COMMON WORK RESULTS FOR ELECTRICAL 260500-1
USDA FOREST SERVICE, R4
NEWLAND RANCH WASTEWATER TELEMETRY ALARM OPTION
SECTION 260500 - COMMON WORK RESULTS FOR ELECTRICAL
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Site and system description.
2. Operational requirements and general work description
3. Electrical equipment coordination and installation.
4. Common electrical installation requirements.
1.2 SUBMITTALS
A. Product Data:
1. For any substitutions for equipment referred to by name in Division 26 specifications.
B. Design Data:
1. Include calculations for battery backup and charging, transmitter and receiver with any interface equipment to accomplish intended design as described.
C. Programing Data:
1. Include programming information, and settings for transmitter, receiver, and existing SCAT machine controlling PLC.
D. As-built Drawings.
1.3 QUALITY ASSURANCE
A. The installation shall conform to the 2017 Edition of the National Electrical Code (NFPA
70) and to the requirements specified herein.
B. The Contractor shall perform all work necessary and required to accomplish the task as detailed in these specifications. All work shall be done by a state licensed electrician.
1.4 MEASUREMENT AND PAYMENT
A. The work in this section, including all incidentals in other electrical sections and Division 27, shall be measured and paid for by the following method as shown in the Schedule of Items:
1. Electrical Telemetry Alarm System - Lump Sum including full compensation for all labor, materials, and incidentals necessary to complete the work as called for in
COMMON WORK RESULTS FOR ELECTRICAL 260500-2
these specifications including all wiring, and all other incidentals necessary for a functional system.
PART 2 - PRODUCTS
2.1 PRODUCTS REFERRED TO BY NAME
A. The materials referred to by trade name, make, or catalog number shall be regarded as establishing a minimum standard of quality; substitutions of equal or greater quality can be made by submitting a data sheet of the proposed substituted item to the Contracting Officer, for approval.
PART 3 - EXECUTION
3.1 SITE AND SYSTEM DESCRIPTION
A. From the lower area utility building roof peak to the upper lift station is line of site and approximately 800 feet.
B. Existing 120/240 VAC power is readily available at the existing controls at both locations for powering the controls and radio equipment.
3.2 OPERATIONAL REQUIREMENTS AND GENERAL WORK DESCRIPTION
A. This project addition is to install a radio telemetry system to the Newland Ranch Wastewater system which shall indicate an alarm condition from the upper lift station to the trailer dump/scat/lower lift station area and limit the operation of the lower system to avoid sewage overflow spillage.
B. Communications is only required in one direction with the upper lift station area transmitting an alarm on/off condition to the lower area.
C. The radio antennae for the lower area shall be mounted at the utility building roof peak.
The radio antennae for the upper may be mounted directly to the radio transmitter as long as the antennae is not blocked from direct view of the lower site by other control equipment.
COMMON WORK RESULTS FOR ELECTRICAL 260500-3
Lower Lift Station Utility Building
Notes: Left exterior is lift station control panel. In left room is load center and water lines and where the new reciever shall be installed. The right room is the SCAT machine and controls. Circled is the location for the receivers antennae.
COMMON WORK RESULTS FOR ELECTRICAL 260500-4
Upper Lift Station
Note: Circled is barely the top of the Lower Lift Station Utility Building roof ridge.
D. Mount the radio transmitter on the rear of the support for the upper lift station controls, or similar if lift station controls are replaced.
1. Power the radio transmitter from the existing 15 amp controls breaker or similar protected circuit.
a. Also provide a rechargeable battery as backup power for the transmitter to provide a minimum of 10 minutes backup for the transmitter with charging circuit.
2. Provide a dry, normally closed, contact based on the high level alarm float to the radio transmitter. High level alarm system shall remain operational.
a. During normal operation the existing alarm float hangs down. The relay for the dry contact for the transmitter shall be wired to be powered, opening the normally closed contact, the radio transmitter shall transmit normal operation signal to lower area at a set timing interval not to exceed every 5 minutes.
b. When the float indicates an alarm condition the relay for the radio contact shall lose power and the relay shall close indicating an alarm condition to the transmitter, the transmitter shall transmit an alarm signal to the lower area at the set timing interval.
c. Note: Normally closed relay contact is used as a fail safe operation of the upper lift station, such that if the upper lift station loses power, the radio transmitter sends an alarm signal.
3. Setup transmitter to relay alarm condition on/off to lower lift station receiver as appropriate for proper operation as described above.
