1 | 26-Dec | 2030 | Installed Feb 2025 | ||
| 10lb ABC | |||||||
| North Emergency Exit | Buckeye | P2 | Dec-26 | 2030 | Installed Feb 2025 | ||
| 10lb ABC | |||||||
| South Emergency Exit | Buckeye | P3 | Dec-26 | 2030 | Installed Feb 2025 | ||
| 10lb ABC | |||||||
| 44/ Alamo Dorm | |||||||
| Front Entrance | Buckeye | AL1 | Dec-26 | 2030 | Installed Feb 2025 | ||
| 10lb ABC | |||||||
| West Emergency Exit | Buckeye | AL2 | Dec-26 | 2030 | Installed Feb 2025 | ||
| 10lb ABC | |||||||
| East Emergency Exit | Amerex | AL3 | Dec-26 | 2030 | Installed Feb 2025 | ||
| 10lb ABC | |||||||
| 34/ Student Union | |||||||
| Lobby Entrance | Buckeye | SU1 | Dec-26 | 2030 | Installed Feb 2025 | ||
| 10lb ABC | |||||||
| South Emergency Exit | Amerex | SU2 | 26-Dec | 2030 | Installed Feb 2025 | ||
| 10lb ABC | |||||||
| North Emergency Exit | Amerex | SU3 | Dec-26 | 2030 | Installed Feb 2025 | ||
| 10lb ABC | |||||||
| 14/ Gym |
Southwest Entranace Buckeye 10lb ABC G1 Dec-26 2030 Installed Feb 2025
Northwest Back Wall Buckeye 10LB ABC G2 Dec-26 2030 Installed Feb 2025
| Northeast Back Wall | Buckeye | G3 | Dec-26 | 2030 | Installed Feb 2025 | ||
| 10lb ABC | |||||||
| Southeast Entrace | Buckeye | G3 | Dec-26 | 2030 | Installed Feb 2025 | ||
| 10lb ABC | |||||||
| Building | Location | Manufacture Type and Size | Extinguisher ID | Annual Due | 5 yr Due | Status If non-compliant | Remarks |
| 14/Theater | |||||||
| Southeast Entrance | Buckeye 10LB ABC | T1 | 26-Dec | 2030 | Installed Feb 2025 |
Southwest Entrance Buckeye 10LB ABC T2 26-Dec 2030 Installed Feb 2025
| 43/ Education | ||||||
| North Entrance | Amerex 10lb ABC | ED1 | 26-Dec | 2030 | Installed Feb 2025 |
| Southwest Entrance | Amerex | ED2 | Dec-25 | 2030 | Installed Feb 2025 | |
| 10lb ABC | ||||||
| 35/ Bumpers Dorm | ||||||
| Northwest Wing | Amerex | B1 | Dec-26 | 2030 | Installed Feb 2025 | |
| 10lb ABC | ||||||
| Northeast Wing | Amerex | B2 | Dec-26 | 2030 | Installed Feb 2025 | |
| 10lb ABC | ||||||
| Southwest Wing | Buckeye | B3 | Dec-26 | 2030 | Installed Feb 2025 | |
| 10lb ABC | ||||||
| Southeast Wing | Amerex | B4 | Dec-26 | 2030 | Installed Feb 2025 | |
| 10lb ABC | ||||||
| South Mechanical Room (outside) | Buckeye | BMR 1 | Dec-26 | 2030 | Installed Feb 2025 | |
| 10lb ABC | ||||||
| North Mechanical Room (outside) | Buckeye | BMR1 | Dec-26 | 2030 | Installed Feb 2025 | |
| 10lb ABC | ||||||
| 41A/ Dining Hall | ||||||
| South Entrance Wall | Buckeye | DH1 | Dec-26 | 2030 | ||
| 10lb ABC | Installed Feb 2025 | |||||
| North Wall | Buckeye | DH2 | Dec-26 | 2030 | ||
| 10lb ABC | Installed Feb 2025 | |||||
| Cook Area Southwest wall | Amerex | DH3 | Dec-26 | 2030 | Installed Feb 2025 | |
