30” http://www.novapdf.com Carl Madson

PROJECT

TITLE

DRAWN

CHECKED

APPROVED

SCALE WEIGHT SHEET

DWG NO REVCODESIZE

1:308/20/20Carl Madson

B

CRD Lightpole

Shallow Bedrock Base

42.00

42.00

30.00

12.00

6.00

36" above grade

Rebar Circular Upright #5 Hoops 8" TYP #5 Verticals 8" TYP 2" Clear space from edges and top

Rebar Square Base

5 #5 EW & EF

3" Clear from Edges

3/4" x 18" SS bolts with 2" x 1/8" SS washer. Drilled into and secured to bedrock with waterproof epoxy

Bolts per light pole manufacturer installation instructions.

6.00

36.00

18.00

Actual depth may vary according to distance from finish grade to bedrock. 18" shown here.

3/4" PVC

SCH 80

Conduit

A2

See A1-A, A1-C and A1-D2 for elevation view, electrical section and fastening details.