E. Mount the radio receiver inside the utility building, next to the load center and water system controls powered from a new Square D QO115 breaker and circuit installed within
COMMON WORK RESULTS FOR ELECTRICAL 260500-5
the load center. Provide cable from the radio system manufacturer to antennae and mount, mounted on the exterior front of the building at the roof peak.
1. Provide the following interfaces from the receiver with existing controls:
a. Upper lift alarm and indicator that the trailer dump station and SCAT machine are inoperable. Shall be the same alarm light, indicating that the lower lift station is inoperable, existing on the side of the building (or its replacement).
1) Forest Service shall provide signage indicating that when the alarm light is operating that the area is closed.
Lower Lift Station Controls before latest pump contract.
Lower Lift Station Control Diagram before latest pump contract
COMMON WORK RESULTS FOR ELECTRICAL 260500-6
Note: Circled are the overload relays for both pumps, the new alarm contacts may be installed in series with these or similar. The open contact drawn parallels the existing alarm circuit and indicates a method, or similar, that may be used to activate the alarm flashing light.
b. Lift station controls to allow/prevent the operation of the lower lift station.
c. Dump station water supply electronic actuator valve (new) to allow/prevent water flow to the dump station.
1) Install an electronic actuator valve in the dump station water supply line. Size and location as directed by Contracting Officer. Power hold open with spring close, or, power open and close types may be used.
Picture of water supply lines. Contracting Officer to determine which line the actuator valve must be installed in.
d. SCAT machine controls wired into existing PLC with programming to allow/prevent the operation of the SCAT machine.
COMMON WORK RESULTS FOR ELECTRICAL 260500-7
1) Install an alarm flashing light to the control panel exterior to indicate that the SCAT machine is not operational. Provide programming to tie the alarm light to radio receiver input interface.
SCAT Machine Controls
SCAT Machine PLC
COMMON WORK RESULTS FOR ELECTRICAL 260500-8
F. Operation, normal operation signal:
1. While the radio receiver gets an upper lift station normal signal, the receiver outputs a signal to the following until an alarm signal is received:
a. Two dry contact closed signals in line with each lower lift station pump controls allowing the pump to operate.
b. An open dry contact signal to the lower lift station alarm light in parallel with the existing alarm light controls.
c. A closed dry contact signal to the dump station water supply actuator valve keeping or turning the valve to the open position.
d. A closed dry contact to a SCAT Machine PLC input allowing the SCAT machine to operate normally.
G. Operation, alarm signal:
1. While the radio receiver gets an upper lift station alarm signal, the receiver outputs a signal to the following until a normal signal is received:
a. Two dry contact open signals in line with each lower lift station pump controls causing the pump to stop operating.
b. A dry contact closed signal to the lower lift station alarm light, in parallel with the existing alarm light controls causing the alarm light to operate.
c. An open dry contact signal to the dump station water supply actuator valve keeping, or similar contact signal turning the valve to the closed position shutting off the water to the dump station only.
d. An open dry contact to a SCAT Machine PLC input Shutting down SCAT machine operation and operating the new alarm light.
H. Power outage operation:
1. Partial power outage: A partial power outage is one that only affects the upper lift station. Upon loss of power at the upper lift station the transmitter will transmit an alarm signal creating the alarm condition in the lower lift station until receipt of the normal signal from the upper lift station. Thus the battery backup for the transmitter at the upper lift station.
2. Full power outage: Well things are shut down anyway, the only difference is that there is not required to be any alarm light notification. No special action required.
I. Note that if another signal method is chosen, it must be approved by the Contracting Officer for demonstration, and shall be demonstrated to work without error in expected weather and partial and full power outage situations.
J. Dry contact ratings: Provided contacts shall be rated capable for not only rated current draws, but for surges caused by making or breaking the currents expected from the various devices, coils, and motors they directly interface with.
1. Provide submittals indicating the rating of the device and the expected inrush and break currents that they will experience when installed.
3.3 COMMON REQUIREMENTS FOR ELECTRICAL INSTALLATION
COMMON WORK RESULTS FOR ELECTRICAL 260500-9
A. Comply with NECA 1.
B. Equipment: Install to facilitate service, maintenance, and repair or replacement of components of both electrical equipment and other nearby installations. Connect in such a way as to facilitate future disconnecting with minimum interference with other items in the vicinity.
3.4 RACEWAY AND SIMILAR PENETRATIONS (NON-FIRE RATED, NOT
SLEEVED)
A. Roof-Penetrations: Seal penetration of individual raceways with flexible boot-type flashing units applied in coordination with roofing work.