| 6lb K | ||||||
| Loading Dock East Wall | Amerex 10lb ABC | DH4 | Dec-26 | 2030 | Installed Feb 2025 |
| 21A/ Health and Wellness | ||||||
| Northwest Entrance | Amerex 10lb ABC | HW1 | Dec-26 | 2030 | Installed Feb 2025 |
Northeast Entrance Amerex 10lb ABC HW2 Dec-26 2030 Installed Feb 2025
Southeast Back Entrance Buckeye 10LB ABC HW3 Dec-26 2030 Installed Feb 2025
| Building | Location | Manufacture Type and Size | Extinguisher ID | Annual Due | 5 yr Due | Status If non-compliant | Remarks |
| 15A/Center Maintnenance | |||||||
| Front Door Entrance | Amerex | CM1 | Dec-26 | 2030 | Installed Feb 2025 | ||
| 10lb ABC | |||||||
| Outside Northwest Corner | Sentry | CM2 | Dec-26 | 2025 | Replace OD 5yr | ||
| 10lb ABC | |||||||
| 48-Storage | Maintenance Storage Building | Buckeye | Dec-26 | 2030 | Installed Feb 2025 | ||
| 5lb ABC | CM3 | ||||||
| 63/ FM Trade | |||||||
| North Entrance | Amerex 10lb ABC | FM1 | Dec-26 | 2030 | Installed Feb 2025 |
| Southeast Entrance | Amerex 10lb ABC | FM2 | Dec-26 | 2030 | Installed Feb 2025 | |
| 10lb ABC | ||||||
| Shop West Wall | Amerex | Dec-26 | 2030 | Installed Feb 2025 | ||
| 10lb ABC | FM3 | |||||
| Southwest Back Shop | Amerex | Dec-26 | 2030 | Installed Feb 2025 | ||
| 10lb ABC | FM4 | |||||
| 71/ Carpentry | ||||||
| Northwest Bay Wall | Amerex 10lb ABC | CPT1 | Dec-26 | 2030 | Installed Feb 2025 |
Southwest Bay Wall Amerex 10lb ABC CPT2 Dec-26 2030 Installed Feb 2025
Southeast Bay Wall Amerex 10lb ABC CPT3 Dec-25 2030 Installed Feb 2025
Classroom Amerex 10lb ABC CPT4 Dec-26 2030 Installed Feb 2025
| Instructor Office | Amerex | CPT5 | Dec-26 | 2030 | Installed Feb 2025 |
| 10lb ABC | |||||
| Storage Room | Amerex 10lb ABC | CPT6 | Dec-26 | 2030 | Installed Feb 2025 |
| 72/ Lumber Storage Shed | Storage Shed | Buckeye | Dec-26 | 2030 | Installed Feb 2025 | |
| 10lb ABC | CPT7 | |||||
| 55/ Welding (Forsetry) | ||||||
| North Entrance | Amerex 10lb ABC | WLD1 | Dec-26 | 2030 | Installed Feb 2025 |
South Entrance Amerex 10lb ABC WLD2 Dec-26 2030 Installed Feb 2025
East Wall Buckeye 10lb ABC WLD3 Dec-26 2030 Installed Feb 2025
| Building | Location | Manufacture Type and Size | Extinguisher ID | Annual Due | 5 yr Due | Status If non-compliant | Remarks |
| 47/ Brick Trade | |||||||
| North Classroom Wall | Buckeye 10lb ABC | BR1 | Dec-26 | 2030 | Installed Feb 2025 |
| South Back Bay (Mixer Room) | ? | BR2 | Dec-26 | ? | ||
| 10lb ABC | ||||||
| East Entrance | Amerex | BR2 | Dec-26 | 2030 | Installed Feb 2025 | |
| 10lb ABC | ||||||
| 17A/ Paint Trade | ||||||
| North Entrance | Amerex 10lb ABC | PA1 | Dec-26 | 2030 | Installed Feb 2025 |
South Back Bay ? PA2 Dec-26 ?