B. Stick-built and Similar Interior-Wall Penetrations: Repair wall to within 1/8-inch (3 mm) to match the surrounding wall finish.
1. Allow for a small gap or flexible fill to allow expansion and contraction to minimize cracking.
C. Aboveground, Exterior-Wall Penetrations: Seal exterior opening around the raceway or cable, using a flexible, waterproofing, joint sealant appropriate for size, depth, and color to closely match the surrounding surface. Finish interior openings, filling opening and matching the exiting surface with appropriate materials and finish quality for the space.
END OF SECTION 260500
July 2018
LOW‐VOLTAGE ELECTRICAL POWER CONDUCTORS 260519‐1
NEWLAND RANCH WASTEWATER TELEMETRY ALARM OPTION
SECTION 260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Building wires and cables rated 2000 V and less.
2. Connectors, splices, and terminations rated 2000 V and less.
1.2 MEASUREMENT AND PAYMENT
A. No separate measurement or payment will be made for work specified in this section. All work will be included in other items listed in the Schedule of Items.
PART 2 - PRODUCTS
2.1 CONDUCTORS
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
B. Conductors: Copper, complying with NEMA WC 70/ICEA S-95-658.
1. Conductor Insulation: Comply with NEMA WC 70/ICEA S-95-658 for Type THHN/THWN-2.
2.2 CONNECTORS AND SPLICES
A. Description: Factory-fabricated connectors and splices of size, ampacity rating, material, type, and class for application and service indicated; listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
PART 3 - EXECUTION
3.1 CONDUCTOR WIRING METHODS
A. Circuits: Single conductors in raceway.
B. Equipment grounding: Install insulated equipment grounding conductors with all feeders and branch circuits.
3.2 INSTALLATION OF CONDUCTORS AND CABLES
LOW‐VOLTAGE ELECTRICAL POWER CONDUCTORS 260519‐2
A. Complete raceway installation between conductor and cable termination points according to Section 260533 "Raceways and Boxes for Electrical Systems" prior to pulling conductors and cables.
B. Use manufacturer-approved pulling compound or lubricant where necessary; compound used must not deteriorate conductor or insulation. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values.
C. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips, which will not damage cables or raceway.
3.3 CONNECTIONS
A. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A-486B.
B. Make splices, terminations, and taps that are compatible with conductor material and that possess equivalent or better mechanical strength and insulation ratings than un-spliced conductors.
END OF SECTION 260519
RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533‐1
NEWLAND RANCH WASTEWATER TELEMETRY ALARM OPTION
SECTION 260533 - RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Metal conduits, tubing, and fittings.
2. Boxes, enclosures, and cabinets.
1.2 MEASUREMENT AND PAYMENT
A. No separate measurement or payment will be made for work specified in this section. All work will be included in other items listed in the Schedule of Items.
PART 2 - PRODUCTS
2.1 METAL CONDUITS, TUBING, AND FITTINGS
A. Listing and Labeling: Metal conduits, tubing, and fittings shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
B. EMT: Comply with ANSI C80.3 and UL 797.
C. LFMC: Flexible steel conduit with PVC jacket and complying with UL 360.
D. Fittings for Metal Conduit: Comply with NEMA FB 1 and UL 514B.
1. Fittings for EMT:
a. Material: Steel.
b. Type: compression.
2.2 BOXES, ENCLOSURES, AND CABINETS
A. General Requirements for Boxes, Enclosures, and Cabinets: Boxes, enclosures, and cabinets installed in wet locations shall be listed for use in wet locations.
B. Sheet Metal Outlet and Device Boxes: Comply with NEMA OS 1 and UL 514A.
C. Cast-Metal Outlet and Device Boxes: Comply with NEMA FB 1, Type FD, with gasketed cover.
D. Small Sheet Metal Pull and Junction Boxes: NEMA OS 1.
E. Cast-Metal Access, Pull, and Junction Boxes: Comply with NEMA FB 1 and UL 1773, with gasketed cover.
RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533‐2
F. Hinged-Cover Enclosures: Comply with UL 50 and NEMA 250, Type 1, 3R, or 12 with continuous-hinge cover with flush latch unless otherwise indicated.
1. Metal Enclosures: Steel, finished inside and out with manufacturer's standard enamel.
PART 3 - EXECUTION
3.1 RACEWAY APPLICATION
A. Outdoors: Apply raceway products as specified below unless otherwise indicated:
1. Exposed Conduit: EMT where UL listed rain tight compression fittings are used and the raceway is 3-ft (1-m) minimum above finished grade.
2. Boxes and Enclosures, Aboveground: NEMA 250, Type 3R.
B. Indoors: Apply raceway products as specified below unless otherwise indicated:
1. Exposed: EMT.
2. Boxes and Enclosures: NEMA 250, Type 1.
3. To actuator valve: Flexible wiring method is allowed where 5-ft (1.5-m) maximum length.
3.2 INSTALLATION
A. Comply with NECA 1 and NECA 101 for installation requirements except where requirements in this article are stricter.
B. Complete raceway installation before starting conductor installation.
C. Support within 12 inches (300 mm) of changes in direction.
D. Install conduits parallel or perpendicular to building lines.
E. Support conduit within 12 inches (300 mm) of enclosures to which attached.
F. Install raceways square to the enclosure and terminate at enclosures with locknuts.
G. Cut conduit perpendicular to the length.
H. Fasten junction and pull boxes to or support from building structure. Do not support boxes by conduits.
END OF SECTION 260533
IDENTIFICATION FOR ELECTRICAL SYSTEMS 260553-1
NEWLAND RANCH WASTEWATER TELEMETRY ALARM OPTION
SECTION 260553 - IDENTIFICATION FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 SUMMARY
A. This Section includes the following:
1. Identification for conductors and communication and control cable.
2. Warning labels.
3. Instruction signs.
4. Control diagrams.
1.2 QUALITY ASSURANCE
A. Comply with NFPA 70.
1.3 MEASUREMENT AND PAYMENT
A. No separate measurement or payment will be made for work specified in this section. All work will be included in other items listed in the Schedule of Items.
PART 2 - PRODUCTS
2.1 CONDUCTOR AND COMMUNICATION- AND CONTROL-CABLE
IDENTIFICATION MATERIALS
A. Marker Tapes: Vinyl or vinyl-cloth, self-adhesive wraparound type, with circuit identification legend machine printed by thermal transfer or equivalent process.
2.2 WARNING LABELS
A. Warning Label Colors:
1. Identify system voltage with black letters on an orange background.
B. Warning labels and signs shall include, but are not limited to, the following legends:
1. Multiple Power Source Warning, OSHA standard Danger Sign: "DANGER -
ELECTRICAL SHOCK HAZARD - EQUIPMENT HAS MULTIPLE POWER
SOURCES.” Then list shutoff locations of sources in smaller font.
2.3 INSTRUCTION SIGNS
A. Provided and installed by Government.
2.4 CONTROL DIAGRAMS
IDENTIFICATION FOR ELECTRICAL SYSTEMS 260553-2
A. New Control Panels: Laminated, created in CAD or similar computer generated method acceptable to the Contracting Officer.
B. Existing Control Panels: Laminated, showing as-built corrections in a method acceptable to the Contracting Officer.
1. It is not required that the control diagrams be created for existing controls where existing control diagrams are not available.
PART 3 - EXECUTION
3.1 APPLICATION
A. Conductor Identification: Identify new conductors within controls consistent with existing labeling and new as-built drawings.
B. Equipment with Multiple Power or Control Sources: Apply to door or cover of equipment including, but not limited to, the following:
1. Controls with external control power connections.
3.2 INSTALLATION
A. Verify identity of each item before installing identification products.
B. Location: Install identification materials and devices at locations for most convenient viewing without interference with operation and maintenance of equipment.
C. Self-Adhesive Identification Products: Clean surfaces before application, using materials and methods recommended by manufacturer of identification device.
D. Attach non-adhesive signs and plastic labels with screws and auxiliary hardware appropriate to the location and substrate.
1. Laminated Control diagrams may be taped to the inside cover of the equipment.
END OF SECTION 260553
OTHER ELECTRICAL TESTS AND CALIBRATIONS 269999-1
NEWLAND RANCH WASTEWATER TELEMETRY ALARM OPTION
SECTION 269999 - OTHER ELECTRICAL TESTS AND CALIBRATIONS
PART 1 - GENERAL
1.1 SUMMARY
A. This Section includes the following:
1. System Testing.
1.2 QUALITY ASSURANCE
A. Comply with NFPA 70.
1.3 COORDINATION
A. Coordinate with the Contracting Officer for witnessing these tests.
1.4 MEASUREMENT AND PAYMENT
A. No separate measurement or payment will be made for work specified in this section. All work will be included in other items listed in the Schedule of Items.