East Bay Sentry 10lb ABC PA3 Dec-26 2026
Storage Shed Buckeye 10lb ABC PA4 Dec-26 2030 Installed Feb 2025
| 25/ HEO Trade | |||||
| West Bay Entrance | Buckeye | Dec-26 | 2030 | Installed Feb 2025 | |
| 10lb ABC | |||||
| East Bay Entrance | Buckeye | Dec-25 | 2030 | Installed Feb 2025 | |
| 10lb ABC | |||||
| Instructor Office | Sentry | Dec-26 | 2026 | ||
| 10lb ABC | |||||
| Fuel Distribution | Buckeye | Dec-25 | 2030 | Installed Feb 2025 | |
| 10lb ABC | |||||
| Storage Shed | Buckeye | Dec-25 | 2030 | Installed Feb 2025 | |
| 10lb ABC | |||||
| Training Field | Amerex 10lb ABC | Dec-25 | 2030 | Installed Feb 2025 |
Training Field Amerex 10lb ABC Dec-25 2030 Installed Feb 2025
| 24/ Fire Cache | |||||
| West Door Entrance | Amerex 10lb ABC | Dec-26 | 2030 | Installed Feb 2025 |
East Bay Entrance Amerex 10lb ABC Dec-26 2030 Installed Feb 2025
Instructor Office Amerex 10lb ABC Dec-26 2030 Installed Feb 2025
Fire Exting. Inventory Equipmen
| Building | Location | Manufacture Type and Size | Extinguisher ID | Annual Due | 5 yr Due | Status If non-compliant | Remarks |
| Training Equipment | |||||||
| 0166 Dozer | Kiddie 2.5lb ABC | Dec-26 | 2030 |
0766 Crawler, Tractor Kiddie 2.5lb ABC Dec-26 2030
1128 JCB Backhoe Kiddie 2.5lb ABC Dec-26 2030
3146 Excuvator Kiddie 2.5lb ABC Dec-26 2030
| 6030 John Deere Backhoe | Kiddie 2.5lb ABC | Dec-26 | 2030 |
| 4224 Tractor Semi | Kiddie 2.5lb ABC | Dec-26 | 2030 |
0182 Telescoping Forklift Kiddie 2.5lb ABC Dec-26 2030
2115 Motor Grader Case 856C Kiddie 2.5lb ABC Dec-26 2030
| Center Equipment | ||||
| 1129 Sterling 10k Forklift | Kiddie 2.5lb ABC | Dec-26 | 2030 |
6024 Mihindra Tractor Kiddie 2.5lb ABC Dec-26 2030
Carpentry Electric Cart Kiddie 2.5lb ABC Dec-26 2030
Brick Electric Cart Buckeye 5lb ABC Dec-26 2030
Center Maintenance Electric Cart Kiddie 2.5lb ABC Dec-26 2030
Dining Hall Electric Cart Kiddie 2.5lb ABC Dec-26 2030
7123 8 Passenger Van Buckeye 5lb ABC Dec-26 2030
7124 8 Passenger Van Buckeye 5lb ABC Dec-26 2030
7096 GMC Arcadia Kiddie 2.5lb ABC Dec-26 2030
2118 Electric Cart (HUMMV) Kiddie 2.5lb ABC Dec-26 2030
2150 Scissor Lift Kiddie 2.5lb ABC Dec-26 2030
Paint Electric Cart Buckeye 5lb ABC Dec-26 2030
| 9111 Bus | Buckeye 5lb ABC | Dec-26 | 2030 |
| 5043 Bus | Buckeye 5lb ABC | Dec-26 | 2030 |
| 1002 | Kiddie 2.5lb ABC | Dec-26 | 2030 |
| 1003 | Kiddie 2.5lb ABC | Dec-26 | 2030 |
| 4227 | 2.5lb Amerex ABC | Dec-26 | 2030 |
| 5043 | Buckeye 5lb ABC | Dec-26 | 2030 |
| 0118 | Kiddie 2.5lb ABC | Dec-26 | 2030 |
| 4226 | Kiddie 2.5lb ABC | Dec-26 | 2030 |
| chevrolet | Buckeye 5lb ABC | Dec-26 | 2030 |