PART 2 - PRODUCTS
A. Not applicable.
PART 3 - EXECUTION
3.1 SYSTEM TESTING
A. Verify signal strength at each receiver from all sources to be 10 dBm above minimum signal needed for proper operation.
1. Signal from upper lift station to lower lift station utility building.
B. Verify normal operation from radio signals.
1. Signal from upper lift station.
2. Signals to:
a. Lower lift station pump controls.
b. Alarm flashing light off.
c. Dump station actuator valve, water flow to dump station.
d. SCAT Machine controls and operation.
C. Verify alarm operation.
OTHER ELECTRICAL TESTS AND CALIBRATIONS 269999-2
1. Lower lift station pump controls shutdown even when duplex or in lower lift station high level alarm condition.
2. Alarm flashing light on.
3. Dump station actuator valve closed, no water flow.
4. SCAT machine off and new alarm flashing light on.
D. Verify proper reset to normal condition after alarm and normal operation signal received by radio receiver.
E. Any failures shall be corrected and then the system completely retested. Record final signal strength values and give to contracting officer.
END OF SECTION 269999
WIRELESS RADIO TRANSMISSION 277999-1
NEWLAND RANCH WASTEWATER TELEMETRY ALARM OPTION
SECTION 277999 - WIRELESS RADIO TRANSMISSION
PART 1 - GENERAL
1.1 SUMMARY
A. This Section includes the following:
1. Radio Transmitter/Receivers.
2. Antenna Cables.
3. Coax Surge Arresters.
4. Antennae.
5. Programming and Setup.
1.2 SUBMITTALS
A. Product Data.
B. Design/Build Radio Path and Equipment: Show design signal strength and losses for entire paths from transmitters to receivers along with all required equipment.
C. Signal Strength: Measured signal strength after all adjustments at receivers. See specification 269999 3.3A.
D. Radio Operation and Maintenance Manual: Include cut sheets, installation requirements, operation, maintenance needs, and test procedures for all equipment.
1.3 QUALITY ASSURANCE
A. The installation shall conform to the 2017 Edition of the National Electrical Code (NFPA 70); FCC Part 15.247, Part 15, and Part 90; IEEE 802.11; and to the requirements specified herein.
B. The Contractor shall perform all work necessary and required to accomplish the task as detailed in these specifications. All work shall be done by a state licensed electrician.
1.4 COORDINATION
A. Coordinate with the Contracting Officer for witnessing these tests.
1.5 MEASUREMENT AND PAYMENT
A. No separate measurement or payment will be made for work specified in this section. All work will be included in other items listed in the Schedule of Items.
PART 2 - PRODUCTS
WIRELESS RADIO TRANSMISSION 277999-2
2.1 PRODUCTS REFERRED TO BY NAME
A. The materials referred to by trade name, make, or catalog number here shall be regarded as establishing a minimum standard of quality; substitutions of equal or greater quality can be made by submitting a data sheet of the proposed substituted item to the Contracting Officer, for approval.
PART 3 - EXECUTION
3.1 RADIO TRANSMITTER/RECEIVER
A. The following manufacturers equipment may be incorporated into the design subject to the requirements herein:
1. Remote Control Technology, (Phone 866-701-1146, wwwremotecontroltech.com).
Based on model SRWSS.
2. ELPRO Technologies; a division of Cooper Industries, Inc. (Cooper). Based on model 905U-1.
B. Frequency and power output shall be within unlicensed allowed power level, channels and bands.
C. Any interface requirements shall be designed into the design/build.
D. Transmitter/Receiver shall have built in ability to charge the battery from commercial power.
3.2 ANTENNA CABLE
A. Cable shall be rated for direct sunlight exposure.
B. Do not bend tighter than manufacturers minimum bend radius during installation.
3.3 COAX SURGE ARRESTER
A. The following manufacturers equipment may be incorporated into the design subject to the requirements herein:
1. Remote Control Technology.
2. ELPRO Technologies.
3. PolyPhaser Corp.
B. Broadband DC blocked protector for the frequency and connectors used.
C. Protection may be built into the device.
3.4 ANTENNA
A. Mount securely and shall have an 80 mph wind speed withstand.
3.5 PROGRAMMING AND SETUP
WIRELESS RADIO TRANSMISSION 277999-3
A. Program and setup the entire radio system to operate as described and intended in these specifications.
B. Any interface issues shall be corrected.
END OF SECTION 269999